Grounded Wye Primory

Wire)

Neutrol
NOTE: The High-Voltoge

neutrol of the tronsformer


bonk must be connected to
the primory neutrol.

Surge Arrester
NOTE:'Wild Leq '

Fused Cutout

'

208 V. To

Ground.

Primory ond Secondory


neutrols must De
neutrats
be \\

interconnected. \

NOTE:'Wild Leo

208 V.

To

Ground.

Pole
Ground

Use seven
terminol
meter.

Wire Open Delto


Secondory 12A/240

V.

VOLTAGE POTENTIALS-SECONDARY

PHASES I
to supply lorqe sinqle-phose, 12O/24O voll
loods with smoll omount'bf thre-e phoSe loods. Also used
when only two phoses of primory ore ovoiloble or during
emergencies when one unit of o four-wire, wye-delto bonk

APPLICATION Used

is

disobled.

See drowing 'G2.1' or "VG2.1'for construction detoils.


One-bushing or two-bushing tronsformers moy be used.
Usuolly tronsformers of different KVA sizes ore used.
BANK RATING: This bonk hos only 86.6%

of the rotino of

|I

240

b-N
c-N

I
I

't20 voLTS
208 VOLTS

o-c
o-N

I
I

24O
24O
12O

VOLTS
VOLTS
VOLTS
VOLTS

2.I O. ANGUI.AR DISPLACEMENT

the

ffi fiiffiAkino uo the three-bhose bonk ond onlv-57.7% oJ


the three-ohose'rotinq of o clo3ed delto-delto bonk of three
tronsformers. Thus, i[ is relotively inefficient where
three-phose loods predominote.

VOLTAGE

o-b
b-c

(lAaitive Polority-See

... ,fi"
TRANSFORMER SPECIFICATIOI

TRANSFORMER/METER CONNECTTON
THREE_PHASE, OPEN_WYE _

FOR 12O/24O VOLT POWER

GUTDE

OPEN DELTA
LOADS

APRIL 2OO5

RUS

G2.1G