1. Operation
A Recommended Strategy for Operation and Control
For normal operation all power components such as ACBs, MCCBs, ELCBs and
MCBs status should be ON.
An Outline of the General Operating Mode
The operations of the complete low voltage switchboards are similar except the
controls logic (i.e.) the circuit breakers / power contactors should be ON / closed to
ensure the power supply is being fed to the downstream switchboards / equipment.
In case of motor control centers the closing / opening operation of the starters is
dependent on the BMS command if auto mode is selected.
Control Data
All starter of the MCCs can be tripped from a remote point in the Auto mode, and a
manual remote stop is also possible by means of emergency stop push button
located near the equipment.
Precautions Necessary to Overcome Known Hazards
-
The Means by which any Potentially Hazardous Plant may be Made Safe
-
PROJECT NAME
2.
Maintenance
Sl.No
1
2
3
4
5
6
7
8
Checklist item
Check the condition of arc
chutes of Air circuit breaker.
Check the condition of
terminals of moulded case
circuit breaker.
Check the condition of
terminals of Isolators,
contactors and capacitors
All connections to be
tightened.
Check busbars and link
supports for any damage.
Dust settlement on the
busbars, links and supports.
Check for damage to busbar
and other shrouds.
Check control circuit
connections and operation.
Frequency
After each break on short
circuit.
After each break on short
circuit.
Periodically.
Every year.
Every year.
Every 6 months
Every year.
Every year.
PROJECT NAME
MECHANICAL INDICATORS :
Mechanical indication on the front of the ACB is provided to indicate the following:
1.
2.
3.
4.
5.
6.
7.
TRIP UNIT :
The trip unit is solid state type , Self powered, energised by
internally mounted current transformers. It is not required any external power supply
to operate the tripping mechanism.
The trip unit has the following prime settings.
1. Short time protection ( Im):- Adjustable.
2. Instantaneous protection (I) : Adjustable.
3. Earth fault protection : Adjustable.
For other protection & settings refer the attached relevant catalogue copies.
All adjustments of protection settings are made from the front.
FAULT INDICATION :
Indicator/reset button :
Indicates that a fault trip has occurred. This will prevents re-closure of the breaker
until fault reset.
All ACBs are equipped with safety shutters in the drawout position to prevent
accidental contact with live supply. Safety shutters will be closed automatically when
the breakers are in drawout position.
MAINTANANCE :
After each break on short circuit , condition of arc chutes must be checked. Arc
chutes are removable at site to check the conditions of the arc chutes.
PROJECT NAME
The isolation of the power supply is possible by switching off the circuit breaker
at the switchboard level or by the switching off the local isolator or by means of
emergency push-button located near the equipment.
Proper measures to be taken prior to the isolation of the circuit breakers, which
are feeding various essential loads.
The Exchange of components assembly