PRINT - CONTENTS
1 Settings groups
1.1 Group Power System Data 2; Group General
1.2 Group Differential Protection; Group General
1.3 Group Differential Protection; Group I-Diff
1.4 Group Differential Protection; Group Characteristic
1.5 Group Underexcitation Protection; Group Underexcitation
1.6 Group Underexcitation Protection; Group Characteristics
1.7 Group Impedance Protection; Group General
1.8 Group Impedance Protection; Group Zones
1.9 Group Impedance Protection; Group Power swing
1.10 Group Out-of-Step Protection; Group Out-of-Step
1.11 Group Undervoltage Protection; Group Undervoltage
1.12 Group Overvoltage Protection; Group Overvoltage
1.13 Group Frequency Protection; Group Frequency Prot.
1.14 Group 100% Stator-Earth-Fault Protection; Group 100% SEF-PROT.
1.15 Group Rotor Earth Fault Protection (1-3Hz); Group REF 1-3Hz
1.16 Group Breaker Failure Protection; Group Breaker Failure
1.17 Group Measurement Supervision; Group MeasSupervision
2
2
2
2
2
3
3
3
3
4
4
4
5
5
5
6
6
7
Page 1 of 7
SIMATIC
03.08.16 16:42:31
1 Settings groups
1.1 Group Power System Data 2; Group General
No.
Settings
Value
Group
Settings
Value Group
ON
A
A
Settings
Value
Group
0.00 sec
2031
4.0 I/InO
0.00 sec
Settings
Value
Group
0.25
0.00 I/InO A
0.50
2.50 I/InO A
0.10 I/InO A
1.0
2053
5.0 sec
A
A
4.00 I/InO A
15 Cycle
Page 2 of 7
SIMATIC
03.08.16 16:42:31
Settings
Value
ON
Group
3001
Underexcitation Protection
3011
3012
ON
3013
4.48 V
21.7 %
Settings
Value
Group
79
5.00 sec A
93
5.00 sec A
90
1.00 sec A
Settings
Value
Group
ON
140 %
ON
69.6 %
5.00 sec A
Page 3 of 7
SIMATIC
03.08.16 16:42:31
Settings
Value
Group
0.089 Ohm A
0.20 sec
0.254 Ohm A
0.254 Ohm A
1.50 sec
Settings
Value
ON
Group
3313
3314
3315
1.878 Ohm A
Zone Z1
2.00 sec
Settings
Value
ON
Group
A
0.201 Ohm A
0.190 Ohm A
0.412 Ohm A
90.0
20.00 sec
0.05 sec
Page 4 of 7
SIMATIC
03.08.16 16:42:31
Settings
Value
Group
4001
Undervoltage Protection ON
4002
U< Pickup
70.0 %
4003
5.00 sec A
4004
U<< Pickup
70.0 %
4005
5.00 sec A
A
A
Settings
Value
Group
4101
Overvoltage Protection
ON
4102
U> Pickup
120.0 %
4103
3.00 sec
4104
U>> Pickup
120.0 %
4105
3.00 sec
Settings
Value
Group
ON
4202 f1 Pickup
47.90 Hz
10.00 sec
4205 f2 Pickup
47.90 Hz
10.00 sec
4208 f3 Pickup
47.90 Hz
10.00 sec
4211 f4 Pickup
47.70 Hz
0.10 sec
Page 5 of 7
SIMATIC
03.08.16 16:42:31
Settings
Value
Group
5301
ON
5302
9982.6 Ohm A
5303
5304
10.00 sec
5305
0.30 sec
5306
0.97 A
5307
5308
5309
0.0 Ohm
oo Ohm
Settings
Value
Group
6101
ON
6102
40.0 kOhm A
6103
5.0 kOhm
6104
10.00 sec
6105
1.00 sec
6106
3.3 kOhm
A
A
Settings
Value
ON
Group
A
7002 Start with Internal TRIP Command Start Breaker Failure with CFC A
7003 Supervision Current Pickup
20 %
7004 TRIP-Timer
0.25 sec
Page 6 of 7
SIMATIC
03.08.16 16:42:31
Settings
Value Group
OFF
43.5 % A
0.75
52 %
0.50
52 %
0.50
8.7 %
0.75
Page 7 of 7