General catalogue

Epoxy resin and silicon rubber insulators

Contents

Introduction

02

Insulators for indoor use

04

Insulators for outdoor use

27

Products for SF6 insulated switchgear

39

Introduction
Veneta Isolatori
is a leader company specialised in the production of MV epoxy resin insulators for electrical and
electromechanical industry. The company was established in 1974, in 1990 it became a subsidiary
of COMEM S.p.A, leader in oil transformer component and solution. In 2009 all the activities were
moved to a new factory located in Ceggia close to Venice.
The long experience achieved by Veneta Isolatori gave the possibility to develop a wide range of
products, having suitable and tested electrical and mechanical technical characteristics. Recently
the company has also developed insulators in silicon rubber for outdoor installation. Nowadays
Veneta Isolatori represents a reference point for many of electrical companies, that use Veneta
Isolatori partnership for the development and realisation of insulators according to their own
basic design. The export, almost 50% of the total production, cover a winde range of countries
and MV application.

Certification
The Quality System conforms to the ISO 9001 Standards, the Environmental Management System
conforms to the ISO 14001 Standards and the Health and Safety Management System conforms to
the OHSAS 18001 Standards, also regarding application in building site activities. All the systems are
certified by an external independent organisation.
Laboratories
The Unit has internal laboratories equipped with state-of-theart apparatus for carrying out tests on
materials, experimental, climatic, mechanical life, dielectric and partial discharge.
Operation
Each design parameter is known, measured and recorded for each piece of insulator produced, so
that their functional suitability can be declared in accordance with what is prescribed in the Standards.
Production is also supported by lines which operate using the fabrication system with functional blocks.
Thanks to this innovative system, the production lines can outfit each typical unit with maximum
efficiency and speed.

Insulators for indoor use

ISA

IPA

DC - DCP

DCL

10

SF - SC

12

SCD - SCB - SDY

14

IPAN

16

PSE/PSL

18

PRC

20

PRB

22

IPAR - ISOF - IPA

24

Type ISA

Low voltage post insulators for indoor installation

General characteristics
Post insulators made of epoxy resin (EP UL94V0) or
polyesther reinforced with fiberglass (UP FG), suitable for
indoor application with internal metal fitting. These insulators
are particularly suitable to be used as single supports for
bus-bars, fuses and for other equipment.
Application
For indoor applications with working condition at max.
operating temperature of 160 C (epoxy resin - EP UL94V0)
and 130 C (polyesther - UP FG)
Working voltage
From 0,4 up to 2 kV
Reference standards
IEC 216 - DIN 53452 - DIN 53455
Identification
Fig.

Type

Drawing

ISA 20/20 M5

U2215

2a

ISA 30/30 M8

U3306

2b

ISA 30/30 M6

ISA 40/40 M10

Fig. 1

U3308

Technical data
Ultimate
tensile
Material
stress
N ( 10%)

Maximum
operating
voltage
kV

Ultimate
bending
stress
N ( 10%)

0,4

1500

2500

4000

8000

Color

Weight

EP UL 94V0

RAL 9005

0,01

EP UL 94V0

RAL 9005

0,06

kg.

P3308

0,75

3000

6000

UP FG

RAL 7030

0,05

U4410

7000

12000

EP UL 94V0

RAL 9005

0,13

P4410

5000

10000

UP FG

RAL 7030

0,11

Fig. 2a

Fig. 2b

Fig. 3

Type IPA

post insulators for indoor installation

General characteristics
Epoxy resin post insulators, for indoor application, with internal metal fitting.
These insulators are particularly suitable to be used as single supports for conductors, for
fuses and for other equipment (as switchgears).
Application
For indoor installation with working condition at T max. 100 C.
Working voltage
From 12 up to 36 kV
(40,5 kV available on request)
Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (Fascicolo S/663)
IEC 60137
Commercial code
1G101 + drawing (example IPA 7,2/4000 commercial code = 1G10107204)
Identification

Mechanical data

Maximum
operation
voltage

Lightning
impulse
voltage
whitstand

Dry power
frequency
voltage
whitstand

kV

kV

kV

Ultimate
bending
stress

Technical data

Maximum
deflection
difference
between 20% Creepage
and 50% of distance
the specifield
load

Reference to
IEC
designation

Type

Drawing

JO 4 - 60

IPA 7,2/4000

07204

JO 8 - 60

IPA 7,2/8000

07208

JO 4 - 75

IPA 12/4000

10010

JO 8 - 75

IPA 12/8000

10020

JO 16 - 75

IPA 12/16000

10025

16000

>230

JO 8 - 95

IPA 17,5/8000

20020

8000

>260

JO 16 - 95

IPA 17,5/16000
IPA 24/4000
Standard
Enel DJ1053
IPA 24/3000
Standard
Enel DJ1056
IPA 24/4000

20026

JO 4
125

Electrical data

7,2

60

28

12

75

35

N
4000
8000

17,5

95

45

16000

mm

kg.

1,5

>150

0,6
0,7

>235
2

2,7

>175

>300

125

3,2

55

1,1
2,2
1,1

4000
24

0,8
1,5

>360

24210
24220

Weight

mm

4000
8000

Fins

1,2

>370

24225
1,6

JO 8 - 125

IPA 24/8000

30030

8000

>350

JO 10 - 125

IPA 24/10000

30026

10000

>400

JO 4 - 170

IPA 36/4000

40010

4000

>520

13

1,8

JO 8 - 170

IPA 36/8000

40012

>520

12

2,9

JO 10 - 170

IPA 36/10000

40026

>570

10

3,4

36

170

75

8000
10000

2,6

AccessorIes
Nichel-plated male reduction.

Drawing

Drawing

3012

3016

Technical data
h

Isnulator
height

mm. (+-1)
95
130

175

d1

Maximum
Upper
nominal
threaded
diameter of centre
hole
insulating
(tapped)
part

83

d2

t2

d3

t3

D1

D2

Hole
depth
d1

Base
threaded
centre hole
(tapped)

Hole
depth
d2

Distance
between
base face
and lower
threaded
end

Auxiliary
upper
threaded
hole
(tapped)

Hole
depth
d3

Distance
between
threaded
holes
d3

Maximum
diameter
base face

Maximum
diameter
upper face

mm. (min.)

mm.

mm.

mm.

mm. (min.)

mm.
82

t1

M12

18

M12
M16

25

M12

18

M16

25

116

M16

25

M20

32

83

M12

18

M16

25

118

M16

25

M20

32

M16

25

75

mm. (min.)

mm.

18

M8

15

46

14

70

55
70

70

65

75

65

M6

15

36

36

M10

20

46

100

91

35

M6

15

36

76

62

36

M10

20

46

100

91

M6

15

36

80

54,5

77

70

100

90

80

55

94

76

100

90

18

210
80
225

80
310

98
110

35

18

93
110

25
M12

M16

25

18
M20

32

M12

18

M16

25

M16

25

M20

32

42
32
60
42

M10

20

46

M6

15

36

M10

20

46

Type DC - DCP

Capacitive insulators with low voltage lower reading connection

General characteristics
Epoxy resin post insulators with capacitive devider for the reading of the voltage.
Manufactured with internal metal fitting, they can be equipped with couplings and low
voltage light signal box.
These insulators are mainly suitable to be used as insulated supports of equipment, bus bar
or fuses.
Safety information
The insulators can be equipped with:
- S afety valve type ATS drawing 4500 that, in case of incoming voltage higher than 600 V,
connect to earth the system;
- S ignal box type SF 5600, SC 5583, SCD 5500, and SCB 5590 that, through a gas arrester
installed inside, in case of incoming voltage higher than 600 V, automatically connect to
earth the system.The heart connection system is self-resetting.
Application
Indoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
(40,5 available on request)
Reference standards
IEC 60137
Commercial code
1G103 + drawing (example DC 10 commercial code = 1G10350010)

Identification

Type

Mechanical data

Electrical data

Maximum Lightning Dry power


Drawing operation impulse frequency Capacivoltage
voltage
tance
voltage
whitstand whitstand

Ultimate
bending
stress
(PO)

Insilator
height

D1

D2

Technical data

Maximum
nominal
Diameter Diameter diameter
Creepage
of base of upper
of
distance
face
face
insulating
part

Fins

Weight

kV

kV

kV

pF

mm.

mm.

mm.

mm.

mm.

kg.

DC 10

50010

12

75

35

220

3000

130

75

65

75

175

0,8

DC 15

50012

17,5

95

45

150

3000

175

76

62

83

260

1,1

DC 20

50013

24

125

55

150

3000

225

69

62

78

355

1,3

DC 30

50021

36

170

75

75

3000

310

80

55

80

520

13

1,8

DCP 10

50015

12

75

35

220

5000

130

70

65

75

175

0,8

DCP 15

50017

17,5

95

45

150

5000

175

76

62

83

260

1,1

DCP 20

50018

24

125

55

150

5000

225

76

69

85

350

1,6

DCP 30

50019

36

170

75

75

5000

310

94

76

98

520

12

2,9

type DC

type DCP

Upper

Base

Connection type ATS 4482

Insulator gaps
type ATS
Drawing 4500
Washer
Steework hole
16,5 mm

Grow

Screw M12/14
Safety valve for
overvoltage protection

Grow

Tc M4

Voltage presence indicators

Standard
ENEL
DY 811
type SF

type SC

type SCB

type SCD

type SDY

drawing 5600

drawing 5583

drawing 5590

drawing 5500

drawing 5811

Type DCL

Capacitive insulators with low voltage side reading connection

General characteristics
Epoxy resin post insulators with capacitive devider for the
reading of the voltage
Manufactured with internal metal fitting, they can be
equipped with couplings and low voltage light signal box.
These insulators are mainly suitable to be used as insulated
supports of equipment, bus bar or fuses.
Safety information
The insulators can be equipped with:
- Safety valve type ALS drawing 4700 that, in case of
incoming voltage higher than 600 V, connects to earth the
system;
- Signal box type SF 5600, SC 5583, SCD 5500 and SCB
5590 that, through a gas arrester installed inside, in case of
incoming voltage higher than 600 V, automatically connect
to earth the system.The heart connection system is
self-resetting.
The DCL 24/I capacitive insulator, that utilise epoxy resin as
dielectric; it has low capacitance condenser and low voltage
outlet.
Application
Indoor installation at max working temperature of 85 C.

Reference standards
IEC 60137 (electrical tests)
Enel standard DJ 1054 - DJ 1550 (DCL 24/I)

Working voltage
From 12 to 36 kV

Commercial code
1G105 + drawing (example DCL 10 commercial code =
1G10550030)

Identification
Type

DCL 10

DCL 15

DCL 24

DCL 24/I
Standard
Enel DJ 1054

Electrical data

Outlet Type

Drawing

50030

Technical data

Maximum
operation
voltage

Lightning
impulse voltage
whitstand

Dry power
frequency
voltage
whitstand

Capacitance

kV

kV

kV

20% pF

12

75

35

220

Cable type

Model of
comatible
signal box

50032

50031

SF 5600

50070

SC 5583

50072

50071

17,5

95

45

150

standard

SCB 5590
SCD 5500

50040

50041

SDY 5811

50042

52054

52050

52055

SDY 5811

50310

SC 5583

50311

50312

24

125

55

150

24

125

55

SCB 5590
RG 58

SCD 5500
SF 5600

DCL 30

36

170

75

75

standard

SCB 5590
SCD 5500
SDY 5811

10

With type C outlet it is possible to connect


safety valve type ALS drawing 4700 for overvoltage protection

L.V. Side reading connection type

Connection 1G10604580

Voltage presence indicators

Standard
ENEL
DY 811
type SF

type SC

type SCB

type SCD

type SDY

drawing 5600

drawing 5583

drawing 5590

drawing 5500

drawing 5811

Mechanical
data

Identification

D1

D2

D3

Insilator
height

Diameter
of base
face

Diameter
of upper
face

Quote
D3

Creepage
distance

Fins

Weight

mm.

mm.

mm.

mm.

mm.

kg.

4000

130

74

53

87

165

0,9

4000

175

74

53

87

245

1,1

3500

225

74

55

87

350

1,4

3500

225

74

55

87

350

1,75

3000

310

80

55

90

490

13

2,2

Ultimate
bending
stress
Type

DCL 10

DCL 15

DCL 24

DCL 24/I
Standard
Enel DJ 1054

DCL 30

Outlet
type

Drawing

50030

50032

50031

50070

50072

50071

50040

50041

50042

52054

52050

52055

50310

50311

50312

Technical data

11

Type SF - SC

Voltage presence indicators

General characteristics
The voltage presence indicators are devices used to supply information about the main
circuit status inside the equipment where the devices are installed. To each lamp placed
inside the indicator (L1 L2 L3) corresponds one phase of the input line. The line voltage
presence is indicated by switching of the relevant lamp. The signal of voltage presence
necessary to switch the lamps is sourced out by a capacitive coupling with an insulator
equipped with capacitive output.
Application
In MV cubicles for operating voltages from 1 to 36 kV.

Type SF
The indicator SF is a light signal device made of one single
fix part. The indicator is equipped with a safety system,
composed of one gas arrester for each phase, which
connects the system to ground in case of overvoltage
> 600 V. The arresters are self-resetting, this means that at
the end of the discharge the device will start again to function
normally.

Capacitive source

Type SC
The indicator SC is a light signal device made of one fix part
and one mobile and removable part.The lamps are placed
in the mobile part. The indicator is equipped with a safety
system, composed of one gas arrester for each phase, which
connects the system to ground in case of overvoltage > 600
V. The arresters are self-resetting, this means that at the
end of the discharge the device will start again to function
normally.

Insulator type

Maximum
operation voltage

Nominal
capacitance

Indicator

kV

pF 20%

kV

SF 5600 - SC 5583
Voltage on indicator at
max. operating
voltage
kV
V

DC - DCP - DCL 10

12

220

1,2

150

DC - DCP - DCL 15

17,5

150

1,1

130

DC - DCP - DCL 20/24

24

150

12

100

DCL 24/I

24

75

DC - DCP - DCL 30

36

75

10

145

Pulsating lamp
lightning at

Fix lamp
lightning at

The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.

12

type SF 5600

Steelwork Lay-Out

Front side

Back side

type SC 5583
Back side

Steelwork Lay-Out

Back side

Mobile part

Complete set

Back side

13

Type SCD - SCB - SDY


Voltage presence indicators

General characteristics
The voltage presence indicators are devices used to supply
information about the main circuit status inside the equipment
where the devices are installed. To each lamp placed inside
the indicator (L1 L2 L3) corresponds one phase of the input
line. The line voltage presence is indicated by switching of the
relevant lamp. The signal of voltage presence necessary to
switch the lamps is sourced out by a capacitive coupling with
an insulator equipped with capacitive output.
Application
In MV cubicles for operating voltages from 1 to 36 kV.
Type SCD
The indicator SCD is a light signal device made of one single
fix part. Below each lamp there are relevant contact holes
which allow to verify the phase accordance between two or
more equipments, through the use of a phase accordance
device DCF 6500. The indicator is equipped with a safety
system, composed of one gas arrester for each phase, which
connects the system to ground in case of overvoltage >
600 V. The arresters are self-resetting, this means that at the
end of the discharge the device will start again to function
normally. The signal device SCD can be used even to read a
low input signal.

Type SCB
The indicator SCB is a light signal device made of one fix part
and one mobile and removable part.The lamps are placed
in the mobile part. The indicator is equipped with a safety
system, composed of one gas arrester for each phase, which
connects the system to ground in case of overvoltage > 600
V. The arresters are self-resetting, this means that at the The
signal box SCB is used to read a low input signal.

Phase accordance device DCF 6500


Thanks to the phase accordance device DCF 6500 it
is possible to verify if the lamps L1 (or L2 or L3) of two
indicators SCD 5500 placed on two different equipments
are connected to the same phase. When the phases are in
accordance the lamp of the device DCF 6500 is off, while in
case of non accordance of the phases the lamp is on.

Type SDY
The signal device SDY is realized according to ENEL (National
Power Company) specification DY 811. It is made of 1 front
board base and of 3 mobile parts, one for each phase,
equipped with removable and separated light indicators.
The fix part is suitable to be connected with RG DAT
monitoring device, according to Enel specification DY 1059.

Capacitive source

Indicator

SCD 5500 - SCB 5590 - SDY 5811


Voltage on indicator at
Fix lamp
max. operating
lightning at
voltage

Insulator type

Maximum
operation voltage

Nominal
capacitance

Pulsating lamp
lightning at

kV

pF 20%

kV

kV

Volts

DC - DCP - DCL 10

12

220

2,5

50

DC - DCP - DCL 15

17,5

150

45

DC - DCP - DCL 20/24

24

150

13

38

DCL 24/I

24

3(*)

36

DC - DCP - DCL 30

36

75

50

The above mentioned values were reached by using a standard cable (3 meters length) to connect the capacitive insulator and the voltage indicator.
The values have a 20% variability.
(*) To reach the pulsation level required by DY 811 homologation it is necessary to use a screened RG 58 cable to connect the capacitive insulator DCL
24/I and the voltage indicator SDY 5811.

14

tipe SCB 5590

type SCD 5500


Back side

Steelwork Lay-Out
Back side

Mobile part

Steelwork lay-out

Back side

Front side

Complete set

serie SDY

Steelwork Lay-Out
Back side

15

Type IPAN

Bushing for indoor use

General characteristics
12 36 kV epoxy resin bushing insulators.The insulators can be fitted with copper bars
designed from 250 up to 2000 A.
They are equipped with internal metal fittings for installation on the relevant frame and with
brass nuts and washers for fastening of phase connectors.
Application
Indoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
Reference standards
IEC 60137 (electrical tests).
Commercial code
1G107 + drawing (example IPAN 10/250 commercial code = 1G10781010)
Identification

Electrical data
Maximum
operation
voltage

Nominal
current

Dry power
frequency
voltage
whitstand

Lightning
impulse
voltage
whitstand

Creepage
distance

Fins

kV

kV

mm.

Type

Drawing

IPAN 10/250

81010

250

IPAN 10/400

81011

400

IPAN 10/630

81012

630

IPAN 10/800

81240

IPAN 10/1000

81014

1000

IPAN 10/1500

81015

1500

IPAN 10/2000

81016

2000

IPAN 15/250

82010

250

IPAN 15/400

82011

400

IPAN 15/630

82012

630

IPAN 15/800

82240

IPAN 15/1000

82014

1000

IPAN 15/1500

82015

1500

IPAN 15/2000

82016

2000

10,4

IPAN 20/250

83010

250

3,5

IPAN 20/400

83011

400

IPAN 20/630

83012

630

IPAN 20/800

83240

IPAN 20/1000

83014

1000

IPAN 20/1500

83015

1500

IPAN 20/2000

83016

2000

12

IPAN 30/250

84010

250

9,8

IPAN 30/400

84011

400

10,4

IPAN 30/630

84012

630

11,2

kV

16

Technical data

12

17,5

24

800

800

800

800

Weight
kg.
2,3

220

3+3

2,5
2,8

35

75

6
230

4+4

7
8,2
9
3,1

390

3,4
3,8

45

95

6+6

6,8
8

330

9,5

480

3,8
4,5

55

125

8+8

440

75

170

620

7,5
10,9

IPAN 30/800

84013

IPAN 30/1000

84014

1000

14,1

IPAN 30/1500

84015

1500

16,2

IPAN 30/2000

84016

2000

17,9

36

8+8

12,3

Steelwork holes Lay-Out

Identification
Type

Drawing

IPAN 10/250

81010

IPAN 10/400

81011

IPAN 10/630

81012

IPAN 10/800

81340

IPAN 10/1000

81014

IPAN 10/1500

81015

Dimensional data
A

140

140

280

106

75

87

380
M8x20

8,5
175

175

350

134

110

126

470

R
Diameter

Pitch

12

1,5

16

1,5

20

1,5

24

30

36

IPAN 10/2000

81016

42

IPAN 15/250

82010

12

1,5

IPAN 15/400

82011

16

1,5

IPAN 15/630

82012

20

1,5

IPAN 15/800

82240

24

IPAN 15/1000

82014

30

IPAN 15/1500

82015

36

IPAN 15/2000

82016

42

IPAN 20/250

83010

12

1,5

IPAN 20/400

83011

16

1,5

IPAN 20/630

83012

20

1,5

24

30

36

205

205

410

106

75

87

510
M8x20

8,5
215

215

430

134

106
260

260

520

110

75

126

87

550

620
M8x20

8,5

IPAN 20/800

83240

IPAN 20/1000

83014

IPAN 20/1500

83015

IPAN 20/2000

83016

42

IPAN 30/250

84010

12

1,5

IPAN 30/400

84011

16

1,5

IPAN 30/630

84012

20

1,5

24

30

36

42

IPAN 30/800

84013

IPAN 30/1000

84014

IPAN 30/1500

84015

IPAN 30/2000

84016

134

110

126

670

940
405

405

810

10,5

160

120

118

M10x20
960

Lenght
45

55

45

55

45

70

60

70

17

Type PSE - PSL

Bushing for indoor/outdoor use

General characteristics
12 36 kV cicloaliphatic resin bushing insulators.The insulators can be fitted with copper
bars designed from 250 up to 1000 A. They are equipped with internal metal fittings for
installation on the relevant frame and they are supplied completed with:
B rass nuts and washer for fastening of phase connectors
O-Ring gasket
Screws and nuts for assembling of the bushing on the metallic frame
Application
Outdoor installation at max working temperature of 85 C.
Working voltage
From 12 to 36 kV.
Reference standards
IEC 60137 (electrical tests).
Commercial code
1G110 + drawing (example PSE 10/250 commercial code = 1G11071010)
Identification

Electrical data
Maximum
operation
voltage

Nominal
current

Dry power
frequency
voltage
whitstand

Lightning
impulse voltage
whitstand

Creepage
distance
side (B)

kV

kV

mm.

Weight

Type

Drawing

PSE 10/250

71010

PSE 10/400

71011

PSE 10/630

71012

PSE 10/800

71013

800

4,2

PSE 15/250

72010

250

4,5

PSE 15/400

72011

400

PSE 15/630

72012

PSE 15/800

72013

800

5,8

PSE 20/250

73010

250

5,7

PSE 20/400

73011

400

PSE 20/630

73012

PSE 20/800

73013

800

7,3

PSE 30/250

74010

250

10,7

PSE 30/400

74011

PSE 30/630

74012

PSE 30/800

74013

800

13

PSE 30/1000

74014

1000

14,7

kV

PSl 20/400
Standard Enel

18

Technical data

73016

250
12

17,5

24

400
630

630

630

35

45

55

75

95

125

350

540

740

400
36

24

630

400

kg.
3,2
3,4
3,8

4,8
5,3

6
6,7

11,2
75

55

170

125

860

740

12

9,6

Steelwork holes Lay-Out

Identification

Dimensional data
R

Type

Drawing

A1

PSE 10/250

71010

mm.

mm.

mm.

mm.

mm.

mm.

mm.

mm.

mm.

mm.

mm.

PSE 10/400

71011

PSE 10/630

71012

PSE 10/800

71013

24

PSE 15/250

72010

12

1,5

PSE 15/400

72011

16

1,5

20

1,5

96

163

20

20

164

232

280

415

8,5

8,5

130

130

114

114

88

88

87

87

380

510

M8x20

M8x20

Diameter

Pitch

Threded
lenght

mm.

mm.

mm.

12

1,5

16

1,5

20

1,5

PSE 15/630

72012

PSE 15/800

72013

24

PSE 20/250

73010

12

1,5

PSE 20/400

73011

16

1,5

PSE 20/630

73012

20

1,5

PSE 20/800

73013

24

PSE 30/250

74010

12

1,5

PSE 30/400

74011

16

1,5

PSE 30/630

74012

20

1,5

PSE 30/800

74013

24

PSE 30/1000

74014

30

16

1,5

PSl 20/400
Standard Enel

73016

235

20

305

560

8,5

130

114

88

87

660

M8x20

940
365

40

405

810

10,5

159

160

120

M10x20

118
960

235

325

305

865

8,5

130

114

88

87

965

M8x20

45

45

45

60

70
45

19

Type PRC

Protection insulators

General characteristics
Epoxy resin protection insulators, bell shaped, with internal metal fitting.
Application
Indoor application with working condition at T max. 100 C.
Working voltage
From 12 to 36 kV.
Commercial code
1G123 + drawing (example PRC 12 commercial code = 1G12386010)
Technical data

PRC 12 PRC 17 PRC 24 PRC 36

Drawing

86010

87015

88020

89030

H (mm.)

170

230

290

350

H1 (mm.)

275

335

395

455

D (mm.)

145

140

135

130

Maximum operation voltage (kV)

12

17,5

24

36

Dry power frequency


voltage whitstand (kV)

38

50

50

75

Lightning impulse voltage


whitstand (kV)

75

95

125

170

Creepage distance (mm.)

210

280

345

430

Fins (N)

Weight (kg.)

Tightening torque M10 (Nm)

30

30

30

30

Creepage
distance

Steelwork holes Lay-Out

20

21

Type PRB 24-36 kV


Air-air bushing for indoor use

General characteristics
The PRB bushings can be used as medium voltage inlet for indoor air insulated devices
such as switchgears, in particular for applications in quite small machines.
The bushings are realized on the one side with a coupling interface in accordance with
EN 50180-50181 (DIN 47636; HN 52-S-61) standards. This type of interface allows a
connection with the relevant moving connector. On the other part the sheded side allows a
bare electrical wire connection.
Accessories
Plastic cap for coupling interface protection.
Only on request, alluminium flange suitable to fix the bushing to the steelwork.
The fixing flange is necessary for the 400A version for mobile connector fastening.
Working voltage
24-36 kV
Reference standards
IEC 60137 (electrical tests)
EN 50180-50181 (DIN 47636; HN 52-S-61)
Commercial code
1G1240 + drawing (example PRB 24/400 commercial code = 1G12402430)

Identification
Fig.

22

Type

Electrical data

Drawing

Maximum
operation
voltage

Nominal
current

Lightning
impulse
voltage
whitstand

kV

kV

Standards
Dry power
frequency
voltage
whitstand
kV

PRB 24/400

2430

24

400

125

55

PRB 24/630

2431

24

630

125

55

PRB 36/630

3670

36

630

170

75

Coupling
type

EN 50180
EN 50181
DIN 47636
EN 50180
EN 50181
DIN 47636
EN 50180
EN 50181
DIN 47636

Electrical
tests

Connection Creepage
type
distance

Weight

mm.

kg.

IEC 137

Sliding
contact

380

2,65

IEC 137

M16

380

2,65

IEC 137

M16

730

4,2

Assembling instructions
Bushing insulator PRB
Prepare the holes on the body of the tank as indicated in the steelwork holes Lay-out. Remove the paint, or any insulating coat
in the area of fixing holes, in order to guarantee a correct earth connection of the bushing.
Moreover, make sure that the surface where the bushing is placed is without any type of roughness or unevenness. It must be
completely clean in order to guarantee a perfect tightness. It is recommended to use the fixing flange in order to strengthen the
area where the bushing is fixed to the tank. For 400A version the use of the flange is necessary for mobile connector fastening.
Place the flange, when used, and tighten the 3 fixing screws M6, together with their relevant washers, with a tightening force
value of 911 Nm. The tightening operation must be done crosswise. The lower connection (M16) must be fastened with a
tightening force value of 90100 Nm.
During mounting operations the plastic protective cap must be fitted and pressed right down on the bushing, in order to avoid
faults caused by dirt or accidental scratching of the interface.

Fig. 1

Fig. 2

Color RAL 3013

Color RAL 3013

23

Type IPAR - ISOF - IPA

Epoxy resin insulators for rotative switchgear 24 kV

IPAR
Three phase rotating bushing block with recessed
metal fitting for assembling on the steelwork.
Commercial code
1G108 + drawing (example IPAR 65012 commercial code = 1G10865012)
ISOF
Drawing: 69020
Conductor connection insulator with air room for arc estinguishing.
Its equipped with internal metal fitting for the assembling on the steelwork and of the upper
contact.
Reference standards
1G10869020
IPA
Drawing: technical at page 6
Conductor connection insulator with internal metal fitting for the assembling on the
steelwork and of the upper contact.
Application
For indoor use, vertical and horizontal installation.

IPA

IPAR

ISOF

24

Identification
Fig.

Type

Drawing

20 mm.

Alluminium

65012

Copper - and
silver plated
alluminium

67012

Alluminio

65017

Copper - and IPAR


silver plated
alluminium

Alluminium

67017

Dimensional data

Standards

Maximum
operation
voltage

mm.

mm.

67021

Copper - and
silver plated ISOF
alluminium

69020

Dry power
frequency
voltage
whitstand

Creepage
distance

Weight

kV

kV

mm.

kg.

75

35

>350

11

95

55

>350

12

125

55

>350

13

125

55

400
690

210

12

770

250

17,5

870

300

24

630
400

65021

Copper - and
silver plated
alluminium

Nominal
current

Lightning
impulse
voltage
whitstand

630
400

Fig. 1
Three phase rotating bushing block type IPAR

24

630

2,3

IPAR
Special bushing
block IPAR for small
switchgears (500 mm).

Drawing 65016

Fig. 2
insulator with air room type
ISOF

25

26

Insulators for outdoor use

IPAE

28

PRG 24

30

PRG 36

32

PGS 24-36

34

BSL

36

27

Type IPAE

Post insulator for outdoor installation

General characteristics
Cicloaliphatic resin post insulators, for outdoor application, with internal metal fitting.
These insulators are mainly indicated to be used as insulating supports for bus
bar, fuses and other equipment (as outdoor switchgears).
Application
For outdoor installation with heavy (III) pollution level, according to IEC 60815, 71-2.
Working condition temperatures: max 90 C.
Working voltage
From 12 to 36 kV.
(40,5 kV available on request)
Reference standards
IEC 60273 (CEI 36/12) - CENELEC HD 578 S1
IEC 60660 (File S/663)
IEC 60815, 71-2.
Commercial code
1G102 + drawing (example IPAE 10 commercial code = 1G10270100)
Identification

28

Electrical data

Lightning
impulse
voltage
whitstand

Mechanical data

Dry power
frequency
voltage
whitstand

Ultimate
bending
stress

Type

Drawing

Maximum
operation
voltage

kV

kV

kV

IPAE 10

70100

12

75

35

10000

IPAE 15

70200

17,5

95

45

IPAE 20

70300

24

125

55

IPAE 30

70400

36

170

75

Maximum
deflection
difference
between 20%
and 50% of
the specifield
load

Technical data

Creepage
distance

Fins

mm

mm

kg.

320

1,4

8000

2,7

520

2,3

6000

3,2

730

10

3,2

4000

910

13

3,9

Weight

Identification

Technical data
h

Type

d1

Maximum
Upper
nominal
Insulator
threaded
Drawing height diameter of centre
hole
insulating (tapped)
part

t1

d2

t2

d3

t3

Hole
depth
d1

Base
threaded
centre
hole
(tapped)

Hole
depth
d2

Distance
between
base face
and lower
threaded
end

Auxiliary
upper
threaded
hole
(tapped)

Hole
depth
d3

D1

D2

Distance Maximum Maximum


between
diameter
threaded diameter
base
upper
holes
face
face
d3

IPAE 10 70100

130

130

M12

18

M16

26

27

M6

15

36

90

70

IPAE 15 70200

210

130

M12

18

M16

26

27

M6

15

36

90

70

IPAE 20 70300

295

130

M12

18

M16

26

27

M6

15

36

90

70

IPAE 30 70400

360

130

M12

18

M16

26

27

M6

15

36

90

70

Accessories
Nichel-plated male reduction.

Drawing

3012

Drawing

3016

29

Type PRG 24 kV

SF6 - Air silicon rubber bushing

General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.
Application
For outdoor application and connection with bare electrical wire. The PRG bushings can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly
Working voltage
Up to 24 kV
Reference standards
IEC 60137(eletrical test) - Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Technical data

Mod. 1998

Mod. 2400

Nominal current

400 A

630 A

Maximum operation voltage

24 kV

24 kV

Frequency withstand voltage

55 kV

55 kV

Impulse withstand voltage

125 kV

125 kV

780 mm.

780 mm.

3,3 kg.

4,5 kg.

1G11701998

1G11702400

Creepage distance
Weight
Commercial code
Pos.

Components
Top connection fixing screw and nuts

Fixing cap

Silicon bushing

O-Ring gaskit

Aluminium insulator fixing flange

Lower connection fixing screws and nuts

Steelwork holes Lay-Out



The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on



request

30

Kit

Assembling instructions
- P repare the holes on the body of the tank as indicated (item 7).
- Remove the paint, or insulating coat, in the area of fixing holes in order to guarantee a correct earth connection of the

bushing.
- More over make sure that the surface where the bushing hods is without any type of roughness, or unevenness and it must
be perfectly clean in order to guarantee a perfect tightening-up of the flat gaskets (item 4).
- Place the bushing (item 3) on the tank after having positioned the gasket (item 4).
- Place the aluminium flange (item 5) inside the tank and tighten the six fixing screws (item 6) together with the relevant
washers with a tightening force value of 911 Nm. The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be fixed with a tightening force value of 3035 Nm.

Mod. 2400

Mod. 1998

Color RAL 7030

Color RAL 7030

Steelwork holes Lay-Out

31

Type PRG 36 kV

SF6 - Air silicon rubber bushing


with internal core made by epoxy resin

General characteristics
The PRG bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for outdoor applications. The external side is made by silicon rubber
with internal core made by epoxy resin. The body guarantee solidity to the complex and
perfect seal of SF6 gas filled in the inner part of electrical device.
Is equipped with galvanized copper conductor and it is supplied completed with:
- Top fixing cap made by galvanized brass brass;
- Top connection fixing screw & nuts made by galvanized brass;
- O-Ring gasket made by EPDM for SF6 gas seal;
- Upon request, aluminium flange, screw & nuts for assembling of the bushing on the
metallic frame.
Application
For outdoor application and connection with bare electrical wire. The PRG bushing can be
assembled in any position with the exception of the situation where the sheds are turned
upside down, even if slightly
Working voltage
Up to 36 kV
Reference standards
IEC 60137(eletrical test) Enel unification chart DY 1806 Cap. 4
IEC 60507 (1991): salinity salt fog test (type test)
IEC 61109 (1992-03) 5000 hours accelerated ageing test (type test)

Dati tecnici

Mod. 3600

Nominal current

630 A

Maximum operation voltage

36 kV

Frequency withstand voltage

75 kV

Impulse withstand voltage

170 kV

Creepage distance

1050 mm.

Weight

5,1 kg.

Commercial code

1G11703600
Pos.

Components
Top connection fixing screw and nuts

Fixing cap

Silicon bushing

O-Ring gaskit

Aluminium insulator fixing flange

Lower connection fixing screws and nuts

Steelwork holes Lay-Out



The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on



request

32

Kit

Assembling instruction
Prepare the holes on the body of the tank as indicated
(item 7).
Remove the paint, or insulating coat, in the area of fixing
holes in order to guarantee a correct earth connection of
the bushing.
Moreover make sure that the surface where the bushing
holds is without any type of roughness, or unevenness and
it must be perfectly clean in order to guarantee a perfect
tightening-up of the flat gaskets (item 4).
Place the bushing (item 3) on the tank after having
positioned the gasket
(item 4).
Place the aluminium flange (item 5) inside the tank and
tighten the six fixing screws (item 6) together with the
relevant washers with a tightening force value of 911 Nm.
The tighting of the screws must be done crosswise.
- The lower connection to the M10 threaded hole must be
fixed with a tightening force value of 3035 Nm.

Steelwork holes Lay-Out

Mod. 3636

Color RAL 7030

33

Type PGS 24-36 kV

SF6 - Air silicon rubber bushing

General characteristics
A
The PGS bushings can be used as a fixed part for medium voltage input on SF6 gas or
oil insulated machines. It is provided with a coupling interface according to DIN 47636
standard that allows a connection with the relevant movable connectors. It is forbidden to
use the bushing in outdoor applications without the relevant movable connectors or without
the silicon rubber protection (B).
A+B
The PGS bushing with the silicon rubber protection can be utilized outdoor for connections
with bare electrical wire. The PGS can be assembled in any position except for the situation
where the sheds of silicon rubber protection are turned upside down, even if slightly.
Working voltage
Up to 36 kV
Reference standards
IEC 60137 (electrical tests)
IEC 60507 (1991): Salinity salt fog test (type test)
IEC 61109 (1992-03) C: 5000 hours accelerated ageing test (type test)
A 1990

A 1996

A 1990 +
B 2000

A 1996 +
B 3000

Normal current

630 A

630 A

630 A

630 A

Maximum operation voltage

24 kV

36 kV

24 kV

36 kV

Frequency whitstand voltage

55 kV

75 kV

55 kV

75 kV

Impulse whitstand voltage

125 kV

170 kV

125 kV

170 kV
1050 mm.

Technical data

Creepage dustance
Weight
Color
Commercial code
Pos.
1

Components
Top connection fixing screw and nuts

Fixing cap

Silicon bushing

Plastic protective cover

Grease poket

Connection intarface DIN 47636

Epoxy resin bushing

O-Ring gaskit

Steelwork holes Lay-Out

10

Aluminium insulator fixing flange

11

Lower connection fixing screws and nuts

The highlighted items are included in the


supplied Kit

The highlighted items can be supplied on



request

34

Kit

780 mm.

2,4 kg.

2,9 kg.

4,1 kg.

5,1 kg.

RAL 3013

RAL 3013

RAL 7030

RAL 7030

1G11701990

1G11701996

1G11702000

1G11703000

Silicon rubber protection (Fig. 3 and 4):


R emove the plastic protective cover (4) from the bushing.
The plastic protective cover must be fitted and pressed
right down on the bushing always when:
the bushing is not connected to the movable connector;
 the bushing does not have silicon rubber protection.
T his prevents faults caused by dirty or incidental scratching
of the interface (6).
C lean with alcohol the interface (6) and the area of contact
with the silicon rubber protection (3).
After the complete evaporation of the solvent, spread
evenly over the connection interface (6) the grease
contained in the enclosed pocket (5).
P ull the silicon rubber protection (3) on the bushing (7)
and screw down tightly until maximum torque is obtained
(90100 Nm). This can be done with the aid of a 20
mm spanner used on the top cap (2). The silicon rubber
protection is correctly clamped if the bushing is totally
covered with it.
Turn the silicon rubber protection slightly to the left and to
the right to distribuite grease evenly over the connection
interface (6).

Fig. 2

H - 290 mm - Mod. 2000 - 24 kV


H - 356 mm - Mod. 3000 - 36 kV

Fig. 1

Fig. 3
L - 68,5 mm - Mod. 1990 - 24 kV
L - 108,5 mm - Mod. 1996 - 36 kV

Assembling instruction
PGS bushing (Fig. 1 and 2):
Drill the holes on the body of the tank as indicated (9).
Remove the paint, or insulating coat, in the area of the
fixing fastener holes in order to guarantee a correct earth
connection of the bushing.
M oreover make sure that the surface where the bushing
holds is without any type of roughness, or unevenness and
it must be perfectly clean in order to guarantee a perfect
tightness of the flat gaskets.
Place the bushing (7) on the metal structure after having
positioned the gasket (8). Place the aluminium flange
(10) inside the tank and tighten the six fixing screws (11)
together with the relevant washers with a tightening force
value of 911 Nm. The tighting of the screws must be done
crosswise.The lower connection to the M10 threaded hole
must be fixed with a tightening force value of 3035 Nm.

Fig. 4

35

Type BSL

Composite insulators for line switches

General characteristics
The composite insulators type BSL are suitable to be used in MV line switches.
These insulators are realized with a fiberglass and epoxy resin core and aluminium end
fittings and covered by silicon rubber. This material gives best performances for an outdoor
use: abrasion resistance against UV rays, in environements with very high pollution level and
with high salinity concentration. Silicon is unbreakable and hidrophobic. It is not necessary
to plan any maintenance operation, even in particularly difficult environement conditions.
Application
Outdoor line switches.
Reference standards
IEC 60815

Identiification

Fig.

Dimensional characteristics
D

D1

Drawing

Drawing

Drawing

Drawing

2501

333

2502
2503
2504

543

2505

663

2506

873

325 kV

2507

873

2508

673

2509

643

34341

860

mm.

36

Eletrical data

Mechanical data

Technical data

Dry impulse
withstand
voltage (BIL)

Theorical
tensile
stress

Theorical
compressive
stress

Minimum
creepage
distance

Fins

kV

weight

mm.

kg.

75 kV

450

0,5

393

95 kV

600

0,6

423

125 kV

675

0,72

170 kV

975

13

0,93

250 kV

1275

17

1,15

1800

24

1,45

325 kV

1935

18

2,1

250 kV

1400

13

1,55

170 kV

1120

10

1,15

10+9

2,4

80

115
145

110

325 kV

10000

12000

Fig. 1

Fig. 2

37

38

Products for SF6 insulated


switchgear
INV - PPC/PPT - PPS - PTS/IPC - IPF - INV

40

PPC - PPT - PPE

42

PTC

44

PTS

46

PRI

48

39

Type INV - PPC/PPT - PPS - PTS


IPC - IPF - INV

Fuse holder, bushings and accessories for SF6 insulated devices

INV
Drawing: 1745 - 1736
Epoxy resin fuse holder completed with lower and central contacts for fuse and silicon
gasket for bushings assembling.
PPC/PPT
Drawing: 3236 - 3220
SF6 gas tight type, it is equipped with innen coupling type
EN 50180-50181 (DIN 47637).
PPS
Drawing: 1945 - 1521
No SF6 tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) and connection for L.V. reading.
PTS
Drawing: 1921
SF6 gas tight type, it is equipped with external coupling type EN 50180-50181
(DIN 47636) DIN 47636 and connection for L.V. reading.
IPC
Drawing: 1830
Wire-test SF6 gas tight bushing completed with O-Ring type gasket.
IPF
Drawing: 1730
Fuse holder SF6 gas tight support bushings completed with O-Ring type gasket.
INV
Drawing: 1760
Fuse holder cover completed of upper contact, mechanism for fuse and silicon gasket for fuse holder coupling.
Application
For indoor use, vertical and horizontal installation.

PPC/PPT 3236/3220
PPS 1945/1521

PTS 1921
INV 1745/1736

IPC 1830

INV 1760

IPF 1730

40

Fuse holder type INV


Fig. 1A
Fig. 1B

24 kV
Drawing: 1745
A = 592 mm.
B = 90 mm.

36 kV
Drawing: 1736
A = 687 mm.
B = 185 mm.

Fig. 2

Fig. 3A

Fig. 3B

Bushing type IPF - Drawing: 1730

Bushing type PPS - Drawing: 1945

Bushing type PPS - Drawing: 1521

Electrical data

Identification
Fig.
1A
1B
2
3A
3B
4

with cover drawing n. 1760

Type
INV
IPF
PPS
IPC

kg.

Drawing

Maximum operating
voltage

Nominal current

Lightning impulse
voltage whitstand

Dry power frequency


voltage whitstand

Weight

1745 - 1760

24 kV

200 A

125 kV

55 kV

14

1736 - 1760

36 kV

200 A

170 kV

75 kV

15

1730

24 kV

250 A

125 kV

55 kV

1945
1521
1830

24 kV

250 A

125 kV

55 kV

24 kV

500 A

125 kV

55 kV

Silicon rubber extension for bushing type


IPC - Drawing: 1840

1
1,1
1,78
1

Fig. 4
Bushing type IPC
Drawing: 1830

41

Type PPC - PPT - PPE

Bushing with internal plug connection

General characteristics
The PPC, PPT and PPE epoxy resin bushings can be used as medium voltage inlet
connections for oil or SF6 insulated device, such as transformers or switchgears.
They are equipped with internal coupling type DIN 47637 to be coupled with relevant mobile
connectors.
The PPC-DC 400-630 A bushing is equipped with a connection for the reading of L.V. by a
light signal box.
Application
Indoor installation at max working temperature of 85 C
Reference standards
IEC 60137
Electrical data

Identification
Fig.

1
2
3

42

Type

Drawing

Maximum
operating
voltage

Reference standards

kg.

Nominal
current

Lightning
impulse
voltage
whitstand

Dry power
frequency
voltage
whitstand

Coupling type

Weight

PPC 20/250

3236

24 kV

250 A

125 kV

55 kV

DIN 47637 / ENEL DJ 1115

2,4

PPC-DC 30/630

3206

24-36 kV

400-630 A

170 kV

75 kV

DIN 47637 / ENEL DJ 1113

2,5

PPT 20/250

3220

24 kV

250 A

125 kV

55 kV

DIN 47637 / ENEL DJ 1115

1,9

PPT 30/630

3195

24-36 kV

400-630 A

170 kV

75 kV

DIN 47637 / ENEL DJ 1113

PPE 20/1250

3227

24 kV

1250 A

125 kV

55 kV

DIN 47637 / ENEL DJ 1153

5,8

PPC 20/250

PPC-DC 30/630

drawing nr. 3236

drawing nr. 3206

PPT 20/250

PPT 30/630

drawing nr. 3220

drawing nr. 3195

PPE 20/1250
drawing nr. 3227

Color RAL 3013

Pos.

Technical data

PPC
20/250

PPC/DC
30/6330

PPT
20/250

PPT
30/630

PPE
20/1250

Mobile connector fastening

Fastening insulator insert

Earth socket or outlet of the capacitive potential divider

Threaded central conductor

Epoxy resin insulated part

Connection socket

Electrical field deflector

Coupling type DIN 47637

Equipotential screen

10

Gasket O-ring

11

Gasket O-ring

12

Insulator fixing flange

13

Insulator screws and nuts

14

Screws plastic pretective cover

15

Coupling plastic pretective cover

16

Insulated insert

17

Screw M5

The highlighted items are included in the supplied kit.

43

Type PTC

Bushing with external plug connection

General characteristics
The PTC bushings can be used as a fixed part in medium voltage
inlet for oil or SF6 insulated devices, such as transformers or switchgears.
They are equipped with a connection for the reading of low voltage by a light signal box.
Application
For indoor application, suitable for vertical or horizontal installation.
Working voltage
24 - 36 kV
Reference standards
IEC 60137 (electrical tests)
DIN 47636/HN 52-S-61 (coupling interface)

Electrical data

Identification

Fig.

kg.

Type

Drawing

Maximum
operation
voltage

Nominal
current

Lightning
impulse
voltage
whitstand

Dry power
frequency
voltage
whitstand

Coupling
type

105

184

PTC 24/250

1922
I-6284-02

24 kV

250 A

125 kV

55 kV

DIN 47636
HN 52-S-61

Sliding
contact

M8

1,3

60

140

PTC 24/250-R
Corto

1930
I-7113-02

24 kV

250 A

125 kV

55 kV

DIN 47636
HN 52-S-61

Sliding
contact

M8

1,1

105

228

PTC 36/400

1933
I-6274-02

36 kV

400 A

170 kV

75 kV

EN 50180
HN 52-S-61

Sliding
contact

M10

2,3

60

183

PTC 24/400-R
Corto

1935
NI-959

24 kV

400 A

125 kV

55 kV

EN 50181
HN 52-S-61

Sliding
contact

M10

1,9

105

230

PTC 36/630

1923
I-6250-2

36 kV

630 A

170 kV

75 kV

EN 50181
DIN 47636

M16

M10

2,3

60

184,5

PTC 24/630-R
Corto

1936
I-7094-04

24 kV

630 A

125 kV

55 kV

EN 50181
DIN 47636

M16

M10

1,9

We recommend the use of flange

44

Standards

Connetion Threded
Weight
type
hole

Fig. 1

Fig. 2

250 A

400-630 A

Pos.

Components

Lower connection

Epoxy resin insulated part

O-Ring gasket

Coupling interface DIN 47636

Copper bar

Insulator fixing flange

Fastening insulator screws

Plastic protective cover


All items are included in the supplied kit

45

Type PTS

Bushing with external plug connection

General characteristics
The PTS bushings can be used as a fixed part in medium voltage inlet for oil or SF6
insulated devices, such as transformers or switchgears .
They are equipped with a copper conductor and is supplied completed with O-ring gasket,
aluminium flange and screws and nuts for assembling operations on the metallic tank.
Application
For indoor application, suitable for vertical or horizontal installation.
Working voltage
24-36 kV
Reference standards
IEC 60137 (eletrical test)
EN 50180-50181 (DIN 47636 / HN 52-S-61) coupling interface.
Electrical data

Identification
Fig.

Type

Drawing

PTS 24/250

1921

PTS 24/630

1925 M

PTS 36/400

1942

PTS 36/630

1925

PTS 24/630

1929

Maximum
operation
voltage
kV

2
3

46

24
36
24

Nominal
current

Lightning
impulse
voltage
whitstand

Dry power
frequency
voltage
whitstand

Contact
type

Threded
hole

L
Weight

mm. (min.)

mm. ( 1)

mm.

kg.

250

Lamellare

M8

222

150

1,4

M16x29 mm.

M12

239

120

2,2

630
400
630
630

125 kV

55 kV

170 kV

75 kV

125 kV

55 kV

Lamellare

M8

266,5

150

2,4

M16x29 mm.

M12

269

150

2,4

M16x29 mm.

M12

234

120

3,2

Fig. 1

Fig. 2

Fig. 3

Pos.

11

10

Components

Lower connection

Epoxy resin insulated part

Earth socket or outlet of the capacitive potential divider

O-Ring gasket

Coupling interface DIN 47636

Copper bar

Upper connection

Insulator fixing flange

Fastening insulator screws

10

Mobile connector fastening 25 e 400 A.

11

Plastic protective cover


All the items are included in the supplied kit

6
4
3

2
1

47

Type PRI 24 kV

SF6 - air bushing for indoor use

General characteristics
The PRI bushings can be used as medium voltage inlet for SF6 insulated devices such as
switchgears suitable for indoor applications.
They are equipped with nichel-plated copper conductor and it is supplied completed with
O-Ring gasket made by EPDM for SF6 gas seal.
Application
For indoor application and connection with bare electrical wire.
Working voltage
Up to 24 kV
Reference standards
IEC 60137
Commercial code
1G12185024

Assembling instructions
Bushing insulator PRI.
Prepare the holes on the body of the tank as indicated in the
steelwork holes Lay-out. Remove the paint, or any insulating
coat in the area of fixing holes, in order to guarantee a
correct earth connection of the bushing.
Moreover, make sure that the surface where the bushing is
placed is without any type of roughness or unevenness. It
must be completely clean in order to guarantee a perfect
tightness.
Connect to earth, when not used as capacitive outlet, the M5
thread (A) connected to the equipotential screen.
Tighten the 6 fixing screws M6, together with their relevant
washers, with a tightening force value of 9 11 Nm. The
tightening operation must be done crosswise. The lower
connection (M10) must be fastened with a tightening force
value of 30 35 Nm.

48

Technical data

Mod. 85024

Nominal current

630 A

Max operating voltage

24 kV

Frequency withstand voltage

55 kV

Impulse withstand voltage

125 kV

Creepage distance

380 mm.

Weight

1,95 kg.

Steelwork holes Lay-Out

49

50

51

Note

52

53

Contact us

Veneta Isolatori
Via Sile 22
30022 Ceggia (VE) - ITALY
Tel.: +39 0444 449311
Fax: +39 0444 449381
E-mail : venis@comem.com
www.comem.com

54

The data and the illustrations are not binding. We reserve


the right to modify the contents of this document on the
basis of technical development of the products, without
prior notice.
Copyright 2010 Veneta Isolatori.
All rights reserved.