Electrical - Bill of Quantities

ELECTRICAL CONSULTANT
12-13-521/3, Street No.14, Nagarjuna Nagar Colony, TARNAKA, Hyderabad -17.
Phone: +91 9849008379, E- Mail: srinivasarayudu@gmail.com

Road No-10, Banjara Hills,


Hyderabad

Inner Space Project of


M/s. Brahmakumaris Educational Society
at Gachibowli
19-03-2016

TENDER SCHEDULE FOR INTERNAL ELECTRICAL WORKS


SUMMARY OF COST
SUB
HEAD

AMOUNT

DESCRIPTION

Wiring

II

Light Fixtures

III

Sub-mains

IV

Distribution System

M.V Cables

VI

Earthing

VII

Miscellaneous

SUPPLY

ERECTION

TOTAL

Taxes: WCT 5% on Total


ST 14.5% on Installation

GRAND TOTAL

Employer

Bidder

Electrical - Bill of Quantities

Sl.No.

1.1

DESCRIPTION

QTY

UNITS

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

WIRING

Point Wiring

Supplying and wiring for light points and 6A 5 pin


sockets with 3 runs of 1.5 sq.mm FRLS PVC insulated
1100V grade copper wire for phase, neutral and earth in
PVC FRLS conduit of thick 2mm concealed in the
slab/wall, surface mounted/above false ceiling including
all accessories such as bends, junction boxes etc. The
cost should include modular type 6A switches, front
plates, metal boxes, ceiling roses or holders as required
and with all other accessories to make the installation
complete including testing, commissioning and
termination of wires on both ends.

1.1.1

Primary light points (average length 12m)

164

Nos

1.1.2

Secondary light points (average length 4m)

112

Nos

1.1.3

Two way light points controlled by a 2 nos. 6A two way


switches

Nos

1.1.4

Ceiling fan point controlled by a 6A switch and stepped


type electronic regulator. Rate to include cost of 10mm
M.S hook housed in 16 gauge M.S box flush mounted
in ceiling slab. Rate to include cost of regulator and
switch.

11

Nos

1.1.5

Same as above but for two way Ceiling fan point


controlled by a 2 nos. 6A two way switches

Nos

1.1.6

Same as above item no.1 but for for Exhaust fan point
controlled by a separate 6A modular type switch.

10

Nos

1.1.7

Supplying and wiring for 6A, 5 pin socket controlled by


6A switch combined mounted on common control switch
box.

Nos

1.2

Power Receptacles
Supply, installation, testing and commissioning only of
Power Receptacles with modular switch and socket
mounted on a suitable anodised metal box of approved
make with all other accessories to make the installation
complete.

Employer

1.2.1

6A, 2/3 pin socket controlled by 6A Switch (raw power


sockets) at various locations as indicated in the drawing

51

Nos

1.2.2

2 nos. 6A, 2/3 pin sockets controlled by 2 nos. 6A


Switches (raw power sockets) at various locations as
indicated in the drawing

22

Nos

1.2.3

6/16A, 3 pin socket controlled by 16A Switch at various


locations as indicated in the drawing

12

Nos

1.2.4

25A, 3 pin socket controlled by 1 no. 25A switch with


indicator, 230V for UPS input & output.

Nos

1.2.5

20A DP switch with indicator for Hi-wall split AC control


as indicated in the drawing

Nos

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

1.2.6

Supplying and fixing of M.S fan hook plate with a set of


anchor fasteners to slab for specified points.

13

Nos

1.2.7

Supplying and fixing of recessed night lamp LED (Foot


lamp) of approved make with concealed metal box and
front plate.

Nos

1.3

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Circuits

Supplying and wiring for lighting, power and UPS


circuits in concealed in the slab/wall, surface
mounted/open conduit system above false ceiling. The
wiring shall be carried out using FRLS PVC insulated
1100 Voltage grade, multistrand copper conductor
wires/cables for phase, neutral and earth in heavy duty
rigid PVC FRLS conduit of wall thickness 2mm with
necessary conduit accessories, junction boxes, G.I fish
wire, fixing hardware, modular type back boxes etc,
complete and there is no sub-circuit measurement.

1.3.1

3 runs x 2.5 sq.mm copper wire in 25mm dia. conduit for


Lighting circuits from the respective lighting Distribution
board to the Switch board and UPS circuits.

2070

Rmt

1.3.2

3 runs x 4.0 sq.mm copper wire in 25mm dia. conduit for


Power circuits from the respective Raw power
Distribution board to 6/16A sockets and Hi-wall spilt AC
single phase.

525

Rmt

1.4.1

Supply, installation, testing and commissioning only of


RJ 11 telephone/intercom outlet (Jack type) at various
locations as indicated in the drawing with single front
plate and metal box of approved make with all other
accessories to make the installation complete.

12

Nos

1.4.2

Supply, installation, testing and commissioning only of


RJ 45 LAN outlet at various locations as indicated in the
drawing with single front plate and metal box of
approved make with all other accessories to make the
installation complete.

23

Nos

1.4.3

Supplying and laying only of CAT 6 UTP cable in


suitable FRLS PVC conduit of thickness as specified in
the drawing from the LAN / Telephone outlets to LAN
DB complete.

1525

Rmt

1.4.4

Supplying and fixing only of 16 way SPN DB S/D


(MELVJB) suitable to hold telephone CAT 6 cables to
terminate in EPABX and LAN CAT 6 cables at HUB. All
CAT 6 cables with RJ 45 for Data and all CAT 6 cables
with RJ 11 jacks for Voice to be crimped with a minimum
loop length of 1.5 mtr.

Nos

1.4.5

Supplying and laying only of 5 pair jelly filled armoured


Telephone cable from external source to internal
MELVDB in existing pipe

R/o

Rmt

1.4.6

Supplying and laying only of data (internet) cable from


external source to internal DB in existing pipe

R/o

Rmt

1.4

1.5

Employer

LAN / Telephone:

AV

Bidder

Electrical - Bill of Quantities

Sl.No.

QTY

UNITS

Nos

200

Rmt

1.5.1

Supply, installation, testing and commissioning only of


TV socket mounted on a suitable M.S anodised metal
box of approved make with all other accessories to make
the installation complete.

1.5.2

Supplying and laying only of RG-6 Co-axial cable for


Wall mounted TV outlets as per arrangement shown in
drawing in suitable FRLS PVC conduit of thickness as
specified in the drawing from the television outlets to
TVJB complete.

1.5.3

Supply and fixing of 4M AVJB, 4M AVDB with front


plates and necessary blanking plates interconnected
with 40mm PVC conduit for 5.2 AV system / Wall
mounted TV outlets (LAN outlet excluded)

Nos

1.5.4

Supplying and laying only of CAT 6 cable for ceiling


mounted projector in 25mm dia PVC conduit

15

Rmt

1.5.5

Supplying and laying only of 40mm dia conduit only for


ceiling mounted projector

15

Rmt

1.5.6

Supply and laying of HDMI cable for ceiling mounted


projector

15

Rmt

1.5.7

Supply, installation, testing and commissioning only of


TVJB of Hensel make weatherproof junction of IP 65,
size 217x253x115 mm Empty box without mounting
plate (with opaque lid) (KG 9003 IN) at terrace for dish
TV suitable to accommodate TV splitters (will be
supplied by the service provider).

Nos

1.6.1

Supplying and laying only of 2 core x 0.75 sq.mm 18


gauge 99.96% Speaker cable of Bandridge make (or as
per AV consultant) for distributed audio system from
AVDB located near DB location to speaker outlets in
zone wise loops in suitable PVC conduit.

960

Rmt

1.6.2

Supply, installation, testing and commissioning only of


Ceiling surface mounted speakers

R/o

Nos

1.6.3

Supply, installation and wiring for Volume controllers.


CAT 6 cabling required for VC to audio distribution
point.

R/o

Nos

1.6

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Channel Music (conduiting & cabling only)

1.7

Closed circuit camera system (conduiting & cabling


only)

1.7.1

Supplying and laying only of CAT 6 UTP cable for


Closed circuit cameras from CCTV DB located in Bed
room-2 to CCTV outlets in suitable PVC conduit.

150

Rmt

1.7.2

Supply, installation, testing and commissioning only of


Closed circuit camera - IP based (1920 x 1080 pixels)

R/o

Nos

1.7.3

Supply, installation, testing and commissioning only of


Net video recorder (4 channels) & system
commissioning

R/o

Nos

1.8

Employer

DESCRIPTION

Conduits

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

1.8.1

Supply and laying only of the following PVC FRLS


conduits concealed / open in wall / ceiling / false ceiling
with necessary accessories.

QTY

UNITS

25 mm dia

20

Rmt

32 mm dia

50

Rmt

40 mm dia

20

Rmt

75 mm dia

20

Rmt

110 mm dia

30

Rmt

1.8.2

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Supply and laying only of the following PVC Flexible


hose with Steel Reinforced complete with necessary
accessories.

25 mm dia

300

Rmt

32 mm dia

20

Rmt

40 mm dia

20

Rmt

TOTAL CARRIED OVER TO SUMMARY


II

Employer

LIGHT FIXTURES

2.1

Supply, installation, testing and commissioning only of


the following internal lighting fixtures of Philips or
equivalent make with HF/HPF ballast, lamps and
mounting bracket including supply of down rods with ball
and socket shall be provided wherever is required and
all necessary hardware to make the installation
complete.

a.

Ceiling surface mounted CFL/LED fixtures (Architect's


choice of reputed make)

89

Nos

b.

Wall bracket lights (Architect's choice of reputed make)

54

Nos

c.

Recessed wall lights (Architect's choice of reputed


make)

23

Nos

d.

TCH207 1xTL528W Vector light fixture for Mirror lights

Nos

LL199X 1XDLED57-6500 PSE OD WH Optimus LED


Trunking.

50

Nos

RC869B LED 30S-6500 PSE D8 GR Sereno recessed


mounted LED luminaire

44

Nos

Pendent lights (BY400V LED145S CW SK NB FG WH


light fixture)

Nos

LED strip (14.5W/m) for cove lighting including drivers


(outdoor)

150

Rmt

Updown lights with 12W LED (Architect's choice of


reputed make)

17

Nos

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

Bollard lights (BCP151 LED 150/NW PSU 220-240V


7043 Smart LED Bollard II)

18

Nos

WT202W LED 6S PSU S1 PC EnduraLED Bulkhead


luminaires

Nos

2.2

Supply, installation, testing and commissioning of 48"


sweep ceiling fans without regulators including all
mounting accessories as required.

13

Nos

2.3

Supply, installation, testing and commissioning of 6" or


9" dia (as per site condition) exhaust fans single phase
1420 RPM.

10

Nos

2.4

Supply, installation, testing and commissioning of 12"


dia wall mounting fan without regulator including all
mounting accessories as required.

Nos

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

TOTAL CARRIED OVER TO SUMMARY

III

SUB-MAINS

Supplying and laying only of sub-mains in concealed or


surface / open conduit system. The wiring shall be
carried out using FRLS PVC insulated and round
sheathed 1100 Voltage grade, multistrand copper
conductor flexible cables for phase, neutral and earth.
The cost of 2 mm thick FRLS PVC conduit shall include
with necessary accessories, fixing hardware, complete
and there is no sub-circuit measurement.
End terminations with polyamide gland, Bi-metallic lugs
using crimping tool, insulation tape, identification tags
etc. including earthing of Gland.

3.1

2 runs x 6 sq.mm Cu wires + 1 run x 4 sq.mm Cu wires


in 32 mm dia. conduit for UPS DB

20

Rmt

3.2

4 runs x 6 sq.mm Cu wires + 2 runs x 4 sq.mm Cu wires


in 32 mm dia. conduit for LDBs & Ductable AC OUD's

415

Rmt

3.3

4 runs x 10 sq.mm Cu wires + 2 runs x 6 sq.mm Cu


wires in 32 mm dia. conduit for MLDB, PDBs & 8.5 TR
Ductable ODU's

360

Rmt

3.4

6 runs x 10 sq.mm Cu wires + 2 runs x 6 sq.mm Cu


wires in 32 mm dia. conduit for Airwashers

40

Rmt

3.5

2 core x 0.5 sq.mm Cu flexible Cable in 25 mm dia.


conduit for thermostats to AC ductable ODU's

400

Rmt

End Termination for the above

22

Nos

3.5.1

TOTAL CARRIED OVER TO SUMMARY

Employer

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

4.1.1

8 way three phase MCB DB D/D (VTPN) for lighting


(MLDB) comprising of:
Incoming:
1 no. 63A TP MCB - 10kA, 'C' curve
Outgoings:
4 nos. 32A TP MCB - 10kA, 'C' curve
3 nos. 32A SP MCB - 10kA, 'C' curve

Nos

4.1.2

12 way three phase MCB DB D/D (ETPN) with PPI kit


for lighting (LDB-1) comprising of:
Incoming:
1 no. 32A TP MCB - 10kA, 'C' curve
Outgoings:
3 nos. Indication lamps
3 nos. 25A DP RCCB (30mA)
27 nos. 6A SP MCB - 10kA, 'C' curve

Nos

4.1.3

6 way three phase MCB DB D/D (ETPN) with PPI kit for
lighting (LDB-2) comprising of:
Incoming:
1 no. 32A TP MCB - 10kA, 'C' curve
Outgoings:
3 nos. Indication lamps
3 nos. 25A DP RCCB (30mA)
12 nos. 6A SP MCB - 10kA, 'C' curve

Nos

4.1.4

12 way single phase MCB DB D/D (SPN) for Reception


area lighting (LDB-3) comprising of:
Incoming:
1 no. 32A TP MCB - 10kA, 'C' curve
Outgoings:
6 nos. 6A SP MCB - 10kA, 'C' curve

Nos

4.1.5

12 way single phase MCB DB D/D (SPN) for Silent


room lighting (LDB-4) comprising of:
Incoming:
1 no. 32A TP MCB - 10kA, 'C' curve
Outgoings:
6 nos. 6A SP MCB - 10kA, 'C' curve

Nos

4.1.6

12 way single phase MCB DB D/D (SPN) for Display


area lighting & power (LPDB) comprising of:
Lighting incoming:
1 no. 25A DP MCB - 10kA, 'C' curve
Lighting outgoings:
2 nos. 6A SP MCB - 10kA, 'C' curve
ACU outgoing control from panel:
1 no. 63A TP MCB - 10kA, 'C' curve

Nos

4.1.7

4 way three phase MCB DB D/D (VTPN) for Power


(PDB-1) comprising of:
Incoming:
1 no. 40A FP RCBO (100mA)
Outgoings:
3 nos. 16A SP MCB - 10kA, 'C' curve
3 nos. 20A SP MCB - 10kA, 'C' curve

Nos

IV

DISTRIBUTION SYSTEM

4.1

Distribution Boards

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Supply, installation, testing and commissioning of


following type Ready Made Distribution Boards, with
Double Door arrangement with magnetic lock complete
with following switch gears. The DB shall be IP 42,
powder coated type using CRCA sheet steel enclosure.
The DBs shall have separate Earth & Neutral bus bars,
including all interconnections etc. as required.

Employer

Bidder

Electrical - Bill of Quantities

Sl.No.

QTY

UNITS

4.1.8

4 way three phase MCB DB D/D (VTPN) for Power


(PDB-2) comprising of:
Incoming:
1 no. 40A FP RCBO (100mA)
Outgoings:
7 nos. 16A SP MCB - 10kA, 'C' curve
2 nos. 20A SP MCB - 10kA, 'C' curve

Nos

4.1.9

4 way three phase MCB DB D/D (VTPN) for Power


(ACDB for Reception) comprising of:
Incoming:
1 no. 63A FP RCBO (100mA)
Outgoings:
2 nos. 40A TP MCB - 10kA, 'C' curve

Nos

4.1.10

4 way three phase MCB DB D/D (VTPN) for Power


(ACDB for Silent room) comprising of:
Incoming:
1 no. 40A FP RCBO (100mA)
Outgoings:
2 nos. 32A TP MCB - 10kA, 'C' curve

Nos

4.1.11

12 way single phase MCB DB D/D (SPN) for UPS


(UPS DB) comprising of:
Incoming:
1 no. 32A DP MCB - 10kA, 'C' curve
Outgoings:
6 nos. 10A SP MCB - 10kA, 'D' curve
1 no. 16A SP MCB - 10kA, 'C' curve

Nos

4.1.12

63A FP Isolator with w/p Hensel make (KV 7104) or


M.S enclosure (IP 65) suitable for wall mounting type for
8.5 TR Ductable AC outdoor units.

Nos

4.1.13

40A FP Isolator with w/p Hensel make (KV 7104) or


M.S enclosure (IP 65) suitable for wall mounting type for
Ductable AC outdoor units, Airwashers at terrace and
Bore well.

10

Nos

4.1.14

32A DP MCB - 10kA, 'C' curve with M.S enclosure


suitable for wall mounting type for 3 kVA UPS in & out.

R/o

Nos

4.1.15

63A FP ATS, 230 series of ASCO make with M.S


enclosure suitable for wall mounting type

Nos

4.2

DESCRIPTION

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Main L.T Panel

Supply, erection, testing and commissioning of floor


mounting, free standing, cubicle type Main L.T Panel for
dual power operation with single Bus bar arrangement,
dust & vermin proof generally conforming to IS: 8623
and should be fabricated out of 14 gauge CRCA sheets
as per IEE regulations comprising of:
Incoming:
1 no. 250A FP ATS (230 Series of Asco make)
1 no. 250A FP MCCB - 36kA
1 no. 40A FP MCB wired with 4.0 sq.mm between
incoming of MCB and the EB limb of ATS for voltage
sensing cable termination for DG Set Auto Start/Stop
command.
Bus bar:
A set of electrolytic E91 grade 250A Aluminium bus bar
with complete interconnections for both phase and
neutral as per IS: 5032.
1 x 50 x 6 mm for phase
1 x 50 x 6 mm for neutral

Employer

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

Nos

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Metering & indication:


1 no. Multi-function Meter to measure all parameters
(Cumulative kWh must).
3 nos. CTs 250/5A, CL-1, 15VA
1 no. CT 250/5A, CL-1, 15VA for APFC Panel relay
voltage sensing preferably connected on Y-phase.
6 nos. LED based phase indication lamps with MCB
protection
A set of ON/OFF/Trip lamps
Surge protection (TVSS):
1 set of OBO Bettermann or equivalent Hager make
Class B / Type-1 Surge protection system with
protection level from 10/350S Lightning current
Impulse
Model: 3 nos. Line to Neutral : MCD50-B
1 no. Neutral to Earth : MCD125-B
Uc=320V, Ipeak (8/20s)=25kA, Iimp(10/350s)=50kA, Up
1.3kV
Outgoings:
1 no. 160A TP MCCB (36kA)
4 nos. 63A TP MCCB (25kA)
6 nos. 63A TP MCB - 10kA, 'C' curve
5 nos. 32A TP MCB - 10kA, 'C' curve
1 no. 32A TP MPCB for TVSS protection
4.4

APFC Panel
Supply only of floor mounting, free standing, cubicle
type APFC Panel with Single Bus bar arrangement,
dust and vermin proof generally conforming to IS: 8623
and should be fabricated out of 14 gauge CRCA sheets
as per IEE regulations comprising of
75 kVAr (70 kVAr on APFC + 5 kVAr on Fixed)
Capacitor panel
Incomer:
1 no. 160A TP MCCB (36kA)
Bus bar:
A set of electrolytic E91 grade 160A Aluminium bus bar
with complete interconnections for both phase and
neutral as per IS: 5032.
1 x 40 x 6mm for phase
1 x 40 x 6mm for neutral
Relay:
8 stage APFC relay with suitable features for sequential
selection and time delay etc to be used for PF
controlling with online display of PF
Metering & indication:
1 no. Voltmeter (0 to 500V) with selector switch of (96 x
96) size
1 no. Ammeter (0 to 160A) with selector switch of (96 x
96) size
3 nos. CTs 160/5A CL-1 accuracy and 15VA burden
3 nos. LED based indication lamps with MCB protection
Outgoings:
1 no. 32A TP MCB with capacitor duty contactor
suitable for (1 x 1 kVAr) MPP-H Capacitor.
2 nos. 32A TP MCB with capacitor duty contactor
suitable for (2 x 2 kVAr) MPP-H Capacitor.
1 no. 32A TP MCB with capacitor duty contactor
suitable for (1 x 5 kVAr) MPP-H Capacitor.
4 nos. 32A TP MCB with capacitor duty contactor
suitable for (4 x 15 kVAr) MPP-H Capacitor.
1 no. 32A TP MCB with (1 x 5 kVAr) MPP-H Capacitor
for fixed compensation, not to be wired through APFC
relay.

Employer

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

Each Capacitor Bank shall have the following:


1. ON/OFF indication lamps
2. Auto/Manual Selector switch with 1 set of ON/OFF
Push buttons for Manual Operation and all required
wiring accessories suitable for power and control wiring.

QTY

UNITS

Nos

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

TOTAL CARRIED OVER TO SUMMARY


V

5.1

Supply, laying and commissioning only of following size


1100 Voltage grade XLPE insulated armoured
aluminium / copper conductor under ground cable, in
built up cable trench / already laid RCC Hume pipe or on
cable tray including clamping and dressing with all
required hardware for fixing and to make the installation
complete. The cable shall conform to IS 7098/ Part I.
End terminations with single compression type Brass
gland, Bi-metallic lugs using crimping tool, insulation
tape, identification tags etc. including earthing of Gland.

3.5 core x 95 sq.mm A2XFY Cable for APFC Panel


incoming

Rmt

a1

End Termination for the above

Nos

3.5 core x 35 sq.mm A2XFY Cable for Reception AC


DB

35

Rmt

End Termination for the above

Nos

4 core x 16 sq.mm A2XFY Cable for Silent room ACDB


& Display room 8.5 TR ductable AC

65

Rmt

End Termination for the above

Nos

4 core x 10 sq.mm A2XFY Cable for Reception and


Silent room LDBs

80

Rmt

End Termination for the above

Nos

4 core x 2.5 sq.mm YWY Cable for APFC relay Voltage


sensing

Rmt

End Termination for the above

Nos

4 core x 1.5 sq.mm YWY Cable for external lighting

150

Rmt

f1

End Termination for the above

68

Nos

3 core x 4 sq.mm YWY Cable for Display room LDB


incoming

20

Rmt

End Termination for the above

Nos

b
b1

c
c1

d
d1

e
e1

g1

Employer

M.V CABLES

10

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

Nos

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

TOTAL CARRIED OVER TO SUMMARY

VI

EARTHING

6.1

Supply, installation, testing and commissioning of


standard earth stations as per IS:3043, 1987 with 40mm
dia 'B' class G.I Pipe 10ft long, 3/4" G.I Pipe one foot
long reducer and funnel mesh, spreading a
homogeneous mixture of salt, charcoal around the pipe
etc, 18"x18" cast iron cover including all necessary civil
works.

6.2

Body of the DB's & Panels


Supply, laying and fixing of G.I / HDBC earth strips of
following sizes including all necessary interconnections
with earth station and equipment.

25 x 6 mm hot dip G.I strip

40

Rmt

SWG No.8 HDBC wire for earthing of DB's & AC


outdoor units

50

Rmt

SWG No.14 HDBC wire for earthing of Glands

20

Rmt

TOTAL CARRIED OVER TO SUMMARY

VII

MISCELLANEOUS

7.1

Cable Trays :

7.1.1

Employer

Supply, installation, testing and commissioning only of 2


mm thick perforated type hot dip galvanized cable trays
including supply of necessary anchor bolts, threaded
down rods, grouting and all G.I hardware materials etc.
as required.

a.

450 x 50 mm (corridor area)

60

Rmt

b.

150 x 50 mm (for AC ODU's cables at terrace)

75

Rmt

7.2

Supply, installation, testing and commissioning only of


adopter boxes fabricated out of 14 gauge CRCA sheet
duly painted with a coat of primer and 2 coats of enamel
grey paint to shade No. 631 of I.S:5 including G.I nuts &
bolts suitable for fixing adaptor box (Rate to be quoted
per sq.mtr of the surface area).

Sq.m

7.3

Supplying, fabrication and fixing of M.S angles, channel


for support of cable trays, supports for D.Bs, cable
trenches etc. including supply of all consumables for
welding and also welding machine along with wiring
connections to be arranged by the contractor only.
Power supply will be provided at one point by the client.

200

Kgs

7.4

Supply, installation, testing and commissioning only of 3


kVA UPS with 30 min back-up, 1 Phase incoming & 1
Phase outgoing along with SMF batteries, IGBT based
technology for UPS power.

Nos

7.5

Junction Boxes :

11

Bidder

Electrical - Bill of Quantities

Sl.No.

QTY

UNITS

Supply & fixing of 1/2/3/4 module junction boxes

Nos

Supply & fixing of 6/8 module junction boxes

Nos

Supply & fixing of 12 module junction boxes

Nos

7.5.1

Employer

DESCRIPTION

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Supply and fixing of floor mounting junction boxes made


out of 14 gauge anodised metal sheet with top
removable cover sheets with screwing arrangement and
suitable knock outs suitable to connect PVC conduits.

a.

50 x 50 x 50 mm

15

Nos

b.

100 x 100 x 50 mm

Nos

c.

150 x 150 x 50 mm

Nos

12

Bidder

Electrical - Bill of Quantities

Sl.No.

QTY

UNITS

7.9

Supply & erection only of Hensel make (D 9125) cable


junction box of IP 65 with suitable terminals to terminate
1.5 / 2.5 sq mm Cu Ar. Cable for external lighting.

34

Nos

7.10

Supply & erection only of Hensel make (KF 9250) cable


junction box of IP 66 with suitable terminals to terminate
1.5 sq mm Cu wires from SB & Ar. Cable upto external
lights.

Nos

7.11

Supply & erection only of Hensel make (K 9100) size


167Lx125Bx82D mm enclosure box of IP 65 for LED
drivers (Note: size may vary as per product & site
conditions)

17

Nos

7.12

Supply, installation, testing and commissioning only of 5


HP DOL Starter Panel for Bore well (3 ph) along with
one way water level controller including all
interconnections.

Nos

7.13

Supply, installation, testing and commissioning only of 1


HP DOL Starter Panel for OHT feeding pump (1 ph)
along with two way water level controllers including all
interconnections.

Nos

7.14

Supply, installation, testing and commissioning only of 1


HP DOL Starter Panel for irrigation pump (1 ph)
including all interconnections.

Nos

7.15

Supply, installation, testing and commissioning only of


11 kW VFD with bi-pass on Star/Delta start in a suitable
compact enclosure for Airwashers

Nos

7.16

Supply, installation, testing and commissioning only of


27U closed Valrack with selves, power strips, cable
manager etc to mount EPABX, modem, switcher, NVR,
PSU's & security system devices etc.

Nos

7.17

Safety Equipment :

a.

Supplying and laying only of 3.3 kV, 2.5 mm thick


rubber mats with ISI mark in front of the Panels, UPS
room & Battery room etc. as per IEE regulations. Size :
1m x 1m

Nos

b.

Supplying and fixing of CO2-5Kg Fire extinguishers with


ISI mark
Makes: Firex/Safex/Ceasefire

Nos

c.

Supply and fixing of shock treatment charts fixed in


glazed frame (English & Hindi)

Nos

d.

Supply only of 440 V tested rubber hand gloves


including test certificate.

Sets

e.

Supply and providing of Laminated SLD.

Nos

f.

Supply and providing of St. John make first aid box.

Nos

Nos

7.16

a.

Employer

DESCRIPTION

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

Construction of Manhole chambers with 230 mm best


quality TM bricks in CM 1:4 over a bed of 100 mm thick
PCC 1:4:8
600 L x 600 W x 750mm D

13

Bidder

Electrical - Bill of Quantities

Sl.No.

DESCRIPTION

QTY

UNITS

RATE
SUPPLY

ERECTION

AMOUNT
SUPPLY

ERECTION

TOTAL CARRIED OVER TO SUMMARY

Employer

14

Bidder