BATTERY LOAD CALCULATION FOR 2 ZONES CO2 PANEL AT LV MSB ROOM

CALCULATION FOR STANDING & ALARM LOAD

Standing Load

Current Consumption per zone

0.0036 A

For

(0.0036 x

2
-----------

2 ) Amp
--------0.0072 Amp
----------

Current Consumption per smoke detector

0.003

For

(0.003

0.006 A
---------

(0.0072
-----------

0.0132 A
---------

Total Current Consumption for the system per hour

0.0132 A
---------

Therefore Standing Load for 72 hours

(0.0132 x 72 ) AH
----------

0.9504 AH
-----------

Current Consumption per bell

0.05

For

0.05

0.05
A
---------

(0.05
x
---------

0.15
AH
---------

(0.9504 + 0.15 ) AH
---------------------

1.10
AH
----------

Contingency 25%

1.37
AH
---------

Recommended Battery Capacity

4
AH
---------

2
-----------

zone

no. smoke detector

Total Standing Load

2
)
---------

+ 0.006 ) A
----------

During Alarm Condition

1 no. bell
----------

Alarm Load For 3 hours

Capacity Of Battery

1
A
---------

3 ) AH
----------

BATTERY LOAD CALCULATION FOR 2 ZONES CO2 PANEL AT GENSET ROOM

CALCULATION FOR STANDING & ALARM LOAD

Standing Load

Current Consumption per zone

0.0036 A

For

(0.0036 x

2
-----------

2 ) Amp
--------0.0072 Amp
----------

Current Consumption per smoke detector

0.003

For

(0.003

0.006 A
---------

(0.0072
-----------

0.0132 A
---------

Total Current Consumption for the system per hour

0.0132 A
---------

Therefore Standing Load for 72 hours

(0.0132 x 72 ) AH
----------

0.9504 AH
-----------

Current Consumption per bell

0.05

For

0.05

0.05
A
---------

(0.05
x
---------

0.15
AH
---------

(0.9504 + 0.15 ) AH
---------------------

1.10
AH
----------

Contingency 25%

1.37
AH
---------

Recommended Battery Capacity

4
AH
---------

2
-----------

zone

no. smoke detector

Total Standing Load

2
)
---------

+ 0.006 ) A
----------

During Alarm Condition

1 no. bell
----------

Alarm Load For 3 hours

Capacity Of Battery

1
A
---------

3 ) AH
----------

BATTERY LOAD CALCULATION FOR 2 ZONES CO2 PANEL AT LV MSB ROOM

CALCULATION FOR STANDING & ALARM LOAD

Standing Load

Current Consumption per zone

0.0036 A

For

(0.0036 x

2
-----------

2 ) Amp
--------0.0072 Amp
----------

Current Consumption per smoke detector

0.003

For

(0.003

0.006 A
---------

(0.0072
-----------

0.0132 A
---------

Total Current Consumption for the system per hour

0.0132 A
---------

Therefore Standing Load for 72 hours

(0.0132 x 72 ) AH
----------

0.9504 AH
-----------

Current Consumption per bell

0.05

For

0.05

0.05
A
---------

(0.05
x
---------

0.15
AH
---------

(0.9504 + 0.15 ) AH
---------------------

1.10
AH
----------

Contingency 25%

1.37
AH
---------

Recommended Battery Capacity

4
AH
---------

2
-----------

zone

no. smoke detector

Total Standing Load

2
)
---------

+ 0.006 ) A
----------

During Alarm Condition

1 no. bell
----------

Alarm Load For 3 hours

Capacity Of Battery

1
A
---------

3 ) AH
----------

BATTERY LOAD CALCULATION FOR 2 ZONES CO2 PANEL AT LV MSB ROOM


(TOWER 1 LOWER LEVEL 1) FOR M/S NILAI ARIF SDN. BHD.

CALCULATION FOR STANDING & ALARM LOAD

Standing Load

Current Consumption per zone

0.0036 A

For

(0.0036 x

2
-----------

2 ) Amp
--------0.0072 Amp
----------

Current Consumption per smoke detector

0.003

For

(0.003

0.009 A
---------

(0.0072
-----------

0.0162 A
---------

Total Current Consumption for the system per hour

0.0162 A
---------

Therefore Standing Load for 72 hours

(0.0162 x 72 ) AH
----------

1.16
AH
-----------

Current Consumption per bell

0.05

For

0.05

0.05
A
---------

(0.05
x
---------

0.15
AH
---------

(1.16
+ 0.15 ) AH
---------------------

1.31
AH
----------

Contingency 25%

1.63
AH
---------

Recommended Battery Capacity

4
AH
---------

3
-----------

zone

no. smoke detector

Total Standing Load

3
)
---------

+ 0.009 ) A
----------

During Alarm Condition

1 no. bell
----------

Alarm Load For 3 hours

Capacity Of Battery

1
A
---------

3 ) AH
----------