PCXZAM15

Air-Cooled Scroll
Modular Chiller
Non-Inverter D series & Inverter E Series

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
http://www.daikin.com/global_ac/

All rights reserved


Specifications, designs and other content appearing in this brochure are current as of December 2014 but subject to change without
.
notice

Printed in Malaysia

R410A
Cooling Only

Daikin Modular Chiller


Chilled Water System....

Everthing you need under one roof

Daikin Chilled Water System works by using air to cool down the refrigerant circuit. The
cooled refrigerant is then circulated to the Brazed Plate Heat Exchanger (BPHE) where
heat exchange takes place to cool down the water. The chilled water is next circulated to
the Fan Coil Unit (FCU) for cooling at desired places.

Cooling only
non-inverter and
inverter
unit available

Water Flow Protection

Centralized
control
Network
supports up to
16 chillers in a
group

Multiple
Temperature
Zone Control

Serviceability &
Error Code
Troubleshooting

Energy Saving
Programmable
Timer

Operation can be
managed
according to
zones for
different comfort
need

Easy access for


servicing all
components. Error
code displayed on
Control Panel for
troubleshooting
purpose

Customizable
operation schedule
of chiller and FCU
based on
requirement to
promote energy
saving

Master/Slave
Option
Control based on
network
grouping or
application

Dry Contact
BMS
Compatibility

BMS &
MODBUS
Compatibility

Ability to be
integrated with
BMS

Able to be
integrated with
BMS and
MODBUS

Expansion Tank *

Daikin Modular Chiller

Water Pump *

Wall Mounted, FWW-L

Ceiling Cassette Compact, FWF-C

Ceiling Cassette, FWK-E

Ceiling Convertible, FWE-E

Ceiling Concealed, FWC-C

Ducted Blower, FUD-B

* Field Installed

Air-Cooled Modular Chiller Applications


School/university, office, shopping mall, hotel, hospital, warehouse, factory and highrise building.

Shopping Mall

Factory

Hall
Office

Long Piping Application


Unlike normal Direct Expansion system with constraints in piping
design and installation, Daikin Chilled Water System has no
limitation in piping lengths by correct pump sizing. All refrigerant
circuit is within the system making it no risk of leakage in building
and no oil return issue.

Long
Piping
Application

Time and Cost Saving


Daikin modular chiller is designed to best facilitate user
installation. It is fully assembled, complete with all necessary
components and undergo a series of stringent testing and quality
check in the factory. Customers do not need to refill refrigerant or
invest more money due to refrigerant is pre-charged to achieve
time and cost saving.

Zero ODP

R410A

Zero ODP R410A Refrigerant

Refrigerant

With the absence of chlorine molecules, R410A referigerant


system causes no harm to the ozonosphere due to it is zero Ozone
Depletion Potential (ODP).

Modular Design for Expandable


Capacity
Daikin modular chiller allows for combination of up to 16 base
modules unit where each modular can be connected to form a
much larger system or capacity.

Slave Unit

Master Unit

UAL210D

UAL230D

UAL230E

UAL420D

UAL640D

UAL640E

UAL630D

UAL690D

UAL690E

UAL840D

UAL920D

UAL920E

UAL1050D

UAL1150D

UAL1150E

UAL1260D

UAL1380D

UAL1380E

UAL1470D
Air-Cooled
UAL1680D
Modular Chiller
UAL1890D
D-Series &
E-Series
UAL2100D

UAL1610D

UAL1610E

UAL1840D

UAL1840E

UAL2070D

UAL2070E

UAL2300D

UAL2300E

UAL2310D

UAL2530D

UAL2530E

UAL2520D

UAL2760D

UAL2760E

UAL2730D

UAL2990D

UAL2990E

UAL2940D

UAL3220D

UAL3220E

UAL3150D

UAL3450D

UAL3450E

UAL3360D

UAL3680D

UAL3680E

Base Module

Investment Flexibility
As the capacity of modular chiller is expandable, so does the
investment. Especially for the capacity expansion project in phases,
modular chiller can be installed separately in phases to reduce high
initial investment and installation cost.

has

P
ond

Sec
t
Firs

se

Pha

Easy Installation
Unit designed to best facilitate user installation. Due to its compact size, its dimensions and weight are significantly reduced and
hence provides highest mobility. It can be lifted without large lifting tools and located on the roof, balcony or any possible outdoor
space. Space utilization can also be maximized by installing the modular chiller separately in non-uniform compound due to
building layout.
Modular chiller can be installed into non-uniform compund

Roof top

Obstacle

Space for Ventilation & Maintenance

Installation Space for Non-modular chiller

Roof top

Partial Loading
Daikin Chilled Water System is designed with two or more separate refrigerant circuits with multiple compressors. By doing so,
the unit has part load capabilities. This will improve the reliability and energy efficiency especially during low loading operations.

Redundant Operation
For modular chiller, if one of the systems breaks down, the others can still operate normally due to independent refrigerant
system design with two compressors. Similarly, if one of the units breaks down, the others can still operate normally without
affecting the whole building operation.
Condenser 1

Normal
Operation

Normal Operation

Power off
in repairing

Condenser 2

Power off in repairing


Evaporator 2
Evaporator 1

800
Current (A)

Power Start Up In Stages


Unit adapts modular design and start one by one, reducing
the impact upon the grid when starting and hence reduce
initial starting power surge. Unit features 2-grade modulation
which can be transformed to multi-grade modulations in
modular combinations. With operation grades controlled
electronically, the unit exerts less shock to the power grid
and saves more energy.

600
400
200
0
0

5 10 15 20 25 30 35 40 45 50 55 60
MHS150

Time (s)

UAL*6

Operation Time

Minimum Compressor Running Time

Optimal Operation

Optimal Operation

The compressor with shortest running time will always be


started first to prolong compressor's life span and enhance
systems reliability.

Low Sound Level


The specially designed spiral blades ensure smooth air flow, significantly reducing the turbulence and lowering air flow sound level.
On top of that, quiet mode (low fan mode) is also available to reduce the operating noise especially in night time for a much pleasant
resting environment.

100%
Capacity
Load 50%

50

Operating Noise
dB(A)

100

0
80

Vortex Core

Quite Mode
60

High Fan
Speed
12:00

Blade Tip Vortex

Maximum outdoor ambient temperature

16:00

20:00

Quiet Mode

Low Fan
Speed
0:00

4:00

8:00

Bell Mouth

Integrated Hydronic Components


Unit features leading-edge scroll technology and name-brand accessories which are strictly tested for high compatibility and
reliability. Equipped with efficient scroll compressors and precise electronic expansion valves, these units feature high EER and COP,
especially at partial load.

Fan & motor

Outlet air deflector

Fin tube heat exchanger

Protective screen at the front

Accumulator

Scroll compressor

Liquid receiver

Electrical components

Water outlet pipe

10

Water intlet pipe

1
2
3
4
5
6

10

7
8

Brazed Plate
Heat Exchanger (BPHE)

Electronic Expansion
Valve (EXV)

The BPHE is a stainless steel counter


flow plate heat exchanger. Whereby,
counter flow brazed plate heat
exchanger ensures high heat transfer
efficiency. Both refrigerant circuits
are neighboring to water circuit within
the compact and efficient plate heat
exchanger.

Compare to other expansion valves,


EXV is able to control the flow more
precisely electronically.

Scroll Compressor
High reliability and outstanding
performance scroll compressor.

Fin Tube Heat


Exchanger
High efficiency inner groove air side
heat exchanger to enhance heat
transfer.

Easy Serviceability
Servicing becomes easy when all the important components are placed at easy-access locations. Only the service panels need to
be removed in order to access the parts like compressors, electrical components and so on.

Protection Features
Daikin modular chiller is equipped with multiple protections to ensure a safe and reliable operation.

High Pressure
Protection

Low Pressure Protection


Ambient Temperature
Protection

Suction Temperature
Overheat Protection
Discharge Temperature
Overheat Protection

Self Diagnosis
Water Flow Protection
Access Valve

Motor Overload
Protection

Other than that, there are also High Leaving & Entering Water Temperature Protection, BPHE Anti-Freeze Protection, Power
Protection, Refrigerant Leakage Alarm, High/Low Ambient Temperature Protection and many more.

Intelligent Control System


An user friendly intelligent control system is built into the Daikin modular chiller. Whereby, the micro chip and large-scaled LCD display
remote controller is employed to make the control easy.
Group control: One single controller can control a group up to
maximum 15 slave units.
BMS (option): Unit provides port for BMS. Maximum 31 gateway
and one gateway can support one master unit and maximum 15
slave units.
Basic operating mode
Parameter setting
Parameter display
Fault alarm and protection
Memory function
7 days programmable timer
Self diagnosis

Intelligent Control & Interface

MODBUS Gateway (Optional)


Option is provided to enter to the Building Management System (BMS) via MODBUS Gateway protocal conversion. It will convert the
internal communication protocol into MODBUS communication protocol to ensure that the unit is connected to the Building Management
System (BMS). By having this option, the building energy can be optimised by efficient monitoring from the master control room.

MODBUS
PROTOCOL

Each group 16 units

BMS

Master
32 Groups

Slave

Air-Cooled Modular Chiller D Series

Inverter Air-Cooled Modular Chiller E Series

Inverter
Model

Capacity (kW)
500
1000

UAL210D

65 kW - 1040 kW

UAL230D

60 kW - 960 kW

Model

UAL230E

Capacity (kW)
500
1000
66 kW - 1056 kW

Daikin is committed to offer the new high efficiency inverter air-cooled modular chiller that meets the challenging
need of todays market. With advanced technology, it combines both the benefits of R410A refrigerant and inverter
in one united body. It is proper designed to provide the best coefficient of performance by option of using variable
speed compressor instead of fixed-speed compressor to ensure the end product is compatible with various
applications. Inverter air-cooled modular chiller E-series is surely a people oriented solution for the next generation.

Inverter Highlights

Other than the common features, the highlights for inverter air-cooled modular chiller
are as the followings:

Increase

20%

IPLV
4.3
3.6

Super IPLV Design (High Efficiency)

3.4
3.2
3.0
2.6

Non Invert
er
Air-Cooled
Modular Ch
iller

Inverter
Air-Cooled
Modular Ch
iller

Non Inverter Air-Cooled Modular Chiller


Inverter Air-Cooled Modular Chiller

COP

COP increases
~ 30%

Note:
Centralized Air Conditioning
system operates between
30%-80% load most of
the time

4.5

Saving
Region

As R410A inverter air-cooled modular chiller adopts the extreme DC inverter Hermetic
Scroll Compressor and DC inverter fan motor technology, it enables the chiller to
achieve an IPLV of 4.36, which is 20% higher than of the non-inverter air-cooled
modular chiller. Moreover, it can also meet COP of 3.38 during full load condition. With
all the energy saving features in this inverter system, it helps to minimise the operating
cost for better cost and development planning.

3.5
0

0%

25%

50%

75%

100%

R410A Leading-Edge Inverter Technology


By advanced DC inverter technology, it provides the outstanding energy efficient performance. The module is equipped with a DC
inverter compressor and fan motor, as well as intelligent inverter control system.

DC Inverter Hermetic
Scroll Compressor
The inverter driven features multi speed driven
compressors precisely match their output capacity
according to load requirement, so that the module is
always maintain at optimum energy efficiency operation.

DC Inverter Fan Motor


It regulates speed according to load change to
achieve energy saving.

%
100

Intelligent Inverter
Control System
The specialized inverter control module is built-in
with various inverter control system so that it is
more reliable, precise and with wider coverage.

High Efficiency at all speeds


Magnetic DC Motor

90
AC Motor

80

otor
High Mrgy
Ene cy
n
Efficie

70
10

20

30

40

50

60

70

80

90 100 110

Step-less Capacity Control

Load

Unlike non-inverter chiller with only 2-stage capacity


control (0% - 50% - 100%), Inverter E-Series can
perform step-less capacity control (15% ~ 100%)
precisely which is to control the output capacity
according to dynamic load requirements by adjusting
compressor frequency. In other words, it can be adjusted
to low output capacity to suit to low load condition for
energy saving.

100%
75%
50%
25%

8
Load Curve

Precise Temperature Control

Room
Temperature

Inverter System

12

14

16

Inverter Capacity Modulating Curve

18

20

22 Time (Hour)

Non-Inverter Capacity Modulating Curve

Precise & Stable Temperature Control

The unique inverter keeps room temperature stable by controlling the


compressor at variable speed with minimum temperature fluctuation.
Thus, each unit auto adaptive to real capacity needs for a high level of
comfort.
Besides that, it is also equipped with good humidifying function even
for low load and high humidity conditions. With that, it can be applied
at process cooling as well as high humidity industrial area.
Temperature

10

Conventional Non-Inverter System

Set Temperature
(C)
10
9
8
7
6
5

Time
Inverter System

Conventional Non-Inverter System

Rapid Cooling
With the utmost operation performance and hence shorter cooling time
is required for inverter system.

Shorter Cooling Time

Better Compressor Reliability


Set
Temperature
Time

Reliability of inverter compressor is always better since there is lesser


ON/OFF of the system especially during the low load condition.

Low Inrush Current

By utilising the innovative inverter variable speed fan motor,


the sound performance introduces sound level as low as 58
dBA with respect to conventional non-inverter unit. At
part-load conditions, typical at the night, the inverter device
adjust speed variation to have lower sound levels than
conventional on-off compressor systems in both running
and start-up periods.

Sound Level (dBA)

Silent Operation

Load Percentage (%)

Inverter driven compressor requires lower starting torque which features soft starter to ensure a smooth ramp up profile
without withdrawing high current. This aspect avoids peak fluctuation that potential to harm sensitive equipment and no
need of expensive additional components for power factor correction.

100

Full load

50
0
66

Low
noise
(Night)

58
12:00

16:00

20:00

0:00

4:00

8:00

Diverse System Solution


Other than the beauty of expandable capacity flexibility up to combination of 16 units to cater for the additional cooling requirements,
mix modules among inverter and non-inverter system are also available.

Fully inverter modules


[Inverter master unit + N x Inverter slave unit]

Mix modules
[Inverter master unit + N x Non-Inverter slave unit]

Daikin Air-Cooled Scroll Modular Chiller (Cooling Only)


Non-Inverter UAL-D Series

Specification for Air-Cooled Scroll Modular Chiller - Cooling Only (R410A)


Model Unit UAL

BTU/h
Ton
kW
kW
A
BTU/h/W
W/W
V/Ph/Hz

Nominal Cooling Capacity


Nominal Total Input Power
Norminal Running Current
EER
Power Source
Flow Control (Expansion Device)
Refrigerant
Water Flow Rate
Water Pressure Drop
Sound Pressure Level
Unit Dimension
Packing Dimension
Weight

Compressor

Condenser

Fan & Motor

Evaporator

Height X Width X Depth


Height X Width X Depth
Net (unit weight only)
Gross (with packaging)
Type
Quantity
Insulation Grade
Oil Type
Rated Input Power
Rated Running Current
Tube
Fin

Type
Charge

Material
Diameter
Material
Row

Air Flow
Quantity
Index of Protection (IP)
Insulation Grade
Rated Input Power
Rated Running Current
Type
Plate Material
Max. Water Operating Pressure
Connection

UAL210D
205,000
17.0
60
18.8
36.0
10.90
3.19

kg
m3/h
kPa
dBA
mm
mm
kg
kg

5.8 + 5.8
10.3
38
66

kW
A

8.4
16.3

mm

m3/hr (CFM)

kW
A

kPa
mm

UAL230D
222,000
18.5
65
19.2
36.9
11.56
3.39

380-415 / 3 / 50
EXV
R410A

1840 X 840 X 1990


2010 X 890 X 2010
520
570
Scroll
2
E
POE

Copper
7
Aluminium
3
14442 (8500)
2
IP44
F
1.0
1.7
Brazed Plate Heat Exchanger
Stainless Steel
4500
28.7

6.8 + 6.8
11.2
44
66

8.6
16.7

Notes: Nominal cooling conditions: EWT/LWT: 12/7C


Ambient DB temperature is 35C
All specifications are subjected to change by manufacturer without prior notice

Specification for Inverter Air-Cooled Scroll Modular Chiller - Cooling Only (R410A)
Model Unit UAL

BTU/h
Ton
kW
kW
A

Nominal Cooling Capacity


Nominal Total Input Power
Norminal Running Current
IPLV

BTU/h/W
W/W
V/Ph/Hz

EER
Power Source
Flow Control (Expansion Device)
Refrigerant
Water Flow Rate
Water Pressure Drop
Sound Pressure Level
Unit Dimension
Packing Dimension
Weight

Compressor

Condenser

Fan & Motor

Evaporator

Height X Width X Depth


Height X Width X Depth
Net (unit weight only)
Gross (with packaging)
Type
Quantity
Insulation Grade
Oil Type
Tube
Fin

Type
Charge

Material
Diameter
Material
Row

Quantity
Index of Protection (IP)
Insulation Grade
Type
Plate Material
Max. Water Operating Pressure
Connection

kg
m3/h
kPa
dBA
mm
mm
kg
kg

mm

kPa
mm

Inverter
Inverter UAL-E Series
UAL230E
225,255
18.8
66
19.5
38
4.36
11.55
3.38
380-415 / 3 / 50
EXV
R410A
9.8 + 9.8
11.4
46
58 - 66
1840 X 840 X 1990
2010 X 890 X 2010
565
605
Scroll
3
E
POE
Copper
7
Aluminium
3
2
IP43
E
Brazed Plate Heat Exchanger
Stainless Steel
4500
28.7

Notes: Nominal cooling conditions: EWT/LWT: 12/7C


Ambient DB temperature is 35C
All specifications are subjected to change by manufacturer without prior notice

10

PCXZAM15

Air-Cooled Scroll
Modular Chiller
Non-Inverter D series & Inverter E Series

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
http://www.daikin.com/global_ac/

All rights reserved


Specifications, designs and other content appearing in this brochure are current as of December 2014 but subject to change without
.
notice

Printed in Malaysia

R410A