SEPAM B21

Proteksi
27 - 1
27 - 2
27D - 1
27D - 2
27R
27S
59 - 1
59 - 2
59N - 1
59N - 2
81H
81L - 1
81L - 2

GMR
Proteksi

Nama

Phase-to-Phase Undervoltage
Phase-to-Phase Undervoltage
Positive Sequence Undervoltage
Positive Sequence Undervoltage
Remanent Undervoltage
Phase-to-Neutral Undervoltage
Phase-to-Phase Overvoltage
Phase-to-Phase Overvoltage
Neutral Voltage Displacement
Neutral Voltage Displacement
Overfrequency
Underfrequency
Underfrequency

Status
On
Of
Of
Of
Of
Of
Of
Of
Of
Of
On
On
Of

(Generator Management Relay)


Nama Proteksi
Undervoltage Trip
Overvoltage Trip
Phase Reversal Trip
Underfrequency Trip

Status
Latched
Latched
Latched
Latched

Overfrequency Trip

Latched

Neutral Overvolatge Trip


Neutral Undervolatge Trip

Of
Of

Setting
92%Unp
20%Unp
15%Unp
30%Unp
90%Unp
20%Vnp
110%Unp
120%Unp
20%Unp
10%Unp
53Hz
47Hz
49Hz

Delay
4s
100ms
100ms
100ms
100ms
100ms
100ms
100ms
100ms
100ms
4s
3s
100ms

Setting
0.90*Rated
1.10*Rated
Voltage Level Cutof : 0.80*Rated
Level 1 : 45Hz
Level 2 : 44Hz
Voltage Level Cutof : 0.80*Rated
Level 1 : 55Hz
Level 2 : 57Hz

GE 489
Delay
5s
5s
Block Underfrequency from Online : 1s
Delay 1 : 5s
Delay 2 : 2s
Block Overfrequency from Online : 1s
Delay 1 : 5s
Delay 2 : 2s

Reset Rate
1s
1.4s

Curve Element
Definite Time
Definite Time
Definite Time
Definite Time
Definite Time
Definite Time
Definite Time
Definite Time