Вы находитесь на странице: 1из 1

SPECIFICATIONS OF WATER TRATMENT PLANT

LEGEND

D.M WATER

TDS < 2PPM, CONDUCTIVITY < 10MICROMHO


Ph = 7 - 7.5

P1 & P2(S)

SOFT WATER

TDS < 300PPM. HARDNESS AS CAC03 < 20PPM


PH = 7 - 7.5
TREATED WATER QUALITY(I.R FILTER):IRON < 0.3PPM
TREATED WATER QUALITY(SOFTNER):HARDNESS < 10PPM

DESCRIPTION
ELECTRIC PUMP
FLOW: 1325 LPM
PRESSURE: 6.0 kg/cm,
MODEL:KIRLOSKAR DB 65/20 @ 40HP, S/D-80mm/65mm

P3 & P4(S)

P5

COOLING
TOWER
P.H.E.

ELECTRIC PUMP
FOR DM COOLING
DISCHARGE: 1035LPM
PRESSURE: 3.5 kg/cm,
MODEL: 325PH15M @ 15HP, S/D- 80mm/65mm
DIESEL PUMP
FOR EMERGENCY WATER
DISCHARGE: 800 LPM
PRESSURE: 2.0 kg/cm
MODEL:KIRLOSKAR NW+ SERIES*
COOLING TOWER
CAPACITY: 1400LPM
TEMP: 46C- 32C

DM HEAT EXCHANGER FOR POWER UNIT


'Y' TYPE FILTER

PS

NON-RETURN VALVE (FLANGE TYPE)


GATE VALVE (FLANGE TYPE)
BALL VALVE (FLANGE TYPE)
BUTTERFLY VALVE (FLANGE TYPE)
FLOAT VALVE

PS
T

TEMP METER(0-100c)

PRESSURE GAUGE(0-10KG/SQ.CM)

PS

PR. SWITCH(0- 8BAR)

ALL G.I PIPE LINE : CLASS=B, I.S 1239(PART-1)


PS

PS

THIS IS ONLY THE BASIC SCHEMATIC DRAWING, NOT THE PIPE ROUTING DRAWING.