Detailed Performance Summary For 165kW

Project: Cristi_MC_Construct
Prepared By:

07/10/2012
04:01PM

Mechanical Cooling Mode Information

Unit Information
165kW
Tag Name:
30RB0232-B
Model Number:
Air Cooled
Condenser Type:
Scroll
Compressor Type:
400-3-50
Nameplate Voltage:
1
Quantity:
Montluel, France
Manufacturing Source:
R410A
Refrigerant:
4
Capacity Control Steps:
25.0
Minimum Capacity:
2039
Shipping Weight:
2123
Operating Weight:
2410
Unit Length:
2253
Unit Width:
2297
Unit Height:
-20
Minimum Outdoor Operating Temp:
Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan Motor Power:
Total Unit Power:
Efficiency:

206.1
76.7
6.24
83.6
2.47

Acoustics Information
A-Weighted Sound Power Level:
Evaporator Information
Fluid Type:
Fouling Factor:
Leaving Temperature:
Entering Temperature:
Fluid Flow:
Total Pressure Drop:

%
kg
kg
mm
mm
mm
C

kW
kW
kW
kW
kW/kW

91 dbA
Fresh Water
0.0000
7.0
12.0
9.85
25.9

Condenser Information
Altitude:
Number of Fans:
Total Condenser Fan Air Flow at 20C:
Entering Air Temperature:
Electrical Information
Unit Voltage:
Standby Power:
Minimum Voltage:
Maximum Voltage:
Power Factor:

Amps (Un)
Max Unit Current
Draw (RLA)
Max Start Up
Current (ICF)

V-Ph-Hz

100 m
4
18054 L/s
40.0 C

400-3-50
0.7
360
440
0.84

Electrical
Circuit 1
175.2

(sqm-K)/kW
C
C
L/s
kPa

V-Ph-Hz
kW
Volts
Volts

Electrical
Circuit 2

348.2

Packaged Chiller Builder EMEA 3.29n

Page 1 of 4

Detailed Performance Summary For 165kW


Project: Cristi_MC_Construct
Prepared By:
Nominal Unit
Current Draw (A)

07/10/2012
04:01PM

135.2

Integrated Pump Information


No Pump Selected
Accessories and Installed Options
Opt. 118A DX Free Cooling System
Opt. 254 Cu/Al coils
Opt. 148C CCN to Bac-Net Gateway
Opt. 23A Side Panels Only
Opt. 28 Winter Operation (down to -20 deg C)
Opt. 280 DX Evaporator
Opt. 41 Evap Freeze Protection

Free Cooling Mode Information

Performance Information
Cooling Capacity:
Total Compressor Power:
Total Fan and Refrigerant Pump Power:
Total Unit Power:
Efficiency:
Evaporator Information
Fluid Type:
Fluid Flow:
Pressure Drop:
Leaving Temperature:
Entering Temperature:

120.1
0.0
8.0
8.6
13.97

Fresh Water
9.85
25.6
10.0
12.9

kW
kW
kW
kW
kW/kW

L/s
kPa
C
C

Condenser Information
Entering Air Temperature:

-5.0 C

Integrated Part Load Value (ARI)


IPLV:

4.52 kW/kW

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, kW
Total Unit Power, kW
Efficiency, kW/kW
Evaporator Data
Fluid Entering Temperature, C
Fluid Leaving Temperature, C
Fluid Flow Rate, L/s
Fouling Factor, (sqm-K)/kW
Condenser Data
Entering Air Temperature, C

100
100
A
218.8
75.6
2.89

75
56
A
164.1
42.6
3.86

50
29
A
109.4
22.2
4.94

(1)
25
13
A
54.7
10.2
5.38

12.2
6.7
9.42
0.0176

10.8
6.7
9.42
0.0176

9.4
6.7
9.42
0.0176

8.0
6.7
9.42
0.0176

35.0

26.7

18.3

12.8

Values given are interpolated and are not directly measurable under laboratory conditions.
(1) Compressor cycling is expected. Stated performances are average.
Packaged Chiller Builder EMEA 3.29n

Page 2 of 4

Detailed Performance Summary For 165kW


Project: Cristi_MC_Construct
Prepared By:

07/10/2012
04:01PM

European Seasonal Energy Efficiency Ratio (EUROVENT)


3.94 kW/kW
ESEER:

Unit Performance
Percent Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Cooling Capacity, kW
Total Unit Power, kW
Efficiency, kW/kW
Evaporator Data
Fluid Entering Temperature, C
Fluid Leaving Temperature, C
Fluid Flow Rate, L/s
Fouling Factor, (sqm-K)/kW
Condenser Data
Entering Air Temperature, C

100
100
A
221.1
76.6
2.89

75
62
A
165.8
47.6
3.48

50
35
A
110.6
26.8
4.12

(1)
25
16
A
55.3
12.6
4.39

12.0
7.0
10.57
0.000

10.7
7.0
10.57
0.000

9.5
7.0
10.57
0.000

8.2
7.0
10.57
0.000

35.0

30.0

25.0

20.0

Values given are interpolated and are not directly measurable under laboratory conditions.
(1) Compressor cycling is expected. Stated performances are average.

NPLV
NPLV:

Unit Performance
Percent of Full Load Capacity, %
Percent of Full Load Power, %
Unloading Sequence
Capacity, kW
Total Unit Power, kW
Efficiency, kW/kW
Evaporator Data
Fluid Entering Temperature, C
Fluid Leaving Temperature, C
Fluid Flow Rate, L/s
Fouling Factor, (sqm-K)/kW
Condenser Data
Entering Air Temperature, C

4.38 kW/kW

100
100
A
206.7
83.0
2.49

75
52
A
155.0
42.9
3.61

50
26
A
103.3
21.3
4.86

(1)
25
11
A
51.7
9.5
5.43

12.0
7.0
9.85
0.0000

10.7
7.0
9.85
0.0000

9.5
7.0
9.85
0.0000

8.2
7.0
9.85
0.0000

40.0

29.8

19.6

12.8

Values given are interpolated and are not directly measurable under laboratory conditions.
(1) Compressor cycling is expected. Stated performances are average.

Packaged Chiller Builder EMEA 3.29n

Page 3 of 4

Detailed Performance Summary For 165kW


Project: Cristi_MC_Construct
Prepared By:

07/10/2012
04:01PM

Free Cooling Load Line


Unit Performance
Capacity, kW
Total Unit Power, kW
Efficiency, kW/kW
Evaporator Data
Fluid Entering Temperature, C
Fluid Leaving Temperature, C
Fluid Flow Rate, L/s
Condenser Data
Entering Air Temperature, C

73.7
8.5
8.72

116.1
8.5
13.62

120.1
8.6
13.96

120.5
4.6
25.97

117.5
4.7
25.10

11.82
10.00
9.85

12.85
10.00
9.85

12.95
10.00
9.85

12.96
10.00
9.85

12.89
10.00
9.85

3.0

0.0

-5.0

-10.0

-15.0

Calculations done in accordance with standard performances (as per EN14511-3 : 2011) and certified by Eurovent.
Sound Power Lw according to ISO 9614-1 and EUROVENT standard 8/1.

Packaged Chiller Builder EMEA 3.29n

Page 4 of 4