Liquid Level
Displacer Transmitter
Notes
Notes contain information that augments or clarifies an
operating step. Notes do not normally contain actions.
They follow the procedural steps to which they refer.
Cautions
Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce a
components mechanical integrity. Cautions are also
used to alert the technician to unsafe practices or the
need for special protective equipment or specific materials. In this manual, a caution box indicates a potentially
hazardous situation which, if not avoided, may result in
minor or moderate injury.
Warnings
Warnings identify potentially dangerous situations or
serious hazards. In this manual, a warning indicates an
imminently hazardous situation which, if not avoided,
could result in serious injury or death.
Safety Messages
Follow all standard industry procedures for servicing
electrical and computer equipment when working with
or around high voltage. Always shut off the power supply
before touching any components.
Electrical components are sensitive to electrostatic
discharge. To prevent equipment damage, observe safety
procedures when working with electrostatic sensitive
components.
WARNING! Explosion hazard. Do not connect or
disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
E3 Modulevel
Displacer Level Transmitter
Installation, Operation and Maintenance Manual
Table of Contents
1.0 FOUNDATION fieldbus Overview
1.1 Description ...............................................................4
1.2 Benefits .....................................................................5
1.3 Device Configuration................................................5
1.4 Intrinsic Safety ..........................................................6
1.5 Link Active Scheduler (LAS).....................................6
2.0 QuickStart Installation
2.1 Getting Started..........................................................7
2.1.1 Equipment and Tools .....................................7
2.1.2 Configuration Information.............................7
2.2 QuickStart Mounting................................................7
2.2.1 Tank Top........................................................7
2.2.2 External Chamber ..........................................8
2.3 QuickStart Wiring ....................................................8
2.4 QuickStart Configuration .........................................9
3.0 Complete Installation
3.1 Unpacking ..............................................................10
3.2 Electrostatic Discharge (ESD) Handing Procedure..10
3.3 Before You Begin.....................................................11
3.3.1 Site Preparation ............................................11
3.3.2 Equipment and Tools ...................................11
3.3.3 Operational Considerations..........................11
3.4 Mounting................................................................12
3.4.1 Tank Top Installation (E3A & E3B).............12
3.4.2 External Chamber Installation
(E3C, E3D, E3E, E3F) ................................13
3.5 Wiring ....................................................................14
3.5.1 General Purpose or Non-Incendive ..............15
3.5.2 Intrinsically Safe ...........................................15
3.5.3 Explosion Proof............................................16
4.0 Reference Information
4.1 Overview.................................................................17
4.1.1 Universal Fieldbus Block Parameters ............17
4.2 Resource Block........................................................18
4.3 Modulevel Transducer Block..................................21
4.3.1 Modulevel Transducer Block Parameters .....21
4.3.2 Password Parameters.....................................21
4.3.3 E3 Modulevel Configuration Parameters ....22
4.3.4 Offset Description........................................22
4.4 User-Calibration Parameters....................................22
4.4.1 User Calibration Procedure ..........................22
4.4.2 Factory Parameters .......................................24
4.4.3 Firmware Version .........................................24
4.5 Analog Input Block.................................................24
4.5.1 AI Block Parameters .....................................24
48-640 E3 Modulevel Displacer Level Transmitter - FOUNDATION fieldbus
5.0
6.0
7.0
8.0
1.0
1.1
Description
FOUNDATION fieldbus is a digital communications system
that serially interconnects devices in the field. A Fieldbus
system is similar to a Distributed Control System (DCS)
with two exceptions:
Although a FOUNDATION fieldbus system can use the same
physical wiring as an existing 420 mA device, Fieldbus
devices are not connected point to point, but rather are
multidropped and wired in parallel on a single pair of wires
(referred to as a segment).
FOUNDATION fieldbus is a system that allows the user to
distribute control across a network. Fieldbus devices are
smart and actually maintain control over the system.
Unlike 420 mA analog installations in which the two wires
carry a single variable (the varying 420 mA current), a digital communications scheme such as FOUNDATION fieldbus
considers the two wires as a network. The network can carry
many process variables as well as other information. The
E3 Modulevel transmitter is a FOUNDATION fieldbus registered device that communicates with the H1
FOUNDATION fieldbus protocol operating at 31.25
kbits/sec. The H1 physical layer is an approved IEC 61158
standard.
PC
Power
Conditioner
Terminator
Terminator
Power Supply
Control Room
Figure 1
typical Fieldbus installation
1.2
Benefits
The benefits of FOUNDATION fieldbus can be found
throughout all phases of an installation:
1. Design/Installation: Connecting multiple devices to a single
pair of wires means less wire and fewer I/O equipment.
Initial Engineering costs are also reduced because the
Fieldbus Foundation requires interoperability, defined as
the ability to operate multiple devices in the same system,
regardless of manufacturer, without a loss of functionality.
All FOUNDATION fieldbus devices must be tested for
interoperability by the Fieldbus Foundation. Magnetrol
E3 MODULEVEL FOUNDATION fieldbus device registration
information can be found at www.fieldbus.org.
2. Operation: With control now taking place within the
devices in the field, better loop performance and control are
the result. A FOUNDATION fieldbus system allows for multiple variables to be brought back from each device to the
control room for additional trending and reporting.
3. Maintenance: The self-diagnostics residing in the smart
field devices minimizes the need to send maintenance
personnel to the field.
1.3
Device Configuration
Device Descriptions
The function of a FOUNDATION fieldbus device is determined by the arrangement of a system of blocks defined by
the Fieldbus Foundation. The types of blocks used in a typical User Application are described as follows:
Resource Block describes the characteristics of the
FOUNDATION fieldbus device such as the device name,
manufacturer, and serial number.
Function Blocks are built into the FOUNDATION fieldbus
devices as needed to provide the desired control system
behavior. The input and output parameters of function
blocks can be linked over the Fieldbus. There can be
numerous function blocks in a single User Application.
Transducer Blocks contain information such as calibration
parameters and sensor type. They are used to connect the
sensor to the input function blocks.
An important requirement of Fieldbus devices is the interoperability concept mentioned earlier. Device Description
(DD) technology is used to achieve this interoperability.
The DD provides extended descriptions for each object and
provides pertinent information needed by the host system.
Intrinsic Safety
The H1 physical layer supports Intrinsic Safety (IS) applications with bus-powered devices. To accomplish this, an IS
barrier or galvanic isolator is placed between the power
supply in the safe area and the device in the hazardous area.
H1 also supports the Fieldbus Intrinsically Safe Concept
(FISCO) model which allows more field devices in a
network. The FISCO model considers the capacitance and
inductance of the wiring to be distributed along its entire
length. Therefore, the stored energy during a fault will be
less and more devices are permitted on a pair of wires.
Instead of the conservative entity model, which only allows
about 90 mA of current, the FISCO model allows a maximum of 110 mA for Class II C installations and 240 mA
for Class II B installations.
FISCO certifying agencies have limited the maximum
segment length to 1000 meters because the FISCO model
does not rely on standardized ignition curves.
The E3 MODULEVEL is available with entity IS, FISCO IS,
FNICO non-incendive, or explosion proof approvals.
1.5
2.0
QuickStart Installation
2.1
Getting Started
Question
LvlUnits
Lvl Ofst
Proc SG
ProcTemp
answer
2.2
QuickStart Mounting
3. Position the head flange gasket on the vessel flange and gently lower the displacer into the vessel. To prevent damage to
the stem/spring assembly, avoid tipping the unit or, in any
way, putting lateral forces on the stem.
4. Align the flanges and ensure that the gasket is seated properly.
5. Install the flange bolts and nuts and tighten alternating nuts
in a star pattern. Flange bolting torque specifications are
listed on page 12.
2.2.2 External Chamber
Black (-)
(+)
(-)
Protective
Terminal
Figure 2
integral transmitter Wiring
WARNING: Explosion hazard. Do not connect or disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
Red (+)
Green
Ground
Screws
QuickStart Wiring
NOTE: Ensure that the electrical wiring to the E3 transmitter is complete and in compliance with all regulations and codes.
2.4
Enter
QuickStart Configuration
1.
Down
Up
Figure 3
2.
3.
4.
5.
6.
Liquid
Level
7.
Displacer
Process
S.G.
Operating
Level Offset
Temp.
Figure 4
tank top Mounted
installation
Proc SG
(xxx)
ProcTemp
xxx
The following two parameters must be entered if the default values are
not satisfactory.
Liquid
Level
Process S.G.
LvlUnit
(select)
Lvl Ofst
(xxx)
Level Offset
Operating
Temp.
Figure 5
Chamber type installation
Side-Side Process Connections
3.0
Complete Installation
3.1
Unpacking
Unpack the instrument carefully. Take care not to bend the
displacer stem or enclosing tube. Ensure all components
have been removed from the packing material. Check all the
contents against the packing slip and report any discrepancies to the factory.
Before proceeding with the installation, do the following:
Inspect all components for damage. Report any damage to
the carrier within 24 hours.
On chambered units, remove the shipping strap and wire
assembly holding the displacer in place. This assembly must
be removed through the bottom chamber connection before
start-up.
Serial Number
3.2
10
3.3
11
3.4
Mounting
The E3 MODULEVEL transmitter can be mounted to a
tank using a variety of configurations and process connections. Generally, either a threaded, welded or flanged connection is used with an external cage. A flanged connection
is always used on a tank top model. For information
about the sizes and types of connections available, see
Model Numbers, Section 8.7.
Ensure all mounting connections are in place on the tank
and properly sized for the specific unit being installed.
Compare the model on the nameplate with the product
information to ensure the MODULEVEL transmitter is
correct for the intended installation.
If the MODULEVEL must be insulated, DO NOT insulate
the transmitter head, e-tube or finned extensions.
Flange Bolting
E3A, E3B
E-tube
n/a
110120 ft-lbs
180200 ft-lbs
180200 ft-lbs
370400 ft-lbs
400450 ft-lbs
675725 ft-lbs
Liquid
Level
Displacer
Figure 6
tank top Mounted
installation
12
Figure 7
tank top Mounted
with Stilling Well
Size
Figure 8
transmitter Head
Lock Screws
13
To install:
1. Align the MODULEVEL process connections with
those on the vessel and attach accordingly, based upon the
connection type. Appropriate gaskets and bolting will be
required for flanged connections. Install the flange bolts and
nuts and tighten alternating nuts in a star pattern. Flange
bolting torque specifications are listed on page 12.
Liquid
Level
Caution: All MODULEVEL units are shipped from the factory with the
enclosing tube tightened and the transmitter head set
screws locked to the enclosing tube. Failure to loosen the
set screws prior to repositioning the supply and output connections may cause the enclosing tube to loosen, resulting
in the possible leakage of the process liquid or vapor.
3.5
Black (-)
Red (+)
(+)
Green
Ground
Screws
Wiring
(-)
Terminal
Figure 10
Wiring diagram
14
(-) negative
(+) positive
Power Supply
24 VDC
Figure 11
G.P./i.S./Explosion Proof Model
White
Black
Green
Black
Red
Black
1 2 3 4 5 6
Figure 12
integral & Remote terminal Boards
An intrinsically safe (IS) installation potentially has flammable media present. An approved IS barrier must be installed
in the non-hazardous (safe) area. Consult factory for agency
drawing.
48-640 E3 Modulevel Displacer Level Transmitter - FOUNDATION fieldbus
15
White
Black
Green
Black
Red
Black
Integral
Terminal Board
White
Black
Green
Black
Red
Black
Conduit seal
within 18" of
this housing
entry for
explosion proof
installation
Remote
Terminal Board
Figure 13
Remote Mount Wiring Connections
16
4.0
Function Blocks
4.1
Overview
The E3 MODULEVEL Liquid Level Displacer Transmitter
operates on the Archemedes principle of buoyancy force.
Refer to Bulletin 48-635 for more detailed information on
the MODULEVEL transmitter.
The E3 MODULEVEL is a liquid level transmitter with
four FOUNDATION fieldbus Blocks (one Resource Block,
one Transducer Block, one Analog Input Function block,
and one PID Function block. The idea of Function Blocks,
which a user can customize for a particular application, is a
key concept of Fieldbus topology. Function Blocks consist
of an algorithm, inputs and outputs, and a user-defined
name.
The TRANSDUCER block output is available to the
network through the ANALOG INPUT block.
The ANALOG INPUT block (AI) takes the TRANSDUCER
block level or density value and makes it available as an
analog value to other function blocks. The AI block has
scaling conversion, filtering, and alarm functions.
17
4.2
Resource Block
The RESOURCE block contains data specific to the
E3 MODULEVEL transmitter, along with some
information about the firmware.
MODE_BLK: Must be in AUTO in order for the remaining blocks in the transmitter to operate.
NOTE: A Resource Block in out of service will stop all function block
execution in the transmitter.
18
FEATURES: a list of the features available in the transmitter. The Model E3 features include Reports, and Software
Write Locking.
FEATURES_SEL: allows the user to turn Features on or off.
CYCLE_TYPE: identifies the block execution methods that
are available.
CYCLE_SEL: allows the user to select the block execution
method.
MIN_CYCLE_T: the time duration of the shortest cycle
interval. It puts a lower limit on the scheduling of the
resource.
NV_CYCLE_T: the minimum time interval between copies
of non-volatile (NV) parameters to NV memory. NV memory is only updated if there has been a significant change in
the dynamic value and the last value saved will be available
for the restart procedure. A value of 0 means it will never
be automatically copied. Entries made by human interface
devices to NV parameters are copied to non-volatile memory
at the time of entry.
NOTE: After completing a large copy, allow several minutes before
removing power from the E3 MODULEVEL transmitter to ensure
that all data has been saved.
19
20
4.3
21
Liquid
Level
Process S.G.
Level Offset
Operating
Temp.
Figure 14
Chamber type installation
Side-Side Process Connections
On side-side mounted models E3E and E3F, the zero reference is the centerline of the bottom-side process connection.
Unit is shipped from factory with Level Offset = 0.
Displacer
Process
S.G.
Operating
Level Offset
Temp.
Figure 15
top Mount installation
4.4
User-Calibration Parameters
, then
again.
23
4.5
PV: Either the primary analog value for use in executing the
function, or a process value associated with it.
OUT: The primary analog value calculated as a result of
executing the function block.
SIMULATE: Allows the transducer analog input or output
to the block to be manually supplied when simulate is
enabled. When simulate is disabled, the simulate value and
status track the actual value and status.
24
25
NOTE: This can be caused by the Resource Block being OOS or the AI
Block not scheduled for execution.
*AI OUT*
######uu
Out Value
Figure 16
analog input out display
27
4.6
PID Block
The PID Function Block contains the logic necessary to perform Proportional/Integral/Derivative (PID) control. The
block provides filtering, set point limits and rate limits, feedforward support, output limits, error alarms, and mode shedding.
Although most other function blocks perform functions
specific to the associated device, the PID block may reside
in any device on the network. This includes valve, transmitter, or the host itself.
The Model E3 PID Block implementation follows the specifications documented by the Fieldbus Foundation.
29
30
5.0
2
3
4
5
*Status*
*PV-Lvl*
*AI Out*
PV-Lvl
xx.xx lu
AI Out
Proc SG
x.xxx sg
ProcTemp
xxx F
Password
action
Comment
Transmitter Display
MeasType = Level
None
Transmitter Display
None
Transmitter Display
User
User
User
None
LvlUnits
Lvl Ofst
xx.xx lu
User
LVDT Damp
xx s
User
0 to 45 sec
User
User
User
None
Transmitter Display
Product identification
Firmware version
None
9
10
11
12
13
14
Trim Lvl
xx.xx lu
New Pass
xxx
Language
(select)
E3 ModFF
Ver 1.0
DispFact
(select)
History
Status
None
31
5.1
15
16
17
18
19
20
21
22
23
24
25
26
27a
Run Time
xxxx.x h
History
Reset
MeasType
(select)
Model
(select)
SpringSG
(select)
SprgRate
x.x
SprgMatl
TempLimt
xxx F
Length
xx.xx lu
Diameter
x.xxx in
Weight
xx.x oz
CalSelct
(select)
Factory Cal
Menu
32
AdjSnrLo
AdjSnrHi
Conv Fct
xxxx
Scl Ofst
xxx
LVDT%
xx.xx %
Chan 0
Chan 1
NodeAddr
NSP Value
ElecTemp
xxx C
Max Temp
xxx C
Min Temp
xxx C
Password
None
SuperUser
action
Comment
Press
and select Yes to
clear history
SuperUser
Factory Set
SuperUser
Factory Set
Select from E3A, E3B, E3C, E3D, E3E, E3F, E31, E32, E33,
E34, E35, E36, Custom
SuperUser
Factory Set
SuperUser
Factory Set
SuperUser
Factory Set
SuperUser
Factory Set
SuperUser
Factory Set
SuperUser
Factory Set
SuperUser
Factory Set
User
None
Press
to display the User
Calibration sub-menu
CalSelct = Factory
Submenu on page 33
None
Press
to display the User
Calibration sub-menu
CalSelct = User
Submenu on page 33
None
None
Diagnostic Display
Diagnostic Display
None
Diagnostic Display
None
Diagnostic Display
None
Diagnostic Display
None
None
SuperUser
SuperUser
Diagnostic Display
Diagnostic Display
Diagnostic Display
Diagnostic Display
None
Diagnostic Display
SuperUser
Diagnostic Display
SuperUser
Diagnostic Display
5.1
LVDT%
xx.xx %
Calib SG
x.xxx sg
DrySensr
xx.xx %
SnrCalLo
xx.xx %
LvlCalLo
xx.xx lu
SnrCalHi
xx.xx %
LvlCalHi
xx.xx lu
Escape
Password
None
action
Comment
Diagnostic display
Factory
Factory set
Factory
Press
and
simultaneously to capture
current sensor output
Factory
Press
and
simultaneously to capture
current sensor output
Factory
Factory
Factory
None
Press
and
simultaneously to capture
current sensor output
Press
to exit Calibration
sub-menu; Returns to Factory
Menu
33
Simulation Feature
The E3 MODULEVEL with FOUNDATION fieldbus supports the Simulate feature in the Analog Input block. The
Simulate feature is typically used to exercise the operation of
an AI block by simulating a TRANSDUCER block input.
This feature can not be activated without the placement of a
hardware jumper. This jumper is installed as standard on
the Model E3, and is placed in an inconvenient location to
avoid inadvertent disabling of this feature.
7.0
Documentation
The following two tables are examples of data sheets
describing what information is need to fully specify a
Fieldbus device. The first table shows one device per page,
while table 2 is intended for multiple devices.
Refer to FOUNDATION fieldbus System Engineering
GuidelinesAG-181 for additional information. This
document can be found at www.fieldbus.org.
34
7.1
Segment information
Arithmetic (A)
Execution Time (msec)
Digital Alarm (DA)
Execution Time (msec)
Calculate
Execution Time (msec)
Analog Alarm (AA)
Execution Time (msec)
Miscellaneous information
Device:
Segment #
NO
Deadtime (D)
Execution Time (msec)
Device Lift-off (minimum) voltage:
Manual Loader
Execution Time (msec)
Proportional/Integral/Derivative
(PID)
Execution Time (msec)
NO
DD Revision:
NOTES:
Proportional/Derivative (PD)
Execution Time (msec)
Ratio
Number
Execution Time (msec)
35
7.2
10
11
12
taG nuMBER
Number of AIs
AI Execution Time (msec)
Number of AOs
AO Execution Time (msec)
Number of SSs
SS Execution Time (msec)
Number of TOTs
TOT Execution Time (msec)
Number of ARs
AR Execution Time (msec)
Number of PIDs
PID Execution Time (msec)
Number of
Execution Time
Number of
Execution Time
Number of
Execution Time
Number of
Execution Time
Number of
Execution Time
Number of
Execution Time
Number of
Execution Time
Channel
I.S. Segment (If applicable)
LAS Capable (Yes/No)
DD Revision
ITK Revision
Polarity Sensitive (Yes/No)
CFF Revision
36
8.0
Electronics
Enclosure
Wiring Board
Moving
LVDT Core
Reference Information
LVDT
Printed
Circuit Board
Display
8.1
Description
The E3 MODULEVEL is a level transmitter which utilizes
simple buoyancy principles in combination with a precision
range spring and a highly accurate LVDT (linear variable
differential transformer) to detect and convert liquid level
movement into a stable output value. The electronics are
housed in an ergonomic, dual-compartment enclosure
which is angled for ease of wiring and calibration.
Keypad
Enclosing Tube
Stem
Range Spring
8.2
Theory of Operation
The Electronic MODULEVEL Displacer Level Transmitter
relies on the principles of buoyancy to convert mechanical
movement to an electronic output. See Figure 17.
According to Archimedes principle, the buoyancy force acting on an object immersed in liquid is equal to the mass of
the liquid displaced. As the level changes, the volume of displacer submerged in the liquid changes, thus varying the
buoyancy force acting on the displacer. This change is
detected by the precision range spring from which the displacer hangs, causing it to elongate or compress. The change
in spring length causes movement of a special LVDT core
which is mounted on a rigid stem attached to the spring.
External cage
8.2.2 LVdt
Figure 17
Electronic Modulevel
Components
37
8.2.3 interface
Troubleshooting
The E3 MODULEVEL displacer transmitter is designed,
engineered and constructed for trouble-free operation over a
wide range of operating and application conditions. Below,
common transmitter problems are discussed in terms of
their symptoms and corrective actions.
38
Problem
Solution
Improperly wired or
damaged wiring.
Defective electronics.
Liquid turbulence.
Bent stem impeding smooth Review Status History for Surge event. Inspect stem and replace if
core movement
damaged.
Non-linear output.
Bent stem.
39
1.
2.
3.
4.
5.
Figure 18
LVdt Six-Pin Connector
6.
40
Label
Bit #
Value
PV Status
Quality
Mode
OK
11
0x0800
Good
Non-Specific
Not Limited
Mode
User Access
0x0004
Bad
OOS
Not Limited
Mode
Factory Access
14
0x4000
Bad
OOS
Not Limited
Faults
Default Params
12
0x1000
Bad
Configuration Error
Not Limited
Faults
Primary Fault
0x0200
Bad
Device Failure
Constant Limited
Faults
Core Drop
0x0100
Bad
Sensor Failure
Low Limited
Faults
SecFaultHi
10
0x0400
Bad
Sensor Failure
High Limited
13
0x2000
Bad
Sensor Failure
Low Limited
PV Sub Status
Limit
Faults
SecFaultLo
Warning
Default Cal
0x0020
No Effect
No Effect
No Effect
Warning
Hi Temperature
0x0010
No Effect
No Effect
No Effect
Warning
Lo Temperature
0x0008
No Effect
No Effect
No Effect
Warning
Cal Span
0x0040
No Effect
No Effect
No Effect
Warning
Initializing
0x0002
Uncertain
Initial Value
Constant Limited
Faults
Fault 1
15
0x8000
No Effect
No Effect
No Effect
Warning
Warning 2
0x0001
No Effect
No Effect
No Effect
Warning
Warning 1
0x0080
No Effect
No Effect
No Effect
41
The next set of conditions is the device warnings. The condition will not jeopardize the level measurement. However,
knowledge of the condition may be useful in troubleshooting
the device.
The following table describes the conditions that can be
seen in Device Status:
display Message
action
Comment
OK
None
User Access
Factory Access
Default Params
Primary Fault
LVDT Primary circuit open condition. Check LVDT winding resistance. Replace LVDT if values
are out of range.
Core Drop
Sec Fault Hi
A/D readings from LVDT secondary Check for broken spring or leaking displacer. This fault disabled
windings are below expected range. when measurement type is interface or density.
Bad LVDT wiring connection.
Default Cal
Consult factory.
Hi Temperature
Present temperature in electronics com- 1) Transmitter may need to be moved to ensure ambient
partment is above 80 C.
temperature is within specification.
2) Change to remote mount transmitter.
Lo Temperature
Cal Span
Initializing
None
* Can occur when unit is designed for interface and no liquid is on the displacer.
42
number of Spurs
1 device
2 devices
3 devices
4 devices
2532
1924
1518
1314
112
Pair
Shield
twisted
Size
Length
type
Single
Yes
Yes
Multi
Yes
Yes
Multi
No
Yes
Multi
Yes
No
43
8.4
Agency Approvals
agency
Model
FM
EXX-XXXX
x11,
x21,
x31,
x41,
x51,
x61,
x81,
x12,
x22,
x32,
x42,
x52,
x62,
x82,
x13,
x23,
x33,
x43,
x53,
x63,
x83,
x14
x24
x34
x44
x54
x64
x84
EXX-XXXX
x15,
x25,
x35,
x45,
x55,
x65,
x85,
x16,
x26,
x36,
x46,
x56,
x66,
x86,
x17,
x27,
x37,
x47,
x57,
x67,
x87,
x18
x28
x38
x48
x58
x68
x88
EXX-XXXX
x11,
x21,
x31,
x41,
x51,
x61,
x81,
x12,
x22,
x32,
x42,
x52,
x62,
x82,
x13,
x23,
x33,
x43,
x53,
x63,
x83,
x14
x24
x34
x44
x54
x64
x84
non-incendive
Class I, Div. 2; Groups A, B, C, D
Class II, Div. 2; Groups E, F, G
Class III, Div. 2; T4
Type 4X, IP66
EXX-XXXX
x11,
x21,
x31,
x41,
x51,
x61,
x81,
x12,
x22,
x32,
x42,
x52,
x62,
x82,
x13,
x23,
x33,
x43,
x53,
x63,
x83,
x14
x24
x34
x44
x54
x64
x84
approval
Explosion Proof
Class I, Div. 1; Groups B, C, D
Type 4X, IP66
intrinsically Safe
Class I, Div. 1; Groups A, B, C, D
Class II, Div. 1; Groups E, F, G
Class III, T4
Entity
Type 4X, IP66
44
transmitter Codes
digits 8, 9 and 10
agency
Model
CSa
EXX-XXXX
x11,
x31,
x51,
x81,
EXX-XXXX
x15,
x35,
x55,
x85,
EXX-XXXX
x11,
x31,
x51,
x81,
approval
Explosion Proof
Class I, Div. 1; Groups B, C, D
Class II, Div. 1; Groups E, F, G
Class III, T4
Type 4X, IP66 & IP67
intrinsically Safe
Class I, Div. 1; Groups A, B, C, D
Class II, Div. 1; Groups E, F, G
Class III, T4
Entity
Type 4X, IP66
Non Incendive
Class I, Div. 2; Groups A, B, C, D
Class II, Div. 2; Groups E, F, G
Class III, T4
Type 4X, IP66
agency
Model
atEX
EXX-XXXX
x1E,
x2E,
x3E,
x4E,
x5E,
x6E,
x8E,
x1F,
x2F,
x3F,
x4F,
x5F,
x6F,
x8F,
x1G,
x2G,
x3G,
x4G,
x5G,
x6G,
x8G,
x1H
x2H
x3H
x4H
x5H
x6H
x8H
EXX-XXXX
x1a,
x2a,
x3a,
x4a,
x5a,
x6a,
x8a,
x1B,
x2B,
x3B,
x4B,
x5B,
x6B,
x8B,
x1C,
x2C,
x3C,
x4C,
x5C,
x6C,
x8C,
x1d
x2d
x3d
x4d
x5d
x6d
x8d
EXX-XXXX
x1a,
x2a,
x3a,
x4a,
x5a,
x6a,
x8a,
x1B,
x2B,
x3B,
x4B,
x5B,
x6B,
x8B,
x1C,
x2C,
x3C,
x4C,
x5C,
x6C,
x8C,
x1d
x2d
x3d
x4d
x5d
x6d
x8d
non-Sparking
ATEX Ex II 3 G Ex ic II T6
EN 60079-0
EN 60079-11
94/9/EC
EXX-XXXX
Flameproof
IECEx Ex d IIC T6 Ga/Gb
IEC 60079-0
IEC 60079-1
IEC 60079-26
EXX-XXXX
iEC
approval
Flameproof
ATEX Ex II 1/2 G Ex d IIC T6
EN 60079-0, EN 60079-1,
EN 60079-26
94/9/EC
intrinsically Safe
ATEX Ex II 1 G Ex ia IIC T4
EN 60079-0, EN 60079-11,
EN 60079-26, EN 60079-27
94/9/EC
intrinsically Safe
IECEx Ex ia IIC T4 Ga
IEC 60079-0
IEC 60079-11
IEC 60079-26
IEC 60079-27
45
46
8.5
Parts
3
4
4c
7
11
12
13
Z30-9151-003
Z30-9151-004
012-2201-237
089-6606-004
089-6606-005
089-6606-009
089-6606-010
089-6606-013
089-6606-014
089-6606-015
089-6606-016
089-6606-017
089-6606-018
Consult
Consult
Consult
Consult
089-7827-007*
089-7827-008*
089-7827-009*
089-7827-010*
Electronic Module
Wiring Board
Transmitter Housing O-rings (2)
Meter/Bezel Compartment Cover
Wiring Compartment Housing Cover
Terminal Junction Box Covers (2)
LVDT Assembly
LVDT Housing Cover
7
8
9
10
11
12
13
Factory
Factory
Factory
Factory
089-7837-001
089-7837-002
089-7837-003
012-2222-123
030-3609-001
037-7917-001
* Field replacement of this part requires a user calibration of the repaired unit.
** Contains LVDT Core, Item 20.
Parts identification
1
2
3
4a
4b
4c
5
6
Z31-2845-001*
037-3226-0xx
037-3227-0xx
5
4b
4c
3
11
7
4a
13
12
3
Figure 19
Remote
transmitter
11
4c
47
48
*
**
Spring Kits* 16
Stem Kit*
15
089-5565-004
089-5565-003
089-5565-003
089-5565-008
089-5565-007
089-5565-007
089-5565-002
089-5565-001
089-5565-001
089-5565-006
089-5565-005
089-5565-005
089-5565-006
089-5565-005
089-5565-005
089-5565-004
089-5565-008
089-5565-002
089-5565-006
089-5565-004
089-5565-008
089-5565-002
089-5565-006
089-5565-013**
089-5565-015**
089-5565-014**
089-5565-016**
inconel
316 SS
089-5340-002
089-5340-005
089-5340-008
n/a
089-5340-003
089-5340-006
089-5340-009
089-5340-002 089-5340-001
089-5340-005 089-5340-004
089-5340-008 089-5340-007
089-5340-002
089-5340-005
n/a
089-5340-008
089-5340-003
089-5340-006
n/a
089-5340-009
089-5340-010
n/a
089-5340-011
089-5340-011
Field replacement of this part requires a user calibration of the repaired unit.
For ultra high temperature LVDT stem kits, LVDT core is not included.
Cage
Pressure
Rating
150# ANSI
300# ANSI
600# ANSI
900# ANSI
1500# ANSI
2500# ANSI
Head
Flange
Size
3"
4"
6"
3"
4"
6"
3"
4"
6"
3"
4"
6"
4"
6"
4"
6"
316 SS
89-4242-017
89-4242-021
89-4242-027
89-4242-018
89-4242-022
89-4242-028
89-4242-019
89-4242-023
89-4242-029
89-4242-020
89-4242-024
89-4242-030
89-4242-025
89-4242-031
89-4242-026
89-4242-032
4a
Meter/Bezel
Compartment
Housing Cover
4b
Wiring
Compartment
Housing Cover
High Pressure
900, 1500, 2500#,
Ultra High Temp LVDT
S.G. Range
0.55 1.09
89-6125-010
89-6125-011
89-6125-012
89-6125-013
n/a
n/a
n/a
n/a
n/a
14"
32"
48"
60"
72"
84"
96"
108"
120"
S.G. Range
0.230.54 & 0.551.09
1.10 2.2
89-6125-001
89-6126-001
89-6125-002
89-6126-002
89-6125-003
89-6126-003
89-6125-004
89-6126-004
89-6125-005
89-6126-005
89-6125-006
89-6126-006
89-6125-007
89-6126-007
89-6125-008
89-6126-008
89-6125-009
89-6126-009
15 Stem Assembly
20 LVDT
Core
Transmitter
3 Housing
O-rings
5 LVDT
Assembly
7
LVDT
Cover O-ring
Electronic Module
Wiring
Board
18 displacer Kits*
10 Grip Ring/Spacer
8
TFE Spacer
16
Range Spring
in Protector
Enclosing Tube
and Gasket
14
19
Cotter
Pins
Flange 17
or
Flange
Assembly
19 Cotter pins
all units
10-5203-001
Kit definitions
Head flange kit includes: head flange, studs, nuts and gasket
(top mounting units) or head flange only (chambered unit)
E-tube kits include: E-tube, E-tube extension(s) and gasket
Stem kits include: stem assembly, stem extension, LVDT core
18
Figure 20
Displacer
Replacement Parts
Electronic Module
FOUNDATION fieldbus
Z31-2845-001*
89-7827-010*
Field replacement of this part requires a user calibration of the repaired unit.
Contains LVDT Core, Item 20.
49
8.6
Specifications
8.6.1 Functional
System design
Measurement Principle
input
Measured Variable
Physical Range
Up to 120" (300 cm) based on displacer length (C/F for longer ranges)
user interface
Keypad
Indication
Digital Communication
LAS capable
DEV Revision
0X01
Available Blocks
Polarity Sensitive
No
Damping
15 msec
9 to 32 VDC
IS/FISCO/FNICO
9 to 32 VDC
Cable Entry
Ingress Protection
Chamber
Materials
Carbon steel
316/316L stainless steel
Wetted parts
Process connections
Tank Top:
Chambered:
50
Process Conditions
Steam applications:
-20 to +800 F (-29 to +427 C)
Non-steam applications:
Environment
Electronics Operating Temperature
-40 to +176 F
(-40 to +80 C)
-5 to +160 F
(-20 to +70 C)
Storage Temperature
-50 to +185 F
(-40 to +85 C)
Humidity
0-99%, non-condensing
Electromagnetic Compatibility
Shock Class
Vibration Class
Altitude
2000 m
Pollution Degree
Repeatability
Hysteresis
Response Time
<1 second
Warm-up Time
<5 seconds
Repeatability
Consult factory for low temperature applications down to -330 F (-200 C).
With aluminum housing only. Does not apply to models with 316 SS
transmitter housings.
51
4.02
(102)
" NPT
Dual Conduit
Entries
" NPT
Dual Conduit
Entries
4.02
(102)
" NPT
Dual Conduit
Entries
ANSI standard
B
D
C
2.81
(71)
0.87
(22)
3.86
(98)
Level range
3.95
(100)
H
6.28
(159)
10.32
(262)
8.10
(206)
4.04
(103)
70
Dia.
Figure 21
Figure 22
Figure 23
3.99
(101)
2.84 502
(72) (128)
15.95
(405)
A minus 3.34 (85)
Level
range
Level
range
G
E
5.31
(135)
45
6.25 (159)
5.42
(138)
15.95
(405)
6.48
(165)
4.02
(102)
52
3.85
(98)
3.96 (101)
8.73
(222)
2.39
(61)
Up to 75' (23 m) of connecting cable part
number 037-3226-0XX or 037-3227-0XX,
run in conduit.
Last 2 digits in part number are cable
length in feet.
Cable must be ordered separately.
E
F
Figure 24
Figure 25
Cage Press.
Rating
Process
Conn. Size
Spring
S.G. Range
0.23 0.54
112"
0.55 1.09
1.10 2.20
1, 2, 3, 4, 5, 6
0.23 0.54
2"
0.55 1.09
1.10 2.20
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
112"
0.55 1.09
2"
0.55 1.09
900# anSi
1500# anSi
2500# anSi
900#
1500#
2500#
dimension
B
6.75
(171)
4.75
(121)
4.75
(121)
6.75
(171)
4.75
(121)
4.75
(121)
6.75
(171)
6.75
(171)
6.75
(171)
6.75
(171)
6.75
(171)
6.75
(171)
8.25
(210)
8.25
(210)
8.25
(210)
8.25
(210)
8.25
(210)
8.25
(210)
8.25
(210)
8.25
(210)
9.31
(236)
7.31
(186)
7.31
(186)
9.31
(236)
7.31
(186)
7.31
(186)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
7.31
(186)
7.31
(186)
9.31
(236)
7.31
(186)
7.31
(186)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
9.31
(236)
3.19
(81)
3.19
(81)
3.19
(81)
3.31
(84)
3.31
(84)
3.31
(84)
3.19
(81)
3.31
(84)
3.19
(81)
3.31
(84)
4.00
(102)
4.38
(111)
3.19
(81)
3.31
(84)
3.19
(81)
3.31
(84)
3.19
(81)
3.31
(84)
4.00
(102)
4.38
(111)
7.00
(178)
7.00
(178)
7.00
(178)
7.13
(181)
7.13
(181)
7.13
(181)
7.00
(178)
7.13
(181)
7.00
(178)
8.13
(207)
9.00
(229)
9.81
(249)
7.00
(178)
7.13
(181)
7.00
(178)
7.13
(181)
7.00
(178)
8.13
(207)
9.00
(229)
9.81
(249)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.44
(87)
3.44
(87)
3.44
(87)
3.44
(87)
3.00
(76)
3.00
(76)
3.00
(76)
3.00
(76)
3.44
(87)
3.44
(87)
3.44
(87)
3.44
(87)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.00 + range
(76 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
3.44 + range
(87 + range)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
6.43
(163)
7.43
(189)
10.21
(259)
11.08
(281)
5.43
(138)
5.43
(138)
5.43
(138)
5.43
(138)
6.43
(163)
7.43
(189)
1021
(259)
11.08
(281)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
10.32
(262)
11.60
(295)
11.60
(295)
11.60
(295)
11.60
(295)
11.60
(295)
11.60
(295)
11.60
(295)
11.60
(295)
a dimension
Cage Press. Rating
150# anSi
300# anSi
600# anSi
900# anSi
1500# anSi
2500# anSi
a, B, C
d, E, F
J, K, L
M, n, P
3"
16.97 (431)
24.97 (634)
12.97 (329)
20.97 (533)
4"
16.97 (431)
24.97 (634)
12.97 (329)
20.97 (533)
6"
17.03 (433)
25.03 (636)
13.03 (331)
21.03 (534)
3"
17.16 (436)
25.16 (639)
13.16 (334)
21.16 (537)
4"
17.28 (439)
25.28 (642)
13.28 (337)
21.28 (541)
6"
17.47 (444)
25.47 (647)
13.47 (342)
21.47 (545)
3"
17.53 (445)
25.53 (648)
13.53 (344)
21.53 (547)
4"
17.78 (452)
25.78 (655)
13.78 (350)
21.78 (553)
6"
18.16 (461)
26.16 (664)
14.16 (360)
22.16 (563)
3"
17.78 (452)
25.78 (655)
13.78 (350)
21.78 (553)
4"
18.03 (458)
26.03 (661)
14.03 (356)
22.03 (560)
6"
18.47 (469)
26.47 (672)
14.47 (368)
22.47 (571)
3"
18.16 (461)
26.16 (664)
14.16 (360)
22.16 (563)
4"
18.41 (468)
26.41 (671)
14.41 (366)
22.41 (569)
6"
19.53 (496)
27.53 (699)
15.53 (394)
23.53 (598)
4"
19.28 (490)
27.28 (693)
15.28 (388)
23.28 (591)
6"
20.53 (521)
28.53 (725)
16.53 (420)
24.53 (623)
53
8.7
Model Numbers
Cage side/bottom
316 SS
steel
C
d
Cage side/side
316 SS
steel
E
F
1&4
Std.
4"
8"
12"
8"
Temperature Extension
J
K
L
a
B
C
M
n
P
d
E
F
M
n
P
E
F
Q
3"
n/a
n/a
G
Top Mount
4"
6"
n/a
n/a
H
n/a
n/a
K
Type
NPT
SW
Flange
LEVEL RanGE
All Pressures / 9th Digit = 8
14
32
48
60
356
813
1219
1524
a
B
C
d
72
1829
E
600# or below
84
96
108
2134
2438
2743
F
G
H
120
3048
i
Inches
mm
Code
E
54
F
48-640 E3 Modulevel Displacer Level Transmitter - FOUNDATION fieldbus
outPut/SiL RatinG
FOUNDATION fieldbus
F
MountinG/tEMPERatuRE
integral Mount
Maximum Process Temperature
+550 F (+290 C)
1
+551 to +600 F (+291 to +315 C)
3
Remote Mount
Maximum Process Temperature
4
6
8
+550 F (+290 C)
+551 to +600 F (+291 to +315 C)
+601 to +850 F (+316 to +454 C)
4
"
NPT
1
2 Cast aluminum, FM XP, M20
3 Cast stainless steel, FM/CSA XP, 34" NPT
4 Cast stainless steel, FM XP, M20
1,3,4,6,8
5 Cast aluminum, FM/CSA IS, 34" NPT
6 Cast aluminum, FM IS, M20
7 Cast stainless steel, FM/CSA IS, 34" NPT
8 Cast stainless steel, FM IS, M20
a Cast aluminum, ATEX/IEC IS, 34" NPT
B Cast aluminum, ATEX/IEC IS, M20
C Cast stainless steel, ATEX/IEC IS, 34" NPT
1,3,4,6,8
d Cast stainless steel, ATEX/IEC IS, M20
55
dESiGn tYPE
E3
Cage side/bottom
316 SS
steel
C
d
Cage side/side
316 SS
steel
E
F
integral integral
or
or
Remote transmitter Mounting
Remote Remote
2&5
3&8
6 & 8 Use with Mounting/Temp. codes (9th Digit)
integral
Remote
Std.
4"
Std.
8"
12"
8"
Temperature Extension
Top Mount
4"
n/a
n/a
n/a
n/a
G
H
3"
Type
6"
n/a
n/a
K
NPT
SW
Flange
300# RF
600# RF
900# RF
1500# RF
2500# RF
LEVEL RanGE
All Pressures / 9th Digit = 8
14
32
48
60
356
813
1219
1524
a
B
C
d
72
1829
E
600# or below
84
96
108
2134
2438
2743
F
G
H
120
3048
i
Inches
mm
Code
E
56
F
48-640 E3 Modulevel Displacer Level Transmitter - FOUNDATION fieldbus
outPut/SiL RatinG
FOUNDATION fieldbus
F
MountinG tEMPERatuRE
integral Mount
Maximum Process Temperature
+300 F (+150 C)
1
+301 to +450 F (+151 to +230 C)
2
+451 to +500 F (+231 to +260 C)
3
Remote Mount
Maximum Process Temperature
4
5
6
8
+300
+301
+451
+501
F (+150 C)
to +450 F (+151 to +230 C)
to +500 F (+231 to +260 C)
to +800 F (+261 to +427 C)
9th digit
1,2,3,4,5,6,8
1,2,3,4,5,6,8
57
8.8 References
1. FOUNDATION fieldbus, A Pocket Guide
Ian Verhappen, Augusto Pereira
2. FOUNDATION fieldbusSystem Engineering Guidelines, AG181
PaRaMEtER naME
PaRaMEtER LaBEL
BLOCK_STRUCTURE
1
2
58
itEM
PaRaMEtER naME
PaRaMEtER LaBEL
BLOCK STRUCT
40
HISTORY_CONTROL
History Control
ST_REV
ST REV
41
RESET_HISTORY
Reset History
TAG_DESC
TAG DESC
42
CALIBRATION_SELECT
Calibration Select
STRATEGY
STRATEGY
43
LVDT_OUTPUT
LVDT%
ALERT_KEY
ALERT KEY
44
SENSOR_UNIT
Sensor Unit
MODE_BLK
MODE BLK
45
BLOCK_ERR
BLOCK ERR
46
FACTORY_DRY_SENSOR
UPDATE_EVT
UPDATE EVT
47
BLOCK_ALM
BLOCK ALM
48
TRANSDUCER_DIRECTORY XD DIRECTORY
49
FACTORY_LEVEL_CAL_LO
10
TRANSDUCER_TYPE
XD TYPE
50
FACTORY_LEVEL_CAL_HI
11
XD_ERROR
XD ERROR
51
FACTORY_SG_CAL_LO
Factory SG Cal Lo
12
COLLECTION_DIRECTORY
COLLECT DIR
52
FACTORY_SG_CAL_HI
Factory SG Cal Hi
13
MEASUREMENT_TYPE
Measurement Type
53
USER_DRY_SENSOR
14
PRIMARY_VALUE
Primary Value
54
USER_SENSOR_CAL_LO
15
PRIMARY_VALUE_UNIT
55
USER_SENSOR_CAL_HI
16
LVDT_DAMPING
LVDT Damping
56
USER_LEVEL_CAL_LO
17
PROCESS_SG
Process SG
57
USER_LEVEL_CAL_HI
18
PROCESS_TEMPERTURE
Process Temperature
58
USER_SG_CAL_LO
User SG Cal Lo
19
LEVEL_OFFSET
Level Offset
59
USER_SG_CAL_HI
User SG Cal Hi
20
TRIM_LEVEL
Trim Level
60
ADJUSTED_SENSOR_LO
Adjusted Sensor Lo
21
MODEL_NUMBER
Model Number
61
ADJUSTED_SENSOR_HI
Adjusted Sensor Hi
22
LEVEL_UNIT
Level Unit
62
CONVERSION_FACTOR
Conversion Factor
23
DISPLACER_LENGTH
Displacer Length
63
SCALE_OFFSET
Scale Offset
24
DIAMETER_UNIT
Diameter Unit
64
LVDT_CHANNEL_0
LVDT Channel 0
25
DISPLACER_DIAMETER
Displacer Diameter
65
LVDT_CHANNEL_1
LVDT Channel 1
26
WEIGHT_UNIT
Weight Unit
66
TEMPERATURE_UNIT
Temperature Unit
27
DISPLACER_WEIGHT
Displacer Weight
67
28
SPRING_SG
Spring SG
68
MAX_ELECTRONICS_TEMPERATURE
Max Temperature
29
SPRING_RATE
Spring Rate
69
MIN_ELECTRONICS_TEMPERATURE
Min Temperature
30
SPRING_MATERIAL
Spring Material
70
RESET_ELECTRONICS_TEMPERATURE
Reset Temperatures
31
PROCESS_TEMP_LIMIT
71
LCD_LANGUAGE
LCD Language
32
LOWER_SG
Lower SG
72
NSP_VALUE
NSP Value
33
UPPER_SG
Upper SG
73
FACTORY_PARAM_1
Factory Param 1
34
SPECIFIC_GRAVITY_UNIT
SG Unit
74
FACTORY_PARAM_2
Factory Param 2
35
TRIM_SG
Trim SG
75
NON_VOL_STAT
36
ENTER_PASSWORD
Enter Password
76
DATE_CODE
Date Code
37
NEW_PASSWORD
77
38
DEVICE_STATUS
Device Status
78
FIRMWARE_VERSION
39
HISTORY_STATUS
History Message
Firmware Version
E3 Modulevel
Displacer Level Transmitter
FOUNDATION Fieldbus Configuration Data Sheet
Copy blank page and store calibration data for future reference and troubleshooting.
Item
Value
Value
Value
TROUBLESHOOTING
Working Value
Non-Working Value
Vessel Name
Vessel #
Process Medium
Tag #
Serial #
Model #
Meas Type
Level Units
Process SG
Process Temperature
Level Offset
LVDT Damping
Trim Level
Spring SG
Spring Rate
Spring Material
Temperature Limit
Displacer Length
Displacer Diameter
Displacer Weight
CalSelect
Conv Fct
Scl Ofst
Calib SG
DrySensr
SnrCalLo
LvlCalLo (or SGCalLo)
SnrCalHi
LvlCalHi (orSGCalHi)
Name
Date
Time
59
Service Policy
1.
2.
3.
4.
5.
Company Name
Description of Material
Serial Number
Reason for Return
Application
Copyright 2016 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Performance specifications are effective with date of issue and are subject to change without notice.
Magnetrol, Magnetrol logotype and Modulevel are registered trademarks of Magnetrol International, Incorporated.
CSA logotype is a registered trademark of Canadian Standards Association.
HART is a registered trademark of the HART Communication Foundation.
Inconel is a registered trademark of Special Metals Corporation.
Teflon is a registered trademark of DuPont.
BuLLEtin: 48-640.3
EFFECtiVE: January 2016
SuPERSEdES: June 2015