Frequency:
Fuel Type:
C250 D5
50
Diesel
Fuel consumption
Ratings
Load
US gph
L/hr
Standby
Prime
kW (kVA)
kW (kVA)
200 (250)
182 (228)
1/4
4.0
15
1/2
7.4
28
3/4
Full
11.1
42
15.1
57
1/4
3.6
14
1/2
7.1
27
Engine
Standby rating
Engine manufacturer
Engine model
Configuration
Aspiration
Gross engine power output, kWm
BMEP at set rated load, kPa
Bore, mm
Stroke, mm
Rated speed, rpm
Piston speed, m/s
Compression ratio
Lube oil capacity, L
Overspeed limit, rpm
Regenerative power, kWm
Governor type
Starting voltage
Cummins
6CTAA8.3G2
4 Cycle; In-line; 6 Cylinder Diesel
Turbo Charged and Charge Air Cooled
231
205
1984
2230
114
135
1500
6
16.7:1
18.9
1800 50
12.7
Electronic
12 Volts DC
208
102
60
Air
Combustion air, m3/min
Maximum air cleaner restriction, mm H2O
15.3
635
2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins
are registered trademarks of Cummins Inc. Our energy working for you. is a trademark of Cummins
Power Generation.
APSB-1154-07 (9/07)
Full
13.6
51
Prime rating
Fuel flow
Maximum fuel flow, L/hr
Maximum fuel inlet restriction, mm Hg
Maximum fuel inlet temperature (C)
3/4
10.3
39
14
Exhaust
Standby rating
Prime rating
40.9
35.8
565
548
76
40
9
26
222
6722
5759
12.7
Weights*
Open
Enclosed
2018
2083
3320
3670
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Dimensions
Length "A"
Width "B"
Height "C"
2623
1020
1685
3700
1600
2100
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
TM
www.cumminspower.com
2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are
registered trademarks of Cummins Inc. Our energy working for you. is a trademark of Cummins Power
Generation.
APSB-1154-07 (9/07)
Alternator data
Temp rise
1
Feature code
Connection
degrees C
Duty
Alternator
Voltage
Wye, 3 Phase
150/125C
S/P
UC274J
380-415V
Ratings definitions
Standby:
Notes:
1.
Limited single phase capability is available from some three phase rated configurations. To obtain single phase
rating, multiply the three phase kW rating by the single phase factor. All single phase ratings are at unity power factor.
2.
Standby (S) and Prime (P) ratings.
kW x 1000
Voltage x 1.732 x 0.8
kW x 1000
Voltage