Medium Voltage

Switchgear
AHA
up to 24 kV, up to 5000 A, up to 125 kA
System configuration

T&D
Power Distribution

Terms of delivery
The General Terms of Delivery, as amended, shall apply.
Illustrations
The illustrations are not binding for delivery.

Table of Contents
Introduction
Characteristics
Technical Description
Switchgear panel with drawing unit
Transfer of the drawing unit, actuation of
earthing switch, remote control feature
Shutter, primary cable connection,
low-voltage cubicle
Secondary cable connection, low-voltage
connector, checking for safe isolation from
supply and verification of terminal connections,
cable testing, application of instrumentation
and control
Internal interlocks of switchgear station
Rack concept, state-of-art manufacturing technology for air-insulated switchgear panels,
standard equipment of AHA
Busbar compartment
Busbar system, busbar compartment, busbar
voltage transformer, busbar earthing switch,
end leads on the busbar, bus terminal in the
outgoing feeder block

5
8
9
10

11
12

13

14

Regulations and Directives


Regulations and directives, degree of
protection
Explanations regarding the degree of
protection
Characteristics in the case of an internal
fault

24

General technical data


12 kV AHA Rated data in detail
17.5 kV AHA Rated data in detail
24 kV AHA Rated data in detail

25
26
27
28

22
23

Range of components 12 kV, 17. 5 kV, 24 kV


Standard front view
30
Sectional views, front views
31
Delivery, packing

59

Space requirement, constructional data

60

Introduction

Metal-clad switchgear station


AHA
The prefabricated, type-tested AHA
system is an air-insulated, particularly economical and future-oriented
metal-clad switchgear system designed for a wide range of nominal
ratings. AHA is particularly well suited for application in:
power stations
transformer substations
switching substations for industry
and public utilities
ships/drilling platforms
The modular switchgear station
AHA covers a wide range of nominal ratings for:
rated currents up to 5000 A
rated short-circuit making currents
up to 125 kA
rated short-circuit breaking currents up to 50 kA and
voltage levels up 12 kV,
17.5 kV and 24 kV

current switchgear
each panel is equipped on the
left and right with a partition
made of galvanized sheet metal
(sheet metal - air - sheet metal)
Maximum personal safety
due to
operator-guided operation
the interrogator lock system prevents operating errors
all operating and display procedures are effected mechanically
with closed front

opened using the shutter lifting


device
new integrated voltage detection
system IVIS
in the case of rated short-time
withstand currents of 50 kA and
when criteria 1-6 are met, 1s,
floor to ceiling height only 3.2 m
due to PEHLA application of the
safety system ILIS, floor to ceiling
height only 3.0 m

Characteristics
Air-insulated switchgear panels,
metal-enclosed and metal-clad.
Single-bus switchgear and doublebus switchgear design (Duplex)
for back-to-back installation
Switching devices on drawing
unit
Rated currents 630 A to 5000 A,
and rated short-time withstand
currents of 16 kA bis 50 kA (3s)
Compact design, also for heavy-

Shutter lifting device

Operating procedures with


closed door

verification of the characteristics


in the case of an internal fault
(criteria 1-6) up to 50 kA per second
metallic quadruple cladding
closed metal shutters can only be
5

Voltage detection system


IVIS

Optimum operating safety


due to

Particularly economical
thanks to

clearly arranged, logical allocation of actuating and indicating


devices to the function chambers
mechanical actuation of all
switching devices with the front
closed
make-proof earthing switches up
to 125 kA making current
consistent interrogator lock system
straightforward handling of the
drawing unit within and outside
of the panel
patented twin-scissor design with
dead-centre in operation position
connector top (64-pin) can be
pulled forward and off; with specific storage recess in the switchgear panel
extremely simple adaptation
switchgear panel : transport trolley (coupling and decoupling)
for the drawing unit
front side divided into three areas
with clear function allocation
straightforward single-operator
control and handling even for
heavy-current switchgear

moderate space requirements,


compact switchgear panel design, even for heavy-current panels, no catwalk required at the
rear
cable connection: up to 7 cables
per phase; no cable storey required; no cable connection panels
vacuum circuit-breaker ECA
remote control feature of earthing
switches and movement of drawing unit (optional with motor
drive)

all assembly procedures are possible from the front, despite quadruple cladding
big cable connection compartment for up to 3 x 7 cable end
boxes with separate front door
and inspection window
the removable horizontal partition
between the circuit-breaker and
the outgoing feeder cable compartment facilitates connection of
cables
thanks to the use of lifting rollers
with extremely small tuning circle,
no application of cranes is required in the switchgear area during
assembly

Environmentally-friendly
design

Vacuum circuit-breaker
ECA

Independent closed lowvoltage cubicle

Transport trolley on the


AHA

Easy to install

mechanical interface to panel


rack
electrical interface (screw-fastened
connectors) to the panel
additional sheet-metal cladding
between the low-voltage cubicle
and the switchgear panel as an
integral part of the rack (twin
sheet-metal)
simple retrofitting of the factorybuilt low-voltage cubicles for
spare panels is possible

environmentally compatible in
production and during operation
our company is certified and was
a successful participant in the
EC Eco Audit
in case of disposal via the manufacturer, the switchgear will be
taken back
extremely environmentally compatible quenching medium:
vacuum
minimisation of the effects of any
faults in the case of an internal
fault due to the optional safety system ILIS
minimum application of plastics
environmentally neutral production process

Surface protection
The complete racks including the
low-voltage cubicle are made of
galvanized sheet-metal plates.
The doors and end panels are painted in RAL 4004 (Bordeaux violet).
The doors and end panels can be
painted in the following colours,
without extra charge:
RAL 7044 silk grey
RAL 5014 pigeon blue
RAL 7032 pebble grey
RAL 2003 pastel-orange

AHA in detail

1
8

17

15
10
9

2
16

11
4
13

5
6

14
7

12

18

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Low-voltage cubicle
Mechanical control panel on vacuum
circuit-breaker
Lifting gate, circuit-breaker compartment
Transfer device
Integrated VDS system IVIS
Earthing switch operating mechanism and indicator unit
Lifting gate, cable connection compartment
Busbar system
Vacuum circuit breaker ECA
Funnel-type cable bushings
Earthing switch for outgoing feeder
Voltage transformer
Current transformer
Cable end boxes
Metal shutter for busbar
Metal shutter for outgoing feeder
Low-voltage connector
Base plate

Technical description

Vacuum circuit-breaker ECA on


drawing unit with transport trolley

Switchgear panel with drawing unit


The air-insulated metal-clad switchgear panels feature space-saving
slide-in modular design. Existing
switchgear stations can be extended on both sides.
Due to the functional front design,
individual access to each function
chamber within the switchgear panels is extremely easy from the front
side.
The switchgear panels are subdivided into four function chambers, including the low-voltage cubicle, and
metal enclosed against one another.
The function chambers busbar
compartment, circuit-breaker compartment and cable connection
compartment are equipped with
separate pressure relief devices directed upwards.
Vacuum circuit-breakers ECA in
standard design (no panel-specific
design) are used as switching devices. The AHA system is complemented, amongst other things, by a vacuum contactor, measuring and disconnecting drawing units. The switching devices are installed on easyto-operate drawing units. Handling
of the drawing units within the panels is possible with minimum effort
due to an innovative transfer device
of twin-scissor design with dead
centre in operating position, requiring minimum effort only.
8

This design significantly facilitates


transfer of the drawing units and is
particularly useful for heavy-current
panels. The vacuum circuit breakers
ECA can be switched ON and OFF
mechanically with the panel door
closed, in operating and disconnected position. The circuit-breaker
energy store mechanism is always
motorized. For testing purposes, the
motorized energy store mechanism
can be tensioned, and the circuitbreaker switched on or off mechanically (by hand) with the panel door
opened.

Earthing switch
The make-proof earthing switch in
the outgoing feeder block or on the
busbar is switched on and off using
the detachable lever. In the case of
a motor-driven earthing switch, mechanical actuation is possible with
the panel front closed.

Direct coupling between the contact


elements of the main circuit and the
auxiliary switches, and an extreme
extension for the status messages
ensure precise emulation of the
main circuit in question.

Transfer of the drawing unit


The drawing unit is transferred from
operating into disconnected position
and vice versa in manual mode
with the panel door closed. This
procedure can also be implemented
with the panel door opened, for
testing purposes. When the drawing unit is equipped with motorized
transfer device, a manual emergency mode is available.
Identically equipped drawing units
are interchangeable. Outside the
switchgear panels, the drawing
units are moved on easy-to-handle
trolleys.

Interrogator lock for


earthing switch
Actuation of the earthing
switch using a detachable
lever

Interrogator lock for


racking in the circuitbreaker on the drawing
unit

Earthing switch for outgoing feeder block

Remote control feature

Transfer of drawing unit

The dimensionally stable transport


trolley which serves to move the
drawing unit when outside the
panel, is equipped with casters.
Handling is comparable to that of a
switching truck.

The basic model of the ECA circuitbreakers is equipped with a motorized spring charging mechanism for
the spring energy store mechanism,
and one closing and opening coil
each. The transfer device for the
drawing units and the earthing switches for outgoing feeders can be
equipped optionally to provide remote control features.
9

Shutter
Metallic shutters are installed in
front of the fixed moving contacts.
Intentional opening of these separately for the top or lower shutter
is only possible using the specific
shutter lifting device. When the
drawing unit has been moved out,
each shutter can be closed individually (padlock).

Primary cable connection


AHA permits extremely space-saving and economical building concepts. AHA has been designed so
that even for heavy-current panels,
neither additional cable connection
panels nor catwalks are required
behind the switchgear stations.
The cable connection compartment
is accessible through a separate
door from the panel front side. The
horizontal partition between the circuit-breaker and the cable connection compartment is easily removable for assembly of the cable end
boxes. Depending on the remaining
equipment of the cable connection
compartment and on the size of the
cable end boxes used, the following
cable connections are possible:
up to 3 x 7 cables
500 mm2 each
up to 6 cables
800 mm2 each

Metallic shutter for busbar


system and outgoing feeder compartment

Low-voltage cubicle
The low-voltage cubicle accommodates the secondary equipment for
protection relays, control, measuring, metering and other systems.
The low-voltage cubicle which has
been systematically separated from
the primary section is shockproof
and resistant to accidental arcs. It is
an independent, closed low-voltage
compartment with mechanical and
electrical interface to the panel rack
(screwed plug-and-socket connection). A unique advantage for the
operator is the clear separation between the rack and the low-voltage
cubicle.

View of an open low-voltage


cubicle

Subsequent fitting of spare panels


and conversion or replacement of
complete low-voltage cubicles (e.g.
due to process changes) can also
be accomplished without any problems. The switchgear panel is completely enclosed even without topmounted low-voltage cubicle (IP3X).
The torsion-resistant door of the lowvoltage cubicle can be equipped
optionally with inspection windows,
or to house measuring and control
devices, and protection relays.

10

Cable connection compartment with 3 x 7 cable


end boxes

Door of low-voltage cubicle


with installed secondary
equipment and push-button
switches for circuit-breakers

Secondary cable connection

L1+L2+L3, via flash-type arrow symbols: voltage present yes/no.

External secondary lines are only introduced into the front panel area
from the bottom. The secondary
lines are laid in a cable duct which
is metallically screened against the
medium-voltage section from the
bottom edge of the panel up to the
low-voltage cubicle.

Low-voltage connector
The electrical low-voltage connection between the fixed part and the
drawing unit is established via a
max. 64-pin connector. The connector top section is an integral part of
the rack and can be pulled forward
and off. The connector base is an
integral part of the drawing unit.
The rack is equipped with a separate storage recess for extremely simple storage of the connector top,
above the front side of the drawing
unit.

IVIS display with indicating functions: conductors


L1, L2, L3; voltage present

The electronic IVIS system is an integrated VDS system according to


IEC 61 234-5 and DIN VDE 0682,
part 415. To check for safe isolation, IVIS does not require any auxiliary power. With IVIS, electrical repeat tests are not necessary. The verification of terminal connections is
effected using the IVIS phase monitor MS.

Cable testing

primary connections can be disconnected from or connected to the


busbars quite easily by means of
the flexible primary cables. Visual
inspections of the cable connection
compartment are possible through
the inspection window installed in
the cable compartment door as
standard.

Application of instrumentation and control (I&C)


AHA is optimally suited for operation with switchgear I&C systems.
All switching devices on the drawing units, the outgoing earthing
switch and the drawing unit as such
can be remote controlled. The use
of the intelligent Management Online Systems (e.g. IMOS, manufactured by ALSTOM Sachsenwerk)
which assume all control and monitoring duties, affords a high degree
of automatation which enhances
safety as well as reliability, and facilitates the operators tasks.

Cable DC or AC voltage tests can


be affected with the door of the
cable connection compartment
opened. The voltage transformer
Phase monitor MS 100

Low-voltage connector
with storage recess

Checking for safe isolation


from supply and verification
of terminal connections
AHA is equipped with the Voltage
Detection System VDS IVIS manufactured by ALSTOM Sachsenwerk.
The check for safe isolation from
supply and verification of terminal
connections is effected with the
panel front closed. The stationary
IVIS display shows, directly adjacent to the actuating devices for the
outgoing earthing switch, and simultaneously for all conductors
11

Internal interlocks of switchgear station


The AHA switchgear panels are
equipped with interrogator locks
which only allow admissible actuations. These powerless interrogator
locks reliably prevent insertion of
the operating crank if the operating
states of the switchgear device do
not so permit. Inadmissibly high actuating forces are thus prevented
from acting on locked switching devices right from the start.
The mechanical internal interrogator
lock in the panel integrates circuitbreaker, drawing unit, low-voltage
connector and earthing switch for
outgoing feeder as follows:

Operating position

Moved position

Mechanical interlocks
Interlock
Activity

Move drawing unit into the panel,

Drawing unit

Crank handle*)

Low-voltage
connector

Earthing
switch

Circuit-breaker

released

blocked

blocked

released

released

but do not lock it


Lock drawing unit

blocked

released

released

released

blocked

released

released

released

Insert crank handle*)

blocked

blocked

blocked

blocked

Move drawing unit into operating

blocked

released

blocked

blocked

released

Insert and lock low-voltage


connector

position and remove crank handle*)


Circuit-breaker switched ON

blocked

blocked

blocked

blocked

Circuit-breaker switched OFF

blocked

released

blocked

blocked

Insert crank handle*) and move

blocked

blocked

blocked

blocked

Remove crank handle*)

blocked

released

released

released

released

Earthing switch turned ON

blocked

blocked

released

released

Earthing switch turned OFF

blocked

released

released

released

Unlock and remove low-voltage

blocked

blocked

released

released

drawing unit into disconnected position

connector
*) for actuation of drawing unit
Depending on the interlock request, additional blocking magnets may be required on the drawing unit actuating device and on the actuation for
the earthing switch in the outgoing feeder.
12

Rack concept
The extremely sturdy, torsion-resistant panel rack consists of four
single modules: Front mounting
frame, rear panel, bottom assembly,
and top cover.
Double-walled partitions (sheetmetal - air - sheet-metal) considerably increase the operating safety of
the switchgear and meet the operating requirement for heavy-duty
switchgear particularly well.
The patented lifting doors for the circuit breaker and cable connection
compartments lock into the panel
rack on all sides, and are thus extremely pressure-proof.

technique for galvanized sheet


metal, AHAs are long-life products.
The use of vacuum circuit breakers
with a high number of mechanical
and electrical operating cycles ensures a long service life. Computerised production methods, such as
laser cutting technology, ensure
compliance with maximum quality
requirements.

Standard equipment of AHA

State-of-art manufacturing
technology for air-insulated
switchgear panels

Thanks to a future-oriented manufacturing process combined plate


seaming / bending and riveting

quadruple compartmentalization
metal shutters
galvanized rack
bushings with fixed contacts
matching the moving contacts
double-walled partitions
(sheet-metal air sheet-metal)
inspection window in door of
cable compartment
mechanical powerless interrogator lock (switchgear interlocking)
mechanical indication of all operating states with closed front

pressure-proof lifting doors


divided base plate with cable
entries
removable partition plate between circuit-breaker and cable
connection compartments
storage recess for the 64-pin
connector top
transport trolley with casters
VDS system IVIS for testing for
safe isolation from supply and
verification of terminal connections
patented twin-scissor design with
dead centre in operating position
interlock of drawing unit earthing switch for outgoing feeder
contiguous low-voltage connector
interlock even exceeding VDE
and IEC requirements

Cover plate
Low-voltage cubicle

partition

Function Unit
Rear panel

Bottom assembly

Lifting doors

Front mounting frame

13

Busbar compartment

Busbar system
Busbar compartment

Bus terminal in the outgoing


feeder block

The busbar system consists of flat


copper bars (E Cu). The number of
bars installed per phase depends
on the rated current. The collector
bar sections relating to each panel
are passed through cutouts in the
panel partitions. Busbar bushings
are available section-wise as an option.

Bus terminals in the outgoing feeder


or to the busbar system are established via fully insulated potentialcontrolled busbar connections.

Busbar voltage transformer


Three single-pole voltage transformers can be installed in the busbar
compartment without additional
panel partition.

Busbar earthing switch


For busbars without additional
panel partition, make-proof earthing
switches can be installed in the busbar compartment. Manual actuation
is effected via the detachable lever
in the top front area of the switchgear panel.

End leads on the busbar


An additional busbar top-mounted
box enables connection of fully insulated bars to the busbar system.
14

AHA 12 kV / 17.5 kV
Attachment to busbar
Busbar voltage transformer
Front view

Panel cross section

1 Busbar compartment
2 Low-voltage cubicle
3 Busbar voltage
transformer
4 Connecting cable

AHA 12 kV / 17,5 kV
Attachment to busbar
Busbar earth
Front view

Panel cross section

1 Busbar compartment
2 Low-voltage cubicle
3 Earth
4 Connecting bar

1
2
3
4

15

Door of low-voltage cubicle


Position indicator ON / OFF
Unlocking lever / earthing switch
Insertion opening for actuation of
busbar earthing switch from the front
side of the switchgear panel

Busbar end lead on the busbar


Rated current up to max. 1250 A

Panel width

Rated current up to max. 2400 A

Rated current up to max. 3150 A

16

mm

mm

700

160

900

210

Bus connection in outgoing


feeder block

AHA 12 kV / 17.5 kV
Fully insulated busbar connection
Rated current up to max. 1250 A
Section A - A

AHA 12 kV / 17,5 kV
Fully insulated busbar connection
Rated current up to max. 2500 A
Section A - A

Unit: mm
17

AHA 12 kV / 17.5 kV
Fully insulated busbar connection
Rated current up to max. 3150 A
(higher ratings on request)

Section A - A

Section B - B

Unit: mm
18

Cable connection in outgoing


feeder block
AHA 12 kV / 17.5 kV
shown: 1 x single-conductor plastic-insulated cable
300 mm2, with surge arrester.
The instructions for assembly issued by the cable box
manufacturer and the guidelines for cable laying of
the cable manufacturer must be observed!

Unit: mm
19

AHA 12 kV / 17.5 kV
shown: 3 x single-conductor plastic-insulated cable
500 mm2, with voltage transformer.
The instructions for assembly issued by the cable box
manufacturer and the guidelines for cable laying of
the cable manufacturer must be observed!
Section A - A

AHA 12 kV / 17.5 kV
shown: 7 x single-conductor plastic-insulated cable
500 mm2/phase, with voltage transformer.
The instructions for assembly issued by the cable box
manufacturer and the guidelines for cable laying of
the cable manufacturer must be observed!

Section A - A

Unit: mm
20

AHA 12 kV
shown: 2 x three-conductor plastic-insulated cable
185 mm2, with voltage transformer.
The instructions for assembly issued by the cable
box manufacturer and the guidelines for cable laying of the cable manufacturer must be observed!
Section A - A

AHA 12 kV
shown: 2 x three-conductor paper-insulated mass-impregnated cable 185 mm2, with voltage transformer.
The instructions for assembly issued by the cable box
manufacturer and the guidelines for cable laying of
the cable manufacturer must be observed!

Section A - A

Unit: mm
21

Regulations and Directives

Regulations and Directives


Design and type of construction
Type test, routine test

IEC
IEC
IEC
IEC
IEC

60298
60694
60056
60129
61234-5

VDE
VDE
VDE
VDE
VDE

0670,
0670,
0670,
0670,
0682,

part
part
part
part
part

6
1000
101-107
2
415

Characteristics in the case of an internal fault

IEC 60298
Appendix AA

Installation data, building dimensions,


space requirement

Indoor switchgear can be used according to


VDE 0101

VDE 0670, part 6


Appendix AA
PEHLA Directives no. 4

in enclosed electrical operating areas: rooms or


locations which serve exclusively for operation of
electrical equipment, which are kept closed and
which are accessible to persons having undergone
electrotechnical training. For non-experts, access is
only allowed if they are accompanied by electrical
specialists or by persons having undergone electrotechnical training.
Operation, operator control and work in the
vicinity of live components

VDE 0101
VDE 0105

Protection against the ingress of solid


foreign bodies and against shock-hazard
Protection against the ingress of solid foreign
bodies and against shock-hazard

IEC 60298
IEC 60694
IEC 60529

Degree of protection

Degree of protection on the front and on the sides

IP 4X, IP42

Degree of protection, rear


Module with 700, 900, 1000 mm
Module with 1200 mm

IP 4X, IP42
IP 2XD

Degree of protection, top

IP 4X/IP 42 and
IP 2XD
22

VDE 0670, part 6


VDE 0670, part 1000
VDE 0470, part 1

Explanations regarding the


degree of protection

Degree of protection

IP

Degree of protection

IP

Protection against the ingress of solid foreign bodies

Protection against the ingress of solid foreign bodies

Protection against the ingress


of solid bodies with a diameter
of 1 mm and over

Protection against the


ingress of solid bodies with
a diameter over 1 mm

Protection against the ingress of water

Protection against the ingress of water

Protection against the ingress of dripping water with 15 inclination

No definition
Degree of protection

IP

Protection against the ingress of solid foreign bodies

Protection against the ingress


of solid bodies with a diameter
of 12.5 mm and over
Protection against the ingress of water

No definition
Shock-hazard protection

Protected against access to dangerous components with a test


probe: Test bar with a length of 100 mm and a diameter of
1 mm must be a sufficient distance from dangerous components.

Indoor conditions according to


IEC 60694 and VDE 0670, part 6
Temperature of ambient air
Maximum

+ 40 C
(max. + 55 C with partially reduced current values)

Average over 24 h
Minimum

+ 35 C
5 C (lower temperatures on request)

Ambient air

No essential impurities due to dust, corrosion and/or inflammable gases,


fumes or salts!

Air humidity and condensation

Mixed value of relative humidity, measured over 24 h: 95 %.


Mixed value of steam pressure over 24 h: max. 2.2 K Pa.
Mixed value of the relative humidity over a month: max. 90 %.
Mixed value of steam pressure over a month: max. 1.8 K Pa.
The air humidity within the enclosure may reach high values.
Condensation within the enclosure is prevented by measures within
the switchgear room.

Installation heights

Up to 1000 m above sea level, corresponding to air conditions of


1013 h Pa, + 20C and a water content of 11 g/m3.
Greater installation heights on request.

23

Characteristics in the case of


an internal fault
The AHA switchgear panels have
been tested successfully for their
characteristics in the case of an internal fault, at rated short-time withstand currents up to 50 kA over a
period of 1 second according to
IEC 60298, Appendix AA, VDE
0670, Part 6, Annex AA, and according to PEHLA Directives no. 4
(criteria 1-6).
Thanks to a pressure relief and gas
cooling system developed specifically for AHA, the criteria 1-6 can
even be warranted at high rated
short-time withstand currents up to
50 kA (1 second) and at low room
heights. To minimize the effects of
malfunctions (in the case of an internal fault), IEC 60298/VDE 0670,
part 6, recommends among other
things measures to limit the arc duration. Use of the optional safety system ILIS made by ALSTOM Sachsenwerk achieves a maximum level
of personal safety, and the effects of
malfunctions on the environment are
reduced to a very large extent.

ILIS evaluator

In the case of AHA switchgear


equipped with the ILIS system an
internal fault is switched off within
max. 100 ms independently of
the grading time of the network master relay, which may be higher.
We recommend use of the ILIS safety system in AHA switchgear stations especially in the higher network data range.

24

General technical data

AHA 12
Rated voltage

kV

AHA 17.5

AHA 24

12
IEC/VDE

17,5
IEC/VDE

15
IEC (USA)

12
China

24
IEC/VDE

Rated power-frequency withstand voltage


General value
kV
Over the isolating distance kV

28
32

38
45

36
40

42
48

50
60

Rated lightning impulse withstand voltage


General value
kV
Over the isolating distance kV

75
85

95
110

95
105

95
110

125
145

Rated frequency

Hz

50,601)

Rated current of busbars

1000 4000 (50001)

630 2500

Rated current of branches

630 4000 (5000 )

630 2500

Rated peak withstand current

kA

50 125

40 80

Rated short-time withstand current 1s


3s

kA
kA

20 50
20 44 (50)1)

16 31,5
16 31,5

Rated short-circuit making current

kA
kA

50 125

50 125 (12 kV)


50 100 (13,8 15 kV)
50 80 (17,5 kV)

40 80

Rated short-circuit breaking current

kA
kA
kA

20 50

20 50 (12 kV)
20 40 (13,8 15 kV)
20 31,5 (17,5 kV)

16 31,5

kA

20 50

16 31,5

mm
mm
mm

700, 900, 1200


23302)
1450

800, 1000
23302)
1600

Internal faults (VDE 0670, part 6/


IEC 60298, Appendix AA)
Criteria 1-6 1s
Dimensions

Width
Height
Depth (single busbar)

Switchgear system

1)
2)

Metal-clad
Single and double busbar

on request
without mounted equipment
25

12 kV AHA
Rated data in detail

AHA 12
Rated voltage

kV

12

Rated power-frequency withstand voltage


General value
kV
Over the isolating distance
kV

28
32

Rated lightning impulse withstand voltage


General value
kV
Over the isolating distance
kV

75
85

Rated frequency

Hz

50, 60

Degree of protection
Front / sides
Rear
Top

1)

IP4 X, IP 42
IP4 X, IP 42, 1200 mm Width: IP2XD
IP4X, IP 42, IP2XD

Rated current of busbars


for degree of protection top

4000 (50001)
IP 2XD

1000, 1250, 1600, 2000, 2900, 3150, 3700


IP 4X, IP 42

Panel height

mm

23302)

Panel depth (single busbar)

mm

1450

Panel module with

mm

700
Single/twin busbar

900
Single/twin busbar

1200
Single busbar

Rated short-circuit making current kA

50

63

80

50

63

80

100

125

80

100

125

Rated short-circuit breaking current kA

20

25

31,5

20

25

31,5

40

50

31,5

40

50

Rated peak withstand current

kA

50

63

80

50

63

80

100

125

80

100

125

Rated short-time
withstand current

kA
kA

20
20

25
25

31,5
31,5

20
20

25
25

31,5
31,5

40
40

50
443)

31,5
31,5

40
40

50
443)

Internal faults (VDE 0670, part 6/


IEC 60298, Appendix AA)
Criteria 1-6
1s
kA

20

25

31,5

20

25

31,5

40

50

31,5

40

50

630
1000
1250
1600

630
1000
1250
1600

3150 3150 3150

4000 4000 4000 (50001) (50001) (50001)

1s
3s

Rated current
Circuit-breaker switchgear panels
Protection degree, top IP4X, IP 42 A
A
A
Protection degree, top IP2XD
A
A
A
Protection degree, top and rear
IP2XD + wall clearance 30 cm A
Heavy-duty set 1 and protection degree top IP2XD
A
Heavy-duty set 2 and protection degree top IP2XD
A
1)
2)
3)
4)

630 630 630 630

1000 1000 1000 1000

1250 1250 1250 1250

1600 1600 1600 1600

2000 2000 2000

2500 2500 2500

on request
without mounted equipment
50 kA on request
higher values on request

26

31504) 31504) 31504)

17,5 kV AHA
Rated data in detail

AHA 17,5
Rated voltage

17,5
IEC/VDE

15
IEC (USA)

12
China

Rated power-frequency withstand voltage


General value
kV
Over the isolating distance
kV

28
23

36
40

42
48

Rated lightning impulse withstand voltage


General value
kV
Over the isolating distance
kV

95
110

95
105

95
110

Rated frequency

kV

Hz

50, 60

Degree of protection
Front / sides
Rear
Top
Rated current of busbars
for degree of protection top

1)

IP4 X, IP 42
IP4 X, IP 42, 1200 mm Width: IP2XD
IP4X, IP 42, IP2XD
A

1000, 1250, 1600, 2000, 2900, 3150, 3700


IP 4X, IP 42

Panel height

mm

23302)

Panel depth (single busbar)

mm

1450

Panel module width

mm

700
Single/twin busbar

4000 (50001)
IP 2XD

900
Single/twin busbar

1200
Single busbar

Rated short-circuit making current


at 12 kV
kA
at 13.8-15 kV
kA
at 17.5 kV
kA

50
50
50

63
63
63

80
80
80

50
50
50

63
63
63

80
80
80

100
100

125

80
80
80

100
100

125

Rated short-circuit breaking current


at 12 kV
kA
at 13.8-15 kV
kA
at 17.5 kV
kA

20
20
20

25
25
25

31,5
31,5
31,5

20
20
20

25
25
25

31,5
31,5
31,5

40
40

50

31,5
31,5
31,5

40
40

50

Rated peak withstand current

kA

50

63

80

50

63

80

100

125

80

100

125

Rated short-time withstand 1s


current
3s

kA
kA

20
20

25
25

31,5
31,5

20
20

25
25

31,5
31,5

40
40

50
443)

31,5
31,5

40
40

50
443)

Internal faults (VDE 0670,


part 6/ IEC 60298,
Appendix AA) Criteria 1-6 1s

kA

20

25

31,5

20

25

31,5

40

50

31,5

40

50

A
A
A
A
A
A

630
1000
1250
1600

630
1000
1250
1600

3150 3150 3150

4000 4000 4000 (50001) (50001) (50001)

Rated current
Circuit-breaker switchgear panels
Protection degree, top
IP4X, IP 42
Protection degree, top
IP2XD

Protection degree, top and


rear ID2XD + wall clearance 30 cm A
Heavy-duty set 1 and protection degree top IP2XD
A
Heavy-duty set 2 and protection degree top IP2XD
A
1)
2)
3)
4)

630 630 630 630

1000 1000 1000 1000

1250 1250 1250 1250

1600 1600 1600 1600

2000 2000 2000

2500 2500 2500

on request
without mounted equipment
50 kA on request
at max. 35 C

27

31504) 31504)31504)

24 kV AHA
Rated data in detail

AHA 24
Rated voltage

kV

24

Rated power-frequency withstand voltage


General value
kV
Over the isolating distance
kV

50
60

Rated lightning impulse withstand voltage


General value
kV
Over the isolating distance
kV

125
145

Rated frequency

Hz

50, 60

Degree of protection
Front / sides
Rear
Top

1)

IP4 X, IP 42
IP4 X, IP 42
IP4X, IP 42, IP2XD

Rated current of busbars


A
for degree of protection top

630, 1250, 2000


IP 4X, IP 42

2500
IP 2XD

Panel height

mm

23302)

Panel depth (single busbar)

mm

1600

Panel module width

mm

800
Single/Twin busbar

1000
Single/Twin busbar

Rated short-circuit making current kA

40

63

80

40

63

80

Rated short-circuit breaking current kA

16

25

31,5

16

25

31,5

Rated peak withstand current

kA

40

63

80

40

63

80

Rated short-time withstand current

kA
kA

16
16

25
25

31,5
31,5

16
16

25
25

31,5
31,5

Internal faults (VDE 0670, part 6/


IEC 60298, Appendix AA)
Criteria 1-6
1s
kA

16

25

31,5

16

25

31,5

A
A
A
A
A

630
1000

1250

630
1000

1250

1000

1250

630
1000
1250
1600
2000

630
1000
1250
1600
2000

1000
1250
1600
2000

2500

2500

2500

1s
3s

Rated current
Circuit-breaker switchgear panels
Protection degree, top
IP4X, IP 42
Protection degree, top
IP2XD
Heavy-duty set 1 and
Protection degree top IP2XD
1)
2)

on request
without mounted equipment

28

Range of components 12 kV, 17.5 kV, 24 kV

Outgoing feeder panel


with circuit-breaker

Outgoing feeder panel with


circuit-breaker and fuse

Outgoing feeder panel


with vacuum contactor

Metering panel with


drawing unit

Busbar riser panel with outgoing feeder and instrumenttransformer drawing unit

Coupling with
circuit-breaker

Busbar riser panel

Busbar riser panel


with transformer

Busbar riser panel


with isolating drawing unit

Busbar riser panel with


instrument-transformer
drawing unit

Back-to-back
Coupling with busbar riser

Back-to-back
Coupling with busbar riser and
transformer

Top-mounted box for fully


insulated busbar end lead

Busbar with voltage


transformer

Busbar with earth

Back-to-back
Outgoing feeder panel with
circuit-breaker

Back-to-back
Coupling with CB and
isolating drawing unit

Back-to-back
Coupling with CB with transformer and isolating drawing unit
29

AHA 12 kV / 17.5 kV

Sectional view of panel

Standard front view and sectional


view of panel
Outgoing feeder panel with
circuit-breaker
Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with vacuum circuit
breaker ECA
10 Earthing switch for outgoing feeder
11 Current transformer
12 Voltage transformer
13 IVIS coupler
14 Voltage Detection System (VDS) IVIS

Heavy-current design
Outgoing feeder panel with
circuit-breaker
Module width 1200 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with vacuum circuit
breaker ECA
10 Earthing switch for outgoing feeder
11 Current transformer
12 Voltage transformer
13 IVIS coupler
14 Voltage Detection System (VDS) IVIS

30

AHA 12 kV / 17.5 kV

Sectional view of panel

Outgoing feeder panel with circuitbreaker and fuses


Module width 700 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with vacuum circuit breaker
ECA
10 Earthing switch for outgoing feeder
11 Current transformer
12 HV HBC fuses
13 IVIS coupler
14 Voltage Detection System (VDS) - IVIS

Front view

Mechanical manual operating element of circuit-breaker

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the


drawing unit

Insertion opening for actuation of the drawing unit

Voltage Detection System (VDS) IVIS

Inspection window, circuit-breaker compartment

Grip bar

Position indicator, earthing switch for outgoing feeder

10 Lever to open the insertion opening for actuation of the


earthing switch for outgoing feeder
11 Insertion opening for actuation of the earthing switch for
outgoing feeder

31

AHA 12 kV / 17.5 kV

Sectional view of panel

Outgoing feeder panel with


vacuum circuit breaker
(400 A)
Module width 700 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Vacuum contactor compartment
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door, vacuum contactor compartment
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with vacuum contactor
and fuses
10 Earthing switch for outgoing feeder
11 Current transformer
12 Fuse units
13 IVIS coupler
14 Voltage Detection System (VDS) IVIS
15 Surge arrester

Front view

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Voltage Detection System (VDS) IVIS

Inspection window

Grip bar

Position indicator, earthing switch for outgoing feeder

Lever to open the insertion opening for actuation of the earthing


switch for outgoing feeder

10 Insertion opening for actuation of the earthing switch for outgoing feeder

32

Metering panel with drawing unit


Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Compartment for instrument-transformer
drawing unit
4 Door, low-voltage cubicle
5 Door to instrument-transformer drawing
unit
6 Drawing unit with voltage converter
and fuse

33

AHA 12 kV / 17.5 kV

Sectional view of panel

Busbar riser panel with outgoing


feeder and isolating drawing unit
Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Compartment for isolating drawing unit
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door to isolating drawing unit
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Isolating drawing unit
10 Earthing switch for outgoing feeder
11 IVIS coupler
12 Voltage Detection System (VDS) IVIS

Front view

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Voltage Detection System (VDS) IVIS

Inspection window

Grip bar

Position indicator, earthing switch for outgoing feeder

Lever to open the insertion opening for actuation of the earthing


switch for outgoing feeder

10 Insertion opening for actuation of the earthing switch for outgoing feeder
700

34

Heavy-current design
Busbar riser panel with outgoing feeder
and isolating drawing unit
Module width 900 mm

35

Sectional view of panel

AHA 12 kV / 17.5 kV
Busbar riser panel with outgoing
feeder and instrument-transformer
drawing unit
Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Compartment for instrument-transformer
drawing unit
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door to instrument-transformer drawing unit
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with voltage transformer and
fuse
10 Current transformer
11 IVIS coupler
12 Voltage Detection System (VDS) IVIS

Front view

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Voltage Detection System (VDS) - IVIS

Inspection window

Grip bar

700

36

Heavy-current design
Busbar riser panel with outgoing
feeder and instrument-transformer
drawing unit
Module width 900 mm

37

Sectional view of panel

AHA 12 kV / 17.5 kV
Coupling with circuit-breaker
Lower transfer
Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Busbar connection to busbar riser panel
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door (busbar connection)
8 Inspection window
9 Drawing unit with vacuum circuit-breaker
ECA
10 Earthing switch
11 Current transformer
12 Bushings in partition

Front view

Mechanical manual operating element of circuit-breaker

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Inspection window, circuit-breaker compartment

Grip bar

Position indicator, earthing switch

Lever to open the insertion opening for actuation of the earthing switch

10 Insertion opening for actuation of the earthing switch


(700)

38

Heavy-current design
Coupling with circuit-breaker
Low transfer
Module width 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Busbar connection to busbar riser panel
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door (busbar connection)
8 Inspection window
9 Drawing unit with vacuum circuit-breaker
ECA
10 Earthing switch
11 Current transformer
12 Bushings in partition

39

AHA 12 kV / 17.5 kV

Sectional view of panel

Busbar riser panel


Module width 700 and 900 mm

1 Low-voltage cubicle
2 Door, low-voltage cubicle
3 Panel doors
4 Busbar tie connection and busbar riser
5 Current transformer
6 Voltage transformer

Front view

Central closure for door (on hinge end)

Grip bar

700

40

Heavy-current design
Busbar riser panel
Module width 900 mm

1 Low-voltage cubicle
2 Door, low-voltage cubicle
3 Panel doors
4 Busbar tie connection and busbar riser
5 Current transformer
6 Voltage transformer

41

AHA 12 kV / 17.5 kV

Sectional view of panel

Busbar riser panel with isolating


drawing unit
Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Compartment for isolating drawing unit
4 Compartment for low transfer
5 Door, low-voltage cubicle
6 Door to isolating drawing unit
7 Door, low transfer
8 Inspection window, low transfer
9 Isolating drawing unit
10 Current transformer
11 Voltage transformer

Front view

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Inspection window

Grip bar

(700)

42

Heavy-current design
Busbar riser panel with isolating
drawing unit
Module width 900 mm

43

AHA 12 kV / 17.5 kV

Sectional view of panel

Busbar riser panel with instrumenttransformer drawing unit


Module width 700 and 900 mm

1 Low-voltage cubicle
2 Busbar compartment
3 Compartment for instrument-transformer
drawing unit
4 Door, low-voltage cubicle
5 Door to instrument-transformer drawing unit
6 Door to low transfer
7 Inspection window, low transfer
8 Drawing unit with voltage transformer and
fuse
9 Current transformer

Front view

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Inspection window

Grip bar

700

44

Heavy-current design
Busbar riser panel with instrumenttransformer drawing unit
Module width 900 mm

45

AHA 12 kV / 17.5 kV

Sectional view of panel

Heavy-current design
Outgoing feeder panel with circuitbreaker
(Module width 1200 mm)

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Cable connection compartment
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door, cable connection compartment
8 Inspection window, cable connection
compartment
9 Drawing unit with vacuum circuit-breaker ECA
10 Earthing switch for outgoing feeder
11 Current transformer
12 Voltage transformer
13 IVIS coupler
14 Voltage Detection System (VDS) - IVIS
15 Bushings in the partition

Front view

Mechanical manual operating element of circuit-breaker

Central door closure (on hinge end)

Position indicator, drawing unit

Lever to open the insertion opening for actuation of the drawing unit

Insertion opening for actuation of the drawing unit

Inspection window, circuit-breaker compartment

Grip bar

Position indicator, earthing switch

Lever to open the insertion opening for actuation of the earthing switch

11 Insertion opening for actuation of the earthing switch

46

Heavy-current design
Coupling with circuit-breaker
(Module width 1200 mm)

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Busbar connection to busbar riser panel
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment
7 Door (busbar connection)
15

8 Inspection window
9 Drawing unit with vacuum circuit-breaker ECA
10 Earthing switch
11 Current transformer
12 Bushings in partition

47

AHA 24 kV
Standard front view and sectional view of
panel
Outgoing feeder panel with circuit-breaker
Module width 800 and 1000 mm
Sectional view of panel

2330

5
6

1 Low-voltage cubicle

2 Busbar earthing switch


3 Busbar compartment

480

4 Circuit-breaker compartment
5 Drawing unit with vacuum circuit-breaker ECA
6 Earthing switch for outgoing feeder
7 Current transformer

1600
1640

Front view

800 / 1000

48

AHA 24 kV
Heavy-current design
Outgoing feeder panel with circuit-breaker
Module width 1000 mm
Sectional view of panel

2330

5
6

1 Low-voltage cubicle
2 Busbar earthing switch

3 Busbar compartment
4 Circuit-breaker compartment

480

5 Drawing unit with vacuum circuit-breaker ECA

6 Earthing switch for outgoing feeder


7 Current transformer
8 Voltage transformer

1600
1640

AHA 24 kV
Heavy-current design
Outgoing feeder panel with circuit-breaker
and busbar earthing switch
Module width 1000 mm
Sectional view of panel

1
2
3

2330

5
6

1 Low-voltage cubicle
2 Busbar earthing switch

3 Busbar compartment
4 Circuit-breaker compartment

480

5 Drawing unit with vacuum circuit-breaker ECA

6 Earthing switch for outgoing feeder


7 Current transformer
8 Voltage transformer

1600
1640

49

AHA 12 kV / 17.5 kV
Outgoing feeder panel
Double busbar (Duplex)
Back-to-back with two circuit-breakers

Sectional view of panel

6
6

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Door, low-voltage cubicle
5 Door, circuit-breaker compartment
6 Door for busbar connection
7 Drawing unit with vacuum circuit-breaker
ECA
8 Earthing switch for outgoing feeder
9 Current transformer
10 Voltage transformer
11 IVIS coupler
12 Voltage Detection System (VDS) - IVIS

50

AHA 12 kV / 17.5 kV
Heavy-current design
Outgoing feeder panel
Double busbar (Duplex)
Back-to-back with two circuit-breakers

Sectional view of panel

6
6

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Door, low-voltage cubicle
5 Door, circuit-breaker compartment
6 Door for busbar connection
7 Drawing unit with vacuum circuitbreaker ECA
8 Earthing switch for outgoing feeder
9 Current transformer
10 Voltage transformer
11 IVIS coupler
12 Voltage Detection System
(VDS) - IVIS

51

AHA 12 kV / 17.5 kV
Coupling with circuit-breaker and
isolating drawing unit
Double busbar (Duplex)
Back-to-back

Sectional view of panel

5
5

6
6

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Compartment for isolating drawing
unit
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment /
isolating drawing unit
7 Door for busbar connection
8 Drawing unit with vacuum circuitbreaker ECA
9 Isolating drawing unit
10 Current transformer

52

AHA 12 kV / 17.5 kV
Heavy-current design
Coupling with circuit-breaker and
isolating drawing unit
Double busbar (Duplex)
Back-to-back
Sectional view of panel

5
5

6
6

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Compartment for isolating drawing
unit
5 Door, low-voltage cubicle
6 Door, circuit-breaker compartment /
solating drawing unit
7 Door for busbar connection
8 Drawing unit with vacuum circuitbreaker ECA
9 Isolating drawing unit
10 Current transformer

53

AHA 12 kV / 17.5 kV
Coupling with busbar riser
Double busbar (Duplex)
Back-to-back

Sectional view of panel

4
4

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Door, low-voltage cubicle
5 Door, circuit-breaker compartment
6 Door for busbar connection
7 Busbar connection and busbar riser
8 Drawing unit with vacuum circuitbreaker ECA
9 Current transformer

54

AHA 12 kV / 17.5 kV
Heavy-current design
Coupling with busbar riser
Double busbar (Duplex)
Back-to-back

Sectional view of panel

4
4

1 Low-voltage cubicle
2 Busbar compartment
3 Circuit-breaker compartment
4 Door, low-voltage cubicle
5 Door, circuit-breaker compartment
6 Door for busbar connection
7 Busbar connection and busbar riser
8 Drawing unit with vacuum circuitbreaker ECA
9 Current transformer

55

AHA 12 kV / 17.5 kV
Face-to-face installation
Cable connection

56

AHA 12 kV / 17,5 kV
Face-to-face installation
Fully insulated busbar connection
1250 A
if required

if required

57

AHA 12 kV / 17.5 kV
Face-to-face installation
Fully insulated busbar connection
3150 A
if required

if required

58

Delivery
Packing

Delivery

Packing

The switchgear is delivered ready


for connection in terms of individual
panels. Ring circuits connecting the
various panels are installed on site.

For truck transport


Open packing.
Switchgear panels on pallets with
PE protection film.
For sea transport
For sea-worthy transport, packing is
effected in welded aluminium film
with desiccant, and in a closed box
with leakage-proof wooden base
(also for transport in containers).
For air transport
In the case of air freight, the switchgear panels are packed in wooden
crates with closed wooden bases,
and with a protective hood (dust
protection) of PE film, or in wooden
boxes, also with closed wooden
base, however without protective
hoods (dust protection).

59

Space requirement
Construction data

AHA 12 kV / 17.5 kV
Rated short-time withstand current
25 kA / 1 sec.

Panel arrangement

Detail Y

Panel arrangement

End panel of switchgear


Minimum opening
width for placement
Minimum opening
width for placement

Sectional view of building


Spacer bar / bottom opening

Minimum opening
width for placement

60

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Detail X
Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

61

AHA 12 kV / 17.5 kV
Face-to-face installation
Rated short-time withstand current
25 kA/1sec.

Panel arrangement

Detail Y

End panel of switchgear

Sectional view of building

width for placement

Minimum opening

Spacer bar / bottom opening

62

width for placement

Minimum opening

width for placement

Minimum opening

Panel arrangement

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

63

AHA 12 kV / 17.5 kV
Back-to-back installation
Rated short-time withstand current
25 kA/1sec.

Minimum opening

width for placement

Minimum opening

Sectional view of building

64

width for placement

Spacer bar / bottom openings

Panel arrangement

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Detail X
Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

65

AHA 12 kV / 17.5 kV
Rated short-time withstand current
> 25-50 kA/1sec.

Panel arrangement
Panel arrangement

Minimum opening

Minimum opening

width for placement

width for placement

Detail Y

End panel of switchgear


Sectional view of building

Spacer bar / bottom opening

Minimum opening
width for place-

66

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 par 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

67

AHA 12 kV / 17.5 kV
Face-to-face installation
Rated short-time withstand current
> 25-50 kA/1sec.

Panel arrangement

Detail Y

End panel of switchgear

Spacer bar / bottom opening

width for placement

Minimum opening

Sectional view of building

68

width for placement

Minimum opening

width for placement

Minimum opening

Panel arrangement

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

69

AHA 12 kV / 17.5 kV
Back-to-back installation
Rated short-time withstand current
> 25-50 kA/1sec.

width for placement

Minimum opening

Panel arrangement

Spacer bar / bottom opening

width for placement

Minimum opening

Sectional view of building

70

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

71

AHA 12 kV / 17.5 kV
Rated short-time withstand current
up to 50 kA / 0.15 sec.

Panel arrangement
Panel arrangement

Minimum opening

Minimum opening

width for placement

width for placement

Detail Y

End panel of switchgear

Sectional view of building


Spacer bar / bottom opening

Minimum opening
width for placement

72

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

73

AHA 12 kV / 17.5 kV
Face-to-face installation
Rated short-time withstand current
up to 50 kA / 0.15 sec.

Panel arrangement

Detail Y

End panel of switchgear

Spacer bar / bottom opening

width for placement

Minimum opening

Sectional view of building

74

width for placement

Minimum opening

width for placement

Minimum opening

Panel arrangement

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover with


supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

75

AHA 12 kV / 17.5 kV
Back-to-back installation
Rated short-time withstand current
up to 50 kA / 0.15 sec.

Minimum opening

width for place-

Minimum opening

Sectional view of building

76

width for placement

Spacer bar / bottom openings

Panel arrangement

Detail X

Detail X

Detail X

for busbar end lead up to 2500 A


or 1 to 4 cables / phase

Core drill holes on request

for busbar end lead > 2500 A


or 5 to 7 cables / phase

Openings for outgoing feeders do not cover


with supporting structure
Area for possible longitudinal bracings

Switchgear according to:


IEC 60298 (VDE 0670 part 6)
Appendix AA, criteria 1-6 (operators end)
Rated short-time withstand current: 25 kA / 1 sec.

1
2
3
4

Spacer bars made of steel


50x40x4 or U 50
not included in scope of supplies of ALSTOM Sachsenwerk GmbH
Smaller than specified dimension on request
Facing up to room ceiling to be executed by the customer!
Minimum aisle width to move the drawing unit in front of the switchgear

Dimensional accuracy of the spacer bars


Flatness
Straightness
Parallelism
Difference in height

of

2 mm per meter
2 mm per meter
2 mm per meter
opposite points of spacer bars 2 mm

Weights* (kg):
B

-1250 A

-2000 A

> 2000 A

700

935

995

1165

900

965

1025

1195

1200

1005

1065

1235

* Weight incl. 3 current converters


Weight for 1 voltage converter DIN 42600 part 8: 19 kg

The total weight results from the addition of the individual weights,
depending on the components fitted in the switchgear.

Note:
A pressure calculation should be performed to determine the
compressive strength of the building and of intermediate floors!
Any conditions deviating from this drawing call for an enquiry
at ALSTOM Sachsenwerk GmbH!

77

The technical details and product characteristics described correspond


Printed in the Federal Republic of Germany
SW.06.32 / 1298 EN

ALSTOM Sachsenwerk GmbH Rathenaustrae 2 D-93055 Regensburg P.O.B. 10 01 55 D-93001 Regensburg