Вы находитесь на странице: 1из 56

Introduction to Fault

Studies
Prof. Artemio P. Magabo
Prof. Rowaldo R. del Mundo

Department of Electrical and Electronics Engineering


University of the Philippines - Diliman

Per-Unit Quantities
Definition:

Per

Unit Value

Actual Value
Base Value

Note:
1. The per-unit value is a dimensionless quantity.
2. The actual value may be complex but the base
value is always real.
3. Percent Value = Per-Unit Value x 100
Department of Electrical and Electronics Engineering

Advantages of Per-Unit Calculations


1. Manufacturers specify the impedances of their
equipment in percent (or per-unit) using the
nameplate rating of the equipment.

2. The per-unit impedances of electrical


equipment of the same type but different
ratings usually lie within a narrow range. This
makes the detection of an erroneous
impedance data easy. Also, if the impedance
of a particular equipment is not known, it is
acceptable for most studies to select from a
range of tabulated typical values.
Department of Electrical and Electronics Engineering

Advantages of Per-Unit Calculations


3. In many instances, the base voltages can be
selected so that the per-unit turns ratio of
any transformer in the system is 1:1. This
makes the primary and secondary currents
(and voltages) of any transformer identical.
4. When per-unit values are used, the connection
of a three-phase transformer does not affect
its per-unit equivalent impedance. The
transformer connection, however, determines
the ratio of the base voltages on the two sides
of the transformer.
Department of Electrical and Electronics Engineering

Advantages of Per-Unit Calculations


5. Per-unit representation yields more relevant
information and easily correlated data.
6. Network calculations are the same for singlephase and three-phase systems. There is less
chance of mix-up between phase and line
voltages, single-phase and three-phase
powers, and primary and secondary voltages.

7. Per-unit calculation is more convenient to use


when the solution requires a digital computer.
Department of Electrical and Electronics Engineering

Per-Unit Values
Need to define base values for:
1. Voltage, V
1. Current, I
3. Impedance, Z
4. Volt-Ampere, VA
Note:
1. V, I, Z and VA are not independent of each
other.The base values must be chosen so that
basic electrical laws are satisfied .

2. The rating of electrical equipment specify KVA


(or MVA) and voltage (volts or KV).
Department of Electrical and Electronics Engineering

Choice of Per-Unit Values


1. Choose any two of the electrical parameters.
In general, the base Volt-Ampere and base
Voltage are chosen.
Note: For actual power systems, volt and voltampere are small units. The bases are expressed
in kV and MVA.
2. Calculate the Base Impedance and Base
Current.
Note: The base MVA will also serve as base for
power and reactive power. The base Z will also be
used as base for resistance and reactance.
Department of Electrical and Electronics Engineering

Single-Phase System
Given a base voltage Vp and a base volt-ampere
VAp, find the base current I and base impedance Z.
Since VAp

VpI , then

Base I
Also, since Vp

Base Z

Base VAp
Base Vp

in Amps

IZ, then
Base Vp

(Base Vp )2

Base I

Base VAp

Department of Electrical and Electronics Engineering

in

Example: Given base Vp = 20,000 volts and


base VAp = 2,000,000 volt-amperes

Base I

Base Z

Base VAp
Base Vp

100 A

(Base Vp )2
Base VAp

200

Note:
1. If base Vp=20,000 volts, then base kV=20 kV.
2. If base VAp=2,000,000 , then base kVAp=2,000
and base MVAp=2.
Department of Electrical and Electronics Engineering

Single-Phase System
Other Formulas:

Base I

Base VAp
Base Vp
Base kVAp
Base kVp

in Amps

in Amps

Base MVAp x 1000


Base kVp

Department of Electrical and Electronics Engineering

in Amps

Single-Phase System
Other Formulas:

Base Z

(Base Vp )2
Base VAp

in

(Base kVp )2 x 1000


Base kVAp
(Base kVp )2
Base MVAp

Department of Electrical and Electronics Engineering

in

in

Example: For the single-phase system shown,


find the voltage, power and reactive power at the
source.
100+j300

Vs

Load

VL

100 KVA
@ 0.9 PF lag
VL=20kV

Solution using actual values:

Let VL

20 0o kV , the reference phasor.

PL

KVA(PF)

90 kW

QL

PL tan(cos 1 0.9)

Department of Electrical and Electronics Engineering

43.59 kVars

Solve for the current

PL

jQL

VL

From KVL,

Vs

(100

90

j43.59
20
4.5 j2.18 5

j300)I

VL

(0.32 71.56o )(5


21.1
We get

Ps

jQs

j1.13

25.84 A

25.84)

20.0

21.13 3.07 kV


o
o
Vs I
(21.13)(5) (3.07
25.84 )
105.67 28.91o 92.5 j51.09

Department of Electrical and Electronics Engineering

Solution using per-unit values:


Assume

Base KVAp=100

We get

Base I

Base Z

Let VL

Base KVAp
Base kVp

Base kVp=20

100
20

(Base KVp )2 (1000)


Base kVAp

5A

4k

1.0 0o p.u, the reference phasor.

PL

KVA(PF)

90 kW

QL

PL tan(cos 1 0.9)

Department of Electrical and Electronics Engineering

0.9 p.u.
0.44 p.u.

Solve for the line impedance in per-unit

100 j300
4000

0.025

j0.075 p.u.

0.025+j0.075

Vs

PL

jQL

VL

Load

VL

PL=0.9
QL=0.44
VL=1.0

0.9

j0.44
1.0
0.9 j0.44 1.0

Department of Electrical and Electronics Engineering

25.84 p.u.


Vs

Ps


(0.025 j0.075)I VL
(0.08 71.56o )(1.0
25.84) 1.0
1.06 j0.05 1.06 3.07o p.u.

jQs Vs I
(1.06)(1.0) (3.07o 25.84o )
1.06 28.91o

0.925

j0.5109 p.u.

In actual values,

Vs

1.06(20)

Ps

0.925(100)

Qs

0.5109(100)

21.13 kV
92.5 kW
51.09 kVar

Department of Electrical and Electronics Engineering

Three-Phase System
For a three-phase system,

VA3

3VAp

VL

3 Vp

Define:

Base VA3
Base VL

3 x Base VAp
3 x Base Vp

Note: The base current and base impedance will


still be I and Z, respectively.
Department of Electrical and Electronics Engineering

Three-Phase System
Base I

Base kVAp
Base kVp

in Amps

Base kVA3

in Amps

3 Base kVL
Base MVA3 x 1000 in Amps
3 Base kVL

Base Z

(Base kVp )2
Base MVAp

(Base kVL )2
in
Base MVA3

Department of Electrical and Electronics Engineering

Example: Given Base MVA3 =30 and Base kVL=120,


find the base current and base impedance.

Base I

Base Z

Base MVA 3 x 1000


3 Base kVL
30 x 1000
144.34 A
3 (120)
(Base kVL )2
Base MVA3

(120)2
30

480

Department of Electrical and Electronics Engineering

If we use single-phase analysis, we get


Base MVAp=10 and Base kVp=69.28

Base I

Base Z

Base MVAp x 1000


Base kVp
10 x 1000
144.34 A
(69.28)

(Base kVp )2
Base MVAp

(69.28)2
10

480

Department of Electrical and Electronics Engineering

Example: Determine the per-unit equivalent


circuit for the three-phase network shown.
G1

0.381+j0.508

12 MW
0.9 PF lag
13.8 kV

0.571+j0.762

G2

18 MW
0.95 PF lag

Single-phase equivalent circuit


0.381+j0.508

P1=4 MW
PF=0.9 lag

V1=7.97 kV

0.571+j0.762

V1

V2
PL=6 MW
PF=0.95 lag

Department of Electrical and Electronics Engineering

Define single-phase bases. Let Base MVAp=5 and


Base kVp=7.97.

Base I

Base Z

5 x 1000
627.6 A
7.97
(7.97)2
12.7
5

Per-unit single-phase equivalent circuit


0.03+j0.04
P1=0.8 p.u.
PF=0.9 lag

V1=1.0 p.u.

0.045+j0.06

V1

V2
PL=1.2 p.u.
PF=0.95 lag

Department of Electrical and Electronics Engineering

Define three-phase bases. Let Base MVA3 =15


and Base kVL=13.8.

Base I

Base Z

15 x 1000

627.6 A

3(13.8)
(13.8)2
12.7
15

Per-unit single-phase equivalent circuit


0.03+j0.04
P1=0.8 p.u.
PF=0.9 lag

V1=1.0 p.u.

0.045+j0.06

V1

V2
PL=1.2 p.u.
PF=0.95 lag

Department of Electrical and Electronics Engineering

Generator Impedances
Manufacturers provide the following impedances
in percent or per-unit:
1. Armature Resistance: Ra

2. Direct-Axis Reactances: Xd, Xd and Xd


3. Quadrature-Axis Reactances: Xq, Xq and Xq
4. Negative-Sequence Reactance: X2
5. Zero-Sequence Reactance: X0

Note: The impedances are based on the machines


nameplate rating: MVA (or kVA) and kV.
Department of Electrical and Electronics Engineering

Per Unit Values for Transformers


The ohmic values of the resistance and leakage
reactance of a transformer depend on whether
the impedances are measured on the high- or
low-voltage side of the transformer.
The impedance of a transformer is expressed in
percent (or per-unit) using its Rated MVA and
Rated kVs as bases, respectively.
The per-unit impedance is the same whether it is
referred to the high-voltage or low-voltage side.
The per-unit impedance of a three-phase
transformer bank, from identical single-phase
units, is the same regardless of the connection.
Department of Electrical and Electronics Engineering

Example: Consider a single-phase transformer


with the following nameplate rating:
10 MVA

127-69 kV

From

Base Z
we get

Base Z

Z=8%

(Base kVp )2
Base MVAp

1272
10
692
10

1,612.9
476.1

Department of Electrical and Electronics Engineering

at the HV side

at the LV side

We get the actual impedance of the transformer

0.08(1612.9) 129
0.08(476.1) 38.1

at the HV side
at the LV side

129

Equivalent Circuit
at the HV side

IH

38.1

IH

IX

Equivalent Circuit
at the LV side

Department of Electrical and Electronics Engineering

IX

Assuming the current is rated

Rated MVA x 1000


Rated I
Rated kV

10000
IH
78.74 A at the HV side
127

10000
IX
144.93 A at the LV side
69
Per-unit equivalent circuit: Let Base MVAp=10
Base kVp=127 at the HV side
Base kVp=69 at the LV side
Department of Electrical and Electronics Engineering

We get

Base Z=1612.9
=476.1

We also get

at the HV side
at the LV side

Base I=78.74 A at the HV side


=144.93 A at the LV side

The transformer impedance is 0.8 p.u. regardless


of which side is chosen. The current is 1.0 p.u.
regardless of side.
0.08
Per-Unit Equivalent
Circuit

1.0

Department of Electrical and Electronics Engineering

Example: Given 3 single-phase transformers each


rated 10 MVA, 127-69 kV, Z=8%. The transformers
are connected to form a three-phase bank, wyegrounded at the HV side and delta-connected at
the LV side. What is the rating of the bank?
Volt-Ampere Rating=3x10=30 MVA
Voltage Rating

Base Z

127 3

220 kV at the HV side


69 kV at the LV side

2202
at the HV side
1,612.9
30
692
at the LV side
158.7
30

Department of Electrical and Electronics Engineering

From the previous example, we get the actual


impedance of the transformer. At the HV side,

Z
At the LV side,

129 , connected in wye


129
0.08 p.u.
1612.9

38.1

12.7 , connected in wye


12.7
0.08 p.u.
158.7

, connected in delta

The bank rating: 30 MVA, 220Y-69 kV, Z=8%


Department of Electrical and Electronics Engineering

Change in Base Values


Given a per-unit impedance Zpu1 which is based on
kV1 and MVA1. Suppose the bases are changed to
kV2 and MVA2. Find Zpu2, the new per-unit value.
The actual value can be expressed as

Z in

(kV1 )2
Zpu1
MVA1

(kV2 )2
Zpu2
MVA2

Solving for Zpu2, we get

Zpu2

Zpu1

kV1
kV2

MVA 2
x
MVA1

Department of Electrical and Electronics Engineering

Example: Consider a three-phase transformer


unit with the following nameplate rating:
50 MVA, 220Y-69 Z=10%
Find the percent Z when the bases are 100 MVA,
230 kV at the HV side.
From

Zpu2
we get

Zpu1

kV1
kV2

MVA 2
x
MVA1

Zpu2

220
100
10
x
230
50

18.3%

Note: At the LV side, Base kV=72.1, Zpu2=18.3%.


Department of Electrical and Electronics Engineering

Per-Unit Representation
Procedure:
1. Establish the Base MVA and the Base kVs
a. Assume a Base MVA for the entire system

b. Assume a Base Voltage for any power


system component (Generator,
Transformer or transmission line)
c. Compute the Base Voltages for the
remaining power system components using
the voltage ratios of the transformers

Department of Electrical and Electronics Engineering

Per-Unit Representation
2. Using the base MVA and the base voltages,
compute the base current and base impedance
of each subsystem.
3. Determine the per-unit impedance of every
system component.
a. If the impedance is expressed in ohms,
divide the actual value by the base value.

b. If the impedance is expressed in percent,


use the formula for changing base values.
Department of Electrical and Electronics Engineering

Example: Draw the per-unit reactance diagram


using 50 MVA and 13.8 kV as bases in the circuit
of G1. T1
T2
G1

L2

L1

G2

T3

G3

G1: 20 MVA, 13.8 kV X=20%


G2: 30 MVA, 18 kV X=20%
G3: 30 MVA, 20 kV X=20%
T1: 25 MVA, 220Y-13.8 kV X=10%
T2: Single-phase each 10 MVA, 127-18 kV X=10%
T3: 50 MVA, 220Y-22Y kV X=10%
L1: X=80
L2: X=100
Department of Electrical and Electronics Engineering

Three-phase rating of transformer T2:


30 MVA, 220Y-18 kV X=10%
Base MVA = 50
Base kV = 13.8 in generator G1
= 220 in lines L1 and L2
= 18 in generator G2
= 22 in generator G3
Convert all reactances to the new bases:
G1: X=0.2 x 50/20=0.5 p.u.
G2: X=0.2 x 50/30=0.33+ p.u.
G3:
T1:

X=0.2 x (20/22)2 x 50/30=0.275 p.u.


X=0.1 x 50/25=0.2 p.u.

Department of Electrical and Electronics Engineering

T2:
T3:

X=0.1 x 50/30=0.166+ p.u.


X=0.1 p.u.

In lines L1 and L2,

Base Z

2202
50

968

L1:

X=80/968=0.083 p.u.

L1:

X=100/968=0.103 p.u.
0.2

+
EG1

0.5

0.083

+
EG3

0.103

0.375

Department of Electrical and Electronics Engineering

0.167

0.333
+

EG2

Symmetrical Components
In a three-phase system, a given set of unbalanced
phasors may be replaced by three sets of balanced
phasors which are referred to as the symmetrical
components of the original unbalanced phasors.
The positive-sequence phasors are three-phase
balanced and have the same phase sequence as
the original set of unbalanced phasors.
The negative-sequence phasors are three-phase
balanced but having a phase sequence opposite
to that of the original set of unbalanced phasors.
The zero-sequence phasors are single-phase,
equal in magnitude and in the same direction.
Department of Electrical and Electronics Engineering

Unbalanced Conditions
Causes of unbalanced conditions:

1. Non-transposition of transmission lines


2. Single-phase transformers used in threephase banks are not identical
3. Single-phase loads are not distributed
equally among the phases

4. Faults
Note: Single-phase analysis cannot be used
when the system is unbalanced.
Department of Electrical and Electronics Engineering

Assume a sequence abc for the original set of

unbalanced
phasors.

Vb2
Vc1

Va1

Vb1

PositiveSequence
(abc)

Vc2

ZeroSequence

Va0

Vb0

Department of Electrical and Electronics Engineering

Va2
NegativeSequence
(acb)

Vc0

The vector sum of the sequence components is


shown below to get the phase voltages.

Vc2
Vc1
Va2

Va1
Va
Vb
Vc

Vb2 Vb1
We get

Va

Vb

Vc

Va0

Vb0

Vc0

Va1

Vb1

Vc1

Va2

Vb2

Vc2

Department of Electrical and Electronics Engineering

Express all sequence components using phase a.

Va0

Vc1

Vb0

Vc0

Va1

Vb1

Note: a

Vb1

Vc1

1 120o

a Va1

aVa1
2

Vb2

Vc2

Vb2

aVa2

2
a Va2

Department of Electrical and Electronics Engineering

Vc2

Va2

Substitution
gives

Va

Vb

Vc

Va0

Va0

Va0

Va1 Va2

2
a Va1 aVa2

aVa1 a2 Va2

Using matrix notation, we get

Va
1 1

2
=
V
1
a
b
Vc
1 a
or

Vabc

1
a
a2

Va0

V
a1
Va2

A V012

Department of Electrical and Electronics Engineering

We can show by matrix inversion that A-1 is

1 1
A = 1 a2
1

1
a

A-1 =

a2

1
3

The inverse equations are

Va0

1
=
V
3
a1
Va2
or

V012

1
1

1
a

1
a2

1 a2

Vabc

Department of Electrical and Electronics Engineering

Va

V
b
Vc

1
1

1
a

1
a2

1 a2

The transformation also applies to unbalanced


currents.

Ia
1 1

Ib = 1 a2
Ic
1 a

Ia0

1
=
Ia1
3
Ia2
or

Ia bc

1
1

Ia0

Ia1
Ia2

1
a
a2

1
a

1
a2

1 a2

A I012 and

Ia

Ib
Ic

I012

Department of Electrical and Electronics Engineering

A Ia bc
1

Example: Determine the symmetrical components


of the following unbalanced voltages:

Va

Vb

4 0o

We get

Va0

Va1

90o

Vc

8 143.1o

1
(Va Vb Vc )
3
1
(4 j3 6.4 j4.8)
3
0.8 j0.6 1.0 143.05o

2
1
(
V
a
V
a
Vc )
a
b
3
1
3

(4

3 30

8 23.1 )

4.9 18.38

Department of Electrical and Electronics Engineering


Va2

1
(Va
3

a2 Vb

(4

3 150o

1
3

aVc )
8 263.1o )

2.15
86.08o

We also get
Vb0 Va0 1.0 143.05o

2
Vb1 a Va1 4.9 258.38o

Vb2 aVa2 2.15 33.92o

o
Vc0 Va0 1.0 143.05

o
Vc1 aVa1 4.9 138.38

2
o
Vc2 a Va2 2.15 153.92
Department of Electrical and Electronics Engineering

The sequence components are shown below

Vc1

Vb2

Vc2

Va1
Positive
Sequence

Va2


Va0 Vb0 Vc0

Vb1

Negative
Sequence

Zero Sequence

Department of Electrical and Electronics Engineering

The sum of the sequence components is shown


below.

Vc Vc2

Va0

Vb0

Vc1

Va1

Vc0

Vb1

Va2

Va

Vb2

Vb

Department of Electrical and Electronics Engineering

Zero-Sequence Current
Zero-sequence current cannot flow in or out of a
delta connection.
In a wye-connection with neutral return, the
neutral carries the in-phase zero-sequence
currents.
a

I0

3I0
n
c
b

I0

I0

Department of Electrical and Electronics Engineering

Zero-Sequence Current
Zero-sequence current can circulate in the delta
connected winding of a transformer. Balancing
ampere turns must be satisfied.

I0

I0

I0

b
c

Department of Electrical and Electronics Engineering

Example: Single Line-to-Ground Fault

Ia

Ic

Given: Ia

Ia0

Ia1

Ia2

Ib

1500 0o A Ib
Ic 0

o
1
(
I
I
I
)
500
0
A
a
b
c
3

2
o
1
(
I
a
I
a
I
)
500
0
A
a
b
c
3

2
o
1
(
I
a
I
a
I
)
500
0
A
a
b
c
3

Department of Electrical and Electronics Engineering

Example: Line-to-Line Fault

Ia

Ic

Given: Ia

Ia0

Ia1

Ia2

1
(Ia
3

1
(Ia
3

1
(Ia
3

Ib

Ib
Ic 1500 0o A

Ib Ic ) 0

a Ib a2 Ic ) 866 90o A

a2 Ib a Ic ) 866
90o A

Department of Electrical and Electronics Engineering

Sequence Networks
When the system is unbalanced, currents and
voltages will contain positive-, negative- and zerosequence components. The ratio of a sequence
voltage to its corresponding sequence current
represents a sequence impedance. Thus, the
unbalanced power system can be replaced by
three sequence networks.
1. Positive-Sequence Network
2. Negative-Sequence Network
3. Zero-Sequence Network
Note: A balanced three-phase system is
modeled using the positive-sequence network.
Department of Electrical and Electronics Engineering

The Fault Point


The system is assumed to be balanced except at
the fault point.
a
b

Line-to-

ground Va Vb Vc
voltages

Ia

Ib

Ic

c
Fault
Currents

Ground

Note: An equivalent network at the fault point


can be determined using Thevenins theorem.
Department of Electrical and Electronics Engineering

Вам также может понравиться