FOR
STRING MONITOR BOX
(ST G24_1 1N01)
CLIENT
PROJE CT
PLANT
Page 1 of 7
Page 2 of 7
For the identification of the individual Strings Box it is necessary to set it network address.
How to set the address:
Display
Network address display
INC. S/W
DEC. S/W
Selection Switch
1.
2.
3.
The address must be set via INC and DEC SWITCH installed on the control board
(SPCLPV)
4.
This address can be displayed by seven segment display DS1, DS2 & DS3.
5.
For convention the Strings Box address begin from 1 and continue according the
strings boxes number installed on the plant.
1-ON
2-ON
3-OFF
4-OFF
1-ON
2-ON
3-OFF
4-ON
1-ON
2-ON
3-ON
4-OFF
A) Calibration Mode
1-ON
2-ON
3-ON
4-ON
Page 3 of 7
Description
Access
40001
40002
40003
40004
40005
40006
40007
40008
40009
Current1
Current2
Current3
Current4
Current5
Current6
Current7
Current8
Current9
R
R
R
R
R
R
R
R
R
40010
Current10
40011
Current11
40012
Current12
40013
Current13
40014
Current14
40015
Current15
40016
Current16
40017
Current17
40018
Current18
40019
Current19
40020
Current20
40021
Current21
40022
Current22
40023
Current23
40024
Current24
40025
40026
DC Voltage
SPD Status
Output
Disconnector
Switch Status
Internal Ambient
Temperature
Slave ID
Baud Rate
Digital Input1
R
R
1-OFF, 0-ON
On board temperature
R/W*
R/W*
R
40027
40028
40029
40030
40031
EEPROM
Remarks
Page 4 of 7
40032
Digital Output1
40033
Digital Output2
40034
Analog Input1
40035
Analog Input2
Total Input
channel
Baud Rate
Number
20mA/10V
R/W*
R/W*
40036
40037
Registers marked with * are saved in EEPROM when modified and the saved values
are reloaded at the power-on.
1.1
This is read only registers. The values read at these registers are the values of the input
currents. (If the value of register is X then String Current= X/100A).
1.2
40025: DC VOLTAGE
This is read only register. The value read at this register is the value of string DC Voltage. The value is
expressed in Volts.
Average DC Current = Z/100
1.3
This is a read only register. The value read at this register is the Status of the SPD. If SPD operates
then value of this register will be 1 otherwise value of this register will be 0.
(If the value of register (X) = 1 then SPD operates,
If the value of register (X) = 0 then SPD not operates)
1.4
This is a read only register. The value read at this register is the Position Status of the Output Disconnector Switch.
(If the value of register (X) = 1 then Switch is in OFF position, If
the value of register (X) = 0 then Switch is in ON position)
1.5
This is read only register. The value read at this register is the value of the temperature expressed by
this formula given by the on board sensor. If the value of the register is Y then,
Internal Ambient temperature = Y/10C
1.6
*The permitted Slave ID addresses for the SPCL- 505 are from 1 to 255, settable with the switches INC
and DEC. Each string box connected to the Modbus network must have an only address.
Default: 01
1.7
This register is used to set different Baud Rate i.e. 2400, 4800, 9600, 19200 and 38400.Master
should send these values to change the baud rate. If user wants to change baud rate in string
monitoring box then by these two key it can possible. Press the INC and DEC key at the same time.
Then seven segment displays shows the baud rate. Press the INC or DEC key to change the value
according to table.
Displayed
value
br1
br2
br3
Baud rate
300
600
1200
Page 5 of 7
Default: 9600
1.8
br4
br5
br6
br7
br8
br9
2400
4800
9600
14400
19200
38400
This is read only register. The values read at these registers are the values of the Digital Inputs. If digital
input is present value of this register will be 1 and if digital input is not present value of this register will
be 0.
1.9
This is read only registers. The values read at these registers are the values of the Analog Inputs. The
values are in the range of (0-1000), where 1000 is the value given when the analog input voltage is
10V or analog input current is 20mA.
Baud rate
300
600
1200
2400
4800
9600
14400
19200
38400
Displayed
value
br1
br2
br3
br4
br5
br6
br7
br8
br9
All the data from individual strings is transmitted to control card via shielded multi core
twisted cable. All the sensing is through isolated Hall Effect sensors so that is no way is
high DC Voltage (upto 1000V) transmitted to control section of SMU.
Similarly for sensing of DC bus voltage a separate high isolated power supply is
used. There is adequate opto isolation IC as well to prevent HV entry into SMU.
Surge protection device are provided on communication line as well to prevent surge enter
into system.
Power supply Requirement: String Monitoring Box requires 230V AC, 1Ph 10% supply
to perform the intended function. Other controls supplies such at 15V & +5V are generated
internally. Input power requirement is around 6Watts. The supply requirement can be
changed to 110VDC or 220VDC on costumer requirement.
Page 6 of 7
SIGNAL
X49
LINE (IN/OUT)
X50
X51
Description
Wire Color
White On Blue
NEUTRAL
(IN/OUT)
EARTH
(IN/OUT)
White On Brown
White On Red
X52
RS485 (D-)
Violet On White
X53
RS485 (D+)
Yellow On White
X54
GND
Orange On White
Page 7 of 7