UPS Start-Up Work Instruction

Facilities
Procedure
Illustration
Technician
Start-Up Procedure
1

Verify and check UPS. It must be clear


from unnecesaary items.

Close "Q2" Bypass Isolator Switch.

Close "Q4" Output Isolator Switch.

Ensure that the display screen


initializes and the Amber "Load on
Bypass" LED is flashing + "Manual
Bypass Closed" alarms are present.

Open "Q3" Maintenance Bypass


Switch.

Verify Load Current to the monitoring


screen must not be zero.

Close "Q1" Rectifier Input Isolator.

Note: Closing Q1 will automatically turn on


the INVERTER and the unit will shift to UPS
Mode.
8

Ensure that after approximately 30


seconds, the Green "Load on Inverter"
LED is lit and the bypass LED has
extinguished.

Close Main Battery Circuit Breaker.

Select "Measurements" in the control


10 panel and verify parameters for Input,
Output and Battery.
11 Unit is now on UPS Mode.

UPS Shutdown Work Instruction


Procedure

UPS Start-Up Work Instruction

Facilities
Illustration
Technician

UPS Shutdown Procedure

Procedure
Start-Up Procedure

Route notification form to notify the


area owner/Shift Supervisor/Equipment
Owner and manufacturing area
affected.

Verify and check UPS. It must be clear


from unnecesaary items.

Secure UPS Transfer Procedure


checklist upon shifting of UPS from
UPS to Bypass Mode.

Close "Q2" Bypass Isolator Switch.

Make sure that the UPS is in normal


operation (no alarm present).

Close "Q4" Output Isolator Switch.

Verify if "Q2" Bypass Isolator Switch is


still close and the Unit was on normal
operation.

Ensure that the display screen


initializes and the Amber "Load on
Bypass" LED is flashing + "Manual
Bypass Closed" alarms are present.

Press "INV" inverter button in the left


side of the front panel.

Open "Q3" Maintenance Bypass


Switch.

Press "ENTER" and the inverter will


stop / turn off while the load will transfer
to bypass.

Verify Load Current to the monitoring


screen must not be zero.

Press "Alarm Silence Switch" to


cancel the audible alarm.

Close "Q1" Rectifier Input Isolator.

Open "Main Battery Circuit Breaker"


located at the side of the unit.

Battery Circuit Breaker open will be


displayed on the LCD screen panel.

10 Open the "Q1" Rectifier Input Isolator.

Note: Do not open the Output Isolator Q4


otherwise power will be disconnected from
the load. Power to the load will be coming
from the static bypass switch of the UPS.

11

Check that the UPS was already on


static bypass.

12

Close "Q3" Maintenance Bypass


Switch.

13

Veify Load Current to the monitoring


screen must be zero.

14 Open "Q4" Output Isolator Switch.

15 Open "Q2" Static Bypass Switch.


Observe that the LCD screen panel
16 turned OFF including the control
supply.
Note: Failure to follow breaker switching procedure will result to Load
Shutdown and equipment damage.

Note: Closing Q1 will automatically turn on


the INVERTER and the unit will shift to UPS
Mode.

Ensure that after approximately 30


seconds, the Green "Load on Inverter"
LED is lit and the bypass LED has
extinguished.

Close Main Battery Circuit Breaker.

Select "Measurements" in the control


10 panel and verify parameters for Input,
Output and Battery.

11 Unit is now on UPS Mode.

Facilities
Illustration
Technician

WARNING: Wait 5 minutes for the internal D.C. bus bar capacitors to
discharge.

Revision No.
A

Revision Date
May/04/2012