Академический Документы
Профессиональный Документы
Культура Документы
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
GENERAL INFORMATION
1.1 VARIANTS
2.
3.
ROUTINE CHECKS
2.1 GENERAL
CONTROLLER FUNCTIONS
3.1 GENERAL
10
11
11
12
12
12
12
13
15
15
15
15
16
16
16
16
17
17
17
17
18
19
19
20
20
20
21
21
13
13
21
13
21
22
14
14
22
23
23
14
23
14
24
,17(51$7,21$//7'&203$1<
PAGE 1 of 56
MINERVA
15A-02-S1
03
4/99
42
25
42
26
42
28
4.
28
29
29
30
30
43
43
44
5.
46
6.
FAULT MONITORING
47
6.1 GENERAL
47
47
47
48
34
49
34
50
52
34
35
52
52
30
30
30
35
35
36
36
6.4.1 GENERAL
54
37
54
54
54
37
37
37
37
36
38
38
38
39
39
40
40
PAGE 2 of 56
54
54
54
54
55
7.
SPARES
56
8.
ASSOCIATED PUBLICATIONS
56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
,17(51$7,21$//7'&203$1<
4/99
PAGE 3 of 56
MINERVA
15A-02-S1
03
4/99
PAGE 4 of 56
1.
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
GENERAL INFORMATION
WARNING:
4/99
WARNING:
1)
2)
3)
4)
,17(51$7,21$//7'&203$1<
PAGE 5 of 56
MINERVA
15A-02-S1
03
4/99
1.1
VARIANTS
Fault
0000
2.
ROUTINE CHECKS
2.1
GENERAL
St.
1000
Fault
0000
0000
St.
1000
0000
2.2
The status display for an 80-zone controller is in the same
format as the 16-zone. To display the other zones, e.g. 172 4 , 2 5 - 3 2 , e t c . u s e t h e SCROLL DOWN
or
keys.
SCROLL UP
WEEKLY CHECKS
WARNING:
WARN ALL PERSONNEL THAT THE
SOUNDERS ARE ABOUT TO BE TESTED.
Proceed as follows:
a) If necessary, clean the front panel of the
controller with a suitable cleansing agent.
b) Check all batteries in accordance with
publication 05A-10-S1.
c) Check the tightness of all terminal block
screws inside the controller.
d) Using the walk test function [see sections
3.9.6 and 3.9.7], check the operation of at
least one zone. If a printer is available, print
out the results of the walk test [see section
3.18.4].
e) Set one device [either a callpoint or detector]
from one zone into alarm and check that the
system responds as follows:
PAGE 6 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
2.3
4/99
THREE-MONTHLY CHECKS
Proceed as follows:
a) Perform the weekly checks as detailed in
section 2.2.
b) Check the entries in the log book and carry
out any necessary action.
c) Check the batteries and their connections in
accordance with publication 05A-10-S1.
d) Check all the ancillary functions of the
controller.
e) Check all fault indicators by simulating a
FAULT condition in each zone by either:
i) removing a detector from its base, or;
ii) disconnecting the local circuit from an
ancillary unit, or;
f) Visually check the condition of the controller and other ancillary equipment for signs of
moisture ingress and other deterioration.
g) Visually check the installation to ascertain
whether structural or occupancy changes
have affected the requirements for the siting
of manual callpoints, detectors, line isolator
modules or sounders.
,17(51$7,21$//7'&203$1<
PAGE 7 of 56
MINERVA
15A-02-S1
03
2.4
4/99
ANNUAL CHECKS
Proceed as follows:
a) Perform the three-monthly checks as
detailed in section 2.3.
b) Visually check the inside and outside of the
controller and ancillary devices for damage.
c) Check for damage to, and paint on, heat
detectors; check for dirt, grease, etc. on the
lenses of flame detectors.
d) Clean or exchange units as necessary.
e) Check for damage and accumulations of dirt
on ion-chamber smoke detectors. DO NOT
CLEAN; these units MUST be exchanged
and returned to the factory for disposal.
3.
CONTROLLER FUNCTIONS
3.1
GENERAL
The MINERVA fire controller has a large number of builtin functions. These functions allow system parameters to
be viewed and/or changed and a number of operations to be
performed.
As the available functions allow access to system
parameters, it is necessary to restrict the use of these
functions to trained staff. This is achieved by the use of
passcodes. In order to gain access to the controller
functions, the user enters a passcode via the front panel
keypad. The function is then either selected from the menus
presented, or by entering the appropriate Fast Access Code.
3.2
Table 1 lists the all Fast Access Codes for a MINERVA fire
controller. The codes for each function are listed in the
appropriate paragraphs.
3.2.1
2.5
THREE-YEARLY CHECKS
2.6
FOUR-YEARLY CHECKS
CAUTION:
TAKE CARE WHEN HANDLING THE
BATTERY. DO NOT CONNECT THE
BATTERY THE WRONG WAY
ROUND. WHEN THE BATTERY IS NOT
CONNECTED, COVER TERMINALS WITH
INSULATING TAPE TO PREVENT
ACCIDENTAL SHORT CIRCUIT.
PAGE 8 of 56
MENU
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
CODE
0001
0009
MENU
4/99
CODE
Open VFP?
0070
0080
0010
0081
0011
0082
0012
0083
0013
0084
0085
0016
0020
0086
0021
0087
0022
0088
0030
0090
0091
0031
0092
0032
0033
Unforce point?
0093
0034
0095
0035
Point sensitivity?
0096
Zone sensitivity?
0097
0036
0037
0100
0039
0101
0040
0102
0041
0103
0104
0042
0043
0105
Engineer isolate?
0044
0106
0050
1030
0051
1200
1201
0052
0053
1202
Engineer de-Isolate?
0054
1203
0060
Shutdown loop?
1204
0061
Restart loop?
1205
1206
0062
0063
0064
Table 1:
Table 1:
,17(51$7,21$//7'&203$1<
PAGE 9 of 56
MINERVA
15A-02-S1
03
4/99
MENU
CODE
0004
0004
0005
Isolate signalling?
0045
De-isolate signalling?
0055
0056
0065
1006
1007
1008
1009
1031
1032
1033
1034
Commissioning mode?
1038
1070
1071
1090
3.3
MAIN MENU
Fig. 1
PAGE 10 of 56
Note:
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.4
4/99
,17(51$7,21$//7'&203$1<
PAGE 11 of 56
MINERVA
15A-02-S1
03
4/99
3.5
3.5.3
3.5.1
Fig. 2
The first line shows the event message, followed by the zone
identification message. The third line shows the time and
date of the occurrence of the event. The fourth line gives the
zone, loop and point numbers.
This display remains continuously until an operator
intervention.
The zone, loop and point numbers give the absolute system
address for the point as follows:
to move
MP - Main Processor
PAGE 12 of 56
R - Real point
U - User Number
P - Pseudo point
S - Switch point
to move
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
3) Press SCROLL UP
log backwards.
to move
FIRE [EVACUATE]
FIRE [ALERT]
FAULTS [SYSTEM]
FAULTS [ADDRESSABLE POINTS]
3.7
FAULTS [CLEAR]
3.7.1
RESET/SILENCE
to move
3.6
,17(51$7,21$//7'&203$1<
PAGE 13 of 56
MINERVA
15A-02-S1
03
4/99
Zones
1- 8
3.7.5
View system
Zones Fault St ?
Zones
1- 8
Fault
0000
St.
1000
2) Press YES/ENTER,
The display is in the following format:
Alarm St.
0100
0000
St.
0000
Isol.
1000
3.7.7
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.8
4/99
3.8.1
View system
Common Disa St. ?
2) Press YES/ENTER,
The display is in the following format:
Common Disa. St.
0
A 1 indicates that a Common Disabled condition exists
[i.e. a point is isolated or a function is disabled], a 0
indicates that it does not.
Fig. 4
SET TIME
,17(51$7,21$//7'&203$1<
PAGE 15 of 56
MINERVA
15A-02-S1
03
4/99
3.8.3
SET DATE
3.9
3.9.1
2) Press YES/ENTER.
The display will show:
Enter date as:DDMMYY
where:
DD = Day
MM = Month
YY = Year
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Fig. 5
3.9.2
PAGE 16 of 56
2) Press YES/ENTER.
A message in the following format will be
displayed:
System test 01
Al. Cycle No 0001
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.9.5
3) Press YES/ENTER.
The display will briefly show:
Reset system
S/W Init. count ?
The system software initialisations count has now been reset
to 1.
2) Press YES/ENTER.
The display will show:
3.9.6
3) Press YES/ENTER.
The display will briefly show:
System reset
Al . Cycle count
The system alarm cycle count has now been reset to 0.
Note: A cold restart [i.e. from a completely powereddown state] will reset the counter to 0.
3.9.4
4/99
,17(51$7,21$//7'&203$1<
PAGE 17 of 56
MINERVA
15A-02-S1
03
4/99
4)
3.9.7
3) Press YES/ENTER.
The display will show:
Point no. :
(Quit to exit)
Note:
1) If, during the walk test, a device in a zone not
being tested should go into alarm, the controller will respond to this alarm and the walk test
will be automatically terminated.
2) If the walk test is exited whilst devices are still
in alarm [i.e. the key has not been removed
from a callpoint or the detectors still contain
smoke], the Controller will immediately signal
an alarm.
Always wait five minutes to allow any smoke to
clear from the detectors. Alternatively, wait
until the count of Points in Alarm on the LCD
goes to zero.
PAGE 18 of 56
3.9.8
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.9.9
Reset point
threshold compn ?
Walk test
sounders ?
2) Press YES/ENTER.
The display will show:
2) Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
Zone no:
( Yes = all )
3) Press YES/ENTER.
The display will show:
Point no. :
(Quit to exit)
4)
4)
4/99
5)
Sounders in
walk test
Quit to exit
Note:
1) If the selected device has not been configured,
the controller will display:
Point not found
,17(51$7,21$//7'&203$1<
PAGE 19 of 56
MINERVA
15A-02-S1
03
4/99
3.9.10
Program
Issue X.X/01
S/C xxx-xxx-xxx
Date : 09/01/94
Fig. 6
3.10.2
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.10.4
4/99
Enable
Fast Fault Mode ?
or:
Disable Rate of Rise
Processing?
2) Press YES/ENTER.
The display will show:
Action
COMPLETED
Disable
Fast Fault Mode ?
Action
COMPLETED
then pause and display either:
3) Press YES/ENTER.
The display will briefly show:
Action
COMPLETED
or:
Enable Rate of Rise
Processing ?
3.10.5
LOOP SHUTDOWN
2) Press YES/ENTER.
The display will briefly show:
Action
COMPLETED
3) Press YES/ENTER.
The display will briefly show:
Loop shutdown
completed
,17(51$7,21$//7'&203$1<
PAGE 21 of 56
MINERVA
15A-02-S1
03
4/99
LOOP RESTART
Note:
If the loop has already been started the display
will show:
Loop already
active !
CAUTION:
WHEN IN SINGLE POLL MODE THERE IS
NO DETECTION FROM THAT LOOP [OTHER
THAN FROM THE ADDRESS BEING
POLLED]. THIS OPTION SHOULD ONLY BE
USED FOR FAULT FINDING.
PAGE 22 of 56
5)
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.12.2
Note:
1) When in this mode, events can NOT be
generated from other devices on the same loop
3.12.2.1
a) Press YES/ENTER.
The controller will pause briefly and then
display:
4/99
Isolate
successful
Note:
1) If a non-existent zone number is entered, the
display will show:
Point(s)
not found
or
Zone number xx
invalid; try again
Fig. 7
,17(51$7,21$//7'&203$1<
PAGE 23 of 56
MINERVA
15A-02-S1
03
4/99
3.12.2.2
3.12.3
Isolate
successful
d) The DISABLED LED will light and the internal buzzer will sound intermittently.
Note:
Isolate
successful
b) The DISABLED LED will light and the
internal buzzer will sound intermittently.
Note:
Point(s)
not found
or
Point(s)
not found
or
Zone number xx
invalid; try again
PAGE 24 of 56
Zone number xx
invalid; try again
3.12.3.2
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.12.4
4/99
2) Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
3) Press YES/ENTER.
The display will show:
Point no. :
(Quit to exit)
d) The DISABLED LED will light and the internal buzzer will sound intermittently.
4)
Note:
or
Zone number xx
invalid, try again
isolate
successful
Point(s) already
isolated
Note:
3) The DISABLED LED and the buzzer will
continue to operate as a warning that the zone
is isolated.
,17(51$7,21$//7'&203$1<
PAGE 25 of 56
MINERVA
15A-02-S1
03
4/99
3.12.5
ENGINEER ISOLATE
3.12.5.1 INTRODUCTION
6) Press NO/DELETE .
The display will show:
non-ad. points only
(Y/N)?
WARNING:
7) Press YES/ENTER.
The display will show:
Channel : None
(Y/N)?
8) Press NO/DELETE .
The display will show:
Channel : LBUS
(Y/N)?
9)
Press YES/ENTER.
The display will show:
Chan . addr. :
( Yes = all )
Device type:
( Yes = all )
12) Press YES/ENTER.
The display will show:
3) Press YES/ENTER.
The display will show:
Group no. :
( Yes = all )
4) Press YES/ENTER.
The display will show:
Zone no. :
( Yes = all )
Point No. :
( Yes = all )
10
and
Isolate
successful
The DISABLED LED will light.
5) Press YES/ENTER.
The display will show:
addr. points only
(Y/N)?
PAGE 26 of 56
press
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
Engineer isolate ?
3) Press YES/ENTER.
The display will show:
Device type:
( Yes = all )
4) Enter device type number 29 [SM520
modules] and press YES/ENTER.
The display will show:
Group no. :
( Yes = all )
5) Enter group number 186 [Bell Map Alarm
Sounders] and press YES/ENTER.
The display will show:
Zone no. :
( Yes = all )
6) Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
7)
Press YES/ENTER.
The display will show:
Channel :None
(Y/N)?
Point no. :
( Yes = all )
8)
,17(51$7,21$//7'&203$1<
PAGE 27 of 56
MINERVA
15A-02-S1
03
4/99
10
and
press
Isolate
successful
3.13.2
Zone no. :
( Yes = all )
Note:
1) If a non-existent zone number is entered, the
display will show:
Point(s)
not found
or
Zone number xx
invalid, try again
Fig. 8
PAGE 28 of 56
3.13.3
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
3.13.4
DE-ISOLATE ZONE
[SOUNDERS ONLY]
4/99
De - isolate zone ?
(sounders only)
De-isolate point ?
(addr. loop only)
2) Press YES/ENTER.
The display will show:
2) Press YES/ENTER.
The display will show:
Zone no. :
( Yes = all )
Loop : A
(Y/N)?
3) Press YES/ENTER.
The display will show:
Point no. :
( Yes = all )
De-isolate
successful
The DISABLED LED will go out and the
internal buzzer will cease sounding.
5) Press YES/ENTER.
The controller will pause briefly and then
display:
De-isolate
successful
Note:
1) If a non-existent zone number is entered, the
display will show:
Point(s)
not found
Note:
or
Zone number xx
invalid, try again
Point(s)
not found
Point(s) already
isolated
Point(s) already
de-isolated
,17(51$7,21$//7'&203$1<
PAGE 29 of 56
MINERVA
15A-02-S1
03
4/99
3.13.5
ENGINEER DE-ISOLATE
3.14.2
3) Press YES/ENTER.
The display will show:
Point no. :
( Yes = all )
4) Enter the number of the required device and
press YES/ENTER.
The display will show:
< point name >
Point no. :
( Y / N / UP/DOWN ) ?
SATURN Group
Cleared
Note:
1) Some of the threshold values may change if
threshold compensation has been enabled.
2) A complete list of device numbers and types is
given in section 4.1
DEVICE
DM520/
DMC520
DEVICE
TYPE
30,74
WIN.
MIN-MAX
ID
10.2-12.6
0.0-3.0
3.0-5.7
5.7-9.5
9.5-13.0
13.0-28.0
Clear/Restore
PSU Fault
Normal
Line Fault
Fire Alarm
Invalid response
12.8-15.8
0.0-3.0
3.0-5.5
5.5-9.5
9.5-13.0
13.0-17.5
17.5-28.0
Clear/Restore
PSU Fault
Relay Coil Fault
Normal
Sounder Fault
Sounder Operated
Invalid response
8.1-9.9
0.0-1.4
1.4-3.0
3.0-6.3
6.3-15.5
15.5-28.0
Clear/Restore
Slave cct O/C
Normal
Invalid response
Alarm
Short circuit
4.0-5.0
0.0-1.0
1.0-2.5
2.5-3.5
3.5-5.3
5.3-7.2
7.2-9.5
9.5 +
Clear/Restore
O/C
Normal
Invalid data
Alarm-Evacuate
Alarm-Alert
S/C
Invalid data
COND.
ID
SM520
DEVICE
TYPE
29,75
COND.
ID
CP520/CP530/
CP920
DEVICE
COND.
TYPE
26
ID
CP540Ex
DEVICE
TYPE
27
RM520
DEVICE
TYPE
28
COND.
ID
COND.
ID
CM520
DEVICE
TYPES
31, 32
COND.
ID
ACPM500
DEVICE
TYPE
33
COND.
STATUS
16.2-20.0
0.0-2.0
2.0-4.4
4.4-6.5
6.5-28.0
Clear/Restore
Device Fault
Normal/Relay OFF
Relay Operated
Invalid response
6.4-8.0
0.0-2.8
2.8-4.7
4.7-7.5
7.5-11.2
11.2-15.7
15.7-28.0
Clear/Restore
Open circuit
N/C contact alarm
Normal
N/O contact alarm
Fault
Short circuit
5.6-6.5
0.0-1.7
1.7-4.9
4.9-8.1
8.1-11.5
11.5-15.0
15.0-28.0
Clear/Restore
Device Fault
No battery or mains
[battery ok]
PSU Fault
Mains Failure
[battery flat]
Normal [no battery]
Short cct
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
DEVICE
AM521
DEVICE
TYPE
51
WIN.
MIN-MAX
STATUS
ID
2.0-3.1
0.00-2.1
2.1-3.1
3.1-5
5-8.6
8.6-14.5
14.5-20.0
Clear/Restore
Device Fault
Airflow Fault
Normal
Pre-alarm
Alarm
S/c wiring
12.8-15.8
0.0-3.0
3.0-5.5
5.5-9.5
9.5-13.0
13.0-17.5
15.8-28.0
Clear/Restore
Power supply fault
Relay fault
Normal
Sounder line fault
Sounder active
Short circuit
0.0-2.2
3.1-4.3
4.3-7.6
7.6-11.5
11.5
0.0-2.2
2.2-3.1
3.1-4.3
4.3-7.6
7.6 -11.5
11.5 +
12.8-15.8
0.0-3.0
3.0-5.5
5.5-9.5
9.5-13.0
13.0-17.5
17.5 +
Clear/Reset
PSU Fault
Relay Coil Fault
Clear/Restore
Sounder Fault
Sounder Operated
Invalid Data
7.3-8.3
0.0-2.2
2.2-3.1
3.1-4.3
4.3-7.6
7.6 -11.5
11.5 +
Clear/Reset
Open Circuit
Sensor 1 & 2 active
Sensor 2 active
Sensor 1 active
Normal
Short circuit
7.2-8.0
0.0-2.8
2.8-4.7
4.7-7.5
7.5-11.2
11.2-15.7
15.7 +
Clear/Restore
Open Circuit Fault
Device Fault
Normal
Sensor Active
Device Fault
Closed Circuit Fault
COND.
ID
VM520
DEVICE
TYPE
53
COND.
2.2-3.1
ID
SU521/
PI521
DEVICE
TYPES
63, 64,
65, 66
COND.
ID
LPS520/
LPB521
DEVICE
TYPES
67,68
COND.
ID
SD520
DEVICE
TYPES
76, 77
COND.
ID
LPBD521
DEVICE
TYPE
100
COND
4/99
,17(51$7,21$//7'&203$1<
PAGE 31 of 56
MINERVA
15A-02-S1
03
4/99
DEVICE
WIN
MIN-MAX
STATUS
DEVICE
WIN
MIN-MAX
STATUS
MR501
[High]
DEVICE
TYPE
03, 06Ex
ID
16.2-20.0
0.0-6.0
6.0-11.6
11.6-13.6
13.6-14.8
0.0-6.0
6.0-13.6
13.6-14.8
14.8-18.0
0.0-6.0
6.0-14.8
14.8-18.0
18.0 +
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
MD501
[FT]
DEVICE
TYPE
07, 11Ex
ID
8.1-10.0
0.0-6.0
6.0-11.6
11.6-13.6
13.6-28.0
0.0-6.0
6.0-13.6
13.6-14.8
14.8-28.0
0.0-6.0
6.0-14.8
14.8-18.0
18.0-28.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
12.8-15.8
0.0-2.5
2.5-13.0
13.0-19.5
19.5-20.0
0.0-2.5
2.5-11.5
11.5-13.0
13.0-19.0
0.0-2.5
2.5-10.7
10.7-11.5
11.5-15.0
0.0-2.5
2.5-9.0
9.0-10.7
10.7-13.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
4.8-6.0
0.0-3.0
3.0-6.4
6.4-14.4
14.4-16.2
16.2-28.0
Clear/Restore
Fault
Normal
Pre-alarm
Fire alarm 1
Fire alarm 2
10.2-12.6
0.0-2.6
2.6-10.5
10.5-12.5
12.5-14.5
0.0-2.6
2.6-12.5
12.5-14.5
14.5-18.0
0.0-2.6
2.6-14.5
14.5-18.0
18.0-28.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
5.0-10.5
0.0-5.0
5.0-10.5
10.5-19.9
19.9-28.0
Clear/Restore
Open circuit
Normal
Alarm
Short circuit
10.2-12.6
0.0-1.0
1.0-7.5
7.5-11.5
11.5-15.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
[Normal]
DEVICE
TYPE
02, 05Ex
COND.
[Low]
DEVICE
TYPE
01, 04Ex
MR501T
[High]
DEVICE
TYPE
56, 59Ex
[Med.]
DEVICE
TYPE
55, 58Ex
ID
COND.
[Low]
DEVICE
TYPE
54, 57Ex
MF501
[High]
DEVICE
TYPE 17, 19[D],
22Ex, 24 Ex
ID
[Normal]
DEVICE
TYPE 16, 18[D], COND.
21Ex, 23Ex
[Low]
DEVICE
TYPE
15, 20Ex
MF501 [High
Altitude]
DEVICE
TYPE 34
ID
COND.
PAGE 32 of 56
[G3]
DEVICE
TYPE
08, 12Ex
[G2]
DEVICE
TYPE
09, 13Ex
COND.
[G1]
DEVICE
TYPE
10, 14Ex
MS502Ex/
S251i-S251f
DEVICE
TYPE
25, 92
ID
COND.
ID
M400 Series
Detectors
DEVICE
TYPE
COND.
35 MR, 36 MD,
37 MF, 38 MF[D]
DEVICE
WIN
MIN-MAX
MR901
[High]
DEVICE
TYPE
80
ID
16.2-20.0
0.0-6.0
6.0-11.6
11.6-13.6
13.6-14.8
0.0-6.0
6.0-13.6
13.6-14.8
14.8-18.0
0.0-6.0
6.0-14.8
14.8-18.0
18.0 +
[Normal]
DEVICE
TYPE
79
COND.
[Low]
DEVICE
TYPE
78
MR901T
[High]
DEVICE
TYPE
99
[Normal]
DEVICE
TYPE
98
ID
COND.
[Low]
DEVICE
TYPE
97
MF901
[High]
DEVICE
TYPE 87, 88[D]
ID
[Normal]
DEVICE
TYPE 86, 89[D] COND.
[Low]
DEVICE
TYPE
85
STATUS
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
8.1-10.0
0.0-6.0
6.0-11.6
11.6-13.6
13.6-28.0
0.0-6.0
6.0-13.6
13.6-14.8
14.8-28.0
0.0-6.0
6.0-14.8
14.8-18.0
18.0-28.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
10.2-12.6
0.0-2.6
2.6-10.5
10.5-12.5
12.5-14.5
0.0-2.6
2.6-12.5
12.5-14.5
14.5-18.0
0.0-2.6
2.6-14.5
14.5-18.0
18.0-28.0
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
DEVICE
WIN
MIN-MAX
STATUS
MF901 [High
Altitude]
DEVICE
TYPE 90
ID
10.2-12.6
0.0-1.0
1.0-7.5
7.5-11.5
11.5-15.0
4.8-6.0
0-2.5
2.5-10.3
10.3-11.0
11 +
0-2.5
2.5-11.0
11.0-12.2
12.2 +
0-2.5
2.5-12.2
12.2-15.0
15.0 +
0-2.5
2.5-15.0
15.0-19.0
19.0 +
2.8-4.4
0.0-4.5
4.5-10.0
10.0-11.5
11.5 +
0.0-4.5
4.5-10.0
10.0-14.5
14.5 +
0.0-4.5
4.5-10.0
10.0-19.0
19.0 +
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Clear/Restore
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
Fault
Normal
Pre-alarm
Alarm
MD901
[T2]
DEVICE
TYPE
81
COND.
ID
[G3]
DEVICE
TYPE
82
[G2]
DEVICE
TYPE
83
COND.
[G1]
DEVICE
TYPE
84
MU901
[High]
DEVICE
TYPE
103
[Normal]
DEVICE
TYPE
102
ID
COND.
[Low]
DEVICE
TYPE
101
,17(51$7,21$//7'&203$1<
PAGE 33 of 56
MINERVA
15A-02-S1
03
4/99
3.14.3
3) Press YES/ENTER.
The display will show [for example]:
Loop : A
Quiesc
0.5
Compn
0mA
3.14.5
Cnfm. Stat
Norm
2) Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
3) Press YES/ENTER.
The display will show:
Loop : A
Config
50
Reply
50
Pts.
2) press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
PAGE 34 of 56
L+ R+ L20 30 50
R50
to bring
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
2) Press YES/ENTER.
The display will show:
Group no. :
( Yes = all )
3)
Press YES/ENTER.
The display will show:
Zone no. :
( Yes = all )
Loop : A
4)
L+ R+ L20 30 20
4/99
R30
Press YES/ENTER.
The display will show:
addr. points only
(Y/N)?
5)
Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
3.15.1
6) Press YES/ENTER.
The display will show:
Point no. :
( Yes = all )
Force Successful
Note:
1) If a number is entered that is not an output, the
display will show:
Unable to force!
not an OUTPUT
FORCE POINT ON
Force point on ?
,17(51$7,21$//7'&203$1<
PAGE 35 of 56
MINERVA
15A-02-S1
03
4/99
3.15.3
3.15.4
UNFORCE POINT
Unforce point ?
2) Press YES/ENTER.
The display will show:
2) Press YES/ENTER.
The display will show:
Group no. :
( Yes = all )
3)
Press YES/ENTER.
The display will show:
Group no. :
( Yes = all )
3)
Zone no. :
( Yes = all )
4)
Press YES/ENTER.
The display will show:
Zone no. :
( Yes = all )
4)
Press YES/ENTER.
The display will show:
Loop: A
(Y/N)?
6) Press YES/ENTER.
The display will show:
Point no. :
( Yes = all )
7) Enter the number of the point to be forced off
and press YES/ENTER.
The display will show:
< point name >
Point no. :
( Y / N / UP/DOWN ) ?
8) Press YES/ENTER to confirm the selection
[or use the up/down scroll keys to correct the
entry, then press YES/ENTER ].
The display will show:
Force Successful
Press YES/ENTER.
The display will show:
Press YES/ENTER.
The display will show:
addr. points only
(Y/N)?
5)
Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
6) Press YES/ENTER.
The display will show:
Point no. :
( Yes = all )
7) Enter the number of the point to be unforced
and press YES/ENTER.
The display will show:
< point name >
Point no. :
( Y / N / UP/DOWN ) ?
8) press YES/ENTER to confirm the selection
[or use the up/down scroll keys to correct the
entry, then press YES/ENTER ].
The display will show:
Force Successful
Note:
1) If a number is entered that is not an output, the
display will show:
Unable to force!
not an OUTPUT
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
5) Use the
or
keys to scroll through
the point numbers or NO/DELETE to return to the Point no. selection
display. When the required point is shown,
press YES/ENTER.
The display will show:
Point no. : A 1
MF501 A1
Sensitivity : Conf
Set to
: Conf ?
,
or NO/DELETE to
6) Use the
move
through
the
sensitivity
settings. When the required sensitivity is
set, press YES/ENTER.
The display will show:
update successful
or
permission denied
Point sensitivity ?
2) Press YES/ENTER.
The display will show:
Loop : A
(Y/N)?
Zone sensitivity ?
,
or NO/DELETE to move
3) Use the
through the loops. When the required loop
is shown, press YES/ENTER.
The display will show:
2)
Press YES/ENTER.
The display will show:
Zone no . :
( Quit to exit )
Point no. :
( Quit to exit )
,17(51$7,21$//7'&203$1<
PAGE 37 of 56
MINERVA
15A-02-S1
03
4/99
01
Sensitivity:
Set to
: Conf ?
,
or NO/DELETE to move
4) Use the
through the sensitivity settings [+ high, low or blank for normal]. When the required sensitivity is set, press YES/ENTER.
The display will show:
update successful
or
permission denied
if the device sensitivity cannot be changed.
PAGE 38 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
3) Press YES/ENTER.
The display will show:
Print initiated
and a printout in the format shown in Fig. 13 will be
produced.
3.18.3
2) Press YES/ENTER.
The display will show:
Print initiated
and a printout of all the isolated points will be produced. The
printout format is similar to that shown in Fig. 13, except that
the Test R, Isol and OO Comp columns are omitted.
3.18.4
Press YES/ENTER.
The display will show:
Print initiated
2) Press YES/ENTER.
The display will show:
Loop: A
(Y/N)?
1999 Tyco Electronic Product Group
,17(51$7,21$//7'&203$1<
PAGE 39 of 56
MINERVA
15A-02-S1
03
4/99
3.18.5
3.18.6
Print points
out of compensation ?
2) Press YES/ENTER.
The display will show:
Print initiated
Print event
log backtrack ?
2) Press YES/ENTER.
The display will show:
Event Type ?
All
,
or NO/DELETE to move
3) Use the
through the event types. When the required
event type is shown, press YES/ENTER.
The display will show:
Enter No. events
PAGE 40 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
Dev.
Con.
Id.
LT.Av
Inst.
Cnfm.
Zone 12 A23
34
7.6
11.2
7.1mA
Norm
Norm
Status
Test R
Isol
OO Cmp
etc.....
Fig. 13
Where:
Address gives zone, loop and point number.
Dev [Device type] - stored configured device code number as described in section 8.
Con. Id. LT.Av - current condition, identity and long-term average values in milliamps [range 0-28.3mA]
Inst. Cnfm. Status - instantaneous and confirmed point status i.e. Norm, Alarm, Fault, etc.
Test R [Test result] - last walk-test result. U indicates the point was untested or failed.
Isol [Isolate status] - indicates whether the point is isolated [Y indicates that it is, - that it is not].
OO Cmp [Out of compensation] - indicates whether the point is out of compensation [Y indicates that it is, followed
by + for positive compensation or - for negative compensation.- indicates that it is not].
RESTART
RESPONSE
SILENCE
System Zone
14:58:12:30
30 Jan 90
Zone 00
MP
Factory
15:00:06:00
30 Jan 90
Zone 08
A10
All Zones
11:57:48:32
30 Jan 90
Zone 00
LB00 S02
Note: For non-addressable points, the information logged in the second line is the Zone number, Comms. Channel
and point/type number. For addressable points, it shows the Zone number, loop identifier and Point number.
,17(51$7,21$//7'&203$1<
PAGE 41 of 56
MINERVA
15A-02-S1
03
4/99
3.18.7
Use the
,
or NO/DELETE to move
through the event types. When the required
event type is shown, press YES/ENTER.
The display will show:
Enter No. events
and press YES/ENTER.
The display will briefly show:
Print initiated
2) press YES/ENTER.
The display will show:
Print initiated
and a printout of all the isolated points will be
produced. The printout format is similar to
that shown in Fig. 13.
3.18.8
Address
Point String
Zone String
Count
Zone 02 A
SM520
40
Zone 02 Basement
09
Print Activation
Counts?
Fig. 15 Typical Zone Activation Count Printout
3) If a hard copy is required, press
YES/ENTER.
The display will show:
Print initiated
and a printout similar to that shown in
Fig. 15 will be produced.
3.18.9
PAGE 42 of 56
4.
4.1
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
DEVICE NUMBERS
38 - MF401 delayed
,17(51$7,21$//7'&203$1<
PAGE 43 of 56
MINERVA
15A-02-S1
03
4/99
4.2
GROUP NUMBERS
PAGE 44 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
,17(51$7,21$//7'&203$1<
PAGE 45 of 56
MINERVA
15A-02-S1
03
5.
4/99
REMOVABLE
PLASTIC
STRIP
Fig. 16
FILTER
FILTER BOWL
BOWL
RETAINING
RETAINING CLIPS
CLIPS
Fig. 17
PAGE 46 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
6.
FAULT MONITORING
6.2
6.1
GENERAL
6.2.1
4/99
Message
Point No.
Function
Possible Causes
SIGNALLING FAULT
MP R 01
Fault input.
Remote network signalling fault [stand
alone transmitter in use], either:
Faulty transmitter, or
Transmitter disconnected.
If no transmitter is fitted, 10k
termination resistor not connected.
Message
Point No.
Function
Possible Causes
MAINS FAILURE
MP R 04
Mains fail input.
Mains fault.
Message
Point No.
Function
Possible Causes
BATTERY FAULT
MP R 05
Battery monitor input.
Battery fault
Message
Point No.
Function
Possible Causes
SOUNDER FAULT
MP R 06 or 07
Sounder or sounder line fault.
Sounder fault, either:
Sounder line O/C fault,
Sounder line S/C fault,
Sounder EOL fault.
Message
Point No.
Function
Possible Causes
SYSTEM FAULT
MP P 00
Software error.
Software command error detected in
Digital Outputs sub-system.
Message
Point No.
Function
Possible Causes
DATA ERROR 1, 2, 3 OR 4
MP P 01
Bus configuration errors.
These errors arise only at system
initialisation and occur only as the
Controller checks its environment.
Error 1: multiple RBUS
interfaces on LBUS.
Error 2: RBUS [Channel 1]
interface fault on RBUS.
Error 3: Master directly
connected on LBUS fault.
Error 4: Illegal Slave connected
to LBUS/RBUS.
Action
,17(51$7,21$//7'&203$1<
PAGE 47 of 56
MINERVA
15A-02-S1
03
4/99
Message
Point No.
Function
Possible Causes
DATA ERROR 1, 2, 3 OR 4
MP P 02
Data packet errors
These errors occur when the
communications, interactive or ASCII
output software detect receipt of illegal
data.
Error 1: erroneous format
command to LCUs/printers.
Error 2: erroneous packet size
byte for application.
Error 3: error packet received
from comms. system.
Error 4: illegal packet type
received in comms. system.
Apart from at a complete system failure
Data Errors 2, 3 and 4 may occur if
incompatible devices are connected on
LBUS or RBUS, or personality links of
ancillaries are set incorrectly.
Message
Point No.
Function
Possible Causes
DATA ERROR 1, 2 OR 3
MP P 03
Interactive operator errors.
These errors occur when the interactive
software task detects illegal
applications data or fails to receive
certain expected data.
Error 1: illegal key error number.
Error 2: illegal operator mode error [should never occur].
Error 3: no reply from command
handler software error.
These errors generally result from
excessive comms. noise [although in this
case COMMS FAULT errors would
generally be received first], software errors or a possible overload of the system
with operator commands.
Message
Point No.
Function
Possible Causes
RAM FAULT
MP P 21
RAM read/write fault.
RAM chip failure
PCB failure
Message
Point No.
Function
Possible Causes
CHECKSUM FAILURE
MP P 22 or 23
Checksum failure in ROM or EEPROM.
ROM/EEPROM failure
PCB failure
Message
Point No.
Function
CONFIG INCOMPAT
MP P 23
Configuration EEPROM incompatible
with program software issue number.
Read Program Issue number
compatibility code [View System Issue
Nos. menu step] and check against
Action
PAGE 48 of 56
Message
Point No.
Function
Possible Causes
Message
Point No.
Function
Possible Causes
SYSTEM FAULT
MP P 28
Board fault.
Processor A/D Convertor corruption.
Message
Point No.
Function
Possible Causes
SYSTEM FAULT
MP P 29
Board fault.
Analogue Loop Software failure. [OC1,
NMI failure or stuck in distress poll].
Message
Point No.
Function
Possible Causes
SYSTEM FAULT
MP P 30
Event action failure
Bad configuration by CONSYS.
6.2.2
Message
Point No.
Function
Possible Causes
PRINTER OFFLINE
xB xx R 04
Printer offline
Printer off-line, disconnected, out of
paper or faulty. This is only detected
first when a print packet is sent to the
printer.
Message
Point No.
Function
COMMS FAULT
xx xx P 00
Comms lost on LBUS, RBUS or LNET.
Packet has been lost after prescribed
number of retries by driver.
Slave disconnected or faulty, or
address links set incorrectly.
If fault regularly occurs and
clears, multiple slaves [generally
of the same personality] set at
stated address.
If fault occurs and clears
regularly, but spuriously, this
indicates likely noise
interference.
Possible Causes
Message
Point No.
Function
Possible Causes
RAM FAULT
xB xx P 01
RAM fault.
RAM read/write fault.
RAM chip failure
PCB failure
Message
Point No.
Function
Possible Causes
CHECKSUM FAILURE
xB xx P 02
ROM/EEPROM fault.
Checksum failure on ROM.
ROM/EEPROM chip failure.
PCB failure.
Message
Point No.
Function
Possible Causes
DISPLAY FAILURE
xB xx P 03
LCD fault.
LCD panel failure.
Display control fault [Busy line
continuously at logic 1].
Display disconnected.
Message
Point No.
Function
Possible Causes
SYSTEM FAULT
xB xx P 04
General system fault.
MPIM processor timer fault.
Internal timing check failure faulty processor.
Message
Point No.
Function
Possible Causes
XBUS FAILURE
xB xx P 05
XBUS [Expansion bus] fault.
XBUS failure.
Expansion bus disconnected or
identity link missing.
Slave of wrong personality or
multiple slaves set at this address.
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
6.2.3
Message
Point No.
Cause
MNAU FAULT
LN04 X02
fault detected in HBUS, the link
between the MINERVA and the
MNAU.
Message
Point No.
Cause
MNAU FAULT
LN04 X05
non-specific fault with the local
network Superlink node.
Message
Point No.
Cause
MNAU FAULT
LN04 X06
detected fault in the network Ring.
Message
Point No.
Cause
MNAU FAULT
LN04 X07
invalid MNAU configuration.
Message
Point No.
Cause
MNAU FAULT
LN04 X08
communication failed with remote
network outstation.
Message
Point No.
Cause
MNAU FAULT
LN04 X09
non-specific MNAU internal process
fault.
Message
Point No.
Cause
MNAU FAULT
LN04 X10
Group Isolates failed.
Message
Point No.
Cause
MNAU FAULT
LN04 X12
detected fault with MNAU Random
Access Memory.
Message
Point No.
Cause
MNAU FAULT
LN04 X14
communication failed with
SATURN.
Message
Point No.
Cause
MNAU FAULT
LN04 X16
no more network channels available
from local node.
4/99
,17(51$7,21$//7'&203$1<
PAGE 49 of 56
MINERVA
15A-02-S1
03
4/99
6.2.4
Function
Possible Causes
LOOP FAULT & SHUTDOWNLoop shut down in order to protectLoop wiring fault or
loop hardware
faulty device drawing too much current or
loop driver hardware is faulty
GROUND FAULT
[US and Marine only]
Part of the floating system is making contact
Ground Fault
to a reference voltage
NO RESPONSE
Device not responding
Faulty device, device address set incorrectly
or incorrect config.
UNCONFIG DEVICE
Device responding at unconfigured Device address set incorrectly or
address
incorrect config.
HIGH IDENT
High I.D. current
Incorrect device fitted or faulty device
If several HIGH IDENT faults then there is
extra current draw in the loop either due to
leakage or due to a faulty device
LOW IDENT
DEVICE FAULT
Device fault
INVALID DATA
LOOP WARNING
LOOP FAULT
LOOP CRITICAL
NOISE MEASUREMENT
OUTPUT STUCK
SYSTEM FAULT
PAGE 50 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
Two independent loops have been Wiring fault on more than one loop
crosswired *
COMMS FAULTLBUS
COMMS FAULTRBUS
SIGNALLING FAULT
BATTERY FAULT
Faulty battery
Faulty battery
PSU FAULT
MAINS FAILURE
BATTERY CRITICAL
SOUNDER FAULT
EOL of the Sounder unit connectedNo EOL, sounder wiring fault or faulty
to the Main Processor is faulty
sounder, faulty EOL unit
User definable
Expansion Bus connection from Faulty Expansion Bus cable or MPIM
MPIM to zonal display/XIOM faultyconfigured incorrectly
MPIM cannot communicate with Faulty LCD or MPIM configured incorrectly
LCD
User definable
Refer to section 6.2.1
Contact Monitor or Vesda short
Incorrect device wiring or faulty device
circuit
Contact Monitor or Vesda open
Incorrect device wiring or faulty device
circuit
Refer to section 6.2.1
Refer to section 6.2.1
Refer to section 6.2.1
Refer to section 6.2.1
Refer to section 6.2.
Refer to section 6.2.1
Refer to section 6.2.1
Airflow fault in Vesda unit
Incorrect device fitting or faulty device
As for RAM fault
More than 5 detectors in one loop Loop not connected
not responding *
As for Ground fault
Fault in MINERVA Network AccessFaulty MNAU
Unit
24 Volt supply too high
Faulty ACPM [or external PSU] or faulty
Main Processor board
CONTROL FAILURE
XBUS FAILURE
DISPLAY FAILURE
GENERAL FAULT
RELAY COIL FAULT
WIRING FAULT S/C
WIRING FAULT O/C
CONFIG INCOMPAT
DATA ERROR 1
DATA ERROR 2
DATA ERROR 3
DATA ERROR 4
RAM FAULT
CHECKSUM FAILURE
A.S. FAULT
RAM OVERFLOW
FAULT OVERFLOW
145
EARTH FAULT
MNAU FAULT
160
Note: Faults marked * will not clear until the system is powered down and the loop is debugged.
1999 Tyco Electronic Product Group
Registered Office: 19-21 Denmark Street, Wokingham, Berks RG40 2QE
$
,17(51$7,21$//7'&203$1<
PAGE 51 of 56
MINERVA
15A-02-S1
03
6.3
4/99
6.3.1
Cat
No.
Function
LB 15
A
LB 00
P
123
S01
00
RB 01
01
RB 02
RB 02
X
X
01
80
MP
02
Board
Cat
No.
Function
xB xx
xB xx
xB xx
xB xx
S
S
S
S
01
02
03
04
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
R
R
R
R
R
R
R
R
R
R
01
02
03
04
05
06
07
08
09
10
xB xx
xB xx
xB xx
xB xx
xB xx
xB xx
P
P
P
P
P
P
00
01
02
03
04
05
PAGE 52 of 56
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
4/99
xB xx
01
xB xx
80
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
R
R
R
R
R
R
R
R
R
R
R
01
02
03
04
05
06
07
08
09
10
11
MP
MP
MP
MP
MP
P
P
P
P
P
00
01
02
03
08
MP
MP
MP
MP
MP
MP
MP
MP
MP
P
P
P
P
P
P
P
P
P
10
11
12
13
14
15
16
17
18
Main Processor board, NET MODULE fault, [TLK530 not accepting data]
Main Processor board, NET MODULE fault, [no comms to/from TLK530]
Main Processor board, NET COMMON fault
Main Processor board, NET PORT L fault
Main Processor board, NET PORT R fault
Main Processor board, NET GROUND fault
Main Processor board, NET TRANSFER fault
Main Processor board, NET RING CONTINUITY FAULT
Main Processor board, NET COMMS fault
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
MP
P
P
P
P
P
P
P
P
P
P
P
P
P
21
22
23
24
25
26
27
28
29
30
31
32
33
MP
MP
P
P
50
51
MP
82
LB 1x
LB 1x
LB 1x
LB 1x
P
P
P
P
00
20
21
22
LB 1x
23
,17(51$7,21$//7'&203$1<
PAGE 53 of 56
MINERVA
15A-02-S1
03
6.4
4/99
GENERAL
6.4.4
6.4.8
6.4.3
6.4.7
Check for probable partial shorting on the Loop wiring Loop Warning and/or Loop Fault messages are also
likely to be present.
6.4.9
PAGE 54 of 56
6.4.11
EQUIPMENT:
MINERVA
PUBLICATION:
15A-02-S1
03
If this eliminates the Low Idents, reinstate one and then the
other Line Isolator until the Low Idents reappear - Replace
the Line Isolator[s] which produce the Low Idents.
REFRESH
BI - PHASE
4/99
MEASUREMENT
REFRESH
20V
+15V +0V -1V
10V
0 0 0 0 1 1 0 1 0 0
+2V
1 1
6.4 ms
0V
Fig. 18
7ms
,17(51$7,21$//7'&203$1<
PAGE 55 of 56
MINERVA
15A-02-S1
03
4/99
7.
SPARES
8.
515-001-015
ASSOCIATED PUBLICATIONS
05A-02-S1
05A-10-S1
JM/jm
16th April 1999
PAGE 56 of 56