Академический Документы
Профессиональный Документы
Культура Документы
TABLE OF CONTENTS
SECTION
PAGE NO.
1.0 GENERAL
1.1
1.2
1.3
Introduction
Scope
Units Of Measurement
5
5
5
5
3.0 LOADS
8
10
11
11
12
12
13
15
15
15
5.0 DESIGN
5.1 Concrete Works
5.1.1 Materials
5.1.2 Loads
5.1.3 Load Combinations
5.1.4 Design
5.1.5 Deflection in slabs & beams
5.1.6 Clear Cover to Reinforcement
5.1.7 Anchorage & Lap lengths
5.1.8 Steel fabric reinforcement
5.2 Foundations
16
16
16
17
17
20
20
21
21
22
23
23
24
25
25
25
25
26
26
26
26
26
26
27
27
29
29
31
31
31
33
33
33
34
1.0
35
GENERAL
1.1 INTRODUCTION
DANWAY Electrical & Mechanical Engineering Company has been awarded the
contract of building and commissioning of 1 no. 132/11 kV substation for Dubai
Electricity and Water Authority. The substation is referred as,
(I)
1.2 SCOPE
This document describes the general requirements and various design parameters
that need to be considered in the design of buildings/structures and other
BC A
BS 4
BS 12
BS 497
31.
for
Drainage purpose
BS 648
BS 729
BS 743
BS 812
Testing aggregates
BS 882
BS 1610
BS 1722
BS 1881
Testing concrete
BS 2573
BS 2853
hoist blocks
BS 3148
BS 3692
BS 4027
BS 4102
BS 4190
BS 4248
BS 4360
BS 4449
concrete
BS 4466
BS 4848
BS 4483
BS 4514
BS 4550
BS 4660
BS 5075
Concrete Admixtures
BS 5328
BS 5385
BS 5481
BS 5572
BS 5606
BS 5628
BS5930
BS 5950
BS 6031
BS 6150
BS 6297
BS 6367
BS 6399
Part 1
Part 2
Part 3
BS 6431
BS 6515
BS 6949
Bitumen-based coating
BS 8002
BS 8004
BS 8007
BS 8110
BS 8204
In-situ floorings
BS 8301
BS 8666
UBC 97
DIN 1072
DIN 1045
ASHRAE
Road Note 29
ASTM A775
& A775M
3.1
LOADS
3.2
DEAD LOADS
Dead Loads shall comprise of the weight of the structure including weights
of walls, floors, roof, finishes, and services such as ducts, pipe work etc., and any
other permanent construction. For design, the following weights of materials will be
considered.
Cement sand screed
24.00 kN/m3
25.00 kN/m3
12.00 kN/m3
Structural Steel
78.50 kN/m3
0.20 kn/ m2
Roof Tile
24.00 kN/m3
16.00 kN/m3
16.00 kN/m3
21.00 kN/m3
Plaster
20.00 kN/m3
0.22 kN/m2
0.56 kN/m2
2.00 kN/m2
1.0 kN/m2
0.5kN/m2
0.15 KN/m2
water
10.0 KN/ m3
** Superimposed dead load on all floors shall be considered based on the thickness,
screed and other equipment foundations/loads acting on the respective floors.
** Partition wall should be supported on beams
0.25*16
= 4 kN/m2
0.04*20
= 0.8kN/m2
Total
= 4.8kN/m2
0.2*21
=4.2 kN/m2
0.04*20
= 0.8kN/m2
Total
= 5 kN/m2
0.2*16
=3.2 kN/m2
0.04*20
= 0.8kN/m2
Total
= 4.0kN/m2
0.1*21
=2.1 kN/m2
0.04*20
= 0.8kN/m2
Total
= 2.9kN/m2
20mm thk)
i)
ii)
Masonry Loads in main building fire pump room, Security room & other structures.
Accessible roof
Inaccessible roof&
1.50 kN/m2
IDT & ET roof truss
Equipment Loads on roof (Which ever Minimum 5kN/m2
or
As
per
is greater).
Manufacturers Specification.
Additional loads on platform next to 5kN/m2
equipment lifting openings
3.2.2 First Floor Loads
5.0 kN/m2
covers.
Capacitor Bank Room
5.0 kN/m2
10.0 kN/m2
10.0 KN/m2
33.33kN/m2
or
100
load,whichever is critical.
KN
Point
3.2
Basement Loads
Cable spreader room
5.0 kN/m2
18.0 kN/m3
10.0 kN/m3
The effect of ground water table on the structure will be considered if any. All
hydrostatic & Earth pressure forces will be treated as Dead Load (permanent).
3.5
operated crane of 5 ton capacity ,which one is higher will be considered in the
132 kV GIS room.
e. I-beam supporting the 2T Capacity monorail in the Fire pump room and Off
loading platform area of Main building shall be calculated and designed for the
specified load.
3.6 WIND LOADS
Wind loads are calculated in accordance with British Standard BS - 6399 Part 2
(Amendment 2002 )
Site wind speed, Vs = Vb x Sa x Sd x Ss x Sp
Where,
Basic wind Speed,Vb
Altitude factorSa
= 1 + 0.001 Ds
= 5.0
Direction factor, Sd
= 1.0
Seasonal factor,Ss
= 1.0
Probability factor, Sp
= 1.0
= Vs x Sb
qs = 0.613 Ve2
p = pe pi
pe =
qsCpeCa
pi =
qsCpiCa
Cpe = External pressure co-efficient for building surfaces given sec 2.4 and 2.5
Cpi = Internal pressure co-efficient for building surfaces given sec 2.6
Cp = Net pressure co-efficient for the canopy surface or element given in 2.5.9&2.7
Ca = Size effect factor for external/internal pressure sec 2.1.3.4
The Allowable drift against wind shall be maximum height/500
3.7 SEISMIC LOADS
Seismic forces are calculated in accordance with UBC-97, the following factors
shall be applied.
DesignBase Shear
But,
V=
CV x I x W
RXT
V=
V=
CV x I x W
RXT
V=
0.045 W
T
V max =
2.5 x C a x I x W
R
0.25 x 1.00 x W
5.5 x T
V max =
2.5 x C a x I x W
R
V=
2.5 x C a x I x W
R
V max =
2.5 x C a x I x W ,
R
V max =
V max =
V max =
Also,
V min =0.11 x C a x I x W , V min =0.11 x 0.18 x 1.00 x W
V min =0.020 W
The Earthquake Load E, on an element of the structure resulting from combination
of the horizontal component Eh, and Vertical Component Ev,
E=r x Eh + E v
Where, Eh = the earthquake load due to base shear V. Eh shall be evaluated to
provide an equivalent service load for use in BS-8110 system of calculations
Eh=
0.0327 x W
T
Eh=
Eh=
0.045 x W 1.1
x
T
1.4
0.0327 x W 1.1
0.0327 x W 1.1
1.1
x
V=
x
T
1.4
T
1.4
1.4
0.035 W
Eh=
T
Ev = The Load Effect resulting from the Vertical Component of the earthquake
Eh=
Ground Motion.
Ev =0.5 x C a x I x D x
Ev =0.0707 D
r = 1 (Reliability / Redundancy factor.)
1.1
1.4
D = Dead Load
Base shear thus obtained will be distributed at different floor levels as lateral loads
in mutually perpendicular directions.
i. Lateral loads acting in global X- direction
ii.Lateral loads acting in global Z- direction
Note:
Seismic forces will be calculated by ETABS Program either by UBC or 0.07g
whichever is greater. The base shear for wind load and seismic load should be
calculated and the design shall be carried out for the governing load case.
3.8 BLAST LOADS
Transformer, Reactor bay walls will be checked for 5kN/m 2 Blast pressure shall be
considered as acting inside one transformer room only in one moment.
4.0
4.1 RESULTS
All computer generated results such as member forces ,support reactions,
displacements and graphical output of analysis such as bending moment, shear force
diagram, displacement to substantiate the numerical output to be checked.
5.0
DESIGN
5.1 CONCRETE WORKS
5.1.1 Materials
Cement
The cement type for super-structure and sub-structure shall be as per soil report and
the mix design must be as per Dubai Municipality green building requirements.
Coefficient of thermal expansion of
Concrete is 14.5 x (10^-6/(m k))
Concrete
The concrete grade used in the various works shall be as follows:
All structural concrete:
Grade C40 with 20 mm downgraded coarse aggregates for design
Grade C40 with 20 mm downgraded coarse aggregates for construction
Compressive strength of Concrete at 28 days = 40 N/mm2
Precast Concrete:
Grade C40 with 20 mm downgraded coarse aggregates
Compressive strength of Concrete at 28 days = 40 N/mm2
Blinding & Plain cement concrete: Grade C20 with 20mm down graded
coarse aggregates.
Compressive strength at 28 days = 20 N/mm2
Minimum Blinding thickness to be 75mm
a) Reinforcement
Steel reinforcement shall be deformed, type 2, complying with BS 4449. For design,
the specified characteristic strength considered will be as follows:
Grade of steel
Grade 250
: 250
Grade 460
: 460
Diameter of reinforcement
Bar used shall be
The Epoxy coated reinforcement & its relevant parameters shall be as per ASTM
A775/ A775M
b) Welded wire mesh Steel fabric reinforcement will comply with BS 4483. The
preferred range of designated fabric types will be as per table 1 of BS 4483.
c) Material strength & allowable stresses as per BS 8110 Part I & II
For C40 Concrete (For Design purpose):
E Concrete
: 28kN/mm2
E Steel
: 200 kN/mm2
fcu
: C40 (40N/mm2)
fy
: 460 N/mm2
Poissons ratio
: 0.2
: 0.50 x 40
: 3.16 N/mm2
: 0.63 x 40
: 3.98N/mm2
5.1.2 Loads
Various loads to be considered for design shall be as indicated in item 3.0 of this
design criterion.
5.1.3 Load combinations(BS 8110-part-1 & UBC-97)
The following loading combinations shall be considered to
determine
the
maximum stress condition on the structural member. Wind and Seismic loads are
considered not to occur simultaneously.
Seismic load (the mass on which the seismic acceleration is acting) shall be
calculated using the complete weight of the all structural and permanent elements of
= 0.5*0.18*1*D
= 0.09 DL
(For dead and EL combinations) :
UBC Dead load factor = 1.2 DL
Dead load factor
1612.2)
UBC Dead load factor = 0.9DL
Dead load factor
1612.2)
Load combinations for the Service (SLS)
1.0 DL + 1.0 LL
1.0 DL + 1.0 LL + 1.0 SP + 1.0 EPS
1.0 DL + 1.0 LL + 1.0 SP + 1.0 EPS +1.0 Blast load
1.0 DL + 1.0 SP + 1.0 Crane (V*)
1.0 DL + 1.0 SP + 1.0 Crane (H*)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Blast load
1.0 DL + 1.0 SP +1.0 Crane (V) + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (V)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (V) + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 WL+/-X
1.0 DL + 1.0 SP + 1.0 WL+/-Z
1.0 DL + 1.0 LL+ 1.0 SP + 1.0 EPS + 1.0 WL+/-X
1.0 DL + 1.0 LL+ 1.0 SP + 1.0EPS + 1.0 WL+/-Z
1.0 DL + 1.0 LL + 0.72 EL X+Ve + 1.0 SP
1.0 DL + 1.0 LL + 0.72 EL X-Ve + 1.0 SP
1.0 DL + 1.0 LL + 0.72 EL Z+Ve + 1.0 SP
: 1.5
: 1.5
: 1.1
5.1.4 Design
The structure will be designed for Ultimate limit state & Serviceability limit state for
the worst combination of Dead loads, Live loads, Crane loads, Blast loads, Wind
loads and Seismic loads as applicable.
Design of structural elements (i.e. Raft foundation, Slabs, Columns, Beams, RC
Staircase, and Gantry Girder etc) will be performed by using Software, ETABS. &
Excel spread sheets. Manuals are available for inspection / checking.
Allowable crack width adopted for design of surfaces in contact with water or soil is
0.2mm.
5.1.5 Deflection in concrete slabs and beams
Maximum allowable
Code
deflection
Span/250
Comment
For appearance
Span/250 or 20 mm
Damage
to
brittle
non
two values.
Span/350 or 20 mm
Damage
to
brittle
non
For R.C beams, the span/effective depth ratio shall be as per BS8110-1:1997
Table 3.9 in 3.4.6.3.
For the tension & compression reinforcements the span/effective depth ratio
shall be as per as BS8110-1:1997 clause 3.4.6.4 & 3.46.5
UBC 97-CL-1630.10.2.
Allowable drift is h/40 (fundamental time period is less than 0.7).
&
h/50 (fundamental time period is greater than 0.7).
5.1.6 Clear cover to reinforcement
All members in contact with soil or blinding
75 mm
50 mm
40 mm
40 mm
Slab internal
40 mm
40 mm
40 mm
40 mm
50mm
Note*: Cover noted is the outside bar regardless of whether it is main or secondary
reinforcement.
5.1.7 Anchorage lengths & lap lengths
Anchorage length is the additional length of bar required to insert in
another at the junction. Connections transferring stress may be lapped,
welded or joined with mechanical devices. They should be placed, if possible,
away from points of high stress and should preferably be staggered. Laps in
fabric may be layered or nested to maintain the lapped bars in one plane.
The ultimate anchorage bond lengths and lap lengths as multiples of bar size
35 x D
49x D
70 x D
28 x D
35 x D
a) where a lap occurs at the top of a section as cast and the minimum cover
is less than twice the size of the lapped reinforcement, the lap length
should be increased by a factor of 1.4;
b) where a lap occurs at the corner of a section and the minimum cover to
either face is less than twice the size of the lapped reinforcement or,
where the clear distance between adjacent laps is less than 75 mm or six
times the size of the lapped reinforcement, whichever is the greater, the
lap length should be increased by a factor of 1.4;
c) in cases where both conditions a) and b) apply, the lap length should be
increased by a factor of 2.0.
D is the diameter of the reinforcement steel bar& lap location shall be staggered and
shall not be at the same location. The minimum lap should not be less than 50 times
the diameter of the bar.
*****All laps are in staggered*********
5.1.8 Steel fabric Reinforcement
The ultimate anchorage bond lengths as multiples of bar size.
Concrete strength Class 28/40
Reinforcement Grade 460 Deformed Type-2
Tension Anchorage and Lap length
27 x D
38x D
54 x D
22 x D
27 x D
d) where a lap occurs at the top of a section as cast and the minimum cover
is less than twice the size of the lapped reinforcement, the lap length
should be increased by a factor of 1.4;
e) where a lap occurs at the corner of a section and the minimum cover to
either face is less than twice the size of the lapped reinforcement or,
where the clear distance between adjacent laps is less than 75 mm or six
times the size of the lapped reinforcement, whichever is the greater, the
lap length should be increased by a factor of 1.4;
f) in cases where both conditions a) and b) apply, the lap length should be
increased by a factor of 2.0.
The minimum lap should not be less than 250mm .
*****All laps are in staggered*********
5.2
FOUNDATION
5.2.1
Shallow raft foundation is proposed for the main building and fire pump room. The
raft is modeled as finite elements using ETABS software structure as a part of the
main building and is supported on Wrinkler springs and spring constant is obtained
by multiplying the area of influence of the element with the modulus of sub grade
reaction provided in the soil investigation report.
The plate stress contour obtained from analysis is used for the design of raft.
Safe Bearing Capacity of soil considered in the design as indicated are as
recommended in Soil Investigation Report. Structural settlement shall not be more
than 25mm for raft foundation as a total settlement and 10mm as a differential
settlement based on soil report.
Note : Bearing pressure and subgrade modulus are as per approved soil report.
Main
Building,
Min. Depth
of
Foundation
lvl (m)
Shunt 4.0
Recommonded
SBC
(kN/Sq.m)
Soil Subgrade
Modulus
(kN/sq.m/m)
280
30000
02
03
04
05
06
07
08
09
10
11
12
13
14
15
4.0
0.75
2.725
2.0
1.6
1.7
3.0
1.25
4.0
3
2
4.0
2.5
2.0
280
150
225
200
200
200
225
200
280
225
200
280
225
200
30000
18000
25000
22000
22000
22000
25000
22000
30000
25000
22000
30000
25000
22000
The above soil parameters (coefficients at rest, active and passive pressures,
Dry density,and the angle of friction resistance ) are estimated at depth as given
In below table base on the standard penetration test (SPT) values and the
Coefficient of earth pressure is calculated by Rankines method.
5.2.2 Stability
Over all Structural Stability:
The overall structural stability is obtained by limiting the vertical & lateral
deflection at each floor level and the total lateral deflections for the whole structure
for the given worst combination of the loads.
Also the stability against overturning of the structure is obtained by using the
Mr
1.52.0
Mo
MASONRY
Design of all block work will be carried out in accordance with various provisions
of BS5628.Minimum Characteristic strength of non-load bearing block work will
be 7.0 N/mm2.
The various types of block work walls used shall be as follows:
5.4
S.No Location
1
Internal
Description
200 mm thick single leaf hollow block work
External
Toilet partition
DE
TAILING
Detailing of RCC Elements shall be as per British standards of practice.
Preparation of bar bending schedule will conform to BS: 4466.
5.5
STRUCTURAL STEEL
5.5.1 Materials
BS5950-Part1:2000
Grade
or equal to (mm)
16
S275JR
py (N/mm2)
275
40
265
63
255
80
245
100
235
150
225
:180
: 250
c) For any member normally acting as tie but subject to reversal of stress
The slenderness limit for main beams &Resulting from the action of wind
: 350
5.5.4 Deflections
The maximum permissible deflections shall be as specified in table 5 of BS5950 and
as given by crane manufacturer, whichever is critical.
a.
Crane girders:
Crane gantry girders vertical deflection
: Span / 600
: Span / 500
: Span / 750
:Length /180
: Span / 360
: Span / 200
: Height/
300
d. In each story of a building with more than one story (story drift) : height of
story under consideration/300
5.5.5 Loads
Various loads to be considered for design shall be as indicated in item 3.0
5.5.6 Loads Combinations
The load combinations as listed in BS 5950 shall be considered to determine the
maximum stress condition on the structural members.
Load combinations for the ultimate Limit state (ULS)
1.4 DL + 1.6 LL
1.4 DL + 1.6 LL + 1.4 SP + 1.6 EPS
1.4 DL + 1.6 LL + 1.4 SP + 1.6 EPS +1.0 Blast load
1.4 DL + 1.4 SP + 1.6 Crane (V*)
1.4 DL + 1.4 SP + 1.6 Crane (H*)
1.2 DL + 1.2 SP + 1.6 LL+ 1.6 EPS + 1.0 Blast load
1.4 DL + 1.4 SP +1.4 Crane (V) + 1.4 Crane (H)
1.2 DL + 1.2 SP + 1.4 LL+ 1.4 EPS + 1.4 Crane (V)
1.2 DL + 1.2 SP + 1.2 LL+ 1.2 EPS + 1.2 Crane (H)
1.2 DL + 1.2 SP + 1.2 LL+ 1.2 EPS + 1.2 Crane (V) + 1.2 Crane (H)
1.4 DL + 1.4 SP + 1.4 WL+/-X
1.4 DL + 1.4 SP + 1.4 WL+/-Z
1.2 DL + 1.4 SP + 1.4 WL+/-X
1.2 DL + 1.4 SP + 1.4 WL+/-Z
1.0 DL + 1.4 SP + 1.4 WL+/-X
1.0 DL + 1.4 SP + 1.4 WL+/-Z
1.2 DL + 1.2 LL+ 1.2 SP + 1.2 EPS + 1.2 WL+/-X
1.2 DL + 1.2 LL+ 1.2 SP + 1.2EPS + 1.2 WL+/-Z
1.42 DL + 1.1 LL + 1.1 EL X+Ve + 1.6 SP
1.42 DL + 1.1 LL + 1.1 EL X-Ve + 1.6 SP
1.42 DL + 1.1 LL + 1.1 EL Z+Ve + 1.6 SP
1.42 DL + 1.1 LL + 1.1 EL Z-Ve + 1.6 SP
1.09 DL + 1.1 EL X+Ve + 1.6 SP
1.09 DL + 1.1 EL X-Ve + 1.6 SP
1.09 DL + 1.1 EL Z+Ve + 1.6 SP
1.09 DL + 1.1 EL Z-Ve + 1.6 SP
Note : In Seismic load combinations dead load factor as per approved soil
report.
As per UBC-97(Section 1630)
Ev = (0.5*Ca*I*D) = 0.5*0.18*1*D (Ca =0.18, as per approved soil report)
= 0.09DL
(For dead and EL combinations) :
UBC Dead load factor
= 1.2 DL
1612.2)
UBC Dead load factor
Dead load factor
= 0.9DL
= (0.9+0.09)*1.1 = 1.09 DL (1.1 multiplied as per UBC
1612.2)
Load combinations for the Service (SLS)
1.0 DL + 1.0 LL
1.0 DL + 1.0 LL + 1.0 SP + 1.0 EPS
1.0 DL + 1.0 LL + 1.0 SP + 1.0 EPS +1.0 Blast load
1.0 DL + 1.0 SP + 1.0 Crane (V*)
1.0 DL + 1.0 SP + 1.0 Crane (H*)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Blast load
1.0 DL + 1.0 SP +1.0 Crane (V) + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (V)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 LL+ 1.0 EPS + 1.0 Crane (V) + 1.0 Crane (H)
1.0 DL + 1.0 SP + 1.0 WL+/-X
1.0 DL + 1.0 SP + 1.0 WL+/-Z
1.0 DL + 1.0 LL+ 1.0 SP + 1.0 EPS + 1.0 WL+/-X
1.0 DL + 1.0 LL+ 1.0 SP + 1.0EPS + 1.0 WL+/-Z
1.0 DL + 1.0 LL + 0.72 EL X+Ve + 1.0 SP
1.0 DL + 1.0 LL + 0.72 EL X-Ve + 1.0 SP
1.0 DL + 1.0 LL + 0.72 EL Z+Ve + 1.0 SP
1.0 DL + 1.0 LL + 0.72 EL Z-Ve + 1.0 SP
1.0 DL + 0.72 EL X+Ve + 1.0 SP
1.0 DL + 0.72 EL X-Ve + 1.0 SP
1.0 DL + 0.72 EL Z+Ve + 1.0 SP
1.0 DL + 0.72 EL Z-Ve + 1.0 SP
DL = Dead load , LL = Live load , SP = Soil pressure, EPS = Earth pressure
surcharge
WL = Wind load, EL = Earthquake load
V* = Vertical crane load (Static wheel loads plus and allowance for dynamic effects)
H* = Horizontal Crane Loads
5.5.7 Connections:
All the Braced, Splice, shear and moment connection for the structural elements
shall be designed for the all possible worst load combinations as per BS5950.
5.5.7.1 Ordinary bolts:
Ordinary bolts shall conform to various provisions of BS 3692 & BS 4190
Minimum number of bolts at any joint should be two
Shear capacity:
Shear capacity, Ps
Where ps
=Shear strength,
As
= Shear area
Bearing capacity:
The bearing capacity of bolt
Where,
Pbb
= nominal diameter,
Shear strength, ps
160
Bearing strength, 460
N/mm2
(Ut1000N/mm2)
0.40 Uf
0.70 ( Uf + Yf )
375
1000
Pbb
Tension strength, pt 240
560
0.7 Uf but Yf
Where, Yf = Specified minimum yield strength of the bolts
Uf= Specified minimum ultimate tensile strength of the bolts
Note: Bearing strength of connected parts for ordinary bolts in clearance holes,
Bearing Strength pbs of connected plates:
(Refer Table 32 of BS 5950-2000)
Steel Grade
S 275
S 355
S 460
Other grades
Electrode Classification
35 N/mm2
42 N/mm2
50 N/mm2
220
220b
220b
220a
250a
280
220a
250
250b
Other types
6.0
provided with fixed Spray system shall be connected via storm water pipe to storm
water drainage system. The rooms shall be sloped towards collection point
where storm water pipe with floor tarp shall be provided. Basement drainage
shall be connected to storm water drainage network via submersible pumps.
Capacity of the pumps and type of the pumps shall be as per DEWA Specification.
fire pipe trench shall be provided with independent soak away.
6.3 Oil water drainage system:
The oil water from main transformer rooms, Earthing transformer rooms
shall be mobilized to vehicular tank trucks via pipe and manhole network.
Fire pump house Diesel tank drainage system shall be connected to oil man holes
fire pump Deluge spray system drain shall be connected to storm water network.
6.4 The potable indoor water drainage system:
Potable water layout & arrangement shall be as per approved drawings.
Transfer pumps shall be provided for lifting potable water from ground water
tank to roof storage tank and shall be considered for lifting water to overhead fire
water tanks.
type.
All
the
mm
thick
interlocking
tile
heavy
with
duty
the
the
0.5
mm
thick
Waterproofing
Water proofing details will be as per DEWA specification Revision-14
9.
Road base
Provide one layer of road base material (each 200mm thick) below the All
foundations compacted to 98% Maximum Dry Density (MDD).
10.
Boundary Wall
If road is within 2 m from compound wall then, Surcharge of SLW 60 as
DIN 1072 will be considered in the analysis & design subject to minimum of 33.3
kN/m. The analysis and design will be carried out for the worst combination of
earth pressure & surcharge. Passive resistance of soil inside the plot will be
considered as applicable.
Expansion joint shall be provided at columns after approximately 3 span
(considering each span of 3m). Height of boundary wall above finished pavement
level to be as per approved drawing. The minimum required degree of compaction
shall be, tested according to modified proctor density: 98% for embankment areas.
The height of the boundary wall shall be 3000mm measured from the finished
placed level inside the substation.