Capture Jet Hood with Supply Air and Side-Jet Technology

The KVF Capture Jet hood with Side-Jet technology

Improved indoor air quality for higher productivity

is a highly efficient kitchen ventilation hood that

with reduced energy use. Haltons patented Capture

removes contaminated air and excess heat emitted by

Jet with Side-Jet technology improves the capture

cooking equipment, while delivering compensation air

and containment efficiency of the hood, thus

to the kitchen at low velocity for a comfortable and

reducing the exhaust air volume required.

clean environment.
Draught-free air distribution directly into the chefs
The KVF hood uses the advanced Halton Capture

work area for improved working conditions and

Jet system, combining horizontal and vertical jets at

enhanced capture and containment performance.

the front and also on the sides of the hood to improve


Performance tested by a third party in accordance

the capture and containment of the air flows

with the ASTM 1704 standard.

generated by the cooking equipment, even at the end


of the line. Overall, the system requires 30 to 40%

High-efficiency grease filtration using UL- and NSF-

less exhaust air volume than traditional hoods do to

classified KSA multi-cyclone filters for removal of up

remove an equal heat load.

to 95% of particles with a size of 8 microns or


above.

The Capture Jet with Side-Jet technology is based


on the high entrainment of a compact high-velocity

Standard delivery that includes lighting, integrated

capture air jet. The capture air jets efficiently induce

Capture Jet fan, TAB (Testing and Balancing)

ambient air at the critical front and side area of the

taps, and balancing dampers that allow accurate and

hood, minimising the spillage of the contaminated air

effective commissioning.

and maintaining good air quality in the chefs work


area.

Stainless steel construction with seamless design


for improved hygiene and fire safety.

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
1

20/KVF/0000/0308/EN

KVF

CODE
1
2
3
4
5
6
7
8
9
10
11
12
13

13
11
9

1
10
6

DESCRIPTION
Outer casing visible parts in stainless steel AISI 304
Exhaust air connection and adjustment damper
Supply air connection and adjustment damper type MSM
Access hatch
Light fixture with electrical junction box
Capture Jet nozzles
KSA grease filter
Grease collection tray or drain tap
Thermal insulation
Personal supply air nozzles
Capture Jet fan
Connection plenum and filter
10% perforated front face

Construction
The KVF kitchen canopy comprises a supply

The capture air plenum is thermally insulated using

compensation air unit with control damper type MSM,

non-fibre-releasing material to prevent vapours from

Capture Jet unit with side jets, a Capture Jet

condensing on the inner face of the canopy above the

centrifugal fan (optional), an IP65 light fitting,

cooking equipment.

adjustment dampers, airflow measurement taps and a

Testing and balancing taps (TAB) for flow

KSA grease separator.

measurement are fitted to the exhaust plenum and

All visible parts of the canopy are manufactured from

the Capture Jet air plenum.

polished stainless steel AISI 304 and the unexposed


parts from galvanised steel. Joints on the lower edge

The new Capture Jet family is manufactured in the

are fully welded.

form of modular sections. Large canopies are


assembled using a combination of separate modules

A collection tray or a drain tap is fitted into the grease

without any beams between the modules, meaning

drain channel in order to enable the removal of the

that one long section is created, which is aesthetically

grease and dirt extracted by the KSA multi-cyclone

preferable.

separator.

The modular sections make transportation and site


handling easier.

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
2

20/KVF/0000/0308/EN

3
12

20/KVF/0000/0308/EN

Modular Sections

K V F - (1 clos ed end)

K V F - (2 opened ends )

K V F - (1 clos ed end)

QUICK DATA
L1 (section
length)

Recommended Exhaust air volume


l/s

m 3/h

1500

1600

389 602

1400 2169

2000

2100

519 803

1867 2892

2500

2600

648 1004

2333 3615

5000

5100

1296 2008

4667 7230

7500

7600

1945 3012

7000 10845

10000

10100

2593 4017

9334 14460

Recommended make up air volume H=555

Recommended Capture jet air


volume (with width = 1300)
l/s

200 l/s/linear meter


or
720 m 3/h/linear meter of section
Msm 100% open
Dpst = 50 Pa

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
3

m 3/h

27

97

31

112

35

127

56

202

77

277

98

352

20/KVF/0000/0308/EN

Heat spilling

Capture &
containment

Function
The kitchen canopy above cooking appliances contains

removed flow into a drain channel and towards the

the rising warm air and contaminants (A).

collection tap/tray (D).

The Capture Jet (B) increases the efficiency of


capture of the smoke and contaminated air at both

Replacement air is distributed at a low velocity into

the face and sides for enhanced performance at the

the space through the front panel of the canopy (E).

end of the cooking line and directs the contaminated


air towards the KSA grease separator (C) where the

Individual supply nozzles (F) are adjustable to produce

grease particles and other impurities are separated

increased velocities in the working zone near the

from the exhaust air using the cyclone separation

cooking equipment, which helps to reduce the

principle. Grease and contaminants that have been

effect of the radiant heat given off by the cooking


equipment.

Accessories
Cover Boards where canopies are below ceiling

Non-standard spigots sizes and position

level

Canopy cut outs to fit around columns

Infill Panels

Exhaust/supply roof in stainless steel

KSA grease filters

U profile for hanging

Blind filter in stainless steel

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
4

20/KVF/0000/0308/EN

K V F - (2 clos ed ends )

DIMENSIONS (mm)
KVF (2 closed ends)
L

1100 3100

1200 1700

555

D1

250

D2

315

250

205

170

Note: The dimensions above are for modular sections only;


larger canopies are assembled using a combination of separate
modules, which makes transportation and site handling easier.

Light
25

175

450

720 (L1<or =1500, 2x18W), 1320 ( L1> 1500 2x36W)

LOCATION OF CONNECTIONS (mm)

For typical sizes


2 250

1 160

N1

M1

M1

1600

L/2

L1/2

375

325

375

325

L/2

2100

L/2

L1/2

500

450

500

450

L/2

2600

L/2

L1/2

500

450

500

450

L/2

3100

L/2

L1/2

500

450

500

450

L/2

M1

2 315

N1

1 315
L

Capture Jet

Supply

50

Wall
Exhaust

D2

D1

WEIGHT (KG)
1500

1700

1600

103

109

115

2100

120

126

132

2600

138

144

150

3100

156

162

168

F
Wall

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
5

50

M1

Optional s pigot
160

1300

L/B

L1

KVF

20/KVF/0000/0308/EN

K V F - (1 clos ed end)

DIMENSIONS (mm)
( 1 Closed end)

L2

1050 3050

1200 1700

555

D1

250

D2

315

250

205

170

Note: The dimensions above are for modular sections only;


larger canopies are assembled using a combination of separate
modules, which makes transportation and site handling easier.

Light
25

175

450

720 (L1<or =1500, 2x18W), 1320 ( L1> 1500 2x36W)

LOCATION OF CONNECTIONS (mm)

For typical sizes


2 315

2 250

1 160

N1

M1

N1

1550

(L2-50)/2

325

375

(L2-50)/2

2050

(L2-50)/2

450

500

(L2-50)/2

2550

(L2-50)/2

450

500

(L2-50)/2

3050

(L2-50)/2

450

500

(L2-50)/2

N1

1 315
L2

Wall
50

Capture Jet

M1

Supply

Exhaust

WEIGHT (KG)

D2

D1

1550

98

104

110

2050

115

121

127

2550

133

139

145

3050

151

157

163

M1
E

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
6

L2

1700

L1

1500

1300

N1

L2/B

Optional s pigot J
160

20/KVF/0000/0308/EN

DIMENSIONS (mm)
KVF

K V F - (2 opened ends )

( 2 Open ends)

L1

1000 3000

1200 1700

555

D1

250

D2

315

250

205

170

Note: The dimensions above are for modular sections only;


larger canopies are assembled using a combination of separate
modules, which makes transportation and site handling easier.

Light
25

175

450

720 (L1<or =1500, 2x18W), 1320 ( L1> 1500 2x36W)

LOCATION OF CONNECTIONS (mm)

For typical sizes

L1

N1

M1

M1

N1

1500

L1 /2

325

325

L1 /2

L1 /2

450

450

L1 /2

L1 /2

450

450

L1 /2

3000

L1 /2

450

450

L1 /2

N1

2000
2500

WEIGHT (KG)

D2

D1
1500

1700

1500

93

99

105

2000

110

116

122

2500

128

134

140

3000

146

152

158

Optional s pigot
160

M1

1300

L1/B

J
L1

Capture Jet
1 160

M1

Supply
2 250

N1

2 315

M1

Exhaust
1 315

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
7

20/KVF/0000/0308/EN

$P s t

Pressure drop and sound data, exhaust


H= 555
Ptab

= Pressure loss of filters measured

from Measuring tap


= Total exhaust static pressure loss

30,70,100

= Damper opening in %
$P tab

Pst

Section-1000

Section-1500
30

300

30

300
70

LpA dB(A)

200

LpA dB(A)

200

100

70

100

55

50

55

100

100

pst
[Pa]

50

pst
[Pa]

45

45

50

50

40

40

35

30

35

30

30

20

200

300

720

500

1000

400

500

qv [l/s]

1440

1800

qv [m3/h]

300

500

1000

L = 8 dB
r

qv [l/s]

600
2000

qv [m3/h]

L = 8 dB
r

Section-2000

Section-2500
30

300

LpA dB(A)

200

30

20

30

300

LpA dB(A)

200

70

70

100

100

55

55

100

50

100

50

pst
[Pa]

pst
[Pa]

45

45
50

50

40

40
35

30

300

30

20

30

20

35

30

400

500

400

500
1800

1000

2000

1000

qv [l/s]

qv [l/s]

800

3000

qv [m3/h]

L = 8 dB
r

L = 8 dB
r

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
8

2000

3000

qv [m3/h]

KVF K-FACTOR CHART, EXHAUST


30

300

LpA dB(A)

200

70

100

55
100

KSA (Number of filters)

K factor (m 3/h)

K factor (l/s)

68,7

19,1

137,5

38,2

204,7

56,9

270,9

75,2

339,5

94,3

408,4

113,4

50

pst
[Pa]

45
50

40
35

30

30

20

500

1000

600

2000
L

qv [l/s]

1200

3000

5000

qv [m3/h]

= 8dB

T.A.B. / Exhaust air-flow rate adjustment


Recommended pressure TAB 50-120 Pa

00
15

10

00

100

30

0.4

tio
n5
00
mm

TAB

00

120

ec

$p

25

0.5

00

200

00

Pa

0.8

20

" w.g.

KS
A

ac

tiv

es

0.3

0.2

50

0.12

30
70
20

80

150

250

90 100
200

300

120
250
400

140
300
500

400
600

400

300

160 180 200


500

600
1000

600

1500

700

800 900 1000

1500

1000

700

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
9

500

2000

2000
3000

l/s

1200
2500

4000

2900

cfm

5000

m/h

20/KVF/0000/0308/EN

Section-3000

20/KVF/0000/0308/EN

$P s t

Pressure drop and sound data, supply


H= 555
Ptab

= Pressure loss measured


from Measuring tap

Pst

= Total supply static pressure loss

10, 50,100

= Damper opening in %

$P tab

Section-1000

Section-1500
10

300

LpA dB(A)

200

50

10

300

LpA dB(A)

200

100

50

100

55

55

100

100

50

pst
[Pa]

50

pst
[Pa]

45

45
50

50

40

40
35

30

300

720

500
L

1000

200

qv [l/s]

Section-2000

500

300
1000 1080

500

qv [m3/h]

1200

MAXIMUM FLOW
RECOMMENDED

= 8dB

30

20

200

100

300

25

30

25

20

35

30

qv [l/s]
2000

qv [m3/h]

MAXIMUM FLOW
RECOMMENDED

= 8 dB

Section-2500
10

300

50

10

300

50

LpA dB(A)

200

200

100

55

100

55

pst
[Pa]

45

50

100

100

50

pst
[Pa]

LpA dB(A)

50
45

50

40

40
30

30

35
25

20

200

300

35

30

30

20

400

500

300
1000

1000
L

= 8 dB

1440

500

800

qv [l/s]

3000

qv [m3/h]

qv [l/s]
2000

qv [m3/h]

MAXIMUM FLOW
RECOMMENDED

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
10

= 8 dB

1800 2000
MAXIMUM FLOW
RECOMMENDED

KVF K-FACTOR CHART, SUPPLY


10

300

50

LpA dB(A)

200

100

55

100
pst
[Pa]

L1 (Length of section) mm

K factor (m 3/h)

K factor (l/s)

1000

125,1

34,8

1500

187,7

52,1

2000

250,2

69,5

2500

312,8

86,9

3000

375,3

104,3

50
45

50

40
30

35
30

25

20

500

300

2000 2160

1000
L

3000

1000

qv [l/s]

3500

qv [m3/h]

MAXIMUM FLOW
RECOMMENDED

= 8 dB

600

T.A.B. / Supply air-flow rate adjustment


Recommended pressure TAB 35 Pa

" w.g.

Pa
100

0.4
0.3
0.2

00

00

00

00

10

50

25

20

15

00

00

40

30

00

50

Maximum
values
recommended

30

$p

0.1

TAB

20
0.06
0.05
10

0.04
0.03

0.02

100

120
250
400

140
300
500

400
600

700

400

300

200

160 180

500

600

500

1500

1000

MSM 250 - Supply


300
200
100
pm
[Pa]

50
30
20
10
5

500

1000

qv [m/h]

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
11

2000

2000
3000

l/s

1000 1200

800

1500

1000

700

600 700

2500
4000

2900

cfm

5000

m/h

20/KVF/0000/0308/EN

Section-3000

The hood shall be supplied with a Capture Jet fan to

The kitchen hood shall be constructed from 1.0-mm


AISI 304 stainless steel.

provide the required air flow at the indicated static

The kitchen hood shall be supplied complete with

pressure. The fan is to be provided by the hood


manufacturer, so an additional supply air system is not

Capture Jet technology, high-efficiency multi-cyclone

required for the Capture Jet system.

grease filters, pressure measurement taps, exhaust air


spigots with adjustment dampers, and a fluorescent

Supply air plenum


To minimise any draughts negative impact on hood
capture and containment and to guarantee a fresh and
comfortable work environment, the compensation air
shall be introduced into the space at the lowest
practical velocity (less than 0.5 m/s). The front panel
shall have a double-perforated structure to achieve
uniform, low-velocity air discharge. This panel shall be
easy to remove for cleaning and maintenance
operations, and the supply chamber shall be insulated
to avoid any risk of condensation.

light fitting with installation hatch. The size shall be as


indicated in the drawings.
Outer casing
Outer casing panels are constructed from AISI 304
stainless steel in a brushed satin finish in a modular
construction. The joints of the lower edge shall be
fully welded to be liquid-tight, avoiding harmful
dripping of condensation. All exposed welds are
ground and polished to the metals original finish.
The bottom edge of the exhaust plenum should be
aerodynamically designed (no flat surface or bounce).
Canopy ends shall be of double-sidewall construction
(no single wall permitted).

Grease filters
The hood shall be equipped with a KSA-model multicyclone stainless steel grease extractor. The grease
extraction efficiency is 93% for particles with a
diameter of 5 microns and 98% for those with a
diameter of 15 microns or larger, as tested by an
independent testing laboratory. The pressure loss over
the extractor shall not exceed 120 Pa at the flow rates
calculated. Sound levels shall not exceed an LpA
rating of 50 dB(A). The filter shall be NSF- and
UL-classified. Baffle- or slot-type grease extractors
shall not be used.

Exhaust
The exhaust air flow will be based on the convective
heat generated by the appliances under each canopy.
Submittal shall include convective heat calculations
based on the input power of the appliance served.
The hood mounting height shall be in accordance with
the drawings supplied, as a moderate increase in
exhaust rate is required if the hood is installed higher
than designed.

TAB ports and air flow balancing


The air flows are to be determined via the integral TAB
ports mounted in the hood. The air flows are to be
determined by the pressure vs. air flow curves
supplied by Halton.
The replacement air shall be delivered with a supply
control damper of type MSM.
The spigot connections for supply and extracted air
shall be supplied with a sealing gasket and air-flowbalancing damper plate.

Capture Jet with Side Jet technology


The hood shall be designed with Capture Jet
technology and Side-Jet technology to reduce the
exhaust air flow rate required and to improve the
capture and containment efficiency of the hood not
only at the front but also on the sides of the canopy,
while reducing energy consumption. The Capture
Jet air shall be introduced through a special
discharge panel and shall not exceed 10% of the
calculated exhaust air flow. The Capture Jet
discharge velocity shall be a minimum of 8 m/s. Slotor grille-type discharge shall not be used. The Capture
Jet chamber is to be insulated.

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
12

20/KVF/0000/0308/EN

Suggested specifications

Fire suppression system


The kitchen hood fire extinguishing system shall
protect the kitchen hood against grease fires via a
completely automatic fire control system of the wet
chemical type. The fire detection system shall be
capable of detecting fire in the hood, duct, or surface
equipment and shall automatically discharge liquid
extinguishing agent into the plenum chamber, exhaust
duct collar, and cooking appliance areas to eliminate
the possibility of re-ignition or re-flash. System
components shall include a spring-loaded release
mechanism, agent tank brass nozzles with blow-off
caps and stainless steel appliance drops, a fusible link
detector, wall-mounted emergency pull stations, a
wall-mounted automan and cabinet, and a mechanical
gas valve installed in the gas line serving the cooking
equipment (valve provided by the fire protections
system manufacturer and installed in the gas line by a
plumber). The systems installation shall be performed
by an authorised representative of the system
manufacturer and conform to UL 300 requirements
and local codes.
Type: KVF Manufacturer: Halton

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
13

20/KVF/0000/0308/EN

Light fixtures
Each canopy shall be provided with a fluorescent light
fixture to provide approx. 500 lux at the cooking
appliances work surface. The light is protected with a
stainless steel hatch with plain milled finish,
surrounded by a tempered-glass light diffuser (the
heat tolerance of the glass shall be -40 to 300 C). The
hatch shall be hinged and held in position with
screws.

SAP product code KVF_3

SC = Number of supply connections


1 =

1 spigot

WE = Closed end(s)

2 =

2 spigots

2 =

2 walls

3 =

3 spigots

R =

Right side wall

L =

Left side wall

N =

No wall

555-555

555-400

no spigot

SD = Supply damper

H = Height

N =

1 =

Yes

N =

No

CJ = Capture jet variants

L = Lenght

If WE = N

L = 1000, 1050,3000

If WE = R or L L = 1050, 1100,3050

If WE = 2

L = 1100, 1150,...3100

1 =

CJ fan + connection plenum + grille

2 =

CJ fan + connection plenum + spigot

160

3 =

CJ fan only (no connection plenum)

4 =

Spigot 160 + connection plenum

(No CJ fan)

LF = Light fitting

Nothing (no CJ fan, no connection

T5

T5

T8

T8

No

5 =

plenum...)

CD = Canopy drain


LC = Light color

D =

Drain tap

C =

Collection tray

830

830

840

840

930

930

S =

Standard

940

940

U =

U profile

HS = Hanging system

B = Width

M=Material

If LF = T5 or T8 B = 1200,1250,..1700

If LF = N

B = 1000,1050,..1700

NB = Number of blind filters


NB =

AS =

Full stainless steel

AT =

Full stainless steel 1,2 mm

CS =

Standard

CT =

Standard 1,2 mm

0,1,2,3,4,5,6
Sub product

EC = Number of exhaust connections

KB (cover board)

KI (Infill panel)

1 =

1 spigot

2 =

2 spigots

3 =

3 spigots

N =

no spigot

Code example
KVF/N-1000-1000-555, LF=T5, LC=830, NB=0, EC=N,

ED = Exhaust damper

ED=N, SC=N, SD=N, CJ=3, CD=D, HS=S, MA=CS,

1 =

Yes

ZT=N

N =

No

KVF - Capture Jet Hood with Supply Air and Side-Jet Technology
14

20/KVF/0000/0308/EN

Product code