Вы находитесь на странице: 1из 4

Oil

Winding
Temperature
Transformer

and
Remote
Indicator
of

Temperature Indicator of Transformer


These are generally precision instruments. A temperature indicator of
power transformer is specially designed for protection of transformer in
addition to its temperature indication and cooling control features. That
means, this device performs three functions
1.
These instruments indicate instantaneous temperature of oil and windings of
2.
3.
4.
5.

transformer.
These also record maximum temperature rise of oil and windings.
These instruments operate high temperature alarm at a predetermined
value of allowable temperature limit.
Temperature indicators of transformer can also trip the circuit breakers
associated with the power transformer when the temperature of oil or winding
reaches a predetermined limit.
These devices also control the cooling system of transformer. Switch on the
cooling equipment when the winding attains a preset high temperature and
switch it off when the temperature drops by an established differential.

Types of Temperature Indicator of Transformer


There are mainly two types of temperature indicators used in
transformer. Principally both of the instruments are the same but, one is
used for oil temperature and the other is used for winding temperature.
There is another type of temperature indicator often used in power
transformer, which is little bit different principally and this is remote
temperature indicator.
The types of temperature indicator of transformer are1.
2.
3.

Oil temperature indicator (OTI)


Winding temperature indicator (WTI)
Remote temperature indicator (RTI)

Construction of Temperature Indicator of Transformer


These indicators are provided with a sensing bulb. This sensing bulb is
placed in a pocket on the roof of transformer tank. The pocket is filled
with transformer oil. The bulb is connected to the instrument housing by
means of flexible connecting tubing consisting of two capillary tubes.
One capillary tube is connected to the operating bellow of the instrument
and other to a compensating bellow. Compensating bellow compensates
variation of ambient temperature. The pointer is fixed with a steel
carriage on which normally four mercury switches are mounted. The
make and break temperature of these mercury switches can be adjusted

separately. One mercury switch is use to operate cooling fans, one


mercury switch is used to switch on oil pumps, one mercury switch is for
high temperature alarm and last switch is used to inter trip the
transformer in extremely high temperature condition. In addition to
these the dial of oil temperature indicator is also provided with
dummy pointer which is pushed by main pointer when temperature rises.
When main pointer moves back due to decreasing temperature, the
dummy pointer stays at maximum temperature position of the main
pointer. This indicates maximum temperature rise of transformer during
a preset period of time.

Oil Temperature Indicator or OTI


This device is used to measure the top oil temperature. An oil
temperature indicator or OTI is also used for protection of transformer.

Operating Principle of Oil Temperature Indicator


This device measures top oil temperature with the help of sensing bulb
immersed in the pocket by using liquid expansion in the bulb through a
capillary line to operating mechanism. A link and lever mechanism
amplifies this movement to the disc carrying pointer and mercury
switches. When volume of the liquid in operating mechanism changes,
the bellow attached to end of capillary tube expands and contracts. This
movement of bellow is transmitted to the pointer in temperature
indicator of transformer through a lever linkage mechanism.

Winding Temperature Indicator or WTI


This device measures the LV and HV winding temperature. A winding
temperature indicator or WTI is also used as protection of transformer.

Operating Principle of Winding Temperature Indicator


The basic operating principle of WTI is same as OTI. But only difference
is that the sensing bulb pocket on transformer top cover is heated by a
heater coil surrounded it. This heater coil is fed by secondary of current
transformers associated with transformer winding. Hence the current
through the heater coil is directly proportional to the current flowing
through transformer winding. This is because there is no scope of direct
measuring of temperature inside a winding. When load of transformer
increases, the winding temperature is also increased and this increased
temperature is sensed by sensing bulb as the heater coil surrounds it.
Rest of the working principle of winding temperature indicator is same as
principle of oil temperature indicator.

Remote Temperature Indicator


A precision potentiometer mounted inside the instrument case functions
as a transmitter and operates an electrical repeater for remote reading of
measured temperature. In one scheme the transmitter is directly

connected to the repeaters and alternative scheme is to connect the


transmitter to a resistance transducer, which will supply direct current
for operating repeater.