Академический Документы
Профессиональный Документы
Культура Документы
Capacitor units shall be suitable for continuous operation at an RMS current of 1.30 times the
current that occurs at rated sinusoidal voltage and rated frequency, excluding transients. Taking
into account the capacitance tolerances of 1.1 CN, the maximum permissible current can be up to
143 IN.
These overcurrent factors are intended to take care of the combined effects of harmonics and
overvoltages up to and including1.10 UN, according to IS 13340.
Top
Discharge Device
Each capacitor unit or bank shall be provided with a directly connected discharge device.
Thedischarge device shall reduce the residual voltage from the crest value of the rated value UN
to 50 V or less within 1 min, after the capacitor is disconnected from the source of supply. There
must be no switch, fuse or any other isolating device between the capacitor unit and the discharge
device.
A discharge device is not a substitute for short-circuiting the capacitor terminals together and to
earth before handling.
Where:
t = time for discharge from UN Jr to UR(s),
R = equals discharge resistance
C = rated capacitance (pF) per phase,
UN = rated voltage of unit (V),
UR = permissible residual voltage
k = coefficient depending on both resistance and capacitor unit connections, Value of k to be taken
as per IS13340
Top
capacitor with the star connection results to be subjected to a voltage 3 lower and flows through
by a current 3 higher than a capacitor inserted and delta connected.
Where,
Ur = rated voltage, which the capacitor must withstand indefinitely;
Fr = rated frequeny
Qc = generally expressed in kVAR (reactive power of the capacitor bank)
While deciding the size of capacitor bank on any bus it is necessary to check the voltage rise due
to installation of capacitors under full load and light load conditions. It is recommended to limit the
voltage rise to maximum of 3% of the bus voltage under light load conditions. The voltage rise due
to capacitor installation may be worked out by the following expression.
Top
Where,
% VC = % voltage change or rise due to capacitor
% X = % Reactance of equipment e.g. Transformer
If the capacitor bank is STAR connected than the required value of C will be higher in comparison
to the value of C in DELTA connection for the same value of required kVAR. Higher value of C will
cause higher voltage rise of the system causing nuisance tripping of the equipment provided with
over voltage protection.
It is common practice to leave the star-connected capacitor banks ungrounded (there are separate
reason for leaving it ungrounded) when used in the system or use delta-connected banks to
prevent the flow of third harmonic currents into the power system through the grounded neutral.
Large capacitor banks can be connected in STAR ungrounded, STAR grounded or delta. However,
the wye ungrounded connection is preferable from a protection standpoint. For the STAR
ungrounded system of connecting single capacitor units in parallel across phase-to-neutral voltage
the fault current through any incomer fuse or breaker of capacitor bank is limited by the capacitors
in the two healthy phases. In addition the ground path for harmonic currents is not present for the
ungrounded bank.
For STAR grounded or delta-connected banks, however, the fault current can reach the full short
circuit value from the system because the sound phases cannot limit the current.
Top
Another important aspect is resonance which can occur when p.f. capacitors forms the series or
parallel resonant circuit with impedance of supply transformer. If the resonance frequency of this
LC circuit coincides with one of the harmonic present, the amplitude of the harmonic current
flowing through LC circuit is multiplied several times damaging the capacitors, supply transformer
and other network components.
Top
FR = kVASC / kVARC
Where,
FR = resonant frequency as a multiple of the fundamental frequency
kVASC= short circuit current at the point of study
kVARC = capacitor rating at the system voltage
If FR equals or is closed to a characteristic harmonic, such as the 5th or 7th, there is a possibility
that a resonant condition could occur. Almost all harmonic distortion problems occur when the
parallel resonance frequency is close to the fifth or seventh harmonic, since these are the most
powerful harmonic current components. The eleventh and thirteenth harmonics may also be worth
evaluating.
Top