TM-16509

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

SYNOPSIS
This document presents the On-Line Test Procedure for High Integrity pressure protection System (HIPPS) on
Flare Mitigation (CDU) Unit 011, Butane Splitter Unit 64, Marine Heavy Fuel Oil (MHFO) Unit 11, Catalytic Hydro
Desulphurizer (CHD) Unit 032.
This document is a part of SAMREF Clean Fuels Project (CFP). The intent is to implement SAMREF CFP
according to the requirements described in CFP project documents, Global Practices (GPs) and Design Practices
(DPs), Industry Codes and Standards, SAMREF specific standards, specifications, and procedures,
WorleyParsons corporate and project level standards and best practices, and industry standards.
Disclaimer
This document has been prepared on behalf of and for the exclusive use of SAMREF, and is
subject to and issued in accordance with the agreement between SAMREF and WorleyParsons.
Copying this document without the permission of SAMREF and WorleyParsons is not permitted.
.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 2 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

TABLE OF CONTENTS
1

INTRODUCTION........................................................................................................................................................4

FLAREMITIGATION(CDU011)..................................................................................................................................6

HIPPSBUTANESPLITTERUNIT064..........................................................................................................................19

MARINEHEAVYFUELOIL(MHFO)UNIT11..............................................................................................................30

CATALYTICHYDRODESULPHURIZER(CHD)UNIT032...............................................................................................35
5.1
5.2

TRAIN1......................................................................................................................................................................35
TRAIN2......................................................................................................................................................................45

List of Appendices
Appendix A FLARE MITIGATION (CDU 011) HIPPS REFERENCE DOCUMENTS ........................................... 55
Appendix B HIPPS BUTANE SPLITTER UNIT 064 REFERENCE DOCUMENTS ............................................. 63
Appendix C MARINE HEAVY FUEL OIL UNIT 11 REFERENCE DOCUMENTS ................................................ 69
Appendix D CATALYTIC HYDRO DESULPHURIZER UNIT 32 REFERENCE DOCUMENTS ........................... 72
Appendix E SAFEPLEX SIL 3 (SOV PANEL) TECHNICAL PRODUCT GUIDE ................................................. 79

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 3 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

INTRODUCTION

This document presents the technical guideline for conducting on-line testing of the High Integrity Pressure
Protection System (HIPPS) valves, pumps, and transmitters installed on Flare Mitigation (CDU) Unit 011, Butane
Splitter Unit 64, Marine Heavy Fuel Oil (MHFO) Unit 11, Catalytic Hydro Desulphurizer (CHD) Unit 032.
Actual on-line testing procedure shall be a part of SAMREF Operation Manual

HIPPS operation logic described below:


When any of the following occurs:

PT-xxxA/B/C (2oo3) the pressure exceed HiHi set point or

HS-xxx (2oo3) ESD push button near HIPPS isolation valves is activated or

HS-xxx (2oo3) ESD push button near pumps (on CDU and MHFO units) is activated or

HS-xxx (2oo3) ESD push button in Central Control House is activated

XV-xxx1 and XV-xxx2 will close to cut off process line and

Trip G-xxxA/B/C pumps (on CDU and MHFO units)

HIPPS Trip Alarm activated

Then

HIPPS consists of the following components:


1) Three redundant pressure transmitters installed on process line.
2) One independent/dedicated triple modular redundant (TMR) SIL 3 certified fault tolerant HIPPS Logic Solver
(HIPPS LS) installed in SIH HIPPS Cabinet.
3) Valve skid with piping, two HIPPS isolation valves with limit switches, two bypass valves across the HIPPS
Valves with limit switches and key lock devices, block and bleed valves at each side of the HIPPS Valves, local
ESD pushbutton and two local SOV panels. SOV panels equipped with solenoid package, full stroke and partial
stroke test pushbuttons and lights.
4) Heater charge pumps 11-G-02 A/B/C for CDU 11 with ESD pushbutton installed near the pumps
5) MHFO buster pumps 11-G-021A/B with ESD pushbutton installed near the pumps.
Testing of all HIPPS components and logic is required at periodic intervals no greater than those shown in table 1

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 4 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Table 1 Maximum Allowable Test intervals

Test Method

Interval

Safety Availability / SIL level

Full Stroke Test (FST)

12 month

99.90+% to 99.99% / 3

Partial Stroke Test (PST)

3 month

99.90+% to 99.99% / 3

Transmitters
maintenance/calibration

12 month

99.90+% to 99.99% / 3

Pumps Full Trip Test

12 month

99.90+% to 99.99% / 3

Pumps Interposing Relays Test

3 month

99.90+% to 99.99% / 3

Test data shall be recorded and stored for the life of the HIPPS. Test data shall include but not limited by the
following:

1) StrokingtimeforeachHIPPSvalve;
2) Adetaileddescriptionofallobserveddeficiencies/deviations
The list of Appendixes:
1) Appendix A: CDU 11 P&IDs C0EF-011B1-002A; C0EF-011B1-008; C0EF-011B1-009A; C0EF011B1-020; Figure 1 SOV Panel 11-XV-1001 Layout; Figure 2 SOV Panel 11-XV-1002 Layout; Figure
3 Heater charge pumps HIPPS Cabinet Layout.
2) Appendix B: Butane Splitter Unit 64 P&IDs C0EF-011B1-002A; C0EF-064B1-004; C0EF-064B1-001;
Figure 1 SOV Panel 64-XV-1001 Layout; Figure 2 SOV Panel 64-XV-1002 Layout; Figure 3 Butane
Splitter HIPPS Cabinet Layout.
3) Appendix C: MHFO Unit 11 P&IDs C0EF-011B1-017; Figure 1 MHFO HIPPS Cabinet Layout.
4) Appendix D: CHD Unit 32 P&IDs C0EF-032B1-003D-E; Figure 1 SOV Panel 11-XV-1000 Layout;
Figure 2 SOV Panel 11-XV-1001 Layout; Figure 3 SOV Panel 11-XV-1003 Layout Figure 4 SOV
Panel 11-XV-1004 Layout; Figure 5 CHD HIPPS Cabinet Layout;
5) Appendix E: Safeplex SILstroke-3E (SSOV Panel) Technical Product Guide.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 5 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

FLARE MITIGATION (CDU 011)

The Operator actions and observations during HIPPS operation and testing.
For reference see Appendix A: CDU 11 P&IDs C0EF-011B1-002A; C0EF-011B1-008; C0EF-011B1-009A;
C0EF-011B1-020. Figure 1 SOV Panel 11-XV-1001 Layout; Figure 2 SOV Panel 11-XV-1002 Layout; Figure 3
Heater charge pumps HIPPS Cabinet Layout.

STEP

Operation
Task

Operator Action

Observation/Logic Response

1.1

Verify that Atmospheric Tower 11-C01 overhead pressure is less than


280 kPa-g

1.2

Verify HIPPS Valve Skid


components in normal plant
operation conditions:

HIPPS at
Normal
Operation.

1.3

11900003-000-IC-PRO-0001_r0

DCS Atmospheric tower overhead pressure


11-PI-1230A/B/C (median signal).

HIPPS valves 11-XV-1001 and


11-XV-1002 are OPEN

SOV Panels: green lights 11- ZLH-1001A


and 11-ZLH-1002A ESDV Open are
ON

HIPPS bypass valves XV-803,


XV-804 are CLOSED

DCS alarms: XA-1028 and XA-1029


Bypass Valve OPENED not activated.

SOV Panel XV-1001 solenoid


status lights

SOV Panel: solenoid status lights 11-EL520A/B/C/D are ON. Local Alarm light
EL-526 is OFF.

SOV Panel XV-1002 solenoid


status lights.

SOV Panel: solenoid status lights EL521A/B/C/D are ON. Local Alarm light
EL-527 is OFF.

Ensure that two operating pumps are


running and one on standby, for

Indication lights 11-EL-516A, 11-EL-517A

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 6 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

example, 11-G-02A/B are running


and 11-G-02C on standby.

are ON and 11-EL-518A is OFF on


HIPPS Cabinet in SIH-5
DCS indications 11-EL-516, 11-EL-517 are
ON and 11-EL-518 is OFF

1.4

Verify all maintenance/bypass


switches on HIPPS cabinet in SIH-5
normalized

Bypass lights XL-P-1230A/B/C are OFF.

1.5

Verify SOV panel bypass switch is in


No Bypass position

DCS alarms 11-XA-1048 and 11-XA-1050


Bypass Active are not activated

1.6

Verify all P1 alarms are cleared

P1 Indication/alarm screen in SIH 5: No


alarms activated:

DCS alarms 11-HA_P-1230A/B/C are


OFF.

11-XA-1025A Common bypass


alarm

11-XA-1022 Deviation alarm

11-XA-1023A Forced logic alarm

11-XA-1029A 11-HV-803/804
bypass valves open

11-PAH-1230 Pre-S/D pressure


High alarm

11-XA-1031 Processor fault alarm

11-XA-1028A Pump bypass alarm

SOV Panel
Solenoid
Functional
Test

2.1

The following selector switches deenergize solenoids during SOV


Panel XV-1001 test:

The signal from 11-HS-xxx indicating whether


solenoid Failed sent to HIPPS.

Hold selector switch 11-HS11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 7 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
843 in A position and then
release
Hold selector switch 11-HS843 in B position and then
release

Hold selector switch 11-HS847 in C position and then


release

Hold selector switch 11-HS847 in D position and then


release

Observation/Logic Response
Light 11-EL-520A goes OFF and then ON
when switch 11-HS-843 position A
released
Light 11-EL-520B goes OFF and then ON
when switch 11-HS-843 position B
released

Light 11-EL-520C goes OFF and then ON


when switch 11-HS-847C position A
released

Light 11-EL-520D goes OFF and then ON


when switch 11-HS-847 position D
released
NOTE:
Solenoid status during the test indicating whether
solenoid Failed sent to HIPPS LS and is
duplicated in DCS indication points: 11-HL-843A,
11-HL-843B, 11-HL-847C, 11-HL-847D
respectively.

2.2

The following selector switches deenergize solenoids during SOV


Panel XV-1002 test:
Hold selector switch 11-HS844 in A position and then
release
Hold selector switch 11-HS848 in B position and then
release

11900003-000-IC-PRO-0001_r0

Light 11-EL-521A goes OFF and then ON


when switch 11-HS-844 position A
released
Light 11-EL-521B goes OFF and then ON
when switch 11-HS-844 position B
released

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 8 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Hold selector t switch 11-HS848 in C position and then
release
Hold selector switch 11-HS848 in D position and then
release

Observation/Logic Response
Light 11-EL-521C goes OFF and then ON
when switch 11-HS-848 position C
released

Light 11-EL-521D goes OFF and then ON


when switch 11-HS-848 position D
released
NOTE:
Solenoid status during the test indicating whether
solenoid Failed sent to HIPPS LS and is
duplicated in DCS indication points:11-HL-844A,
11-HL-844B, 11-HL-848C, 11-HL-848D
respectively.

Full Stroke
Test (FST)
HIPPS Isolation Valve 11-XV-1001

3.1

Verify permissive to start FST:


Conduct SOV Panel Solenoid
Functional Test . .All four
solenoids shall pass
functional test (for SOV
Panel solenoids XY-1001A,
B, C, D functional test
sequence see step 2).
Ensure that Local Alarm on
SOV Panel is OFF
Open HIPPS bypass valve
11-HV-803 across the
HIPPS Isolation Valve 11XV-1001.

3.2

11900003-000-IC-PRO-0001_r0

Start FST:

Local Alarm amber light 11-EL-526 is


OFF.
DCS point 11-XA-1028:- Bypass Valve
11-HV-803 OPEN
P1 Alarm Bypass Valve Open 11-XA1029A activated.
After FST started the HIPPS LS de-energizes the
solenoids in the respective SOV panel and
closes HIPPS Isolation Valve.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 9 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

3.3

Operator Action

Observation/Logic Response

Turn hand switch 11-837 FST


Request on SOV Panel. FST
Request signal sent to HIPPS Logic
solver.

DCS light FST Request 11-HL-837


activated

Verify that HIPPS Valve 11-XV-1001


is closed

SOV Panel: green light 11- ZLH-1001A


ESDV OPEN goes OFF
Red light 11-ZLL-1001A ESDV CLOSED
is ON.
SOV Panel: solenoid status green lights
11-EL-520A/B/C/D are OFF.
Local Alarm light EL-526 is ON.
DCS discrepancy 11-XA-1001 alarm is
off.

3.4

After FST complete Operator push


and hold Local Reset push button
11-HS-838.to restore normal Valves
operation.

Operator holds 11-HS-838 until HIPPS


Valve 11-XV-1001 opens.
SOV Panel: green light 11- ZLH-1001A
ESDV OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.5

Close HIPPS bypass valve 11-HV803 across the HIPPS Isolation


Valve 11-XV-1001.

DCS alarm 11-XA-1028:- Bypass valve


11-HV-803 OPEN is OFF.
P1 Alarm Bypass Valve Open 11-XA1029A is OFF (returns to normal).

HIPPS Isolation Valve 11-XV-1002


3.6

Verify permissive to start FST:


Conduct SOV Panel Solenoid
Functional Test ..All four
solenoids shall pass
functional test (for SOV
Panel solenoids XY-1002A,
B, C, D functional test
sequence see step 2).

11900003-000-IC-PRO-0001_r0

Local Alarm amber light 11-EL-527 is

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 10 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Ensure that Local Alarm on
SOV Panel is OFF
Open HIPPS bypass valve
11-HV-804 across the
HIPPS Isolation Valve 11XV-1002

3.7

3.8

Start FST:

Observation/Logic Response
OFF.
DCS point 11-XA-1028:- Bypass valve 11HV-804 OPEN.
P1 Alarm Bypass Valve Open 11-XA1029A activated.
After FST started the HIPPS LS de-energizes the
solenoids in the respective SOV panel and
closes HIPPS Isolation Valve.

Turn hand switch 11-HS-840 FST


Request on SOV Panel. FST
Request signal sent to HIPPS Logic
solver.

DCS light FST Request 11-HL-840


activated.

Verify that HIPPS Valve 11-XV-1002


is closed

SOV Panel: green light 11- ZLH-1002A


ESDV OPEN goes OFF
Red light 11-ZLL-1002A ESDV CLOSED
is ON.
SOV Panel: solenoid status green lights
11-EL-521A/B/C/D are OFF.
Local Alarm light EL-527 is ON.
DCS discrepancy 11-XA-1001 alarm is off.

3.9

After FST complete Operator pushes


and holds Local Reset push button
11-HS-841.to restore normal Valves
operation.

Operator holds 11-HS-841 until HIPPS


Valve11-XV-1002 opens.
SOV Panel: green light 11- ZLH-1002A
ESDV OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.10

11900003-000-IC-PRO-0001_r0

Close HIPPS bypass valve 11-HV804 across the HIPPS Isolation


Valve 11-XV-1002.

DCS alarm 11-XA-1029:- Bypass valve


11-HV-804 OPEN is OFF.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 11 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response
P1 Alarm Bypass Valve Open 11-XA1029A is OFF (returns to normal).

Partial
Stroke
Test (PST)
HIPPS Isolation Valve 11-XV-1001

4.1

Verify permissive to start PST


Operator conducts SOV Panel
Solenoid Functional Test .
.All four solenoids shall pass
functional test.

For SOV Panel solenoids XY-1001A, B, C,


D functional test sequence see step 2.

Operator ensure that Local


Alarm on SOV Panel is OFF

LOCAL Alarm amber light 11-EL-526 is


OFF.

Operator ensures that HIPPS


bypass valve 11-HV-803
across the HIPPS Isolation
Valve 11-XV-1001 is
CLOSED.

4.2

Starts PST:

Turn hand switch 11-HS-836 PST


Request on SOV Panel.

4.3

Verify that HIPPS Valve 11-XV-1001


is traveling to 90% open position

DCS alarm 11-XA-1028:- Bypass valve


11-HV-803.is OFF.

The DVC 6000SIS starts pre-programmed PST


test. DVC 6000 reduces the air supply to HIPPS
Valve actuator and thus triggers the valve to 90%
OPEN position.

DCS point PST Request 11-HL-836 is


ON.
SOV Panel: green light 11- ZLH-1001A
ESDV OPEN goes OFF for the duration
of PST
SOV Panel: solenoid status green lights
11-EL-520A/B/C/D are ON.

NOTES:
11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 12 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

1) If the valve travel takes longer


than initial valve signature time, the
Operator shall take actions
described in Operation manual.

Local Alarm light EL-526 is OFF.

2) During PST, if a trip condition


occurs HIPPS LS will abandon PST
and initiate trip of the HIPPS.

After PST complete SOV Panel: green


light 11- ZLH-1001A ESDV OPEN goes
ON.

Discrepancy alarm 11-XA-1001 is initiated.

HIPPS Isolation Valve 11-XV-1002


4.4

Verify permissive to start PST


Operator conducts SOV Panel
Solenoid Functional Test .
.All four solenoids shall pass
functional test.
Operator ensures that Local
Alarm on SOV Panel is OFF
Operator ensures that HIPPS
bypass valve 11-HV-804
across the HIPPS Isolation
Valve 11-XV-1002 is
CLOSED.

4.5

Start PST:

Turn hand switch 11-HS-839


PST Request on SOV
Panel.
4.6

Verify that HIPPS Valve 11-XV-1002


is traveling to 90% open position

For SOV Panel solenoids XY-1002A, B, C,


D functional test sequence see step 2.
LOCAL Alarm amber light 11-EL-527 is
OFF.

DCS alarm 11-XA-1029:- Bypass valve


11-XV-804 OPEN is OFF.

The DVC 6000 starts pre-programmed PST test.


DVC 6000 reduces the air supply to HIPPS Valve
actuator and thus triggers the valve to 90%
OPEN position%.
DCS point PST Request 11-HL-839
SOV Panel: green light 11- ZLH-1002A
ESDV OPEN goes OFF for the duration
of PST
SOV Panel: solenoid status green lights

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 13 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response
11-EL-521A/B/C/D are ON.

Notes:
1) If the valve travel takes longer
than initial valve signature time, the
Operator shall take actions
described in Operation manual.

Local Alarm light EL-527 is OFF.


Discrepancy alarm 11-XA-1001 is initiated.
After PST complete SOV Panel: green
light 11- ZLH-1002A ESDV OPEN goes
ON.

2) During PST, if a trip condition


occurs HIPPS LS will abandon PST
and initiate trip of the HIPPS.

Heater
Charge
Pumps 11G-02A/B/C
Trip Test
Pump 11-G-02A trip test

5.1

5.2

Full pump trip testing shall be performed annually

Ensure that two operating pumps are


running and one on standby for
example 11-G-02A/B are running
and 11-G-02C on standby.

Indication lights 11-EL-516A, 11-EL-517A


are ON and 11-EL-518A is OFF on
HIPPS Cabinet in SIH-5

Manually turn on standby pump 11G-02C

Indication light on HIPPS Cabinet 11-EL518A is ON

DCS indications 11-EL-516, 11-EL-517 are


ON and 11-EL-518 is OFF

DCS indications 11-EL-518 is ON.

5.3

11900003-000-IC-PRO-0001_r0

Turn Test Enable switch 11-HS852 in HIPPS Cabinet

Test Enable lamp XL-1042 turns ON


indicating that pump trip push buttons
enabled.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 14 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

5.4

Operator Action
Place pumps 11-G-02B and 11-G02C on bypass by turning bypass
switches 11-HS-831B and 11-HS831C

Observation/Logic Response
DCS points Pump Bypass 11-HL-831B
and 11-HL-831C
Make sure that the pumps 11-G-02B, 11G-02C are running by observing the
Pump Run lights 11-EL-517A,and 11EL-518A on HIPPS cabinet.

5.5

Press Trip push button 11-HS-820


for tested pump 11-G-02A

Pump
Stop
light
11-EL-516B
illuminated on HIPPS cabinet

5.6

After test completed restart pump


11-G-02A manually from Local pump
Station and place it on Autostart

Pump Run light 11-EL-516A goes ON

5.7

Manually turn OFF standby pump


11-G-02C

Pump Run Indication light on HIPPS


Cabinet 11-EL-518A is OFF

is

DCS Pump Run indications 11-EL-518 is


OFF.
NOTE:
The same procedure is repeated to
test trip for pumps 11-G-02B and 11G-02C.

Heater
Charge
Pumps 11G-02A/B/C
Interposing
Relays
Test
Pump 11-G-02A interposing relays
test

6.1

11900003-000-IC-PRO-0001_r0

Ensure that two operating pumps are


running and one on standby for

Online testing of the interposing relays shall be


performed every 3 months
Indication lights 11-EL-516A, 11-EL-517A

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 15 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

example 11-G-02A/B are running


and 11-G-02C on standby.

are ON and 11-EL-518A is OFF on


HIPPS Cabinet in SIH-5
DCS indications 11-EL-516, 11-EL-517 are
ON and 11-EL-518 is OFF
.

6.2

Place pumps 11-G-02A on bypass


by turning bypass switch 11-HS831A

DCS points Pump Bypass 11-HL-831A

Make sure that the pumps 11-G-02A, 11G-02B are running by observing the
Pump Run lights 11-EL-516A,and 11EL-517A in HIPPS cabinet.

6.3

Press Trip push button 11-HS-820


for tested pump 11-G-02A

Pump /Relay Trip light 11-EL-820 on


HIPPS cabinet is illuminated (note 1)
Pump /Relay Trip alarm 11-XA-1057A is
OFF in DCS (note 1)

6.4

After test completed return bypass


switch 11-HS-831A to normal and
make sure that pump 11-G-02A is
running

Pump Run light 11-EL-516A is ON.


NOTE:
1. If lamp 11-EL-820 does not turn ON, and
Pump /Relay Trip alarm 11-XA-1057A is
ON it indicates a problem with relays and
requires Operator further investigation.

NOTE: The same procedure is


repeated to test interposing relays
for pumps 11-G-02B and 11-G-02C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 16 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

Pressure
Transmitters
11-PT1230A/B/C
Functional
Test

7.1

Place transmitter PT-1230A on


bypass by turning bypass switch 11HS_P-1230A in SIH-5 SIS cabinet.

SIS cabinet Transmitter in Bypass light


11-XL_P-1230A is ON.
DCS Transmitter in Bypass alarm 11HA_P-1230A is ON.
Common bypass P1 alarm 11-XA-1025A
is activated

7.2

Close transmitter root valve and


tubing instrumentation valves.

DCS indicating point 11-PI-1230A goes to


minimum pressure.

7.3

Provide
standard
pressure
transmitter
maintenance
and
calibration as per Supplier Test and
Calibration procedure.

Use calibration equipment with known


pressure and Hand held communicator.

7.4

After test completed connect 11-PT1230A to process and turn off


bypass switch 11-HS_P-1230A.

Verify alarm trip points. DCS HiHi pressure


alarm 11-PAHH-1230 will be activated
SIS cabinet Transmitter in Bypass light
11-XL_P-1230A is OFF.
DCS Transmitter in Bypass alarm 11HA_P-1230A is OFF
DCS indicating point 11-PI-1230A
enabled.
Common bypass P1 alarm 11-XA-1025A
is OFF.

NOTE:
1) During bypassed Pressure
Transmitter Test, if a trip
condition occurs, HIPPS LS
11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 17 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

will initiate trip based on


measurements of the
remaining two transmitters.
HIPPS.
2) The same procedure is
repeated to test transmitters
11-PT-1230B and 11-PT1230C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 18 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

HIPPS BUTANE SPLITTER UNIT 064

The Operator actions and observations during HIPPS operation and testing.

STEP

See Appendix B: Butane Splitter Unit 64 P&IDs C0EF-011B1-002A; C0EF-064B1-004; C0EF-064B1-001;


Figure 1 SOV Panel 64-XV-1001 Layout; Figure 2 SOV Panel 64-XV-1002 Layout; Figure 3 Butane Splitter
HIPPS Cabinet Layout.

Operation
Task

Operator Action

Observation/Logic Response

1.1

Verify that Butane Splitter 64-C-01 overhead


pressure is less than 1210 kPa-g

1.2

Verify HIPPS Valve Skid components in


normal plant operation conditions:

HIPPS at
Normal
Operation.

HIPPS valves 64-XV-1001 and 64-XV1002 are OPEN


HIPPS bypass valves 64-XV-803, 64XV-804 are CLOSED
SOV Panel 64-XV-1001 solenoid status
lights

SOV Panel 64-XV-1002 solenoid status


lights.

DCS ButaneSplitter overhead


pressure 64-PI-1230A/B/C
(median signal).

SOV Panels: green lights 64ZLH-1001A and 64-ZLH1002A ESDV Open are ON
DCS alarms: 64-XA-1028 and
64-XA-1029 Bypass Valve
OPENED not activated.
SOV Panel: solenoid status
lights 64-EL-520A/B/C/D are
ON. Local Alarm light 64-EL526 is OFF.
SOV Panel: solenoid status
lights 64-EL-521A/B/C/D are
ON. Local Alarm light 64L527 is OFF.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 19 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

1.3

Operator Action
Verify all maintenance/bypass switches on
HIPPS cabinet in SIH-5 normalized

Observation/Logic Response
HIPPS Cabinet Bypass lights
64-XL-P-1230A/B/C are OFF.
DCS alarms 64-HA_P1230A/B/C are OFF.

1.4

Verify SOV panel bypass switch is in No


Bypass position

DCS alarms 64-XA-1048 and


64-XA-1050 Bypass Active
are not activated

1.5

Verify all P1 alarms are cleared

P1 Indication/alarm screen in
SIH 5: No alarms activated:

64-XA-1025A Common
bypass alarm

64-XA-1022 Deviation
alarm

64-XA-1023A Forced
logic alarm

64-XA-1029A 11-HV803/804 bypass valves


open

64-PAH-1230 Pre-S/D
pressure High alarm

64-XA-1031 Processor
fault alarm

SOV Panel
Solenoid
Functional
Test

2.1

The following selector switches de-energize


solenoids during SOV Panel 64-XV-1001 test:

The signal from 64-HS-xxx indicating


whether solenoid Failed sent to
HIPPS.

Hold selector switch 64-HS-843 in A


position and then release

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 20 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

Hold selector switch 64-HS-843 in B


position and then release

Light 64-EL-520A goes OFF


and then ON when switch 64HS-843 position A released

Hold selector switch 64-HS-847 in C


position and then release

Light 64-EL-520B goes OFF


and then ON when switch 64HS-843 position B released

Hold selector switch 64-HS-847 in D


position and then release

Light 64-EL-520C goes OFF


and then ON when switch 64HS-847C position A released
Light 64-EL-520D goes OFF
and then ON when switch 64HS-847 position D released
NOTE:
Solenoid status during the test
indicating whether solenoid Failed
sent to HIPPS LS and is duplicated in
DCS indication points: 11-HL-843A,
11-HL-843B, 11-HL-847C, 11-HL847D respectively.
2.2

The following selector switches de-energize


solenoids during SOV Panel XV-1002 test:
Hold selector switch 64-HS-844 in A
position and then release
Hold selector switch 64-HS-848 in B
position and then release

Hold selector t switch 64-HS-848 in C


position and then release
Hold selector switch 64-HS-848 in D

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Light 64-EL-521A goes OFF


and then ON when switch 64HS-844 position A released
Light 64-EL-521B goes OFF
and then ON when switch 64HS-844 position B released

Light 64-EL-521C goes OFF


and then ON when switch 64Page 21 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

position and then release

HS-848 position C released

Light 64-EL-521D goes OFF


and then ON when switch 64HS-848 position D released
NOTE:
Solenoid status during the test
indicating whether solenoid Failed
sent to HIPPS LS and is duplicated in
DCS indication points: 64-HL-843A,
64-HL-843B, 64-HL-843C, 64-HL843D respectively.

Full Stroke
Test (FST)
HIPPS Isolation Valve 64-XV-1001

3.1

Verify permissive to start FST:


Conduct SOV Panel Solenoid
Functional Test . .All four solenoids
shall pass functional test (for SOV
Panel solenoids 64-XY-1001A, B, C,
D functional test sequence see step
2).
Ensure that Local Alarm on SOV
Panel is OFF
Open HIPPS bypass valve 64-HV-803
across the HIPPS Isolation Valve 64XV-1001.

Local Alarm amber light 64EL-526 is OFF.


DCS point 64-XA-1028:Bypass Valve 64-HV-803
OPEN
P1 Alarm Bypass Valve Open
64-XA-1029A activated.

3.2

Start FST:

Turn hand switch 64-HS-837 FST Request


11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

After FST started the HIPPS LS deenergizes the solenoids in the


respective SOV panel and closes
HIPPS Isolation Valve.
Page 22 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
on SOV Panel. FST Request signal sent to
HIPPS Logic solver.

3.3

Verify that HIPPS Valve 64-XV-1001 is


closed

Observation/Logic Response
DCS light FST Request 64HL-837 activated
SOV Panel: green light 64ZLH-1001A ESDV OPEN
goes OFF
Red light 64-ZLL-1001A ESDV
CLOSED is ON.
SOV Panel: solenoid status
green lights 64-EL520A/B/C/D are OFF.
Local Alarm light 64-EL-526
is ON.
DCS discrepancy 64-XA-1001
alarm is OFF.

3.4

After FST complete Operator push and hold


Local Reset push button 64-HS-838.to
restore normal Valves operation.

Operator holds 64-HS-838 until


HIPPS Valve 64-XV-1001
opens.
SOV Panel: green light 64ZLH-1001A ESDV OPEN
goes ON.
NOTE:
Only one HIPPS valve at a time shall
be tested.

3.5

Close HIPPS bypass valve 64-HV-803 across


the HIPPS Isolation Valve 64-XV-1001.

DCS alarm 64-XA-1028:Bypass valve 64-HV-803


OPEN is OFF.
P1 Alarm Bypass Valve Open
11-XA-1029A is OFF (returns
to normal).

HIPPS Isolation Valve 64-XV-1002


3.6
11900003-000-IC-PRO-0001_r0

Verify permissive to start FST:


SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 23 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

Conduct SOV Panel Solenoid


Functional Test ..All four solenoids
shall pass functional test (for SOV
Panel solenoids 64-XY-1002A, B, C,
D functional test sequence see step
2).
Ensure that Local Alarm on SOV
Panel is OFF
Open HIPPS bypass valve
64-HV-804 across the HIPPS
Isolation Valve 64-XV-1002

Local Alarm amber light 64EL-527 is OFF.


DCS point 11-XA-1028:Bypass valve 64-HV-804
OPEN.
P1 Alarm Bypass Valve Open
64-XA-1029A activated.

3.7

Start FST:

Turn hand switch 64-HS-840 FST Request


on SOV Panel. FST Request signal sent to
HIPPS Logic solver.

3.8

Verify that HIPPS Valve 64-XV-1002 is closed

After FST started the HIPPS LS deenergizes the solenoids in the


respective SOV panel and closes
HIPPS Isolation Valve.
DCS light FST Request 64HL-840 activated.
SOV Panel: green light 64ZLH-1002A ESDV OPEN
goes OFF
Red light 64-ZLL-1002A ESDV
CLOSED is ON.
SOV Panel: solenoid status
green lights 64-EL521A/B/C/D are OFF.
Local Alarm light 64-EL-527 is
ON.
DCS discrepancy 64-XA-1001

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 24 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response
alarm is OFF.

3.9

After FST complete Operator pushes and


holds Local Reset push button 64-HS-841.to
restore normal Valves operation.

Operator holds 64-HS-841


Local Reset until HIPPS
Valve64-XV-1002 opens.
SOV Panel: green light 64ZLH-1002A ESDV OPEN
goes ON.
NOTE:
Only one HIPPS valve at a time shall
be tested.

3.10

Close HIPPS bypass valve 64-HV-804 across


the HIPPS Isolation Valve 64-XV-1002.

DCS alarm 64-XA-1029:Bypass valve 64-HV-804


OPEN is OFF.
P1 Alarm Bypass Valve Open
64-XA-1029A is OFF (returns
to normal).

Partial
Stroke Test
(PST)
HIPPS Isolation Valve 64-XV-1001

4.1

Verify permissive to start PST


Operator conducts SOV Panel Solenoid
Functional Test. .All four solenoids
shall pass functional test.
Operator ensure that Local Alarm on
SOV Panel is OFF
Operator ensures that HIPPS bypass
valve 64-HV-803 across the HIPPS
Isolation Valve 64-XV-1001 is
CLOSED.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

For SOV Panel solenoids 64XY-1001A, B, C, D functional


test sequence see step 2.
LOCAL Alarm amber light 64EL-526 is OFF.
DCS alarm 64-XA-1028:Bypass valve 64-HV-803.is
OFF.

Page 25 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

4.2

Operator Action

Observation/Logic Response

Starts PST:

The DVC 6000SIS starts preprogrammed PST test. DVC 6000


reduces the air supply to HIPPS
Valve actuator and thus triggers the
valve to 90% OPEN position.

Turn hand switch 64-HS-839 PST Request


on SOV Panel.

DCS point PST Request 11HL-836 is ON.


4.3

Verify that HIPPS Valve 64-XV-1001 is


traveling to 90% open position

NOTES:
1) If the valve travel takes longer than initial
valve signature time, the Operator shall take
actions described in Operation manual.
2) During PST, if a trip condition occurs
HIPPS LS will abandon PST and initiate trip of
the HIPPS.

SOV Panel: green light 64ZLH-1001A ESDV OPEN


goes OFF for the duration of
PST
SOV Panel: solenoid status
green lights 64-EL520A/B/C/D are ON.
Local Alarm light 64E-L-526
is OFF.

Deviation DCS alarm 64-XA1001 is initiated.

After PST complete SOV


Panel: green light 64- ZLH1001A ESDV OPEN goes
ON.

HIPPS Isolation Valve 64-XV-1002


4.4

Verify permissive to start PST


Operator conducts SOV Panel Solenoid
Functional Test . .All four solenoids
shall pass functional test.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

For SOV Panel solenoids 64XY-1002A, B, C, D functional


test sequence see step 2.
Page 26 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Operator ensures that Local Alarm on
SOV Panel is OFF
Operator ensures that HIPPS bypass
valve 11-HV-804 across the HIPPS
Isolation Valve 64-XV-1002 is
CLOSED.

4.5

Start PST:

Turn hand switch 64-HS-839 PST


Request on SOV Panel.

Observation/Logic Response
LOCAL Alarm amber light 64EL-527 is OFF.

DCS alarm 11-XA-1029:Bypass valve 64-XV-804


OPEN is OFF.
The DVC 6000 starts preprogrammed PST test. DVC 6000
reduces the air supply to HIPPS
Valve actuator and thus triggers the
valve to 90% OPEN position%.
DCS point PST Request 64HL-839

4.6

Verify that HIPPS Valve 11-XV-1002 is


traveling to 90% open position

Notes:
1) If the valve travel takes longer than initial
valve signature time, the Operator shall take
actions described in Operation manual.
2) During PST, if a trip condition occurs
HIPPS LS will abandon PST and initiate trip of
the HIPPS.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

SOV Panel: green light 64ZLH-1002A ESDV OPEN


goes OFF for the duration of
PST
SOV Panel: solenoid status
green lights 11-EL521A/B/C/D are ON.
Local Alarm light 64-EL-527
is OFF.
Discrepancy alarm 64-XA-1001
is initiated.
After PST complete SOV
Panel: green light 64- ZLH1002A ESDV OPEN goes
ON.

Page 27 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

Pressure
Transmitters
PT1230A/B/C
Functional
Test

5.1

Place transmitter 64-PT-1230A on bypass by


turning bypass switch 64-HS_P-1230A in SIH5 SIS cabinet.

SIS cabinet Transmitter in


Bypass light 64-XL_P-1230A
is ON.
DCS Transmitter in Bypass
alarm 64-HA_P-1230A is ON.
Common bypass P1 alarm 64XA-1025A is activated

5.2

Close transmitter root valve and tubing


instrumentation valves.

DCS indicating point 64-PI1230A goes to minimum


pressure.

5.3

Provide
standard
pressure
transmitter
maintenance and calibration as per Supplier
Test and Calibration procedure.

Use calibration equipment with


known pressure and Hand
held communicator.
Verify alarm trip points. DCS
HiHi pressure alarm 64PAHH-1230 will be activated

5.4

After test completed re-connect 64-PT-1230A


to process and turn off bypass switch 64HS_P-1230A.

SIS cabinet Transmitter in


Bypass light 64-XL_P-1230A
is OFF.
DCS Transmitter in Bypass
alarm 64-HA_P-1230A is
OFF
DCS indicating point 64-PI1230A enabled.
Common bypass P1 alarm 64XA-1025A is OFF.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 28 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
NOTE:

Observation/Logic Response

1) During bypassed Pressure Transmitter


Test, if a trip condition occurs, HIPPS LS will
initiate trip based on measurements of the
remaining two transmitters. HIPPS.
2) The same procedure is repeated to test
transmitters 64-PT-1230B and PT-1230C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 29 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

MARINE HEAVY FUEL OIL (MHFO) UNIT 11

The Operator actions and observations during HIPPS operation and testing.

STEP

For reference see Appendix C: MHFO Unit 11 P&IDs C0EF-011B1-017; Figure 1 MHFO HIPPS Cabinet Layout.

Operation
Task

Operator Action

Observation/Logic Response

Verify that the pressure


downstream of the MHFO
Booster Pumps 11-G-21A/B is
less than HI-HI set point (30
bar-g)

HIPPS at
Normal
Operation.

1.1

1.2

Verify HIPPS Valve Skid


components in normal plant
operation conditions:

1.3

Ensure that one pumps is


running and one on standby, for
example, 11-G-21A is running
and 11-G-21B on standby.

1.4

Verify all maintenance/bypass


switches on HIPPS cabinet in
SIH-5 normalized

1.5

Verify all P1 alarms are cleared

11900003-000-IC-PRO-0001_r0

DCS indication Pressuredownstreamofthe


MHFOBoosterPumps11G21A/B 11-PI1224A/B./C (median signal).

Indication lights 11-EL-512A2 is ON and 11EL-513A2 is OFF on HIPPS Cabinet in SIH5

Bypass lights XL-P-1224A/B/C are OFF.

P1 Indication/alarm screen in SIH 5: No


alarms activated:
-

11-HA-812 Common bypass alarm

11-XA-1000 Deviation alarm

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 30 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response
-

11-PAH-1224 Pre-S/D pressure High


alarm

11-XA-1017 Processor fault alarm

11-HA-823 Switch bypass alarm

MHFO
Booster
Pumps 11G-21A/B
Trip Test
Pump 11-G-21A trip test

Full pump trip testing shall be performed annually

21

Ensure that one operating


pump is running and one on
standby for example 11-G-21A
is running and 11-G-21B on
standby.

Indication lights 11-EL-512A2 is ON and 11EL-513A2 is OFF on HIPPS Cabinet in SIH5

2.2

Manually turn on standby pump


11-G-21B

Indication light on HIPPS Cabinet 11-EL513A2 is ON


DCS indications 11-EL-518 is ON.

2.3

Turn Test Enable switch 11HS-853 in HIPPS Cabinet

Test Enable lamp XL-1043 turns ON


indicating that pump trip push buttons
enabled.

2.4

Place pumps 11-G-21B on


bypass by turning bypass
switches 11-HS-823B

Make sure that the pumps 11-G-21A, and 11G-21B are running by observing the Pump
Run lights 11-EL-512A2,and 11-EL-513A2
on HIPPS cabinet.

2.5

Press Trip push button 11-HS512B2 for tested pump 11-G21A

Pump Stop light 11-EL-512B2 is illuminated


on HIPPS cabinet

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 31 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

2.6

After test completed restart


pump 11-G-21A manually from
Local pump Station and place it
on Autostart

Pump Run light 11-EL-512A2 goes ON

2.7

Manually turn OFF standby


pump 11-G-21B.

Pump Run Indication light on HIPPS


Cabinet 11-EL-513A2 is OFF

NOTE:
The same procedure is
repeated to test trip for pumps
11-G-21B.

Booster
MHFO
pumps 11G-021A/B
Interposing
Relays
Test
Pump 11-G-21A interposing
relays test

3.1
Ensure that one pump is
running and one on standby for
example 11-G-21A is running
and 11-G-21B is on standby.

Online testing of the interposing relays shall be


performed every 3 months
Indication lights 11-EL-512A2 is ON and 11EL-513A2 is OFF on HIPPS Cabinet in SIH5

3.2

Place pumps 11-G-21A on


bypass by turning bypass
switch 11-HS-823A

Make sure that the pumps 11-G-21A is


running by observing the Pump Run lights
11-EL-512A2 in HIPPS cabinet.

3.3

Press Pump/RelayTrip push


button 11-HS-813D for tested
pump 11-G-21A

Pump /Relay Trip light 11-HA-813D is


illuminated (note 1)

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 32 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

3.4

Operator Action

After test completed return


bypass switch 11-HS-823A to
normal and make sure that
pump 11-G-21A is running

Observation/Logic Response

Pump Run light 11-EL-512A2 is ON.


NOTE:
1

If lamp 11-HA-813D does not turn ON, it


indicates a problem with relays and
requires Operator further investigation.

NOTE: The same procedure is


repeated to test interposing
relays for pumps 11-G-21B.

Pressure
Transmitters
PT1224A/B/C
Functional
Test

4.1

Place transmitter PT-1224A on


bypass by turning bypass
switch 11-HS_P-1224A in SIH5 SIS cabinet.

SIS cabinet Transmitter in Bypass light 11XL_P-1224A is ON.


DCS Transmitter in Bypass alarm 11-HA_P1224A is ON.
Common bypass P1 alarm 11-HA-812 is
activated

4.2

Close transmitter root valve and


tubing instrumentation valves.

DCS indicating point 11-PI-1224A goes to


minimum pressure.

4.3

Provide
standard
pressure
transmitter maintenance and
calibration as per Supplier Test
and Calibration procedure.

Use calibration equipment with known


pressure and Hand held communicator.

11900003-000-IC-PRO-0001_r0

Verify alarm trip points. DCS HiHi pressure


alarm 11-PAHH-1224 will be activated

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 33 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

4.4

Operator Action
After test completed re-connect
11-PT-1224A to process and
turn off bypass switch 11HS_P-1224A.

Observation/Logic Response
HIPPS cabinet Transmitter in Bypass light
11-XL_P-1224A is OFF.
DCS Transmitter in Bypass alarm 11-HA_P1224A is OFF
DCS indication 11-PI-1224A enabled.
Common bypass P1 alarm 11-HA-812 is
OFF.

NOTE:

1. During Pressure
Transmitter bypass, if a trip
condition occurs, HIPPS LS
will initiate trip based on
measurements of the
remaining two transmitters.
HIPPS.
2. The same procedure is
repeated
to
test
transmitters PT-1224B and
PT-1224C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 34 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

CATALYTIC HYDRO DESULPHURIZER (CHD) UNIT 032

5.1 TRAIN 1
The Operator actions and observations during HIPPS operation and testing.

STEP

For reference see Appendix D: CHD Unit 32 P&IDs C0EF-032B1-003D-E; Figure 1 SOV Panel 32-XV-1000
Layout; Figure 2 SOV Panel 32-XV-1001 Layout; Figure 3 CHD HIPPS Cabinet Layout.

Operation
Task

Operator Action

Observation/Logic Response

1.1

Verify that the Reactor Effluent


pressure downstream of the
HIPPS is less than HI HI set
point 38.9 bar-g.

1.2

Verify HIPPS components in


normal plant operation
conditions:

HIPPS at
Normal
Operation.

HIPPS valves 32-XV-1000


and 32-XV-1001 are OPEN
HIPPS bypass valves 32XV-935, 32-XV-937 are
CLOSED
SOV Panel 32-XV-1000
solenoid status lights

SOV Panel 32V-1001


solenoid status lights.

1.3

11900003-000-IC-PRO-0001_r0

Verify all maintenance/bypass


switches on HIPPS cabinet in

DCS Atmospheric tower overhead pressure 32PI-1251A/B/C (median signal).

SOV Panels: green lights 32- ZLH-1000A and


32-ZLH-1001A ESDV Open are ON
DCS indications: 32-ZLL-1005A and 32-ZLL1007A Bypass Valve Closed is ON.
SOV Panel: solenoid status lights 11-EL651A/B/C/D are ON. Local Alarm light 32-EL526 is OFF.
SOV Panel: solenoid status lights EL652A/B/C/D are ON. Local Alarm light EL527 is OFF.

Bypass lights 32-XL-P-12510A/B/C are OFF.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 35 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
SIH-5 normalized

Observation/Logic Response
DCS alarms 32-HA_P-1251A/B/C are OFF.

1.4

Verify P1 alarm Bypass valve


open is OFF.

32-XA-1295 is OFF.

1.5

Verify SOV panel bypass switch


is in No Bypass position

SOV Bypass Active LED light inside SOV


Panel is OFF.

1.6

Verify all P1 alarms are cleared

P1 Indication/alarm screen in SIH 5: No alarms


activated:

32-XA-1251A Common bypass alarm

32-XA-1046 Deviation alarm

32-XA-1278 Forced logic alarm

32-XA-1295 32-HV-935/937 bypass


valves open

32-XA-1037 Processor fault alarm

SOV Panel
Solenoid
Functional
Test

2.1

The following selector switches


de-energize solenoids during
SOV Panel XV-1000 test:
Hold selector switch 32HS-935FA/FB in FA
position and then
release
Hold selector switch 32HS-935FA/FB in FB
position and then
release

11900003-000-IC-PRO-0001_r0

The signal from 32-HS-xxx indicating whether


solenoid Failed sent to HIPPS.

Light 32-EL-651A goes OFF and then ON


when switch 32-HS-935FA/FB position FA
released
Light 32-EL-651B goes OFF and then ON
when switch 32-HS-935FA/FB position FB
released

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 36 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

2.2

Operator Action
Hold selector switch 32HS-935FC/FD in FC
position and then
release

Light 32-EL-651C goes OFF and then ON


when switch 32-HS-935FA/FB position FC
released

Hold selector switch 32HS-935FC/FD in FD


position and then
release

Light 32-EL-651D goes OFF and then ON


when switch 32-HS-935FA/FB position FD
released

The following selector switches


de-energize solenoids during
SOV Panel 32-XV-1001 test:
Hold selector switch 32HS-937FA/FB in FA
position and then
release
Hold selector switch 32HS-937FA/FB in FB
position and then
release

Observation/Logic Response

Light 32-EL-652A goes OFF and then ON


when switch 32-HS-937FA/FB position FA
released
Light 32-EL-652B goes OFF and then ON
when switch 32-HS-937FA/FB position FB
released

Hold selector switch 32HS-937FC/FD in FC


position and then
release.

Light 32-EL-652C goes OFF and then ON


when switch 32-HS-937FA/FB position FC
released

Hold selector switch 32HS-937FC/FD in FD


position and then
release.

Light 32-EL-652D goes OFF and then ON


when switch 32-HS-937FA/FB position FD
released:

Full Stroke
Test (FST)

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 37 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

3.1

Operator Action

Observation/Logic Response

HIPPS Isolation Valve 32-XV1000


Verify permissive to start FST:
Conduct SOV Panel
Solenoid Functional
Test . .All four
solenoids shall pass
functional test (for
SOV Panel solenoids
XY-1000A, B, C, D
functional test
sequence see step 2).
Ensure that Local Alarm
on SOV Panel is OFF
Open HIPPS bypass
valve 32-HV-935
across the HIPPS
Isolation Valve 32-XV1000.

3.2

Start FST:

Turn hand switch 32-HS-935A


FST Request on SOV Panel.
FST Request signal sent to
HIPPS Logic solver.
3.3

Verify that HIPPS Valve 32XV-1000 is closed

Local Alarm amber light 32-EL-526 is OFF.


DCS point 32-ZLL1005A - Bypass Valve 32HV-935 CLOSED is not initiated.
P1 Alarm Bypass Valve Open 32-XA-1295
activated.

After FST started the HIPPS LS de-energizes the


solenoids in the respective SOV panel and closes
HIPPS Isolation Valve.
DCS light FST Request 32-HL-xxx activated

SOV Panel: green light 32- ZLH-1005 ESDV


OPEN goes OFF
SOV Panel red light 32-ZLL-1005 ESDV
CLOSED is ON.
SOV Panel: solenoid status green lights 32EL-651A/B/C/D are OFF.
Local Alarm light 32-EL-526 is ON.
DCS discrepancy 32-XA-xxx alarm is off.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 38 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

3.4

Operator Action
After FST complete Operator
push and hold Local Reset
push button 32-HS-935B.to
restore normal Valves
operation.

Observation/Logic Response
Operator holds 32-HS-935B until HIPPS Valve
32-XV-1000 opens.
SOV Panel: green light 32- ZLH-1005 ESDV
OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.5

3.6

Close HIPPS bypass valve 32HV-935 across the HIPPS


Isolation Valve 32-XV-1000.

DCS indication 32-ZLL-1005A:- Bypass valve


32-HV-935 CLOSED is ON.
P1 Alarm Bypass Valve Open 11-XA-1295A
is OFF (returns to normal).

HIPPS Isolation Valve 32-XV1001


Verify permissive to start FST:
Conduct SOV Panel
Solenoid Functional
Test . .All four
solenoids shall pass
functional test (for
SOV Panel solenoids
32-XY-1000A, B, C, D
functional test
sequence see step 2).
Ensure that Local Alarm
on SOV Panel is OFF
Open HIPPS bypass
valve 32-HV-937
across the HIPPS
Isolation Valve 32-XV1001.

3.7

Start FST:

Local Alarm amber light 32-EL-527 is OFF.


DCS point 32-ZLL1007A - Bypass Valve 32HV-937 CLOSED is not initiated.
P1 Alarm Bypass Valve Open 32-XA-1295
activated.

After FST started the HIPPS LS de-energizes the


solenoids in the respective SOV panel and closes
HIPPS Isolation Valve.

Turn hand switch 32-HS-937A

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 39 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

3.8

Operator Action

Observation/Logic Response

FST Request on SOV Panel.


FST Request signal sent to
HIPPS Logic solver.

DCS light FST Request 32-HL-xxx activated

Verify that HIPPS Valve 32XV-1001 is closed

SOV Panel: green light 32- ZLH-1007 ESDV


OPEN goes OFF
SOV Panel red light 32-ZLL-1007 ESDV
CLOSED is ON.
SOV Panel: solenoid status green lights 32EL-652A/B/C/D are OFF.
Local Alarm light 32-EL-527 is ON.
DCS discrepancy 32-XA-xxx alarm is off.

3.9

After FST complete Operator


push and hold Local Reset
push button 32-HS-937B.to
restore normal Valves
operation.

Operator holds 32-HS-935B until HIPPS Valve


32-XV-1001 opens.
SOV Panel: green light 32- ZLH-1007 ESDV
OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.10

Close HIPPS bypass valve 32HV-937 across the HIPPS


Isolation Valve 32-XV-1001.

DCS indication 32-ZLL-1005A:- Bypass valve


32-HV-935 CLOSED is ON.
P1 Alarm Bypass Valve Open 11-XA-1295 is
OFF (returns to normal).

Partial
Stroke Test
(PST)

4.1

HIPPS Isolation Valve 32-XV1000 (PST)


Verify permissive to start PST
Operator conducts SOV
Panel Solenoid
Functional Test . .All
four solenoids shall

11900003-000-IC-PRO-0001_r0

For SOV Panel solenoids 32-XY-1000A, B, C,


D functional test sequence see step 2.
LOCAL Alarm amber light 32-EL-526 is OFF.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 40 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

pass functional test.


Operator ensure that
Local Alarm on SOV
Panel is OFF
Operator ensures that
HIPPS bypass valve
32-HV-1005A across
the HIPPS Isolation
Valve 32-XV-1000 is
CLOSED.

4.2

Starts PST:

Turn hand switch 32-HS-935E


PST Request on SOV Panel.
4.3

Verify that HIPPS Valve 32-XV1000 is traveling to 90% open


position

DCS point 32-ZLL1005A - Bypass Valve 32HV-935 CLOSED is initiated.


P1 Alarm Bypass Valve Open 32-XA-1295 is
not activated.

The DVC 6000SIS starts pre-programmed PST test.


DVC 6000 reduces the air supply to HIPPS Valve
actuator and thus triggers the valve to 90% OPEN
position.

DCS point PST Request 32-HL-xxx is ON.


SOV Panel: green light 32- ZLH-1005 ESDV
OPEN goes OFF for the duration of PST
SOV Panel: solenoid status green lights 11EL-651A/B/C/D are ON.
Local Alarm light 32-EL-526 is OFF.

NOTES:

Discrepancy alarm 32-XA-xxx is initiated.

1) If the valve travel takes


longer than initial valve
signature time, the Operator
shall take actions described in
Operation manual.

After PST complete SOV Panel: green light 32ZLH-1005 ESDV OPEN goes ON.

2) During PST, if a trip condition


occurs HIPPS LS will abandon
PST and initiate trip of the
HIPPS.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 41 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

4.4

Operator Action

Observation/Logic Response

HIPPS Isolation Valve 32-XV1001 (PST)


Verify permissive to start PST

4.5

Operator conducts SOV


Panel Solenoid
Functional Test . .All
four solenoids shall
pass functional test.

For SOV Panel solenoids 32-XY-1001A, B, C,


D functional test sequence see step 2.

Operator ensure that


Local Alarm on SOV
Panel is OFF

DCS point 32-ZLL1007A - Bypass Valve 32HV-937 CLOSED is initiated.

Operator ensures that


HIPPS bypass valve
32-HV-1005A across
the HIPPS Isolation
Valve 32-XV-1000 is
CLOSED.

P1 Alarm Bypass Valve Open 32-XA-1295 is


not activated

Starts PST:

Turn hand switch 32-HS-937E


PST Request on SOV Panel.
4.6

Verify that HIPPS Valve 32-XV1001 is traveling to 90% open


position
NOTES:
1) If the valve travel takes
longer than initial valve
signature time, the Operator
shall take actions described in
Operation manual.

11900003-000-IC-PRO-0001_r0

LOCAL Alarm amber light 32-EL-527 is OFF.

The DVC 6000SIS starts pre-programmed PST test.


DVC 6000 reduces the air supply to HIPPS Valve
actuator and thus triggers the valve to 90% OPEN
position.
DCS point PST Request 32-HL-xxx is ON.
SOV Panel: green light 32- ZLH-1007 ESDV
OPEN goes OFF for the duration of PST
SOV Panel: solenoid status green lights 11EL-652A/B/C/D are ON.
Local Alarm light 32-EL-527 is OFF.
Discrepancy alarm 32-XA-xxx is initiated.

After PST complete SOV Panel: green light 32-

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 42 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
2) During PST, if a trip condition
occurs HIPPS LS will abandon
PST and initiate trip of the
HIPPS.

Observation/Logic Response
ZLH-1007 ESDV OPEN goes ON.

Pressure
Transmitters
PT1251A/B/C
Functional
Test

5.1

Place transmitter 32-PT-1251A


on bypass by turning bypass
switch 32-HS_P-1230A in SIH5 SIS cabinet.

SIS cabinet Transmitter in Bypass light 32XL_P-1251A is ON.


DCS Transmitter in Bypass alarm 32-HA_P1251A is ON.
Common bypass P1 alarm 32-XA-1025A is
activated

5.2

Close transmitter root valve and


tubing instrumentation valves.

DCS indicating point 32-PI-1251A goes to


minimum pressure.

5.3

Provide
standard
pressure
transmitter maintenance and
calibration as per Supplier Test
and Calibration procedure.

Use calibration equipment with known


pressure and Hand held communicator.

After test completed re-connect


32-PT-1251A to process and
turn off bypass switch 32HS_P-1251A.

SIS cabinet Transmitter in Bypass light 32XL_P-1251A is OFF.

5.4

Verify alarm trip points. DCS HiHi pressure


alarm 32-PAHH-1251A will be activated

DCS Transmitter in Bypass alarm 32-HA_P1251A is OFF


DCS indicating point 32-PI-1251A enabled.
Common bypass P1 alarm 32-XA-1251A is
OFF.

NOTE:

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 43 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

1. During bypassed
Pressure Transmitter
Test, if a trip condition
occurs, HIPPS LS will
initiate trip based on
measurements of the
remaining two
transmitters. HIPPS.
2. The same procedure is
repeated to test
transmitters 32-PT1251B and 32-PT1251C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 44 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

5.2 TRAIN 2
The Operator actions and observations during HIPPS operation and testing.

STEP

See Appendix D: CHD Unit 32 P&IDs C0EF-032B1-003D-E; Figure 1 SOV Panel 32-XV-1003 Layout; Figure 2
SOV Panel 32-XV-1004 Layout; Figure 3 CHD HIPPS Cabinet Layout.

Operation
Task

Operator Action

Observation/Logic Response

1.1

Verify that the Reactor Effluent


pressure downstream of the
HIPPS is less than HI HI set
point 38.9 bar-g.

1.2

Verify HIPPS components in


normal plant operation
conditions:

HIPPS at
Normal
Operation.

HIPPS valves 32-XV-1003


and 32-XV-1004 are OPEN
HIPPS bypass valves 32XV-942, 32-XV-944 are
CLOSED
SOV Panel 32-XV-1003
solenoid status lights

SOV Panel 32-XV-1004


solenoid status lights.
1.3

11900003-000-IC-PRO-0001_r0

Verify all maintenance/bypass


switches on HIPPS cabinet in
SIH-5 normalized

DCS Atmospheric tower overhead pressure 32PI-1255A/B/C (median signal).

SOV Panels: green lights 32- ZLH-1012 and


32-ZLH-1014A ESDV Open are ON
DCS indications: 32-ZLL-1012A and 32-ZLL1014A Bypass Valve Closed is ON.
SOV Panel: solenoid status lights 11-EL653A/B/C/D are ON. Local Alarm light 32-EL528 is OFF.
SOV Panel: solenoid status lights 32-EL654A/B/C/D are ON. Local Alarm light 32-EL529 is OFF.

Bypass lights 32-XL-P-1255A/B/C are OFF.


DCS alarms 32-HA_P-1255A/B/C are OFF.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 45 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

1.4

Verify P1 alarm Bypass valve


open is OFF.

32-XA-1298 is OFF.

1.5

Verify SOV panel bypass switch


is in No Bypass position

SOV Bypass Active LED light inside SOV


Panel is OFF.

1.6

Verify all P1 alarms are cleared

P1 Indication/alarm screen in SIH 5: No alarms


activated:

32-XA-1255A Common bypass alarm

32-XA-1047 Deviation alarm

32-XA-1278 Forced logic alarm

32-XA-1298 32-HV-942/944 bypass


valves open

32-XA-1037 Processor fault alarm

SOV Panel
Solenoid
Functional
Test

2.1

The following selector switches


de-energize solenoids during
SOV Panel 32-XV-1004 test:
Hold selector switch 32HS-942FA/FB in FA
position and then
release

11900003-000-IC-PRO-0001_r0

The signal from 32-HS-xxx indicating whether


solenoid Failed sent to HIPPS.

Light 32-EL-653A goes OFF and then ON


when switch 32-HS-942FA/FB position FA
released

Hold selector switch 32HS-942FA/FB in FB


position and then
release

Light 32-EL-653B goes OFF and then ON


when switch 32-HS-942FA/FB position FB
released

Hold selector switch 32HS-942FC/FD in FC

Light 32-EL-653C goes OFF and then ON

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 46 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
position and then
release
Hold selector switch 32HS-942FC/FD in FD
position and then
release

2.2

when switch 32-HS-942FA/FB position FC


released

Light 32-EL-653D goes OFF and then ON


when switch 32-HS-942FA/FB position FD
released

The following selector switches


de-energize solenoids during
SOV Panel 32-XV-1004 test:
Hold selector switch 32HS-944FA/FB in FA
position and then
release
Hold selector switch 32HS-944FA/FB in FB
position and then
release

Observation/Logic Response

Light 32-EL-654A goes OFF and then ON


when switch 32-HS-944FA/FB position FA
released
Light 32-EL-654B goes OFF and then ON
when switch 32-HS-944FA/FB position FB
released

Hold selector switch 32HS-944FC/FD in FC


position and then
release.

Light 32-EL-654C goes OFF and then ON


when switch 32-HS-944FA/FB position FC
released

Hold selector switch 32HS-944FC/FD in FD


position and then
release.

Light 32-EL-654D goes OFF and then ON


when switch 32-HS-937FA/FB position FD
released:

Full Stroke
Test (FST)

3.1

HIPPS Isolation Valve 32-XV1003 (FST)


Verify permissive to start FST:

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 47 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Conduct SOV Panel
Solenoid Functional
Test . .All four
solenoids shall pass
functional test (for
SOV Panel solenoids
XY-10003A, B, C, D
functional test
sequence see step 2).
Ensure that Local Alarm
on SOV Panel is OFF
Open HIPPS bypass
valve 32-HV-942
across the HIPPS
Isolation Valve 32-XV1003.

3.2

Start FST:

Turn hand switch 32-HS-942A


FST Request on SOV Panel.
FST Request signal sent to
HIPPS Logic solver.
3.3

Verify that HIPPS Valve 32XV-1003 is closed

Observation/Logic Response

Local Alarm amber light 32-EL-528 is OFF.


DCS point 32-ZLL1012A - Bypass Valve 32HV-942 CLOSED is not initiated.
P1 Alarm Bypass Valve Open 32-XA-1298
activated.

After FST started the HIPPS LS de-energizes the


solenoids in the respective SOV panel and closes
HIPPS Isolation Valve.
DCS light FST Request 32-HL-xxx activated

SOV Panel: green light 32- ZLH-1012 ESDV


OPEN goes OFF
SOV Panel red light 32-ZLL-1012 ESDV
CLOSED is ON.
SOV Panel: solenoid status green lights 32EL-653A/B/C/D are OFF.
Local Alarm light 32-EL-528 is ON.
DCS discrepancy 32-XA-xxx alarm is off.

3.4

11900003-000-IC-PRO-0001_r0

After FST complete Operator


push and hold Local Reset
push button 32-HS-942B.to

Operator holds 32-HS-942B until HIPPS Valve


32-XV-1003 opens.
SOV Panel: green light 32- ZLH-1012 ESDV

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 48 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
restore normal Valves
operation.

Observation/Logic Response
OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.5

3.6

Close HIPPS bypass valve 32HV-942 across the HIPPS


Isolation Valve 32-XV-1003.

DCS indication 32-ZLL-1012A:- Bypass valve


32-HV-942 CLOSED is ON.
P1 Alarm Bypass Valve Open 11-XA-1295A
is OFF (returns to normal).

HIPPS Isolation Valve 32-XV1004


Verify permissive to start FST:
Conduct SOV Panel
Solenoid Functional
Test . .All four
solenoids shall pass
functional test (for
SOV Panel solenoids
32-XY-1004A, B, C, D
functional test
sequence see step 2).
Ensure that Local Alarm
on SOV Panel is OFF
Open HIPPS bypass
valve 32-HV-944
across the HIPPS
Isolation Valve 32-XV1004.

3.7

Start FST:

Turn hand switch 32-HS-944A


FST Request on SOV Panel.
FST Request signal sent to
HIPPS Logic solver.
3.8
11900003-000-IC-PRO-0001_r0

Verify that HIPPS Valve 32-

Local Alarm amber light 32-EL-529 is OFF.


DCS point 32-ZLL1014A - Bypass Valve 32HV-944 CLOSED is not initiated.
P1 Alarm Bypass Valve Open 32-XA-1298
activated.

After FST started the HIPPS LS de-energizes the


solenoids in the respective SOV panel and closes
HIPPS Isolation Valve.
DCS light FST Request 32-HL-xxx activated

SOV Panel: green light 32- ZLH-1014 ESDV

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 49 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

XV-1004 is closed

OPEN goes OFF


SOV Panel red light 32-ZLL-1014 ESDV
CLOSED is ON.
SOV Panel: solenoid status green lights 32EL-654A/B/C/D are OFF.
Local Alarm light 32-EL-529 is ON.
DCS discrepancy 32-XA-xxx alarm is off.

3.9

After FST complete Operator


push and hold Local Reset
push button 32-HS-944B.to
restore normal Valves
operation.

Operator holds 32-HS-944B until HIPPS Valve


32-XV-1004 opens.
SOV Panel: green light 32- ZLH-1014 ESDV
OPEN goes ON.
NOTE:
Only one HIPPS valve at a time shall be tested.

3.10

Close HIPPS bypass valve 32HV-944 across the HIPPS


Isolation Valve 32-XV-1004.

DCS indication 32-ZLL-1014A:- Bypass valve


32-HV-944 CLOSED is ON.
P1 Alarm Bypass Valve Open 11-XA-1298 is
OFF (returns to normal).

Partial
Stroke
Test (PST)

4.1

HIPPS Isolation Valve 32-XV1003


Verify permissive to start PST

11900003-000-IC-PRO-0001_r0

Operator conducts SOV


Panel Solenoid
Functional Test. All four
solenoids shall pass
functional test.

For SOV Panel solenoids 32-XY-1003A, B, C,


D functional test sequence see step 2.

Operator ensure that


Local Alarm on SOV
Panel is OFF

DCS point 32-ZLL1012A - Bypass Valve 32HV-942 CLOSED is initiated.

LOCAL Alarm amber light 32-EL-528 is OFF.

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 50 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Operator ensures that
HIPPS bypass valve
32-HV-942 across the
HIPPS Isolation Valve
32-XV-1003 is
CLOSED.

4.2

Starts PST:

Turn hand switch 32-HS-942E


PST Request on SOV Panel.
4.3

Verify that HIPPS Valve 32-XV1003 is traveling to 90% open


position

Observation/Logic Response
P1 Alarm Bypass Valve Open 32-XA-1298 is
not activated.

The DVC 6000SIS starts pre-programmed PST test.


DVC 6000 reduces the air supply to HIPPS Valve
actuator and thus triggers the valve to 90% OPEN
position.

DCS point PST Request 32-HL-xxx is ON.


SOV Panel: green light 32- ZLH-1012 ESDV
OPEN goes OFF for the duration of PST
SOV Panel: solenoid status green lights 11EL-653A/B/C/D is ON.
Local Alarm light 32-EL-528 is OFF.

NOTES:

DCS, discrepancy alarm 32-XA-xxx is initiated.

1) If the valve travel takes


longer than initial valve
signature time, the Operator
shall take actions described in
Operation manual.

After PST complete SOV Panel: green light 32ZLH-1012 ESDV OPEN goes ON.

2) During PST, if a trip condition


occurs HIPPS LS will abandon
PST and initiate trip of the
HIPPS.

4.4

HIPPS Isolation Valve 32-XV1004 (PST)


Verify permissive to start PST
Operator conducts SOV

11900003-000-IC-PRO-0001_r0

For SOV Panel solenoids 32-XY-1004A, B, C,

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 51 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action
Panel Solenoid
Functional Test . .All
four solenoids shall
pass functional test.

4.5

D functional test sequence see step 2.


LOCAL Alarm amber light 32-EL-529 is OFF.

Operator ensure that


Local Alarm on SOV
Panel is OFF

DCS point 32-ZLL1014A - Bypass Valve 32HV-944 CLOSED is initiated.

Operator ensures that


HIPPS bypass valve
32-HV-944 across the
HIPPS Isolation Valve
32-XV-1004 is
CLOSED.

P1 Alarm Bypass Valve Open 32-XA-1298 is


not activated.

Operator starts PST:

Turn hand switch 32-HS-944E


PST Request on SOV Panel.
4.6

Observation/Logic Response

Verify that HIPPS Valve 32-XV1001 is traveling to 90% open


position

The DVC 6000SIS starts pre-programmed PST test.


DVC 6000 reduces the air supply to HIPPS Valve
actuator and thus triggers the valve to 90% OPEN
position.

DCS point PST Request 32-HL-xxx is ON.


SOV Panel: green light 32- ZLH-1014 ESDV
OPEN goes OFF for the duration of PST
SOV Panel: solenoid status green lights 11EL-654A/B/C/D are ON.
Local Alarm light 32-EL-529 is OFF.

NOTES:

Discrepancy alarm 32-XA-xxx is initiated.

1) If the valve travel takes


longer than initial valve
signature time, the Operator
shall take actions described in
Operation manual.

After PST complete SOV Panel: green light 32ZLH-1014 ESDV OPEN goes ON.

2) During PST, if a trip condition


occurs HIPPS LS will abandon

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 52 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

PST and initiate trip of the


HIPPS.

Pressure
Transmitters
PT1255A/B/C
Functional
Test

5.1

Place transmitter 32-PT-1255A


on bypass by turning bypass
switch 32-HS_P-1255A in SIH5 SIS cabinet.

SIS cabinet Transmitter in Bypass light 32XL_P-1255A is ON.


DCS Transmitter in Bypass alarm 32-HA_P1255A is ON.
Common bypass P1 alarm 32-XA-1255A is
activated

5.2

Close transmitter root valve and


tubing instrumentation valves.

DCS indicating point 32-PI-1255A goes to


minimum pressure.

5.3

Provide
standard
pressure
transmitter maintenance and
calibration as per Supplier Test
and Calibration procedure.

Use calibration equipment with known


pressure and Hand held communicator.

After test completed re-connect


32-PT-1251A to process and
turn off bypass switch 32HS_P-1255A.

SIS cabinet Transmitter in Bypass light 32XL_P-1255A is OFF.

5.4

Verify alarm trip points. DCS HiHi pressure


alarm 32-PAHH-1255A will be activated

DCS Transmitter in Bypass alarm 32-HA_P1255A is OFF


DCS indicating point 32-PI-1255A enabled.
Common bypass P1 alarm 32-XA-1255A is
OFF.

NOTE:

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 53 of 94

SAMREF CLEAN FUELS PROJECT

STEP

On-Line Test Procedure for HIPPS

Operation
Task

Operator Action

Observation/Logic Response

3. During bypassed
Pressure Transmitter
Test, if a trip condition
occurs, HIPPS LS will
initiate trip based on
measurements of the
remaining two
transmitters. HIPPS.
4. The same procedure is
repeated to test
transmitters 32-PT1255B and 32-PT1255C.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 54 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Appendix A FLARE MITIGATION (CDU 011) HIPPS REFERENCE DOCUMENTS

1) CDU 11 P&IDs C0EF-011B1-002A; C0EF-011B1-008; C0EF-011B1-009A; C0EF-011B1-020.


2) Figure 1 SOV Panel 11-XV-1001 Layout;
3) Figure 2 SOV Panel 11-XV-1002 Layout;
4) Figure 3 Heater charge pumps HIPPS Cabinet Layout.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 55 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 56 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 57 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 58 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 59 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 60 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 61 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 62 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Appendix B HIPPS BUTANE SPLITTER UNIT 064 REFERENCE DOCUMENTS

1)
2)
3)
4)

Butane Splitter Unit 64 P&IDs C0EF-011B1-002A; C0EF-064B1-004; C0EF-064B1-001; ]\


Figure 1 SOV Panel 64-XV-1001 Layout;
Figure 2 SOV Panel 64-XV-1002 Layout;
Figure 3 Butane Splitter HIPPS Cabinet Layout.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 63 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 64 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 65 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 66 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 67 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 68 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Appendix C MARINE HEAVY FUEL OIL UNIT 11 REFERENCE DOCUMENTS

1) MHFO Unit 11: MHFO Unit 11 P&IDs C0EF-011B1-017;


2) Figure 1 MHFO HIPPS Cabinet Layout.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 69 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 70 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 71 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Appendix D CATALYTIC HYDRO DESULPHURIZER UNIT 32 REFERENCE DOCUMENTS

1)
2)
3)
4)
5)
6)

CHD Unit 32 P&IDs C0EF-032B1-003D-E;


Figure 1 SOV Panel 11-XV-1000 Layout;
Figure 2 SOV Panel 11-XV-1001 Layout;
Figure 3 SOV Panel 11-XV-1003 Layout;
Figure 4 SOV Panel 11-XV-1004 Layout;
Figure 5 CHD HIPPS Cabinet Layout.

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 72 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 73 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 74 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 75 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 76 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 77 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 78 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

Appendix E SAFEPLEX SIL 3 (SOV PANEL) TECHNICAL PRODUCT GUIDE

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 79 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 80 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 81 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 82 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 83 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 84 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 85 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 86 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 87 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 88 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 89 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 90 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 91 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 92 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 93 of 94

SAMREF CLEAN FUELS PROJECT


On-Line Test Procedure for HIPPS

11900003-000-IC-PRO-0001_r0

SAMREF Clean Fuels Project CONFIDENTIAL Information

Page 94 of 94