Aggreko

INFORMATION BULLETIN

The Power and Temperature


Rental Leader
Prepared

Date

J.J. van der Waal van Dijk

23.11.99

Rev. nr.

Discipline :

Fluid Chillers High Ambient

Section

AIR COOLED - C - RANGE WCC500HA

1.

Page

of

document nr.

9.5.6

INTRODUCTION
The Aggreko -C- range air cooled fluid chillers are designed for water or water-Glycol cooling. All
units are designed for to be located outside. The units are completely assembled with all
interconnection refrigerant piping and internal wiring, ready for installation.
The unit base and frame is of heavy-gauge steel with the dimensions of a standard 20 ft. container.

2.

KEY-DATA
Cooling Capacity
Absorbed Power
Temperature Range
Maximum ambient temp.
Dimensions
length
width
height
Weight

3.

Notes :

497 kW at 6 degrees leaving water temperature


159 kW
+15 C to -12 C
55 C
standard ISO 20ft. Container.
6.0 metres
2.4 metres
2.6 metres
6395 kg

IDENTIFICATION

TH
E
PO
W
RE E R
NT & T
AL E M
LE P E
AD R A
ER T U
R

RA
MPE
THE R & TE R
E
DE
P O W L LEA
A
T
REN

TUR

Aggreko

INFORMATION BULLETIN

The Power and Temperature


Rental Leader
Page

4.

of

AIR COOLED - C - RANGE WCC500HA

9.5.6

TECHNICAL SPECIFICATIONS
ITEM

UNITS

VALUE

Performance Data
Design Capacity
50/60Hz
Design Operation Fluid Temperature IN / OUT
Minimum / Maximum Outlet Fluid Temperature
Minimum / Maximum Chilled Liquid Temperature Difference
Design Ambient Temperature
Minimum / Maximum Ambient Temperature

kW
C / C
C / C
C / C
C
C / C

497/607
12 / 6
-12 / +15
3.5 / 10.2
35
-18 / +55

Semi Hermetic Screw


2
12.5 / 100

l/s
l/s / l/s
litres
kPa
kPa
p.u.
litres

Shell & Tube


Steel & Copper
19.6
11 / 32
270
1000
17
5.38
2100

kW
m/h
Pa

10
2.3/3.4
139
0

Compressor
Compressor Type
Number Of Compressors
Number Of Capacity Steps
Evaporator Data
Evaporator Type
Evaporator Material
Design Flow
Minimum / Maximum Flow
Chiller Barrel Capacity
Chiller Barrel Maximum Working Pressure
Design Chiller Barrel Pressure Drop
Chiller Barrel Pressure Drop Factor
Recommended System Water Volume
Condenser Data
Number Of Condenser Fans
kW per Fan
Total Air Volume
External Static Pressure

50/60Hz

Refrigerant Data
Refrigerant Type
Number of Circuits
Refrigerant Charge circuit 1 / 2
Type Of Compressor Oil
Oil Charge circuit 1 / 2
Electrical Data
Design Electrical Supply Voltage
Design Electrical Rating
Design / Maximum Operating Current
Starting Current
Pre-Heating Supply
Recommended Generator Set
Required Cable Size per Phase
Electrical Connection
Noise Data
Sound Pressure Level at 10 metres - Lp(A)
Sound Power Level - Lw(A)
Physical Data
Overall Length
Overall Width
Overall Height
Weight
Fluid Coupling Size

kg / kg
litres
50/60Hz

R22
2
56 / 56
ISO 68
17 / 17

Volts
kVA / kW
Ampere
Ampere
Volts / VA
kVA
mm

400/460 3ph
177 / 151
257 / 354
476
220 / 600
250
240
Busbar M12

dB(A)
dB(A)

69
97

metres
metres
metres
kg
mm / inch

6.0
2.4
2.6
5040
100 / 4"

NOTE: Contact Technical Department If Application Conditions Differs From Design Conditions

Notes :

Aggreko

INFORMATION BULLETIN

The Power and Temperature


Rental Leader
Page

5.

of

AIR COOLED - C - RANGE WCC500HA

9.5.6

UNIT PERFORMANCE
based on 50 Hz supply
800

Ambient Temperature C
Cooling Capacity kW

700

20C
30C

600

40C

500

50C

400
300
200
100
-10

-5

10

15

Outlet Fluid Temperature C


Based on 60 Hz Supply

900

Ambient Temperature C

Cooling Capacity kW

800

20C
30C

700

40C

600

50C

500
400
300
200
100
-10

-5

Outlet Fluid Temperature C

Notes :

10

15

Aggreko

INFORMATION BULLETIN

The Power and Temperature


Rental Leader
Page

6.

of

AIR COOLED - C - RANGE WCC500HA

9.5.6

WATER PRESSURE DROP


Pressure Drop kPA
200
150

100

50

30
20

40
45
50

35

30

25

20

15

10

10

15

Flow (l/s)

Pressure Drop Correction Factors

Propylene Glycol

Ethylene Glycol

1.6
1.5

50%

1.4

40%

1.3

30%

1.2

20%
10%

1.1
1
-10

Notes :

1.5

Concentration

Correction Factor

1.7

Correction Factor

Concentration

1.8

1.4

1.3

50%
40%

1.2

30%
20%

1.1
-8
-6
-4
-2
0
2
4
6
Mean Liquid Leaving Temperature C

10%

-12 -10 -8 -6 -4 -2 0
2
4
6
Mean Liquid Leaving Temperature C

Aggreko
The Power and Temperature
Rental Leader
Page

7.

of

INFORMATION BULLETIN

AIR COOLED - C - RANGE WCC500HA

9.5.6

DIMENSIONS
Minimum required Clearance to prevent condenser air recirculation and faulty operation of unit(s) are as
follows: Side to wall 2.5 metres, Rear to wall 2.5 metres, Front to wall 1.5 metres, Top 15 metres.
Distance between adjacent units 3.5 metres. No more then one wall can be higher than the top of the
unit.

RIGHT SIDE VIEW

FRONT VIEW

Notes :

REAR VIEW