Академический Документы
Профессиональный Документы
Культура Документы
Characteristic
By
Dr. Juergen Holbach (Juergen.holbach@siemens.com)
Vythahavya Vadlamani (vythahavya.vadlamani@siemens.com)
Dr. Yuchen Lu (yuchen.lu@siemens.com)
Siemens Power Transmission and Distribution, Inc
Raleigh, North Carolina
Presented to the
61st Conference for Protective Relay Engineers
College Station, Texas
April 1-3, 2008
1st edition
89
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
90
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
measured impedance may be inside the load area or the expected error on the
reactance calculation may be too high. The most common characteristics are the MHO
circle and the quadrilateral characteristic.
Quadrilateral characteristic is most preferred when protecting short transmission lines as
this provides substantial resistive coverage and arc compensation than the traditional
circular characteristics
RF = RARC + RTF
Eq (1)
Where
RF
= Fault resistance
RARC = Arc resistance
RTF = Footing tower resistance
The fault resistance for phase to phase and three phase short circuits mainly includes
only an arc resistance.
It need to be mentioned here that the calculation of a possible arc resistor is no an exact
science and there is not a single but several formula to calculate arc fault resistance,
according to the literature. Two of the most commonly used models are listed here for
91
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
our discussion. In order to arrive at the highest possible estimate for the fault resistance
we consider Eq (2). By using this model, the arc resistance can be higher than the
Warrington formula and there by avoiding any under reach.
The most commonly used formulas to arrive at the arc fault resistance are:
1.
R ARC =
762.l ARC
[:]
I ARC
Eq (2)
Warringtons formula
R ARC =
8750.l ARC
[:]
.4
I 1ARC
Eq (3)
5.v.t B
R*ARC = 1
l ARC
R ARC [:]
Eq (4)
92
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
tower. If it is used, the tower footing resistance and ground wire on the overhead line can
be represented as a T section connected in series [1]
The effective tower footing impedance as derived by [1] is given as
Z ETF
1
RTF Z LNW
2
1
RTF Z LNW
2
Where Z LNW
Eq (5)
( Z 'GW I AS ) 2
1
Z 'GW l AS
RTF Z 'GW l AS
2
4
Eq (6)
Z ETF
1
RTF Z ' GW l AS
2
M
1
RTF Z ' GW l AS e j GW
2
2
Eq (7)
Example:
Distance between the towers
Ground wire resistanc
Ground wire reactance
Tower footing resistor
93
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
measurement. The settings for the reactive reach and resistive reach are done as line
settings. The following consideration helps to understand how the calculated fault
resistor need to be considered inside the settings.
a) Ph-Ph fault with fault resistance at the fault location
IA
XL
RL
IF
V AB
RL
RF
XL
IB
Two phase short circuit with fault resistance
Substituting
= -IB = IF
Eq (8)
V A V B
2 I F
Eq (9)
ZL
RF
2
On phase to phase faults, the measured fault resistance becomes divided by a factor of
2 by the relay to convert from a loop impedance to a line impedance.
b) Ph-ground fault with fault resistance (single ended in feed)
On phase to ground faults it is important to know how the zero sequence compensation
in the relay is done. In the next example a zero sequence compensation method is used
which is implemented in Siemens distance relays with quadrilateral characteristics.
IL
XL
RL
V ph G
RF
XG
RG
IG
94
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
Eq (10)
With introducing the zero sequence compensation factors RG/RL and XG/XL which are
settings inside the relay and the simplification
L
= -IG = IF
we can write:
Z Loop
V ph G
R L calculated
IF
RLoop jX Loop
RLoop
R
1 G
RL
RL
RL (1
RF
R
1 G
RL
RG
X
) RF jX L (1 G ) Eq (11)
RL
XL
Eq (12)
In this case, the fault resistance will not add to the calculated line resistor with half of its
value like on phase to phase faults, but rather depending on the setting RG/RL. We can
see that for the resistive reach setting on phase to phase faults we need to set only half
of the calculated total fault resistor and for ground faults we need to take also the zero
sequence compensation factor RG/RL in consideration. The setting for the resistive
reach for ground faults is determined by the total fault resistor divide by a factor
(1+RG/RL). Before selecting a setting, the way how the particular relay will perform the
zero sequence compensation needs to be understood! The example shown here is only
valid for Siemens relays with quadrilateral characteristic.
Zero Sequence compensation
The majority of the short circuits that occur in the transmission system are ground faults.
In this case the accuracy of the distance protection depends also on the zero sequence
compensation setting for the ground impedance. The exact value of this compensation
factor is often not known. Even if the ground impedance of the line is determined by
measuring the zero sequence impedance prior to commissioning which is usually not
done due to time and cost constraints the actual effect of ground impedance during the
short circuit may be severely dependent on the actual fault location. The effective ground
impedance is often not proportionally distributed along the line length, as it may vary
significantly depending on the consistency of the ground (sand, rocks, water, snow) and
the type of grounding applied (tower grounding, parallel cable screens, metal pipes).
Normally it is sufficient for the zone 1 distance protection function to know the zero
sequence factors which is measured on the remote line terminal. For all other zones the
relay should have a separate zero sequence compensation factor settable because in
may cases the factor can change drastically on the adjacent line/cable.
95
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
We want to point out that modern numerical relays have as a standard function a fault
recorder ability implemented inside the relay. The fault recorder data can be used to
determine the real zero sequence factors on a transmission line.
In the following to methods of zero sequence compensations are introduced and
compared. The compensation with a complex Ko factor is common in many relays and is
simple to implement. On a Mho circle this is actually the only way the zero sequence
compensation can be performed. However, a quadrilateral characteristic offers better
ways to do the compensation what becomes shown in the following.
Setting of residual compensation factors k 0 and { K R
Usually the positive sequence impedance of the line Z 1
impedance Z 0
RG
XG
, KX
}
RL
XL
R1 jX 1 and zero sequence
Z 0 Z1
.
3Z 1
ZG
RG jX G
Z 0 Z1
3
ZL
RL jX L
R1 jX 1
R0 R1
X X1
j 0
3
3
Eq (13)
Eq (14)
KR
KX
RG
RL
XG
XL
R0 R1
3R1
X 0 X1
3X 1
Eq (15a)
Eq (15b)
96
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
IF
XL
RL
V phG
RF
XG
RG
IF
Z ph G
Where V
ph G
V ph G
I F (1 k 0 )
R ph G
real{ Z ph G },
X ph G
imag{ Z ph G }
Eq (16)
R ph G
real{
V ph G
I F (1 K R )
},
X ph G
imag{
V ph G
I F (1 K X )
Eq (17)
The fault resistance is one of the factors which will cause an error in the impedance
calculation. For bolted faults (fault resistance RF 0 ), both compensation methods can
correctly calculate the fault impedance. However, if the fault resistance exists ( RF z 0 ),
the traditional k 0 compensation method and the { K R , K X } compensation method will
produce different impedance calculation errors. This is illustrated in the following Figure.
97
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
X
RF
1 k0
Z ph G
ZL
ZL
RF
1 KR
Z ph G
XG
IF
RL
XL
V ph G
RF
RG
XG
IF
98
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
XG= 10 Ohm
Calculate RL, XL, RG, XG as
RL = R1 = 2 (ohm)
XL = X1 = 10 (ohm)
RG = (R0-R1)/3 = 10 (ohm)
XG = (X0-X1)/3 = 10 (ohm)
Assume the generator phase to ground voltage as (secondary): V G
fault resistance RF=5 (ohm)
IF
VG
= 0.986-j1.741(A)
R L jX L RG jX G R F jX G
k0
ZG
ZL
10 j10
2 j10
1.154 j 0.769
VR
V G I F jX G
69 (17.41 j 9.86)
(51.59 9.86)V
Z ph _ G
VR
I F (1 k 0 )
51.59 9.86
=4.067 + j10.75(ohm)
(0.986 j1.741)(2.154 j 0.769)
R ph _ G
X ph _ G
R ph _ G
X ph _ G
VR
} =2.83 (ohm)
I F (1 K R )
VR
imag{
} = 10 (ohm)
I F (1 K X )
real{
The results show that although the fault resistance causes significant calculation errors
on the R ph _ G for both methods, only the { K R , K X } compensation method produces the
correct X ph _ G value.
99
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
Setting of RG/RL
As discussed earlier, by selecting a setting for the fault resistor reach on ground faults,
the RG/RL factor set inside the relay need also to be taken in consideration. The setting
should be the total fault loop resistor (RL+RG+Rarc+RTF) divided by a factor of 1+RG/RL. If
the RG/RL factor, which results out of the line data is used as a setting in the relay, the
line resistor calculation of the distance protection will only be correct for faults without a
fault resistor as we saw above! On overhead lines many times an arc fault is involved
and the calculated line resistor will therefore always be wrong. This is normally not a
problem, because we set in the quadrilateral characteristic an additional resistor to
compensate for this. Therefore the setting RG/RL which will only help to determine the
line resistor for faults without an additional fault resistor is not of any importance. It is
normally not recommended to set the calculated value which results out of the line data,
which can in some cases result in factor >5 . The disadvantage of such a high factors is
that any loop resistor gets divided by a (high factor +1) and therefore also load and
unfaulty loops on long transmission lines can be seen inside of the trip zone! It is
normally recommended to set RG/RL to a factor of 1, than the line resistor for ground
faults gets calculated whit the same factor as for phase faults!
Load influence on resistive faults
Transmission of load across long transmission lines results in a phase displacement
between the voltages V1 and V2 at the two line ends (Figure 7 and 8).
In the event of a short circuit, the generator voltages (Figure 7) feeding onto the fault will
therefore have different phase angles. In a first approximation, the short circuit currents
from the two ends are also displaced by this angle. The short circuit current flowing from
the two line ends through the ohmic fault resistance RF causes that the relays will see
the fault resistor as resistive and inductive impedance due to this phase displacement.
100
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
Figure 8: Phase shift between the sources voltages and fault currents
101
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
102
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
a graph is presented which helps how much the quadrilateral characteristics needs to
get tilt with the angle D to avoid an overreach based on the influence of load on an fault
resistor.
103
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.
References
[1] Gerhard Ziegler, "Distance Measurement, Influencing quantities," chap. 3 in Numerical
Distance Protection, 2nd ed., Publicis Corporate Publishing, Erlangen, Germany: 2006.
[2] S.Ward, "Comparison of Quadrilateral and Mho distance characteristic," presented at 26th
Annual Western Protective Relay Conference 1999, Spokane, Washington. October 26-29, 1999
[3] G. Swift, D.Fedirchuck, T. Ernst, Arcing Fault Resistance (it isnt) presented at 29th Annual
Western Protective Relay Conference 2002, Spokane, Washington. October 22-24, 2002
[4] 7SA522 Manual V4.6, C53000-G1176-C155-4, page 89, Siemens 2004
[5] S. Kaiser, "Different Representations of the Earth Impedance Matching in Distance Protection
Relays or What Impedance Does a Digital Distance Protection Relay Measure, OMICRON
Anwendertagung 2004
104
Authorized licensed use limited to: SOUTHERN ILLINOIS UNIVERSITY - EDWARDSVILLE. Downloaded on November 16, 2008 at 03:21 from IEEE Xplore. Restrictions apply.