Вы находитесь на странице: 1из 22

Exercises for the Power System Stability

Training Material

- Exercises -

Training Course Documents [Last modified: 5/22/2007]

-2-

DIgSILENT Seminar
Analysing Power System Stability with PowerFactory
The purposes of these exercises are to introduce the basic methods of the analysis of different
phenomena of stability occurring in power systems. Furthermore the calculation functions and various
available tools of the PowerFactory program are introduced during the exercises, which will enable
you to get acquainted with the methods of the stability analysis, visualization and interpretation of the
results.
The instructions in the exercises are brief on purpose. It is the intention that you try to work out
yourself how to perform a certain task. However references to more detailed instructions are given as
[n], where 'n' is the number under which you'll find these instructions in the appendix. You can also
use them after the training to repeat the exercises on you own.
During the exercises there will be two supervisors, who will support and help you with your tasks of
the exercise. Additionally they can provide answers to general questions regarding the topic of the
training or different problems from your own practice.
Please do not hesitate to address the supervisors at any time to any topic!
We wish good success!

Exercise 1: One-Machine Problem in PowerFactory


Start-up PowerFactory with your (training) user name and create a new project PF Stability [1] or
similar. You can leave the name of the grid as it is or change it.
Before starting to create the network in the single-line graphic, we have to build up the library
including the different types with the electrical data of the devices. This is necessary before entering
the elements into the network.

Input data for the types:

In the following tables the electrical data for a overhead line type, a 2-winding transformer
type and a generator type are shown. These shall be inserted into the local library of the
active project, and they are used when inputting the elements of the system [2].

Line Type CCT:


Un
Irated
X

500 kV
1 kA
0.56306 Ohm/km

Training Course Documents [Last modified: 5/22/2007]

-3-

Transformer Trf 500kV/24kV/2220MVA:


Sn
UnHV
UnLV
Xshc

2220 MVA
500 kV
24 kV
15 %

Generator Gen 2220MVA/24kV:


Basic Data:
Sn
Un
cosn
RMS/EMT-Simulation:
Tag
rstr
xl
xrl
xd
xd
xd
xq
xq
xq
Td
Td
Tq
Tq
Main Flux Saturation:
SG10
SG12

2220 MVA
24 kV
1
7s
0.003 p.u.
0.15 p.u.
0
1.81 p.u.
0.3 p.u.
0.23 p.u.
1.76 p.u.
0.65 p.u.
0.25 p.u.
1.325967 s
0.023 s
0.3693182 s
0.02692308 s
0.12396 p.u.
0.177575 p.u.

Input the elements in the single-line graphic:

Setup the case according to the single line diagram below. Insert the elements with the data
given in the figure [5].
Additional load-flow data is shown in the following:
- The voltage magnitude of the voltage source is set to: 0.90081 p.u.
- The generator is set to a constant PQ type.
- The generator dispatch is set to S = 2220MVA and a power factor of 0.9

Training Course Documents [Last modified: 5/22/2007]

Infinite Bus
500. kV

HV
500. kV

DIgSILENT

G
~

1998.00
967.68
53.41

LV
24. kV

472.13
0.94
20.12

24.00
1.00
28.34

1299.40
412.74
1.67

CCT1
Type CCT
100. km

1998.00
967.68
53.41

-1998.00
-634.64
2.56

Trf
Trf 500kV/24kV/2220MVA

G1
Gen 2220MVA/24kV

698.60
221.90
0.90

CCT2
Type CCT
186. km

450.41
0.90
0.00

-1299.40
56.79
1.67

-1998.00
87.32
2.56

Infinite Source

-698.60
30.53
0.90

DIgSILENT

-4-

Exercise 1
Power System Stability and Control
One Machine Problem

PowerFactory 13.1.252

Project: PF Seminar
Graphic: Grid
Date: 11/11/2004
Annex:

Figure 1: Single Line Graphic of the Network

Short-circuit simulation at bus HV:


Simulate a short-circuit at busbar HV with a duration of 110ms and visualize [6]:

Generator Active Power


Generator Reactive Power
Generator Current
Generator rotor angle (with reference to reference bus voltage)
Voltage at Bus Bar HT and LT
Display the P-phi diagram of the run [7]

Therefore you have first to define the variables for the generator and the busbars/terminals you
want to look at in the simulation [8]. Then you have to define two events on the busbar HV,
where the short-circuit is initiated (at 0 s) and cleared again (at 110 ms) [9].
Determine the critical fault clearing time of the system.

Training Course Documents [Last modified: 5/22/2007]

-5-

Short-circuit simulation on line CCT2:


Simulate a short-circuit in the middle (50%) of the overhead line CCT2 with a duration of 100ms.
Clear the fault by opening the line.
Determine the critical fault clearing time.
Additionally you can check the current through the line CCT1 and CCT2 during the simulation, as
well as the speed of the synchronous generator.
Simulate a short-circuit in the end (99.999%) of the overhead line CCT2 with a duration of
100ms. Clear the fault by tripping the line as mentioned above.
Determine the critical fault clearing time again.
Compare the results and the critical fault clearing time of these cases with the case of a shortcircuit directly on the bus HV.

Exercise 2: Small Signal Stability in the One-Machine System


Before running the Eigenvalue Analysis we want to investigate the one-machine system using the
transient simulation function used in Exercise 1. So first a small disturbance is introduced into the
system and the response of the machine will be analysed.
Therefore please put all events in your project out of service.

Introducing a small disturbance:

Insert an event into the event list, which is increasing the torque at t=0s by 0.01 p.u. Use a
Event of a Synchronous Machine to add additional torque [10].
Reduce the electric torque of the generator G1 again to the pre-disturbance value.
Observe the speed of the generator in a subplot.

Determine the frequency and damping of the oscillation of the speed signal.

Now switch off the line CCT2 and investigate the differences in the generator speed
oscillation.

Instead of investigating the system using time domain simulations, now the small signal stability is
analysed with the Modal Analysis function in PowerFactory. I.e. the eigenvalues of the system are
calculated and the eigenfrequencies of modes and their damping is shown.

Training Course Documents [Last modified: 5/22/2007]

-6-

Modal Analysis:

Run a load-flow calculation and calculate the initial conditions.


Run the modal analysis and calculate all eigenvalues for the generator speed [11].
Output all results of the eigenvalue analysis in the output window. Hereby first investigate the
results with only the eigenvalues, and then including the detailed information about the
participation factors [12].

Compare the results of the time domain simulation and of the modal analysis for both
described case.

Exercise 3: Voltage Stability


Now the voltage stability of the one-machine system is to be analysed. This can be done by using
voltage-reactive power (V-Q) curves or active power-voltage (P-V) curves. To automatically go
through the system and change the parameters, we provide to scripts for calculating the important
values and visualizing these voltage stability curves.

V-Q-curves:

First deactivate your project [3].


Import the file named V-Q-Curve.dz directly into the study case [13].
Activate the project again.

Now change the voltage setpoint for the infinite busbar to 1p.u.
Before running the DPL script, you have first to define a DPL command set with the
generator G1 and the terminal LV [14].
Then open the dialog of the DPL script V-Q-Curve and select the DPL command set as the
general selection [15].
Now enter the voltage range to be investigated:
- maximum voltage at LV
- minimum voltage at LV
- voltage step of the simulation
And the active power output of the generator to produce different V-Q-curves:
- maximum active power of G1
- minimum active power of G1
- active power step of the simulation

Now the script will automatically show a number of V-Q-curves according to the number of active
power steps you defined. It is also possible to show all curves in one X-Y plot.
Also see that the script set the generator from controlling P and Q to controlling the active power and
the voltage at LV.

Training Course Documents [Last modified: 5/22/2007]

-7-

P-V-curves:
For visualizing the P-V curves we have first to import another DPL script and change network to
some extent. So it would be best to save your project on your hard disk or to make a new revision
in the project.

First deactivate your project [3].


Import the file named P-V-Curve.dz directly into the study case [13].
Activate the project again.

To analyse the P-V characteristic the generator has to be put out of service and a load Load
should be connected at the terminal LV with a active power consumption and a constant
power factor.
Define a DPL command set with the load Load and the terminal LV [14].
Then open the dialog of the DPL script P-V-Curve and select the DPL command set as the
general selection [15].
Now enter the initial scaling factor for the load depending on the active power you entered for
the load.
Furthermore the power factor of the load can be specified and whether it is capacitive or
inductive
See the differences in the curve and in the maximum transmitted power using various values
of the power factor.

Improving Voltage Stability:


Add in turns the following elements at the load bus bar and analyse the effects on the P-V-curves
and on the stability limit.
Fixed capacitive shunt
Switched capacitive shunt
Static Var Compensator/System (SVC)

Training Course Documents [Last modified: 5/22/2007]

-8-

Exercise 4: Built-in Excitation System


Now into the project there are to be included a voltage controller (AVR) and a power system stabilizer
(PSS). So the control of the generator is no longer neglected but has an influence in the behaviour of
the generator and thus in the stability of the investigated system.

AVR:
A voltage controller is created and the step response of the generator system is analysed (closed-loop
response).

Create a new Composite Model and a new Common-Model inside the Grid folder in the
data manager [16].
Therefore right-click the generator and select Define -> Voltage Controller (vco)
Select the Block-Diagram vco_EXAC1A from the standard IEEE-Library in the global library of
PowerFactory [16].
The Frame IEEE-frame no droop from the standard IEEE-Library in the global library of
PowerFactory is automatically selected.
Enter the name and the parameters of the voltage controller according to the table on the
next page.
Calculate a load-flow and the initial conditions to check your project for errors.

Verify the model by a step-response (closed-loop) test on the voltage setpoint:

Test the model with a step response to the input voltage usetp (closed-loop test) [17]
To check the setup of the controller, show the block diagram of the controller [19].
Define a variable set to monitor for the AVR element and visualize the results of the simulated
step response [18].
You may make changes to the parameters in the variable set for the AVR and analyse the
differences in the response
Visualize the results of the simulated step response [18].

Training Course Documents [Last modified: 5/22/2007]

-9-

AVR Settings for the vco_EXAC1A:


-------------------------------------------------------------------------------|

| PowerFactory |-------------------------------

DIgSILENT

13.0.252

| Project:
| Date:

11/11/2011

-------------------------------------------------------------------------------|Grid:Grid

Syst.Stage:Grid

| Annex:

/ 1

-------------------------------------------------------------------------------|AVR G1

Common Model

/1

-------------------------------------------------------------------------------|Model Definition

\Library\Models\IEEE\Models\vco_EXAC1A

|Out of Service

No

| Parameter

Tr

Measurement Delay [s]

0.0000

Tb

Filter Delay Time [s]

1.0000

Tc

Filter Derivative Time Constant [s]

1.0000

Ka

Controller Gain [p.u.]

500.0000

Ta

Controller Time Constant [s]

0.2000

Te

Excitor Time Constant [s]

0.0100

Kf

Stabilization Path Gain [p.u.]

0.0300

Tf

Stabilization Path Delay Time [s]

1.0000

Kc

Excitor Current Compensation Factor [p.u.]

0.3470

Kd

Excitor Current Derivative Factor [p.u.]

0.0500

Ke

Excitor Constant [p.u.]

1.0000

E1

Saturation Factor 1 [p.u.]

7.4025

Se1

Saturation Factor 2 [p.u.]

0.2416

E2

Saturation Factor 3 [p.u.]

9.8700

Se2

Saturation Factor 4 [p.u.]

1.5373

Vrmin Controller Minimum Output [p.u.]

-10.0000

Vrmax Controller Maximum Output [p.u.]

10.0000

--------------------------------------------------------------------------------

Training Course Documents [Last modified: 5/22/2007]

upss

1/(1+sT)
Tr

Vc-

curex

o12

Vs
Vf

usetp

yi1

sK/(1+sT)
Kf,Tf

(1+sTb)/(1+sTa)
Tb,Tc

yi

Vrmin

K
Kd

_{K/(1+sT)}_
Ka,Ta

Vrmax

Vr

o18

Vfe

KeSe

yi3

uerrs..

[1/sT
Te

Se(efd)+Ke
Ke,E1,Se1,E2,..

vco_EXAC1A: IEEE Modified Type AC1 Excitation System

Ve

_Fex_
Kc

uerrs

-10-

Figure 2: Block Diagram of the vco_EXAC1A voltage controller

Training Course Documents [Last modified: 5/22/2007]

DIgSILENT

Fex

-11-

Now the influence of the AVR is to be analysed on the small and large signal stability of the onemachine problem. Therefore put the frame model and the AVR into service.

Simulate the disturbances introduced in Exercise 1:


Short-circuit at the busbar HV
Short-circuit in the middle (50%) of the overhead line CCT2. Clear the fault by tripping
the line as mentioned above.

Determine the critical fault clearing time for both cases.

Compare the results and the critical fault clearing times of these cases with the case of a
short-circuit directly on the bus HV.

Execute a Modal Analysis for the system with AVR.


Output the eigenvalues as well as the damping and eigenfrequency and analyse the
differences.

PSS:
After we analysed the operation of the generator combined with an AVR, now the system should be
stabilized using also a power system stabilizer. The PSS is connected into the frame of the generator
and the closed-loop response can be simulated.

Create a new controller model for the power system stabilizer in the existing composite model
[16].
Therefore right-click the generator and select Define -> Power System Stabilizer (pss).
The reference inside the existing composite model for the PSS slot is created automatically.
Select the Block-Diagram pss_STAB2A from the standard IEEE-Library in the global library of
PowerFactory [16].
Enter the name and the parameters according to the table on the next page.

Calculate a load-flow and the initial conditions to check your project for errors.

Verify the behaviour of the power plant model using a closed-loop test similar to the AVR before:

Test the model with a step response to the input voltage paux (closed-loop test) [17]
Define a variable set to monitor for the PSS element and visualize the results of the simulated
step response [18] for about one second.
To check the setup of the controller, show the block diagram of the controller [19].

Calculate a load-flow and the initial conditions to check your project for errors.

Training Course Documents [Last modified: 5/22/2007]

-12-

PSS

Settings for the pss_STAB2A:

-------------------------------------------------------------------------------|

| PowerFactory |-------------------------------

DIgSILENT

13.0.252

| Project:
| Date:

11/11/2011

-------------------------------------------------------------------------------|Grid:Grid

Syst.Stage:Grid

| Annex:

/ 1

-------------------------------------------------------------------------------|PSS G1

Common Model

/1

-------------------------------------------------------------------------------|Model Definition

\Library\Models\IEEE\Models\pss_STAB2A

|Out of Service

No

| Parameter

K2

Washout Factor [p.u.]

1.0000

T2

Washout Time Constant [s]

4.5000

K3

Signal Transducer 1th Factor [p.u.]

1.3000

T3

Signal Transducer Time Constant [s]

2.0000

K5

Output Filter Factor [p.u.]

1.5000

T5

Output Filter Time Constant [s]

0.0100

inv

-1 [-1]

-1.0000

K4

Signal Transducer 2th Factor [p.u.]

1.0000

Hlim

Controller Maximum Output [p.u.]

0.0500

--------------------------------------------------------------------------------

Now the influence of the additional PSS is to be analysed on the small and large signal stability of the
one-machine problem. Therefore put the frame model, the AVR and PSS into service.

Simulate the disturbances as above:


Short-circuit at the busbar HV
Short-circuit in the middle (50%) of the overhead line CCT2. Clear the fault by tripping
the line as mentioned above.

Determine the critical fault clearing time for both cases.


Compare the results and the critical fault clearing times of these cases and the cases
without the PSS in service.

Execute a Modal Analysis for the system with AVR and PSS.
Output the eigenvalues as well as the damping and eigenfrequency and analyse the
differences.

Training Course Documents [Last modified: 5/22/2007]

pgt
KsTd/(1+sT1)
K2,T2,T2

KsTd/(1+sT1)
K2,T2,T2

KB
K4

K/(1+sT)
K3,T3

KsTd/(1+sT1)
K2,T2,T2

pss_STAB2A: Power System Stabilizing Unit (ASEA)

K/(1+sT)
K5,T5

KB
inv

K/(1+sT)
K5,T5

Limiter

Hlim

upss

-13-

Figure 3: Block Diagram of the pss_STAB2A power system stabilizer

Training Course Documents [Last modified: 5/22/2007]

DIgSILENT

paux

-14-

Exercise 5: Motor Starting


In this example a nine-bus-bar 230 kV system is used, containing three different generators and some
loads. In this exercise the auxiliary of generator G3 is modeled as an asynchronous motor. Then
different start-up methods are used and the impact of the motor start on the network is analysed.
First import the project file Nine Bus Bar System [4] and activate the project.
Define a new revision of the nine bus bar case [18] with a new study case (i.e. motor
start-up).

M
~

Motor

2.23 MW
0.84 Mvar
3.50 kA
0.39
0.98
26.00

Motor Bus

G3

G
~

85.74 MW
-10.00 Mvar
3.52 kA
14.14
1.02
1.40

83.50 MW
-11.09 Mvar
3.44 kA

Bus 3

Bus 9

237.42
1.03
148.75

-83.50 MW
15.05 Mvar
0.21 kA

47.29 MW
-17.12 Mvar
0.12 kA

Line 5

T3

-2.23 MW
-0.84 Mvar
3.50 kA

Motor Trf
2.24 MW
1.09 Mvar
0.10 kA

0.11 kA

Line 4

36.21 MW
2.08 Mvar
0.09 kA

0.27 kA

Load C

-46.47 MW
-16.79 Mvar
0.12 kA

-45.57 MW
-13.98 Mvar
0 12 kA

92.04 MW
30.77 Mvar
0 24 kA

Figure 4: Single-Line Diagram of the Motor to be added to the Nine Bus Bar Network.

Insert the motor element into the single-line diagram. Therefore see also the figure above.

Insert a new bus bar into the system with a rated voltage Un = 0.4 kV.
Add the motor transformer using the transformer type Motor-Trf from the project library.
Add the motor element using the motor type (TypAsmo) 2500kW Motor from the project
library.
Set the motor to the bus type AS and an active power of 2.23 MW on the load-flow page.
Check the load-flow results with the figure above.

Training Course Documents [Last modified: 5/22/2007]

-15-

Simulate a motor start-up using the direct start-up function of PowerFactory:

(Multi-) Select the motor plus a couple of bus bars whose voltage is of interest.
Run the automatic motor start-up simulation for 10 s.
Observe the plots, which are automatically created, as well as the result objects and the
switching event.

For this simulation only the built-in motor load has been used. Now, a more detailed mechanical load
model will be applied:
Click with the right mouse button on the motor symbol and select Define -> Motor Driven
Machine (mdm).
Select the ElmMdm__3 model.
Enter the data from the table below into the RMS-Simulation page of the MDM.
This will automatically create a composite model for the motor and the mechanical load.
Check the changed mechanical load curve and the torque-speed characteristic on the RMSSimulation page of the motor.
Rerun the simulation.

Visualize the mechanical torque vs. speed characteristic and the electrical torque vs. speed
characteristic of the motor. Therefore use an x-y-plot [7].
Compare the characteristics to the curves shown in the motor dialogue.

-------------------------------------------------------------------------------|

| PowerFactory |-------------------------------

DIgSILENT

13.1.252

| Project:
| Date:

11/11/2004

-------------------------------------------------------------------------------|Grid:Nine_Bus

Syst.Stage:Motor Starting | Annex:

/ 1

-------------------------------------------------------------------------------|Vers. 10.31-Model mdm__3

Vers. 10.31-Model mdm__3

/1

-------------------------------------------------------------------------------|Out of Service

No

|alf1;Torque at synchronous speed

1.0000

p.u.

|slipm;Slip at min. torque

0.8000

p.u.

|exp1;Exponent of first polynom. function

2.0000

|alf2;Torque at standstill

0.2000

|exp2;Exponent of second polynom. function

2.0000

|xkmm;Torque at slip = Slipm

0.1000

(min. torque)

|
p.u.

|
|

p.u.

|
|

--------------------------------------------------------------------------------

Training Course Documents [Last modified: 5/22/2007]

-16-

Simulate a motor start-up using the standard stability function:

Calculate a load-flow with disconnected motor.


Initialize the simulation.
Define the event for closing the motor breaker.
Define the result variables.
Start the simulation (RMS).

Rerun the same case with the EMT function (adaptive step size, min step=0.0001, max step=0.0005)
and compare the results.
Star-Delta Start:
Simulate a star-delta start-up. Therefore events will be created, which will switch the motor to star
connection and back to delta after 15s.
Prepare the simulation as before.
Change the start-up method of the ASM on the second page of the RMS-simulation page in
the element dialogue from Direct Online to Star-Delta.
Set the time Y->D to t = 15s.
Rerun the simulation (mind changing back to RMS again)
Transformer Tap-Changer:
Simulate a motor start-up by changing the tap position of the Motor Trf transformer. The
transformer tap is divided into 2.5% steps. Check the tap controller on the load-flow page of the
transformer type.
Define Set Parameter events for the actual tap position nntap_int of the motor transformer.
Initially set the variable nntap_int first to 75% (tap = 10) at t = 0s.
Then set nntap_int to 90% (tap = 4) at t = 10s.
Finally set nntap_int to 100% (tap = 0) at t = 15s.
Rerun the simulation
Variable Rotor Resistance:
Simulate a start-up with variable rotor resistance. Check the influence of an additional rotor resistance
on the motor onto the start-up behaviour.
Change the start-up method of the ASM on the second page of the RMS-simulation page in
the element dialogue from Direct Online to Variable Rotor Resistance.
Add three new rows to the table.
Set the additional resistance to 50% (0.5 p.u.) at t = 0s.
The set the additional resistance to 30% (0.3 p.u.) at t = 10s.
Then to 15% (0.15 p.u.) at t = 15s.
Finally set the additional resistance to 0% (0 p.u.) at t = 20s to end the start up sequence.
Rerun the simulation

Training Course Documents [Last modified: 5/22/2007]

-17-

Appendix: Detailed Instructions


#1: To create a new project
Main Menu: "File - New" (Ctrl + N). This opens the "New" dialog. Tick the option "New - Project".
Enter the project's name. Make sure that the 'Target Folder' points to the folder in which you want to
create the project (normally that is your user account folder).
Press Execute. A grid is automatically created in the new project and a dialog will pop up asking you
for the name of that grid. The empty single line diagram for the newly created grid will be shown.
You may change the name of the project after you have created it through the main menu: "Edit Project". This menu-option opens the project dialog. Be careful not to change any settings or buttons
which you do not know.
You can change the name of the Study Case through the main menu : "Edit - Study Case". Here you
can change the name of the study case, but you can also change the settings of the Grids that are
activated by the study case. To change the grids, press the button "Grids/System Stages". This opens
a list of all Grids. You can either double-click the name to change it (press "return" twice to confirm
the change), or you can select the Grid that you want to change (by left-clicking the icon in the first
column), and press the "Edit Object" Button in the current window.
#2: Inserting Elements inside the Library
First open the data manager and select the local library of your active project. Then press the New
and select the right device type for inserting into the library for the list shown.
object button
When the data is inserted, you can select this type for the according element from its edit dialog by
using the option Select project type
#3: (De)activating a Project
The last 5 active projects are listed at the "File" menu on the main menu bar. The currently active
project is the first one in this list. To deactivate the currently active project, select it in the list (left
click it). Alternatively, you may choose the option "File - Close Project" from the main menu.
To activate a project, select it in the list of 5 last active projects. To activate a project that is not in
the list of 5 last active projects, use the option on the main menu "File - Open project". This brings a
tree with all the projects in your user account. Select the project that you want to activate.
#4: Import a DZ File from Disk
button in the data manager. Select the file on disk
Press Main Menu: File -> "Import" or the
that you want to import. If required, press the black arrow button to select another path to which you
want to import the objects in the file. This opens a tree with all the folders in your database from
which you can select the correct folder (normally, this would be your user account folder).

Training Course Documents [Last modified: 5/22/2007]

-18-

#5: Inserting Elements into the Single Line Graphic

You may want to maximise the drawing area by pressing the


again to return to normal viewing mode.

Select an object in the drawing toolbox. (start with a busbar or terminal)

Move to the drawing area. Position the element by a left click. When you want to move it,
select it with a left mouse click, then drag it along.

Select a busbar/terminal and drag the small black squares to resize the busbar/terminal

Connect a branch/load/generator etc. by clicking on a busbar/terminal

Double-click an element to open its dialog

button. Press this button

In an element's dialog, press the small button with the down-arrow to select a type. Choose "Select
Project Type" to jump to the local, project specific, type-library.
Tips:

Start entering a new grid by drawing all busbars/terminals. Then connect the branches
between them.

Use the zoom function.

Use the undo button if you have drawn an object of the wrong type

#6: Visualizing Results

add an new graphics page to the case and select Virtual Instrument
With the button
Panel. This will create a new VI page, where plot can be shown.

Append a number of virtual instruments (VIs) to the empty page by using the Append VIs
button
and entering the number of VIs. Thus a specified number of empty plots will occur
in the page.

For a normal plot use the Subplot (VisPlot) VI for showing time dependent variables.

In the edit dialog of the plot you can then define the variables to look at.

#7: Visualizing Dependent Variables

. For
Append a virtual instrument to the VI page by using the Append VIs button
showing a variable depending on a second variable use the X-Y Plot (VisXyplot) and then
define a variable for the x-axis and one for the y-axis in the edit dialog of the plot.

Training Course Documents [Last modified: 5/22/2007]

-19-

#8: Defining a Variable Selection

Before defining the variables to monitor the initial conditions have to be calculated (using the
button)

Then right-click on the element to be monitored and select Define -> Variable Set (Sim)
from the context sensitive menu.

All variable sets of selected elements are now shown. Double-click the element you just
selected.

This brings a selection window, where you can create, select or edit a set of variables. If a
variable set is edited, then a variable set manager will pop up. This variable set manager
shows in the left pane the available variables, and in the right pane the selected variables.
Press the [<<] or [>>] buttons to move the selected variable from the one to the other pane.
Use the various filter settings to show more available variables.

The variable set will now consist of the selected variables, which are now ready to show in a
plot.

#9: Defining Simulation Events


Before running the simulation it is often necessary to define simulation events, which will take place
during the next simulation.

Before specifying an event the initial conditions have to be calculated (using the

Then events can be created and defined by opening the current event list (
create new events using the New Object button

button)

) and then

#10: Changing the Generator Torque

Similar to defining the short-circuit events for this exercise a Event of Synchronous Machine
(ElmSym) is created in the event list (

) using the New Object button

Make sure you reset the calculation


change the events.

Enter the additional torque 0.01p.u. for the first event.

Enter the additional torque -0.01p.u. for the second event to get back to the pre-disturbance
values

or run the initial conditions

Training Course Documents [Last modified: 5/22/2007]

before trying to

-20-

#11: Calculate the Eigenvalues

Before calculating the eigenvalues with the modal analysis you have first to calculate the
initial conditions using the

button

Then the button for the Modal Analysis is becoming active


calculate all system eigenvalues.

. Run the modal analysis to

#12: Output the Calculated Eigenvalues

and then selecting the option


Using the function Output Calculation Analysis
Eigenvalues the output of Eigenvalues is activated.

Select from the options, which information should be printed to the output window:
- Eigenvalues
- Participations
- Participations detailed

When using the Participation/Participation detailed option the Select Eigenvalue(s) dorp down
menu should be set to filtered. You can edit the filter to a specific maximal damping of the
mode or to a maximal period duration time.

#13: Import of DLP Scripts


Press Main Menu: File -> "Import" or the
disk that you want to import.

button in the data manager. Select the project file on

Press the black arrow button to select the study case to which you want to import the script. This
opens a tree with all the folders in your database from which you can select the correct folder
(normally, this would be your user account folder).
#14: Defining a DPL Command Selection

Multi-select the required elements in the grid or in the data manager.

Right-click the selection.

Select Define -> DPL Command Set from the context sensitive menu.

The DPL command set is stored inside the study case.

Training Course Documents [Last modified: 5/22/2007]

-21-

#15: Running a DPL command

Double-click the DPL command.

Insert/Change the listed parameters.

Select the DPL command set for the general selection of the script.

#16: Creating a Common Model


There is also a way of defining the controller models manually:

Open the data manager and select the grid in the left window of the manager.

Select the New Object button

Chose the controller definition vco_ESAC1A from the global library in the folder
\Library\Models\IEEE\Models\.

Press OK and insert the controller parameter.

and select Common Model in the upcoming dialog.

#17: Open-Loop Test

Open the event list (


(EvtPara) event

Select the AVR controller for the element.

Insert the name of the variable usetp and the new value for this variable (=0.9).

) and use the New Object button

to insert a Set Parameter

#18: Defining Variables and Visualizing Results

According to [8] and [6] define and visualize the input variables u and usetp and the output
(excitation) voltage uerrs to the generator.

#19: Show Block Diagram

Open the data manager and select the AVR element inside the grid or

Select the AVR using the button edit calculation relevant objects

Right-click the element AVR G1.

Training Course Documents [Last modified: 5/22/2007]

-22-

Select the option Show Graphic in the context-sensitive menu.

#20: Creating a Composite Model

Open the data manager and select the grid in the left window of the manager.

Select the New Object button

Chose the controller definition IEEE-frame no droop from the global library in the folder
\Library\Models\IEEE\Frames\.

Press OK and insert the references to the generator and the AVR by right-clicking the slot and
select select element/type.

and select Composite Model in the upcoming dialog.

#21: Defining a new Revision

Right-click the active study case in the data manager and select the option New -> Revision.

Insert a name for the new study case (i.e. motor start-up).

Input a name for the new system stage (i.e. also motor start-up).

Now the new study case is activated.

#22: Running an Automatic Motor Start-Up

Select one motor and at least one bus bar or several in the network.

Right-click the motor symbol or another selected element.

Select the option Calculate -> Motor Startup

Insert the time period for the simulation.

Training Course Documents [Last modified: 5/22/2007]

Вам также может понравиться