10. Identify one of the following which does not fall under compatibility
a. earth leakage current
b. unbalanced loads
c. d.c. feedback
d. external influences --> CORRECT ANSWER
YOUR ANSWER: d
11. Electrical installations shall be divided into circuits to
a. allow for more socket outlets
b. reduce power usage
c. allow for expansion without changing the maximum demand
d. minimise inconvenience in the event of a fault condition --> CORRECT ANSWER
YOUR ANSWER: d
12. Diversity and maximum demand should be determined before beginning an installation
a. for reliable and cost effective design --> CORRECT ANSWER
b. because the customer must be provided with the information
c. in order that the correct supply rating is used
d. as it is an REC requirement
YOUR ANSWER: a
13. The term diversity when applied to an electrical installation might mean
a. different appliances may be connected on the same circuit
b. there is a split load consumer unit in use for RCD protection
c. a variety of different circuits can be used in one installation
d. an allowance can be made for equipment not in use at the same time --> CORRECT ANSWER
YOUR ANSWER: none
14. Maximum demand and diversity should be determined before an installation is to begin
a. to enable the REC to prepare the correctly rated supply
b. to ensure the customer receives the correct information
c. as it is a requirement of the REC
d. to ensure economic and reliable design within thermal limits and admissible voltage drop --> CORRECT ANSWER
YOUR ANSWER: d
15. Which one is correct for TN system?
a. only an overcurrent protective device must be used together for fault protection.
b. only an RCD must be used together for fault protection.
c. both an overcurrent protective device and an RCD must be used together for fault protection.
d. both an overcurrent protective device and an RCD may be used for fault protection. --> CORRECT ANSWER
YOUR ANSWER: b
16. For protection against burns the temperature limit under normal load conditions for a hand-held part with metallic
surface is
a. 50 C
b. 55 C --> CORRECT ANSWER
c. 60 C
d. 65 C
YOUR ANSWER: none
17. For protection against burns the temperature limit under normal load conditions for a part intended to be touched (not
hand-held) with metallic surface is
a. 70 C --> CORRECT ANSWER
b. 50 C
c. 80 C
d. 60 C
YOUR ANSWER: none
18. For protection against burns the temperature limit under normal load conditions for a part which need not be touched
with metallic surface is
a. 70 C
b. 80 C --> CORRECT ANSWER
c. 90 C
d. 100 C
YOUR ANSWER: none
19. For an installation with nominal voltage 230/240 V the required minimum impulse withstand voltage of category I
overvoltage protective device (equipment with reduced impulse voltage) is
a. 1.5 kV --> CORRECT ANSWER
b. 2.5 kV
c. 3.5 kV
d. 5 kV
YOUR ANSWER: none
20. For an installation with nominal voltage 400/690 V the required minimum impulse withstand voltage of category I
overvoltage protective device (equipment with reduced impulse voltage) is
a. 2.5 kV --> CORRECT ANSWER
b. 4 kV
c. 5 kV
d. 6 kV
YOUR ANSWER: none
21. Equipotential copper bonding designed as a bonding ring network must have a minimum round diameter of
a. 8 mm --> CORRECT ANSWER
b. 10 mm
c. 12 mm
d. 15 mm
YOUR ANSWER: none
22. Part 4 of the IET Wiring Regulations concerns amongst other things
a. protection against voltage disturbances and electromagnetic disturbances --> CORRECT ANSWER
b. periodic inspection and testing
c. medical locations
d. operating and maintenance gangways
YOUR ANSWER: none
23. The maximum Zs for a 20A Type D circuit breaker protecting a transformer is
a. 0.47
b. 0.57 --> CORRECT ANSWER
c. 3.08
d. 2.38
YOUR ANSWER: none
24. In the diagram below, a ring final circuit is wired in high impact PVC conduit. The number of single core cables
installed in section A to B will be
a. 2
b. 3
c. 5
d. 6 --> CORRECT ANSWER
YOUR ANSWER: none
25. In a.c. systems in the event of the failure of basic protection, additional protection may be provided by
a. supplementary bonding
b. a time delay 100mA RCD
c. an RCD with an operating current not exceeding 30mA --> CORRECT ANSWER
d. electrical separation
YOUR ANSWER: none
26. To minimize electromagnetic disturbances in a TN system, a PEN conductor
a. shall not be used downstream of the origin of the installation --> CORRECT ANSWER
b. shall be installed downstream of the origin of the installation
c. is required under regulation 444.4.3.1
d. should be of the correct type
YOUR ANSWER: none
27. An enclosure that protects against the insertion of British Standard human finger dimensions has an IP rating of
a. IP2X --> CORRECT ANSWER
b. IP47
c. IP57
d. IP3X
YOUR ANSWER: none
28. In two-wire earthed d.c. power circuit the identification colour of positive (of positive earthed) circuit!2' is
a. Grey
b. Brown
c. Blue --> CORRECT ANSWER
d. Black
YOUR ANSWER: none
29. In two-wire earthed d.c. power circuit the identification colour of negative (of positive earthed) circuit is
a. Blue
b. Black
c. Brown
d. Grey --> CORRECT ANSWER
YOUR ANSWER: none
30. Equipment that is intended to be moved in use shall be connected by
a. non-flexible cables.
b. flexible cables, except equipment supplied by contact rails. --> CORRECT ANSWER
c. either non-flexible or flexible cables.
d. contact rails.
YOUR ANSWER: none
31. What type of cables necessarily must be enclosed in conduit, ducting or trunking?
a. Sheathed cables for fixed wiring.
b. Sheathed cables for temporary wiring.
c. Non-sheathed cables for fixed wiring. --> CORRECT ANSWER
d. Non-sheathed cables for temporary wiring.
YOUR ANSWER: none
32. What is the minimum cross-sectional area for copper non-sheathed and sheathed cables used in power circuits?
a. 1.0 mm2
b. 1.2 mm2
c. 1.6 mm2 --> CORRECT ANSWER
d. 2.0 mm2
YOUR ANSWER: none
33. What is the minimum cross-sectional area for copper bare conductors used in signalling and control circuits?
a. 1.0 mm2
b. 2.0 mm2
c. 3.0 mm2
d. 4.0 mm2 --> CORRECT ANSWER
YOUR ANSWER: none
34. Which statement about a fuse base using screw-in fuses is correct?
a. A fuse base using screw-in fuses shall be connected so that the centre contact is connected to the supply and the shell
contact is connected to the conductor to the load. --> CORRECT ANSWER
b. A fuse base using screw-in fuses shall be connected so that the centre contact is connected to the load and the shell
contact is connected to the conductor to the supply.
c. A fuse base using screw-in fuses can be connected so that the centre contact is connected to either the supply or the
load.
d. The connection of centre/shell contacts in fuse base using screw-in fuses to the supply/load shall be determined by the
fuse manufacturer.
YOUR ANSWER: none
35. Which factor shall be considered in selecting the preferred voltage protection level (Up) value of the SPD?
a. The impulse withstand voltage of the equipment (or impulse immunity of critical equipment) to be protected
b. the nominal voltage of the system
c. both the first two answers --> CORRECT ANSWER
d. either the first two answers
YOUR ANSWER: none
36. A fire-fighters switch shall be provided in the low voltage circuit supplying:
a. exterior electrical installations operating at a voltage exceeding low voltage
b. interior discharge lighting installations operating at a voltage exceeding low voltage.
c. exterior discharge lighting installations operating at a voltage exceeding low voltage.
d. either the first two answers --> CORRECT ANSWER
YOUR ANSWER: none
37. Stationary batteries shall be installed so that they are accessible only to
a. skilled persons
b. instructed persons
c. skilled or instructed persons --> CORRECT ANSWER
d. authorized persons
YOUR ANSWER: none
38. Every electric motor shall be provided with control equipment incorporating means of protection against overload in
case it has a rating exceeding
a. 0.25 kW
b. 0.37 kW --> CORRECT ANSWER
c. 0.50 kW
d. 0.67 kW
YOUR ANSWER: none
39. Which system a step-up autotransformer shall not be connected to?
a. TT
b. IT --> CORRECT ANSWER
c. TN
d. TN and TT
YOUR ANSWER: none
40. The minimum cross-sectional area of the extra-low voltage flexible cable with a length of 2 m shall be
a. 1.0 mm2 copper --> CORRECT ANSWER
b. 1.5 mm2 copper
c. 2.0 mm2 copper
d. 2.5 mm2 copper
YOUR ANSWER: none
41. If a cable is buried in a wall less than 50mm depth and is not protected by metallic enclosures, the additional
protection required is
a. RCD protection --> CORRECT ANSWER
b. MCB protection
c. supplementary bonding
d. external notification of cable routes
YOUR ANSWER: none
42. Regarding auxiliary supplies to safety services, the maximum changeover time refers to
a. how long the safety source can supply the rated power output to the safety service
b. the frequency (in cycles per second) of the auxiliary supply feeding the safety service
a. 30 mm in air
b. 20 mm in air
c. 10 mm in air --> CORRECT ANSWER
d. 8 mm in air
YOUR ANSWER: none
54. Which one does a designer or installer of the installation/heating system not need to include in a provided plan for
each heating system?
a. Position of junction boxes
b. Heated volume --> CORRECT ANSWER
c. Rated voltage
d. The leakage capacitance.
YOUR ANSWER: none
55. The specific IP rating for areas within zone 0 of a bathroom is
a. IPXXB
b. IP2X
c. IPX7 --> CORRECT ANSWER
d. IPX4
YOUR ANSWER: none
56. Identify one of the following protective measures against electric shock that is not permitted on a construction site
a. obstacles and placing out of reach --> CORRECT ANSWER
b. electrical separation
c. ADS with additional protection provided by an RCD
d. reduced low voltage
YOUR ANSWER: none
57. In an EV installation which of the standards that apply to sockets and connecting devices is not recognised?
a. BS EN 60998 --> CORRECT ANSWER
b. BS EN 1363-2
c. BS EN 60309-2
d. BS EN 61296-2
YOUR ANSWER: none
58. When designing a single circuit, correction factors are to be used and applied to the
a. nominal rating of the protective device --> CORRECT ANSWER
b. maximum demand of the installation
c. design current of the circuit
d. current carrying capacity of the cable
YOUR ANSWER: none
59. BS EN 50085 relates to
a. conduit systems
b. conductors of insulated cables
c. cable trunking and ducting systems --> CORRECT ANSWER
d. industrial plugs, couplers and socket outlets
YOUR ANSWER: none
60. The maximum floor area served by a single 30A ring final circuit using socket outlets in a domestic installation is
a. 25m2
b. 50m2
c. 75m2
d. 100m2 --> CORRECT ANSWER
YOUR ANSWER: none