The V15 with AS-Interface has 8 inputs and 8 outputs. The V15 AS-i interface occupies 2 addresses
(connection 1 and connection 2) in the AS-i-system. Power to the valves are supplied by the black cable (24V
DC), so it is possible to switch off the valves separately (Emergency OFF).
The addresses are programmed by using a standard programming device. The plugs the programming
devices will be connected with, are installed behind the covering screw on the top side of the housing. It is not
necessary to disconnect the AS-i cable while defining the addresses. The address for the different
connections are configured individually via separate plugs. For the connection of the addressing device with
the interface a special address-cable is necessary (Order-No. 894 605 449 2). Addresses from 1 31 are
valid. It is possible to change the address 15 times, after that the last valid value remains. To ensure the
operational reliability of the system, the valves power supply has to be switched off during the
configuration of the addresses.
Ini connector 1
Ini connector 2
Ini connector 3
Ini connector 4
AS-i connection 1 controls the first 4 coils at the valve-unit, connection 2 the next 4 coils. Active outputs are
indicated with yellow LEDs.
Sensors with 2 and 3 conductor technique can be connected to the input M12 plugs. The sensors are
supplied by the AS-i-interface (see Table 1). This supply is short circuit protected.
Buchse
1
2
3
4
Pin1
20V to 30V
20V to 30V
20V to 30V
20V to 30V
DC
DC
DC
DC
Pin2
Input
Input
Input
Input
1 Pin 1
3 Pin 1
1 Pin 2
3 Pin 2
Pin3
0V
0V
0V
0V
Pin4
Input
Input
Input
Input
0 Pin 1
2 Pin 1
0 Pin 2
2 Pin 2
FAULT (red)
Off
Off
On
On
Flashing
Bottom view
LED's AS-i 1
LED's AS-i 2
LED valve power supply
LED's Output 1, Channel 0
.
.
.
LED's Output 2, Channel 3
ID-Code
IO-Code
Current consumption
Reverse battery protection
Voltage PELV
acceptable current load
for signal 0
for signal 1
Voltage range
acceptable current load
Table 3: Technical Data
F
7
300 mA
Existing
24V 10%
100mA short circuit protected
Iin 1,5mA
Iin 5 mA / Uin 10V
20V-30V DC
2 x 100mA short circuit protected
OUT IN
1.0
1.1
1.2
1.3
2.0
2.1
2.2
2.3
12
12
12
12
Manual operation
14
14
14
Lock screw
Operational condition
Module OK
No supply voltage at AS-interface chip
No communication
Slave has address 0
Overload sensor supply / no communication with the master
Front view
FAULT AS-i
1
2
AUX
AS-Interface
Valve power supply
Programming plug 2
Programming plug 1
Top view