Академический Документы
Профессиональный Документы
Культура Документы
LIST OF FIGURES
1
Pump
WaterPressure
or
Flow
Driving Force
1.
(a)
(b)
The source of supply will provide pressure called Electromotive Force or Voltage.
The symbol for voltage is U.
2.
The load is any device that is placed in the electrical circuit that produces an effect when an
electric current flows through it. When an electric current flows through an incandescent lamp, the
lamp gives off light from heat.
3.
The connecting leads or cables complete the circuit. The cable consists of the conductor to
carry the current and insulation to prevent leakage. A water pipe must have a bore to carry the water
and the pipe material ( e.g. copper ) to prevent leakage.
Circuit Analogy
The simplest analogy of an electric circuit is to consider a hosepipe connected to a tap. The rate of
flow of water from the end of the hosepipe will depend upon:
The water pressure at the tap.
The diameter of the hosepipe
The restriction / resistance of the inner walls of the hosepipe.
The degree of any bends or kinks in the hosepipe.
If there are many restrictions, the water will flow out of the hosepipe at a reduced rate.
Heating Effect
Magnetic Effect
Chemical Effect
An anode or cathode of dissimilar metals placed in an electrolyte can react chemically and produce
an EMF. When a load is connected across the anode and cathode, a current will flow in the circuit.
The chemical effect of an electric current is the principle upon which electric cells operate.
Anode
C a th o d e
L iq u id
Figure 5: Electrolytic Process
Voltage
In a modern power system, electrical energy from the generating station is delivered to the ultimate
consumers through a network of transmission and distribution. For satisfactory operation of motors,
lamps and other loads, it is desirable that consumers are supplied with substantially constant
voltage. Too wide variations of voltage may cause erratic operation or even malfunctioning of
consumers appliances. To safeguard the interest of the consumers, the government has enacted a
law in this regard. The statutory limit of voltage variation is 6% of declared voltage at consumers
terminals.
The principal cause of voltage variation at consumers premises is the change in load on the supply
system. When the load on the system increases, the voltage at the consumers terminals falls due to
the increased voltage drop in (i) alternator synchronous impedance (ii) transmission line (iii)
transformer impedance (iv) feeders and (v) distributors.
Methods of Voltage Control
There are several methods of voltage control. In each method, the system voltage is changed in
Accordance with the load to obtain a fairly constant voltage at the consumers end of the system.
The
Following are the methods of voltage control in an *a.c. power system:
By excitation control
By using tap changing transformers
Auto-transformer tap changing
Booster transformers
Induction regulators
By synchronous condenser
Importance of Voltage Control
In case of lighting load, the lamp characteristics are very sensitive to changes of voltage. In
case of power load consisting of induction motors, the voltage variations may cause erratic
operation.
Too wide variations of voltage cause excessive heating of distribution transformers. This
6
Power in AC Circuits
Power in Purely resistive Load
Consider firstly power dissipation in a resistor when supplied by a dc battery as shown in Fig 1. In
this case the voltage across the resistor is constant and therefore also is the current flowing through
it. Consequently, the power dissipation, given as the product of the voltage and the current, is
constant and invariant with time.
V
+
I
V t Vm Sin t
i(t)
V(t)
i t I m Sin t
RL
VL = V(t)
I m Vm / R
Pi t V(t)i(t)
Pi
PAVE
1 2
T
f
T
Pi t V(t)i(t)
at the load
V t Vm Cos t and
i t I m Cos t
If
Pi Vm I m Cos 2t
Then
Pi
Vm I m
1 Cos2t
Average Power:
Average power is the long-term or average value of the instantaneous power. For a periodic source it
is calculated over one full cycle of the source delivering it to a load.
It is an equivalent value of constant power.
PAVE
1
T
0 Pi dt
1
T
0 V t i t dt
T
V t Vm Cos t
and
i t I m Cos t
If
10
PAVE
Then
PAVE
Vm I m
2T
PAVE
PAVE
1.dt
1 T1
Vm I m 1 Cos 2t
T 0 2
Vm I m
2T
so
Vm I m
V I
(T 0) m m Sin 2T Sin 0
2T
2T2
2
4T
then 2T
4 2x2
T
T
Then
Cos 2t.dt
Vm I m T
V I
T
t 0 m m Sin 2t 0
2T
2T2
2f
But
Vm I m
2T
xT
Vm I m
2
2
V
V I V
I R
Im m then PAVE m m m m
R
2
2R
2
11
Vm
T
Vrms
Vave = 0
By definition:
VRMS
1 T 2
V t dt
T 0
VRMS
1 T 2
Vm Cos 2 t.dt
0
T
VRMS
Vm2
xT
2T
Vm2
2T
(1 Cos2t).dt
Vm2
V
m
2
2
It can be seen from the previous relationship for average power that if:
Im
Vm
R
then
PAVE
Vm I m Vm I m
VRMS I RMS
2
2 2
This is the idea behind an rms value by definition. The rms value of an ac sinusoidal source voltage
is that value of voltage which delivers the same average power to a load as a dc supply of the same
value.
2
VRMS
I 2RMS R
R
Note that for the sinusoidal source the instantaneous power varies between zero, when V(t) = 0, i(t)
= 0 and a maximum which occurs when V(t) = Vm and i(t) = Im. This means that for a sinusoidal
source the average power is half of the peak power.
12
V t Vm Sin t
i t I m Cost
X L L
V t jLi t
i(t)
-j
V(t)
V(t)
i(t)
13
+
+
_
_
14
Pi V t i t Vm Sin t I m Cos t
Instantaneous Power
Pi
Pi
Vm I m
Sin 2t Sin 0
2
Vm I m
2
Sin 2t
PAVE
Average Power
PAVE
PAVE
PAVE
Vm I m
2T
1 T
Vm I m Sin 2t
2T 0
Sin 2t
Vm I m
T
Cos 2t 0
2T2
Vm I m
Cos 4 - Cos 0
2T2
PAVE
Vm I m
11 0
4 T
We conclude that the average power dissipated in a pure inductance is zero. However, it can be seen
that the instantaneous power is not zero, except at zero crossings of the time axis. This means that
power is drawn from the source. What happens is that when the instantaneous power is positive,
energy is drawn from the source and stored in the inductor for a quarter of a cycle. When the
instantaneous power is negative, this stored energy is returned to the source which reabsorbs it.
However, the source must still have the capacity to provide the power required by the inductor, even
though this is not dissipated or consumed.
15
16
17
18
__
+ +
+ +
19
Note: As in the previous case, the instantaneous power alternates between positive and negative
phases at twice the frequency of the source supplying it.
Instantaneous Power
Pi
Pi V t i t Vm Sin t I m Cos t
Vm I m
Sin 2t Sin 0
2
Pi
Vm I m
2
Sin 2t
PAVE
Average Power
Vm I m
2T
Sin 2t 0
Therefore, as was the case for the inductor, the average power dissipated in a capacitor is zero. As
with the inductor, power is drawn from the supply and stored as energy in the capacitor for a quarter
of a cycle and then returned to the source during the following quarter cycle.
Power Factor
In electrical engineering, the power factor of an AC electrical power system is defined as the ratio of
the real power flowing to the load to the apparent power in the circuit,[1][2] and is a dimensionless
number in the closed interval of 1 to 1. A power factor of less than one means that the voltage and
current waveforms are not in phase, reducing the instantaneous product of the two waveforms (V
I). Real power is the capacity of the circuit for performing work in a particular time. Apparent
power is the product of the current and voltage of the circuit. Due to energy stored in the load and
returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn
from the source, the apparent power will be greater than the real power. A negative power factor
occurs when the device (which is normally the load) generates power, which then flows back
towards the source, which is normally considered the generator.
In an electric power system, a load with a low power factor draws more current than a load with a
high power factor for the same amount of useful power transferred. The higher currents increase the
energy lost in the distribution system, and require larger wires and other equipment. Because of the
costs of larger equipment and wasted energy, electrical utilities will usually charge a higher cost to
industrial or commercial customers where there is a low power factor.
Definition of power-factor
The power factor is defined as the ratio of active power to apparent power in a circuit. It varies from
one to zero but is generally given as below:
Power factor = Active power in KW / Apparent power KVA
Power Factor = cosine of angle between active power and apparent power
20
= Cos
Active Power = Apparent power Power Factor
= (KVA). (PF)
Benefits Of Power Factor Improvement
Most benefits provided by a power factor improvement system from the reduction of reactive power
in the system. This may result in
A) Lower purchased-power cost if the utility enforces a power-factor clause
B) Release of system electrical capacity
C) Voltage improvement and
D) Lower system losses
Maximum benefits are obtained when capacitors are located at low power-factor levels. Although
reducing the power bill is still primary reason for improving the power factor, and it is becoming
more important because of conservation of energy, the function of releasing system capacity is
sometimes the decisive factor.
Causes of Low Power Factor.
Most utilization devices require two components of current.
a) The power producing current or working current is that current which is converted by the
equipment into useful work, usually in the form of heat, light or mechanical power. The unit of
measurement of power is WATT.
b) Magnetizing current, also known as Watt-less, reactive or non-working current, is the current
required to produce the flux necessary for the operation of electromagnetic devices. Without
magnetizing current, energy could not flow through the core of transformer. The unit of
measurement of reactive power is VAR.
The normal relationship of these two components of current to each other, to the total current, and to
the system voltage is explained in Fig-1. It shows that the active current and reactive current add
vectorially to form the total current which can be determined from the expression,
always leading. An induction motor or transformer has a lagging power factor as it required both
active and reactive power into in the motor or transformer.(same direction)
How The Power Factor Is Improved
When the reactive power component in a circuit is reduced, the total current is reduced. If the
active power component does not change, as is usually true, the power factor will improve as the
reactive power component becomes zero, the power factor will be unit or 100 percent.
Suppose a transformer load (in the power plant used in DOT) takes an active load of 80A and a
reactive load of 60A from the mains, the total or line current will be of v802 + 1002 = 100 Amps. If
a capacitor is installed so that it will supply the reactive current of 60A, then the supply needs to
deliver only 80A to the exactly same load of the transformer. The supply circuit is now carrying
only active power, hence the system capacity is not wasted in carrying reactive power.
Now, if we increase the capacity of capacitor further to increase the reactive current, the excess
reactive current tends to flow towards the mains, causing the leading power-factor, which is also not
advisable in the view of Electricity authorities.
Therefore the capacitor rating required to improve the power factor is
Reactive power of capacitor = Active power (Tan 1 - Tan 2 )
Harmonics
Non-sinusoidal complex waveforms are constructed by adding together a series of sine wave
frequencies known as Harmonics. Harmonics is the generalised term used to describe the
distortion of a sinusoidal waveform by waveforms of different frequencies.
Then whatever its shape, a complex waveform can be split up mathematically into its individual
components called the fundamental frequency and a number of harmonic frequencies. But what
do we mean by a fundamental frequency.
Fundamental Frequency
A Fundamental Waveform (or first harmonic) is the sinusoidal waveform that has the supply
frequency. The fundamental is the lowest or base frequency, on which the complex waveform is
built and as such the periodic time, of the resulting complex waveform will be equal to the
periodic time of the fundamental frequency.
Lets consider the basic fundamental or 1st harmonic AC waveform as shown.
harmonic frequency would be 100Hz (2 x 50Hz), a 3rd harmonic would be 150Hz (3 x 50Hz), a 5th
at 250Hz, a 7th at 350Hz and so on. Likewise, given a 60Hz fundamental waveform, the 2nd, 3rd,
4th and 5th harmonic frequencies would be at 120Hz, 180Hz, 240Hz and 300Hz respectively.
So in other words, we can say that harmonics are multiples of the fundamental frequency and can
therefore be expressed as: 2, 3, 4, etc. as shown.
Complex Waveforms Due To Harmonics
Note that the red waveforms above, are the actual shapes of the waveforms as seen by a load due to
the harmonic content being added to the fundamental frequency.
The fundamental waveform can also be called a 1st harmonics waveform. Therefore, a second
harmonic has a frequency twice that of the fundamental, the third harmonic has a frequency three
times the fundamental and a fourth harmonic has one four times the fundamental as shown in the
left hand side column.
The right hand side column shows the complex wave shape generated as a result of the effect
between the addition of the fundamental waveform and the harmonic waveforms at different
harmonic frequencies. Note that the shape of the resulting complex waveform will depend not only
on the number and amplitude of the harmonic frequencies present, but also on the phase relationship
between the fundamental or base frequency and the individual harmonic frequencies.
We can see that a complex wave is made up of a fundamental waveform plus harmonics, each with
its own peak value and phase angle. For example, if the fundamental frequency is given as;
E = Vmax(2t), the values of the harmonics will be given as:
For a second harmonic:
E2 = V2max(22t) = V2max(4t), = V2max(2t)
For a third harmonic:
E3 = V3max(32t) = V3max(6t), = V3max(3t)
For a fourth harmonic:
E4 = V4max(42t) = V4max(8t), = V4max(4t)
and so on.
Then the equation given for the value of a complex waveform will be:
Harmonics are generally classified by their name and frequency, for example, a 2nd harmonic of the
fundamental frequency at 100 Hz, and also by their sequence. Harmonic sequence refers to the
phasor rotation of the harmonic voltages and currents with respect to the fundamental waveform in a
balanced, 3-phase 4-wire system.
A positive sequence harmonic ( 4th, 7th, 10th, ) would rotate in the same direction (forward) as
the fundamental frequency. Whereas a negative sequence harmonic ( 2nd, 5th, 8th, ) rotates in the
opposite direction (reverse) of the fundamental frequency.
Generally, positive sequence harmonics are undesirable because they are responsible for overheating
of conductors, power lines and transformers due to the addition of the waveforms.
Negative sequence harmonics on the other hand circulate between the phases creating additional
problems with motors as the opposite phasor rotation weakens the rotating magnetic field require by
motors, and especially induction motors, causing them to produce less mechanical torque.
Another set of special harmonics called triplens (multiple of three) have a zero rotational
sequence. Triplens are the odd multiples of the third harmonic ( 3rd, 6th, 9th, ), etc, hence their
name, and are therefore displaced by zero degrees. Zero sequence harmonics circulate between the
phase and neutral or ground.
24
Unlike the positive and negative sequence harmonic currents that cancel each other out, third order
or triplen harmonics do not cancel out. Instead add up arithmetically in the common neutral wire
which is subjected to currents from all three phases.
The result is that current amplitude in the neutral wire due to these triplen harmonics could be up to
3 times the amplitude of the phase current at the fundamental frequency causing it to become less
efficient and overheat.
Then we can summarise the sequence effects as multiples of the fundamental frequency of 50Hz as:
Harmonic Sequencing
Name
Frequency, Hz
Sequence
Fund.
50
+
2nd
100
3rd
150
0
4th
200
+
5th
250
6th
300
0
7th
350
+
8th
400
9th
450
0
Note that the same harmonic sequence also applies to 60Hz fundamental waveforms.
Sequence
Rotation
Harmonic Effect
+
Forward
Excessive Heating Effect
Reverse
Motor Torque Problems
0
None
Adds Voltages and/or Currents in Neutral Wire causing Heating
25
26