SVM-07013-1
SERVICE MANUAL
SPLIT TYPE
Indoor Unit
Outdoor Unit
42NQV025H
42NQV035H
42NQV035M
42NQV045H
42NQV045M
38NYV025H
38NYV035H
38NYV035M
38NYV045H
38NYV045M
R410A
Revised May, 2007
CONTENTS
1.
2.
SPECIFICATIONS ........................................................................................................ 5
3.
4.
5.
6.
7.
8.
9.
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm2 (H07RN-F or 60245IEC66) polychloroprene
sheathed flexible cord.
CAUTION
New Refrigerant Air Conditioner Installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because
the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the
adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during
installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into
the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging
port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new
and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does
not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings
and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact
separation of at least 3 mm.
DANGER
ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
WARNING
Never modify this unit by removing any of the safety guards or bypass any of the safety interlock
switches.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property
damage can result if the unit falls.
After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas
may generate.
The electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
When wiring, use the specified cables and connect the terminals securely to prevent external
forces applied to the cable from affecting the terminals.
Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
Exposure of unit to water or other moisture before installation may result in an electrical short.
Do not store in a wet basement or expose to rain or water.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise or discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed for a long time under the condition that the outdoor
temperature is 0C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.
For details, contact the dealer.
2.1 Specification
Unit model
2. SPECIFICATIONS
Indoor
42NQV025H
42NQV035M
42NQV035H
Outdoor
38NYV025H
38NYV035M
38NYV035H
Cooling capacity
(kW)
2.5
3.5
3.5
(kW)
1.1-3.0
1.1-3.9
0.8-4.0
Heating capacity
(kW)
3.2
4.2
4.2
(kW)
0.9-4.7
0.9-4.9
0.9-5.7
1Ph/50Hz/220-240V
Power supply
Electric
Indoor
characteristic
Operation mode
Cooling
Heating
Cooling
Heating
Cooling
Heating
(A)
0.21-0.19
0.24-0.22
0.21-0.19
0.24-0.22
0.21-0.19
0.24-0.22
Power consumption
(W)
35
40
35
40
35
40
Power factor
(%)
76
76
75
75
75
75
Cooling
Heating
Cooling
Heating
Cooling
Heating
Running current
Outdoor
Operation mode
Running current
(A)
3.11-2.85
3.71-3.42
4.94-4.56
5.18-4.78
4.69-4.31
5.21-4.76
Power consumption
(W)
623
770
1055
1110
990
1095
Power factor
(%)
91
94
97
97
96
Starting current
(A)
Indoor
noise
3.41/3.70
3.80/3.95
3.21/3.65
(dB-A)
39/40
40/41
40/41
Medium
(Cooling / Heating)
(dB-A)
34/35
34/35
34/35
Low
(Cooling / Heating)
(dB-A)
27/29
27/29
27/29
(Cooling / Heating)
(dB-A)
46/47
48/50
48/50
42NQV025H
42NQV035M
42NQV035H
Height
(mm)
275
275
275
Width
(mm)
790
790
790
Depth
(mm)
205
205
205
Net weigh
(kg)
(W)
20
20
20
5.45-4.98
(Cooling / Heating)
Unit model
Dimension
5.42-5.00
High
Outdoor
Indoor unit
(Cooling / Heating)
3
(m / min)
Unit model
Dimension
Compressor
8.6/9.5
9.4/10.5
9.0/10.2
38NYV025H
38NYV035M
38NYV035H
Height
(mm)
550
550
550
Width
(mm)
780
780
780
Depth
(mm)
290
290
290
(kg)
35
35
35
(W)
750
750
750
Net weigh
Motor output
Type
Model
DA89X1C-23FZ
Type
connection
Indoor unit
Outdoor unit
DA89X1C-23FZ
(W)
Refrigerant
96
3.95-3.64
(Cooling / Heating)
DA111A1F-20F1
43
3
(m / min)
30/30
35/35
37.5/37.5
Flare connection
Flare connection
Flare connection
6.35
Liquid side
(mm)
6.35
6.35
Gas side
(mm)
9.52
9.52
9.52
Liquid side
(mm)
6.35
6.35
6.35
Gas side
(mm)
9.52
9.52
9.52
Maximum length
(m)
20
20
20
(m)
15
15
15
(m)
Name of refrigerant
Weight
Wiring
10
10
10
R410A
R410A
R410A
0.80
0.85
(kg)
0.80
Power supply
connection
Interconnection
Indoor
(Cooling / Heating)
o
( C)
21-32/0-28
21-32/0-28
21-32/0-28
Outdoor
(Cooling / Heating)
o
( C)
-10-46/-15-24
-10-46/-15-24
-10-46/-15-24
Installation plate
batteries
Accessory
Indoor unit
Mounting screw
Pan head wood screw
Outdoor unit
6 ( 4 x 25L)
6 ( 4 x 25L)
6 ( 4 x 25L)
2 ( 3.1 x 16L)
2 ( 3.1 x 16L)
2 ( 3.1 x 16L)
Installation manual
Owner's manual
Drain nipple
* The specification may be subject to change without notice for purpose of improvement.
Indoor
42NQV045M
42NQV045H
Outdoor
38NYV045M
38NYV045H
Cooling capacity
(kW)
4.5
4.5
(kW)
0.8-4.9
0.8-4.9
Heating capacity
(kW)
5.3
5.5
(kW)
0.9-6.1
0.9-6.8
Power supply
Electric
1Ph/50Hz/220-240V
Indoor
characteristic
Operation mode
Running current
Outdoor
(A)
noise
30
35
30
35
65
65
65
Cooling
Heating
Cooling
Heating
(A)
7.44-6.81
7.00-6.42
6.39-5.86
6.86-6.28
Power consumption
(W)
1615
1520
1390
1490
Power factor
(%)
99
99
99
Starting current
(A)
Operation mode
99
7.65-7.00
7.10-6.50
2.74/3.41
3.17/3.61
High
(Cooling / Heating)
(dB-A)
46/46
46/46
Medium
(Cooling / Heating)
(dB-A)
41/41
41/41
Low
(Cooling / Heating)
(dB-A)
31/32
31/32
(Cooling / Heating)
(dB-A)
49/50
49/50
42NQV045M
42NQV045H
Height
(mm)
275
275
Width
(mm)
790
790
Depth
(mm)
205
205
Net weigh
(kg)
(W)
30
30
(m3 / min)
(Cooling / Heating)
Unit model
Dimension
Compressor
(mm)
550
550
(mm)
780
780
Depth
(mm)
290
290
(kg)
35
39
(W)
750
750
Motor output
Type
Model
DA111A1F-20F1
connection
Indoor unit
DA111A1F-20F1
(W)
11.4/12.3
38NYV045H
Width
11.5/12.4
38NYV045M
Height
Net weigh
(m3 / min)
(Cooling / Heating)
35/35
36/32
Flare connection
Flare connection
Liquid side
(mm)
6.35
6.35
Gas side
(mm)
12.7
12.7
Liquid side
(mm)
6.35
6.35
Gas side
(mm)
12.7
12.7
Maximum length
(m)
20
20
(m)
15
15
(m)
Outdoor unit
Refrigerant
0.24-0.22
65
0.21-0.19
(%)
Unit model
Dimension
Heating
0.24-0.22
(W)
Outdoor
Indoor unit
Cooling
0.21-0.19
Power factor
Heating
Power consumption
Running current
Operating
Cooling
Name of refrigerant
Weight
Wiring
(kg)
10
10
R410A
R410A
0.85
1.10
Power supply
connection
Interconnection
Indoor
(Cooling / Heating)
(oC)
21-32/0-28
21-32/0-28
Outdoor
(Cooling / Heating)
(oC)
-10-46/-15-24
-10-46/-15-24
Installation plate
batteries
Accessory
Indoor unit
Mounting screw
Pan head wood screw
Outdoor unit
6 ( 4 x 25L)
6 ( 4 x 25L)
2 ( 3.1 x 16L)
2 ( 3.1 x 16L)
Installation manual
Owner's manual
Drain nipple
* The specification may be subject to change without notice for purpose of improvement.
<Cooling>
<Heating>
10
10
42NQV045H
42NQV045H
42NQV045M
8
42NQV035H
42NQV045M
7
42NQV035H
42NQV035M
42NQV035M
Current (A)
Current (A)
42NQV025H
5
4
5
4
42NQV025H
3
3
Conditions
Outdoor : DB 35oC
Air Flow : High
Pip Length : 5m
Voltage : 230V
Conditions
Indoor : DB 20oC
Outdoor : DB 7oC/WB 6oC
Air Flow : High
Pip Length : 5m
Voltage : 230V
0
0
10
20
30
40
50
60
70
80
10
20
30
40
50
60
70
80
<Cooling>
105
120
100
42NQV025H
42NQV035H
42NQV045H
95
100
90
85
42NQV045M
80
42NQV035M
75
70
65
60
55
Capacity ratio:100%=
2.5kW(42NQV025H)
3.5KW(42NQV035M,
42NQV035H)
4.5kW(42NQV045M,
42NQV045H)
Conditions
Indoor:DB27/WB19
Indoor air flow:High
Pipe length:5m
Voltage:230V
80
60
42NQV025H
42NQV035M
42NQV035H
42NQV045M
42NQV045H
40
Condition
Indoor:DB20
Indoor air flow:High
Pipe length:5m
Voltage:230V
20
50
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
-15
Outdoor temp. ()
-10
-5
Outdoor temp. ()
10
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored
portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary
to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 3-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
R410A
R22
1/4
6.35
0.80
0.80
3/8
9.52
0.80
0.80
1/2
12.70
0.80
0.80
5/8
15.88
1.00
1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Nominal diameter
1/4
6.35
0.50
3/8
9.52
0.60
1/2
12.70
0.70
5/8
15.88
0.80
D
A
Outer
diameter
(mm)
Thickness
(mm)
Clutch type
1/4
6.35
0.8
0 to 0.5
1.0 to 1.5
1.5 to 2.0
3/8
9.52
0.8
0 to 0.5
1.0 to 1.5
1.5 to 2.0
1/2
12.70
0.8
0 to 0.5
1.0 to 1.5
2.0 to 2.5
5/8
15.88
1.0
0 to 0.5
1.0 to 1.5
2.0 to 2.5
Outer
diameter
(mm)
Thickness
(mm)
Clutch type
1/4
6.35
0.8
0 to 0.5
0.5 to 1.0
1.0 to 1.5
3/8
9.52
0.8
0 to 0.5
0.5 to 1.0
1.0 to 1.5
1/2
12.70
0.8
0 to 0.5
0.5 to 1.0
1.5 to 2.0
5/8
15.88
1.0
0 to 0.5
0.5 to 1.0
1.5 to 2.0
Nominal
diameter
Outer diameter
(mm)
Thickness
(mm)
1/4
6.35
0.8
9.1
9.2
6.5
13
17
3/8
9.52
0.8
13.2
13.5
9.7
20
22
1/2
12.70
0.8
16.6
16.0
12.9
23
26
5/8
15.88
1.0
19.7
19.0
16.0
25
29
10
Nominal
diameter
Outer diameter
(mm)
Thickness
(mm)
1/4
6.35
0.8
9.0
9.2
6.5
13
17
3/8
9.52
0.8
13.0
13.5
9.7
20
22
1/2
12.70
0.8
16.2
16.0
12.9
20
24
5/8
15.88
1.0
19.7
19.0
16.0
23
27
3/4
19.05
1.0
23.3
24.0
19.2
34
36
45
to 4
43
to 4
Fig. 3-2-2 Relations between flare nut and flare seal surface
Outer diameter
(mm)
Tightening torque
Nm (kgfcm)
1/4
6.35
14 to 18 (140 to 180)
16 (160), 18 (180)
3/8
9.52
33 to 42 (330 to 420)
42 (420)
1/2
12.70
50 to 62 (500 to 620)
55 (550)
5/8
15.88
63 to 77 (630 to 770)
65 (650)
11
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A
air-water heat pump installation
No.
Used tool
Usage
Existence of
new equipment
for R410A
Conventional air-water
heat pump installation
Whether new equipment
can be used with
conventional refrigerant
Flare tool
Pipe flaring
Yes
*(Note 1)
Flaring by
conventional flare tool
Yes
*(Note 1)
*(Note 1)
Torque wrench
(For 12.7)
Yes
Gauge manifold
Charge hose
Evacuating, refrigerant
charge, run check, etc.
Yes
Vacuum evacuating
Yes
Refrigerant charge
Yes
Refrigerant cylinder
Refrigerant charge
Yes
Leakage detector
Yes
10
Charging cylinder
Refrigerant charge
(Note 2)
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
4.
5.
6.
7.
8.
Reamer
Pipe bender
Level vial
Screwdriver (+, )
Spanner or Monkey wrench
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
12
(Water heat
exchanger unit)
(Outdoor unit)
Opened
Refrigerant cylinder
(with siphon)
Check valve
Opened
Opened
Open/close
valve for charging
Closed
Service port
Electronic balance for refrigerant charging
13
Gauge manifold
Gauge manifold
OUTDOOR unit
OUTDOOR unit
Refrigerant
cylinder
Refrigerant
cylinder
Electronic
balance
Electronic
balance
Siphon
Fig. 3-4-2
3-5-2. Flux
1. Reason why flux is necessary
By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
In the brazing process, it prevents the metal
surface from being oxidized.
By reducing the brazing fillers surface tension,
the brazing filler adheres better to the treated
metal.
14
Used flux
Copper - Copper
Phosphor copper
Do not use
Copper - Iron
Silver
Paste flux
Iron - Iron
Silver
Vapor flux
3-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
M Flow meter
Stop valve
Nitrogen gas
cylinder
Pipe
Nitrogen
gas
Rubber plug
15
4.CONSTRUCTION VIEWS
4-1. Indoor Unit
790
Air inlet
Air filter
205
63
48
48
Heat exchanger
63
275
Front panel
49
62
480
Installation plate hanger
193
157
116
69
56
19
235
215
621
Minimum
distance
Minimum
Minimum
distance
275
to wall
170 or more
40
40
170 or more
190
distance
to wall
84.5
Hanger
150
160.5
160.5
Center line
Hanger
150
84.5
16
26
45
to ceiling
63
84.5
235
215
Hanger
125
65 or more
30
125
600
50
306
86
320
320
R15
36
320
306
6 hole
R5.5
6 hole
11x14 hole
25 Drain outlet
FAN-GUARD
2- 11 x 14 Hole
(For 8 -10 anchor bolt)
36
50
R15
436
COVER-PV
275
550
290
90
600
90
321
342
69
84
Gas side
(Flare 12.7)
(10,13:Flare 9.52)
(16:Flare 12.7)
54
129
Liquid side
(Flare 6.35)
Z View
Service port
2-R5-5 x 17L Ushope
(For 8- 10 anchor bolt)
600
100 or more
Air intlel
320
600 or more
100 or more
Air outlel
600 or more
Installation dimension
17
5. WIRING DIAGRAM
5-1. 42NQV025H / 38NYV025H, 42NQV035H / 38NYV035H
42NQV035M / 38NYV035M
18
19
FILE NO.SVM-07013
No.
1
Fan motor
(for indoor)
Type
42NQV025H, 42NQV035H,
42NQV035M
MMF-240-20-4B
42NQV045H, 42NQV045M
ICF-340-30-2
Specifications
AC240/220V, 20W
DC 340V, 30W
()
10k at 25C
()
10k at 25C
Louver motor
MP24Z3T
No.
Model name
Rating
CH-57
L = 10mH, 16A
ICF-140-43-4R
DC140V, 43W
Reactor
(Inverter attached)
10k (25C)
(Inverter attached)
62k (20C)
(Inverter attached)
10k (25C)
(Inverter attached)
10k (25C)
Compressor
30A, AC600V
38NYV025H,38NYV035M
DA89X1C-23FZ
38NYV035H,38NYV045M
38NYV045H
DA111A1F-20F1
C12A01A
10
VHV
11
Compressor thermo
PW-2AL
20
DC12V
AC220-240V
OFF : 1254C, ON : 905C
T1
Temp. measurement
Indoor heat
exchanger
P Pressure measurement
Gauge attaching port
Vacuum pump connecting port
TA
Allowable height
difference : 10m
TC
Max. : 20m
Min. : 1m
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
Strainer
Muffler
4-way valve
(STF-0108Z)
Pulse Modulating
valve at liquid side
(SEV16RC9)
Muffler
TD
Compressor
DA89X1C-23FZ
Strainer
TS
TO
Outdoor heat
exchanger
Temp. measurement T2
TE
Propeller fan
OUTDOOR UNIT
NOTE :
NOTE :
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
21
INDOOR UNIT
T1
Temp. measurement
Indoor heat
exchanger
P Pressure measurement
Gauge attaching port
Vacuum pump connecting port
TA
Allowable height
difference : 10m
TC
Max. : 20m
Min. : 1m
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
Strainer
Muffler
4-way valve
(STF-0108Z)
Pulse Modulating
valve at liquid side
(SEV16RC9)
Muffler
TD
Compressor
DA111A1F-20F1
TS
TO
Outdoor heat
exchanger
Split capillary
1.2 x 80
1.2 x 80
Temp. measurement T2
TE
Propeller fan
OUTDOOR UNIT
NOTE :
NOTE :
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
22
INDOOR UNIT
T1
Temp. measurement
Indoor heat
exchanger
P Pressure measurement
Gauge attaching port
Vacuum pump connecting port
TA
Allowable height
difference : 10m
TC
Max. : 20m
Min. : 1m
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
Strainer
Muffler
4-way valve
(STF-0108Z)
Pulse Modulating
valve at liquid side
(SEV16RC9)
Muffler
TD
Compressor
DA111A1F-20F1
TS
TO
Outdoor heat
exchanger
Split capillary
1.2 x 80
1.2 x 80
Temp. measurement T2
TE
Propeller fan
OUTDOOR UNIT
NOTE :
NOTE :
The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
23
Standard
pressure
P (MPa)
0.9 to 1.1
0.8 to 1.0
0.8 to 1.0
0.7 to 0.9
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (C)
T2 (C)
12 to 14
37 to 39
11 to 13
39 to 41
11 to 13
46 to 48
10 to 12
47 to 49
11 to 13
40 to 42
Indoor
fan mode
Outdoor
fan mode
High
High
High
High
High
High
High
High
High
High
Standard
pressure
P (MPa)
2.5 to 2.7
2.7 to 2.9
2.6 to 2.8
2.5 to 2.7
2.7 to 2.9
Heat exchanger
pipe temp.
T1 (C)
T2 (C)
39 to 41
0 to 3
43 to 45
0 to 2
41 to 43
0 to 2
39 to 41
0 to 2
43 to 45
0 to 2
Indoor
fan mode
Outdoor
fan mode
High
High
High
High
High
High
High
High
High
High
Compressor
revolution
(rps)
49
77
63
89
83
<Heating>
Tempeature
Model name
condition(C)
RASIndoor Outdoor
20/7/6
42NQV025H
42NQV035M
42NQV035H
42NQV045M
42NQV045H
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
24
Compressor
revolution
(rps)
60
80
66
89
83
M.C.U.
Heat Exchanger Sensor (Tc)
Louver
Motor
Functions
Cold draft preventing Function
Initializing Circuit
Clock Frequency
Oscillator Circuit
Louver Motor
Drive Control
Processing
(Temperature Processing)
Indoor
Fan Motor
Timer
Serial Signal Communication
Clean Function
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
Remote Controller
REMOTE CONTROLLER
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT,FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
25
42NQV025H, 42NQV035H
M.C.U.
Heat Exchanger Sensor (Tc)
Louver
Motor
Functions
Cold draft preventing Function
Initializing Circuit
Clock Frequency
Oscillator Circuit
Louver Motor
Drive Control
Processing
(Temperature Processing)
Indoor
Fan Motor
Timer
Serial Signal Communication
Clean Function
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
Remote Controller
REMOTE CONTROLLER
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT,FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
Night Light
26
M.C.U.
Louver
Motor
Functions
Cold draft preventing Function
Room Temperature Sensor (Ta)
3-minute Delay at Restart for Compressor
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Louver Motor
Drive Control
Processing
(Temperature Processing)
Indoor
Fan Motor
Timer
Serial Signal Communication
Clean Function
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
Remote Controller
REMOTE CONTROLLER
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT,FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
27
M.C.U.
Louver
Motor
Functions
Cold draft preventing Function
Room Temperature Sensor (Ta)
3-minute Delay at Restart for Compressor
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Louver Motor
Drive Control
Processing
(Temperature Processing)
Indoor
Fan Motor
Timer
Serial Signal Communication
Clean Function
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
Remote Controller
REMOTE CONTROLLER
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT,FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
Night Light
28
30
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
220 240 V
50/60 Hz
Noise
Filter
Indoor unit
send/receive
circuit
Relay
circuit
4-way
valve
P.M.V.
Converter
(AC DC)
Driver circuit
of P.M.V.
Input current
sensor
Clock
frequency
16MHz
High Power
factor Correction
circuit
M.C.U
MCC5009 (P.C.B)
Over current
sensor
Inverter
(DC AC)
Over current
sensor
Over current
sensor
Inverter
(DC AC)
Gate drive
circuit
Gate drive
circuit
Over current
detect circuit
Rotor position
detect circuit
Rotor position
detect circuit
Outdoor
Fan motor
Compressor
OUTDOOR UNIT
9. OPERATION DESCRIPTION
Detection of inverter input current and current
release operation
Over-current detection and prevention operation
to IGBT module (Compressor stop function)
Compressor and outdoor fan stop function when
serial signal is off (when the serial signal does not
reach the board assembly of outdoor control by
trouble of the signal system)
Transferring of operation information (Serial
signal) from outdoor unit controller to indoor unit
controller
Detection of outdoor temperature and operation
revolution control
Defrost control in heating operation (Temp.
measurement by outdoor heat exchanger and
control for 4-way valve and outdoor fan)
30
31
1. Basic
operation
Description
1. Operation control
Receiving the users operation condition setup, the operation statuses of indoor/outdoor units are
controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as
shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives
the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the compressor, outdoor fan motor, 4-way valve and pulse Modulating valve.
Remote controller
Selection of
operation conditions
ON/OFF
Ho
Indoor unit
Signal receiving
Indoor unit control
Operation command
Serial signal send/receive
Outdoor unit
Serial signal send/receive
Outdoor unit control
32
Inverter
Compressor
Outdoor fan motor
4-way valve
Pulse Modulating valve
(P.M.V.)
Description
2. Cooling/Heating operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal
starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of 2. Indoor fan
motor control and the louver according to the contents of 9. Louver control, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse Modulating valve and
4-way valve according to the operation signal sent from the indoor unit.
Operation ON
Indoor unit control
3. AUTO operation
Selection of operation mode
As shown in the following figure, the operation starts by
selecting automatically the status of room temperature
(Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
Ta
Cooling operation
Ts + 1
Monitoring (Fan)
Ts 1
Heating operation
4. DRY operation
1) Detects the room temperature (Ta) when
the DRY operation started.
DRY operation is performed according to the difference
between room temperature and the setup temperature as 2) Starts operation under conditions in the
shown below.
left figure according to the temperature
difference between the room temperaIn DRY operation, fan speed is controlled in order to
ture and the setup temperature (Tsc).
prevent lowering of the room temperature and to avoid air
Setup temperature (Tsc)
flow from blowing directly to persons.
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
[C]
3) When the room temperature is lower
Ta
L (W5)
1C or less than the setup temperature,
turn off the compressor.
+1.0
(W5+W3) / 2
+0.5
SUL (W3)
Tsc
Fan speed
33
2. Indoor fan
motor control
Description
COOL ON
MANUAL
(Fig. 1)
Fan speed
Indication
AUTO
W6
L+
(L + M) / 2
W9
M+
(M + H) / 2
WC
(Fig. 2)
+2.5
* Symbols
: Ultra High
: High
: Medium+
: Medium
: Low+
: Low
: Low
: Ultra Low
: Super Ultra Low
UH
H
M+
M
L+
L
LUL
SUL
+2.0
*3
+1.5
*4
+1.0
*5
+0.5
Tsc
(Linear approximation
from M+ and L)
L(W6)
42NQV025H
42NQV035M
Fan speed
(rpm)
Fan speed
(rpm)
42NQV035H
Fan speed
(rpm)
42NQV045M
Fan speed
(rpm)
42NQV045H
Fan speed
(rpm)
WF
UH
1210
571
1240
630
1280
614
1470
743
1510
735
WE
1210
571
1240
630
1280
614
1470
743
1510
735
UH
1170
546
1190
596
1230
583
1440
723
1480
717
1120
515
1140
563
1160
540
1390
691
1430
686
594
WD
UH
WC
WB
M+
M+
M
WA
W9
1040
465
1040
496
1070
484
1250
601
1280
1000
440
1000
469
1030
459
1190
563
1220
557
960
415
960
443
990
434
1120
518
1150
514
L+
L+
L-
L+
L
760
291
760
309
770
UL
L-
760
291
760
309
770
W8
W7
M+
870
359
870
383
870
359
970
421
1000
421
850
347
850
369
860
353
950
408
980
409
297
890
370
920
372
297
870
357
900
360
323
W6
W5
L-
W4
UL
UL
700
253
700
269
720
266
810
318
840
W3
SUL
SUL
650
222
650
236
670
234
750
280
770
280
500
129
500
135
520
141
600
183
620
187
500
129
500
135
500
129
500
119
520
126
W2
W1
SUL
34
2. Indoor fan
motor control
Description
HEAT ON
MANUAL
(Fig. 3)
Indication
AUTO
Fan speed
W8
L+
(L + M) / 2
WA
M+
(M + H) / 2
WE
YES
TC 42C
NO
Limited to Min WD tap
Tc
52
51
42
41
(Fig. 4)
No limit
* Fan speed =
(TC
W8) + W8
Cold draft preventive control
Fan speed
AUTO
TA [C]
TSC
0.5
1.0
1.5
2.0
2.5
L+ (W9)
46
45
Tc
46
45
34
33
33
32
33
32
21
20
*A+4
*A+4
*A+4
*A-4
*A-4
*A-4
H (WE)
c
d
*1
*2
Line-approximate
H and SUL with Tc.
SUL (W2)
*3
Stop
5.0
M+ (WD)
5.5
H (WE)
(Fig. 5)
(Fig. 6)
In stability
35
Description
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed 400
when the motor stopped.
YES
OFF status of
fan motor continues.
YES
Air conditioner
OFF
NO
Fan motor ON
3) Fan lock
Alarm
display
NO
4) Motor operates as shown in the table below.
In cooling operation
Compressor speed (rps)
To
During
ECO mode
~ 13.8
In Heating operation
~ 31.7
32.3 ~ MAX
To > 38C
To > 28C
f2
f3
fC
fD
fE
fF
f2
f3
fA
fC
fD
fF
To > 15C
To > 5.5C
f2
f3
f7
fA
f9
fC
f1
f3
f2
f5
f4
To > 0C
f1
f1
f1
f2
f2
To < 15C
f3
f9
fA
To < 5.5C
f8
fA
fD
To < 5.0C
To > 15C
fB
fC
fD
f7
f3
f3
f6
f4
To < 15C
f3
f3
f8
To < 5.5C
f5
f9
f9
To < 5.5C
f7
fA
fB
fA
fB
fD
To < 0C
f0
f0
f0
f1
f1
f2
To > 38C
f2
f3
fB
fC
fC
fD
To < 38C
f2
f3
f2
f3
fB
fC
fF
fD
fF
When To is abnormal
fD
fF
fD
During
ECO mode
When To is abnormal
38NYV025H
38NYV035M,38NYV035H
38NYV045M
f0
38NYV045H
Tap
38NYV025H
f9
600
650
650
fA
600
700
700
38NYV035M,38NYV035H
38NYV045M
38NYV045H
f1
200
200
200
f2
300
300
300
fB
650
700
700
f3
370
370
370
fC
700
800
800
f4
440
440
440
fD
700
800
800
f5
440
440
440
fE
700
800
800
f6
500
500
500
fF
700
800
900
f7
f8
550
600
550
600
550
600
36
Description
Remote controller
Indoor unit
Ts Ta
Correction of Hz signal
Detection of electromotive force
of compressor motor winding
Detection of motor speed and rotor position
Correction value of Hz signal Operating Hz
Inverter output change
Commutation timing change
Change of compressor speed
5. Current release This function prevents troubles on the electronic parts of the
control
compressor driving inverter.
This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.
Outdoor temp. To
High
Operating current
Setup value
Low
Current decrease
Capacity control continues.
control
Outdoor temp.
38NYV025H
45C
38NVY035M
38NYV035H
38NYV025H
38NYV035M
38NYV035H
38NYV045M
38NYV045H
6.30A
6.30A
7.72A
7.72A
3.97A
4.27A
4.27A
6.45A
44C
4.35A
4.88A
4.88A
6.75A
16C
39C
6.30A
6.30A
8.47A
8.47A
11C
15.5C
40C
38NYV045M
38NYV045H
10.5C
37
6.30A
6.30A
9.22A
9.22A
6.30A
6.30A
10.80A
10.80A
7C
Q
6C
5C
Description
48C
R
Usual heating capacity control
38
10 15
2740
34
Operation time
(Minute)
5C
C zone
7C
A zone
20C
B zone
*
* The minimum value of Te sensor 10 to 15 minutes
after start of operation is stored in memory as Te0.
Table 1
A zone
B zone
C zone
39
Description
The necessity of defrost operation is
detected by the outdoor heat exchanger
temperature. The conditions to detect the
necessity of defrost operation differ in A,
B, or C zone each. (Table 1)
<Defrost operation>
Defrost operation in A to C zones
1) Stop operation of the compressor for
20 seconds.
2) Invert (ON) 4-way valve 10 seconds
after stop of the compressor.
3) The outdoor fan stops at the same time
when the compressor stops.
4) When temperature of the indoor heat
exchanger becomes 38C or lower,
stop the indoor fan.
<Finish of defrost operation>
Returning conditions from defrost
operation to heating operation
1) Temperature of outdoor heat exchanger
rises to +8C or higher.
2) Temperature of outdoor heat exchanger
is kept at +5C or higher for 80 seconds.
3) Defrost operation continues for
15 minutes.
<Returning from defrost operation>
1) Stop operation of the compressor for
approx. 50 seconds.
2) Invert (OFF) 4-way valve approx. 40
seconds after stop of the compressor.
3) The outdoor fan starts rotating at the
same time when the compressor starts.
Description
8. Louver control This function controls the air direction of the indoor unit.
1) Louver
The position is automatically controlled according to the operation
position
mode (COOL/HEAT).
The set louver position is stored in memory by the microcomputer,
and the louver returns to the stored position when the next operation
is performed. (Cooling/Heating memory position)
The angle of the louver is indicated as the louver closes fully is 0.
1) Louver position in cooling operation
Air direction
Horizontal
blowing
3) Swing
Inclined
blowing
Blowing
downward
Inclined
blowing
Horizontal
blowing
40
Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.
Description
<Cooling operation>
<Cooling operation>
This function operates the air conditioner with the difference
between the set and the room temperature as shown in the
following figure.
12
11
10
9
8
7
6
5
4
3
2
+6.5
+6.0
+5.5
+5.0
+4.5
+4.0
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Dry Max
*12
*11
*10
*9
*8
Min
Hz
TSC
-0.5
-1.0
-2.0
OFF
1H
2H
3H
4H
FAN
Fan speed depend on presetting and can change every speed.
Zone Frequency
TA
Time
Cool min
20
20
13
13
DRY max
35
37
31
35
<Heating operation>
<Heating operation>
Time Compressor
speed
0Hz
30 minutes
0
0.5
1.0
1.5
2.0
2.5
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
A
B
A zone
aHz
B zone
a to cHz
C zone
cHz
C
42NQV025H
42NQV035M
42NQV035H
42NQV045M
42NQV045H
20
13
13
50
43
50
Hz
41
YES
Filter lamp ON
NO
NO
YES
YES
Description
1) When pressing [RESET] button, the
temporary [AUTO] operation starts.
2) When keeping [RESET] button pressed
for 3 seconds or more, Pi, Pi, Pi sound is
heard and [AUTO RESTART] control is
changed.
3) When keeping [RESET] button pressed
for 10 seconds or more, Pi sound is
heard and the temporary [COOL]
operation starts.
4) If the filter lamp goes on, press [RESET]
button to go off the filter lamp, and then
press [RESET] button again.
5) To stop the temporary operation, press
the button again.
NO
Switch to [AUTO RESTART] control.
98C
Control operation
Judges as an error and stops the compressor.
Reduce the compressor speed.
Reduce slowly compressor speed.
Keeps the compressor speed.
If the operation is performed with lower speed than one
commanded by the serial signal, speed is slowly raised
up to the commanded speed.
Operates with speed commanded by the serial signal.
42
1. Purpose
This function detects error on the
refrigerating cycle or error on the compressor, and performs protective control.
2. Operation
Control of the compressor speed
The speed control is performed as
described in the left table based upon
the discharge temperature.
Description
12. Pulse
Modulating
valve (P.M.V.)
control
Starting up
Initialize
Move to
initial position
Compressor ON
SH control
Td
release control
Stop by
remote controller
Power OFF
Defrost
43
"B" Display
"00" Display
44
Description
1. Purpose
This operation is to operate only one
indoor unit using one remote controller.
2. Description
When operating one indoor unit in a
situation where two indoor units have
been installed in the same room or
nearby rooms, this operation prevents the
remote controller signal from being
received simultaneously by both units,
thus preventing both units from operating.
3. Operation
The indoor unit on which the remote
controller selection has been set to B
receives the signal of the remote controller also set to B.
(At the factory the remote controller
selection is set to A on all the indoor
units. There is no A setting display.)
Description
15. FILTER
Indicator
45
Description
Purpose
To start the unit immediately for the purpose of
testing, trial...etc, short timer can be used.
maintenance of the unit.
Short Timer Setting
j
k
m
n
1 , 4
ON
OFF
20. Night-Light
(42NQV0325H,
42NQV035H,
42NQV045H) only
ON
OFF
46
Purpose
Motions
The unit is on standby.
RESET button
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
RESET
RESET button
While the filter check indicator is on, the RESET button has the function of filter reset betton.
47
Motions
The unit is on standby.
RESET button
Motions
The unit is in operation.
RESET button
NOTE :
The Everyday Timer is reset while a command signal
can be received from the remote controller even if it
stopped due to a power failure.
48
1
2
3
4
5
6
7
8 On timer button (
9 Off timer button (
!
"
#
$
%
&
(
)
~
+
ON
OFF
13
5
4
)
14
15
6
16
12
ON
10
19
17
18
1. AUTOMATIC OPERATION
To automatically select cooling, heating, or fan only operation.
MODE : Select A.
2. Press
MODE : Select A.
1. Press
2. Press
, or Fan only
Cooling: Min. 17C, Heating : Max, 30C, Fan Only: No temperature indication
3. Press
HIGH
9
11
Note : Some models, remote will have text above the buttons.
1. Press
OFF
, MED
49
, MED+
, or
2. Press
4. Hi-POWER OPERATION
To automatically control room temperature and airflow for faster cooling or heating
operation (except in DRY and FAN ONLY mode)
Press
5. ECO OPERATION
To automatically control room to save energy (except in DRY and FAN ONLY mode)
Press
Note: Cooling operation; the set temperature will increase automatically 1 degree/
hour for 2 hours (maximum 2 degrees increase). For heating operation the
set temperature will decrease.
6. TEMPORARY OPERATION
In case of the misplaced or discharged remote control
Pressing the RESET button, the unit can start or stop
without using the remote control.
Operation mode is set on AUTOMATIC
operation, preset temperature is 24C
and fan operation is automatic speed.
7. TIMER OPERATION
Setting the ON Timer
Press
ON
Press
OFF
Press
SET
Press
SET
Press
CLR
Press
CLR
Everyday timer allows the user to set both the ON & OFF timers and will be activated on a daily basis.
Setting Everyday Timer
SET
Press
ON
Press
Press
OFF
Press
button during the ( or )
mark flashing.
SET
During the every day timer is activation, both arrows ( or ) are indicated.
Note:
Keep the remote control in accessible transmission to the indoor unit;
otherwise, the time lag of up to 15 minutes will occur.
The setting will be saved for the next same operation.
50
51
2. Mode indicator
Indicates the current operation mode.
(AUTO : Automatic control, A : Auto changeover
: Cool,
: Dry,
control,
: Heat)
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
Press the Hi-POWER button to start and press it
again to stop the operation.
3. Temperature indicator
Indicates the temperature setting.
(17C to 30C)
7.
button.
(PRESET) indicator
Flashes for 3 seconds when the PRESET button is
pressed during operation.
mark is shown when holding down the
The
button for more than 3 seconds while the mark is
flashing.
Press another button to turn off the mark.
8. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operation.
9
2
10
4
3
52
170
mm
65 mm or more
or m
ore
Hook
Hoo
1 Installation
plate
170
mm
or m
ore
Air fi
lter
Wall
Shield pipe
(Atta
ch to
the f
ront
pane
l.)
8 Pan head
wood screw
4 Remote control
holder
Nano Silver
6
Ginseng filter Nano Silver
Ginseng filter
600 mm or more
Vinyl tape
Apply after carrying
out a drainage test.
3 Batteries
100
mm
or
Right
Rear
right
ore
Bottom
right
rm
100
o
mm
Saddle
mo
re
ore
rm
600
o
mm
600
Extension
drain hose
(Not available,
provided by installer)
mm
or
mo
re
Loading Batteries
1. Remove the battery cover.
2. Insert 2 new batteries (AAA type)
following the (+) and ( ) positions.
C
L
3 Batteries
53
Left
Rear
left
Bottom left
Parts name
Qty
Refrigerant piping
Liquid side (Outer diameter) Gas side (Outer diameter)
42NQV025H,42NQV035H,42NQV035M
6.35 mm
9.52 mm
42NQV045H,42NQV045M
6.35 mm
12.7 mm
1 ea.
Elongated
drain hole
Suction side
()
Diffuser
Drain hole
()
Part No.
Part No.
Installation plate 1
Drain nipple* x 1
Battery 2
<Others>
Name
Owners manual
Remote control
holder mounting screw
3.1 16L 2
54
Installation manual
Important information and warning*
B/W strips*
(Energy efficiency labels)
Changes
Gauge manifold
Charge hose
Electronic balance
for refrigerant charging
Torque wrench
(nominal diam. 1/2, 5/8)
Incidentally, the refrigerant cylinder comes with the refrigerant designation (R410A) and protector coating in the
U. Ss ARI specified rose color (ARI color code: PMS 507).
Also, the charge port and packing for refrigerant cylinder require 1/2 UNF 20 threads per inch corresponding to
the charge hoses port size.
55
Drilling a hole
When install the refrigerant pipes from the rear.
Pipe
hole
65 mm
CAUTION
Direct sunlight on the indoor unit wireless
receiver should be avoided.
The microprocessor in the indoor unit should
not be too close to r-f sources.
(For details, see the owner's manual.)
100 mm
Fig. 10-3-2
1. After determining the pipe hole position on the
installation plate ( ) drill the pipe hole (65
mm) at a slight downward slant to the outdoor
side.
Remote controller
Should be placed where there are no obstacles,
such as curtains, that may block the signal.
Do not install the remote controller in a place
exposed to direct sunlight or close to a heating
source, such as a stove.
Keep the remote controller at least 1 m away from
the nearest TV set or stereo equipment.
(This is necessary to prevent image disturbances or
noise interference.)
The location of the remote controller should be
determined as shown below.
NOTE :
When drilling into a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe hole
brim ring sold separately.
Indoor unit
(Side view)
82.5
(Top view)
Indoor unit
170
85
Reception
range
Remote
controller
Reception
range
Pipe hole
Remote controller
Hook
Indoor unit
Thread
Pipe hole
Weight
Fig. 10-3-3
Fig. 10-3-1
56
Hook
Mounting screw
Installation
plate
62
Hook
NOTE :
Wire type :
More than 1.5 mm2 H07RN-F or 60245IEC66.
CAUTION
CAUTION
When installing the installation plate with mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Anchor bolt
Projection
15mm or less
NOTE :
Perform wiring work being sure the wire length is
long enough.
Fig. 10-3-4
5 mm dia. hole
Clip anchor
(local parts)
Fig. 10-3-5
CAUTION
Failure to securely install the unit may result in
personal injury and/or property damage if the
unit falls.
In case of block, brick, concrete or similar type
walls, drill 5 mm dia. holes in the wall.
Insert clip anchors for the mounting screws.
NOTE :
Install the installation plate using mounting screws
between 4 to 6, being sure to secure all four
corners.
57
CAUTION
Terminal cover
1
Bottom left
Left
Earth line
Screw
Screw
Bottom right
Right
Connecting cable
Die-cutting
Front panel slit
Rear left
Screw
Piping preparation
Rear right
Terminal block
Changing
drain hose
Cord clamp
Fig. 10-3-10
Fig. 10-3-6
Terminal block
Fig. 10-3-7
Connecting cable
abou
t 15
cm
Fig. 10-3-8
Fig. 10-3-11
110 mm
10 mm
Earth line
10 mm
50 mm
Heat insulator
Fig. 10-3-9
NOTE :
WIRE TYPE : more than 1.0mm2.(H07 RN-F or 60245
IEC 66).
Drain hose
Fig. 10-3-12
58
Slit
Fig. 10-3-16
4 mm
Fig. 10-3-13
No gap
Insert a hexagon
wrench (4mm)
Bend the connecting pipes so that they are positioned within 43 mm above the wall surface.
If the connecting pipes are positioned more than
43 mm above the wall surface, the indoor unit may
be unstable.
When bending the connecting pipe, make sure to
use a spring bender to avoid crushing the pipe.
Fig. 10-3-14
Outer diameter
Bending radius
6.35 mm
30 mm
9.52 mm
40 mm
12.7 mm
50 mm
Gas side
230 mm
CAUTION
Liquid side
43 mm
R30 or less (6.35), R40 or less (9. 52), R50 or less (12. 7)
Use polishing (polyethylene core or the like for bending pipe).
Fig. 10-3-17
Slit
Fig. 10-3-15
NOTE :
If the pipe is incorrectly bent, the indoor unit may be
unstable on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary
pipes and wrap the facing tape around them.
59
CAUTION
NOTE :
Hole should be made at a slight downward slant
on the outdoor side.
Do not rise the drain hose.
Indoor unit
Auxiliary pipes
Connecting
cable
50 mm
or more
Installation
plate
Fig. 10-3-18
Fig. 10-3-21
2. Put water in the drain pan and make sure that the
water is being drained outside.
3. When connecting extension drain hose, insulate
the connection part of extension drain hose with
shield pipe.
Shield pipe
Fig. 10-3-22
CAUTION
Install the drain pipe for proper drainage.
Improper drainage can result in water dripping
inside the room.
Hook here
1 Installation
plate
Push (unhook)
Hook
Fig. 10-3-19
Wall
Drain
guide
Space for
pipes
Push
Push
Fig. 10-3-23
Fig. 10-3-20
60
CAUTION
1. Install the outdoor unit without anything
blocking the discharging air.
2. When the outdoor unit is installed in a place
always exposed to strong winds like on the
coast or on a high story of a building, secure
the normal fan operation using a duct or a
wind shield.
3. Especially in windy areas, install the unit to
prevent the admission of wind.
4. Installation in the following places may result
in trouble.
Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are
likely to be generated, such as from audio
equipment, welders, and medical equipment.
Strong
wind
Fig. 10-4-1
61
Flaring
1. Cut the pipe with a pipe cutter.
90
Obliquity
Roughness
Fig. 10-4-4
2. Insert a flare nut into the pipe, and flare the pipe.
R410A
tool used
Conventional
tool used
6.35
0 to 0.5
1.0 to 1.5
9.52
0 to 0.5
1.0 to 1.5
12.7
0 to 0.5
1.0 to 1.5
Base plate
9 Drain nipple
Outer dia. of
copper pipe
R410A
6.35
1.5 to 2.0
9.52
1.5 to 2.0
12.7
2.0 to 2.5
Die
Pipe
Fig. 10-4-5
Fig. 10-4-2
Warp
Fig. 10-4-6
B
+0
0.4
R22
6.35
9.1
9.0
9.52
13.2
13.0
12.7
16.6
16.2
9 Drain nipple
Commercially available
drain hose
Fig. 10-4-3
62
Flare nut
Externally
threaded side
Internally
threaded side
Use a wrench
to secure.
Fig. 10-4-7
CAUTION
Do not apply excessive force.
Otherwise, the nut may break.
(Unit : Nm)
Outer dia. of copper pipe
Tightening torque
6.35 mm
9.52 mm
12.7 mm
Pressure gauge
-101kPa (76cmHg)
Manifold valve
Handle Lo
Charge hose (For R410A only)
Connecting pipe
Handle Hi
(Keep full closed)
Charge hose
(For R410A only)
Vacuum pump adapter for
counter-flow prevention
(For R410A only)
Vacuum
pump
Flare at
outdoor unit
side
Fig. 10-4-8
Fig. 10-4-9
CAUTION
10-4-4. Evacuating
After the piping has been connected to the indoor
unit, perform the air purge.
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using a vacuum pump.
Do not use the refrigerant in the outdoor unit.
For details, see the vacuum pump manual.
63
1 2 3
Service port
10
10
10
10
40
30
L N
40
30
Earth line
Earth line
Connecting cable
Power cord
Fig. 10-4-12
4m
Fig. 10-4-10
Installation fuse
rating
38NYV025H
38NYV035M
38NYV035H
38NYV045M
38NYV045H
13.0 A
16 A breaker or fuse
(All types can be used.)
Power cord
Connection cable
CAUTION
Incorrect wiring connection may cause electrical parts to burn out.
Be sure to comply with local regulations/codes
when running the wire from outdoor unit to
indoor unit.
(Size of wire and wiring method etc.)
Every wire must be securely connected.
If incorrect or incomplete wiring is carried out,
fire or smoke may result.
Prepare the power supply for the exclusive use
of the air conditioner.
This product can be connected to the main
breaker.
Connection to fixed wiring:
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring when connecting to a main breaker circuit.
Terminal block
Connecting cable
Power cord
Fig. 10-4-11
64
Valve Cover
Fig. 10-5-1
RESET
RESET button
Fig. 10-5-2
B Display
00 Display
Information
The product was shipped with Auto Restart
function in the OFF position.
Turn it ON as required.
ON
OFF
Fig. 10-5-1
65
Page
Troubleshooting Procedure
Troubleshooting Procedure
No.
Page
First Confirmation
69
Primary Judgment
70
83
70
84
71
89
74
10
93
82
IGBT 6
Compressor
Fan motor
Shared potential
Driver
MCU
Amplifier
Driver
Amplifier
Fig. 11-1
66
FET 6
Sensor leads
Fig. 11-2
Do NOT lay the circuit board assembly flat.
Plug of
soldering iron
Inverter cover
P. C. board
(Soldered surface)
Fig. 11-3
67
Description
For smooth operation of the compressor, the compressor motor speed is restricted to Max. 41 rps for 2 minutes, and Max.91 rps for 2 minutes to 3 minutes, respectively after the operation has started.
The compressor motor speed may decrease by hightemp. release control (Release protective operation by
temp.-up of the indoor heat exchanger) or current
release control.
68
Check
code
Block display
OPERATION (Green)
Flashing display (1 Hz)
OPERATION (Green)
Flashing display (5 Hz)
OPERATION (Green)
TIMER (Yellow)
Flashing display (5 Hz)
OPERATION (Green)
FILTER (Orange)
Flashing display (5 Hz)
OPERATION (Green)
TIMER (Yellow)
FILTER (Orange)
Flashing display (5 Hz)
Indoor indication
lamp flashes.
Which lamp
does flash?
NOTES :
1. The contents of items B and C and a part of item E are displayed when air conditioner operates.
2. When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.
3. The check codes can be confirmed on the remote controller for servicing.
69
Press [
] button with a tip of pencil to set the
remote controller to the service mode.
is indicated on the display of the remote
controller.
OF F
ON
Press [
] or [
] button
If there is no fault with a code, the indoor unit will beep
once (Beep) and the display of the remote controller will
change as follows :
to
ON
OF F
OFF
3
Alphanumeric characters are
used for the check codes.
is 5.
is 6.
is A.
is B.
is C.
is D.
Press [
Fig. 11-4-1
70
button.
Table 11-4-1
Block distinction
Check
code
Block
Air
conditioner
status
Cause of operation
Operation
continues.
Displayed when
error is detected.
Operation
continues.
Displayed when
error is detected.
All off
Displayed when
error is detected.
Not
displayed
Operation
continues.
Displayed when
error is detected.
Connecting
cable and
serial signal
Operation
continues.
Flashes when
trouble is detected
on Return serial
signal, and normal
status when signal
is reset.
Indoor P.C.
board etc.
71
Block
Check
code
Air
conditioner
status
Cause of operation
Remarks
Inverter over-current
protective circuit
operates. (Short time)
All off
Displayed when
error is detected.
Position-detect circuit
error or short-circuit
between windings of
compressor
All off
Displayed when
error is detected.
Current-detect circuit
error
All off
Displayed when
error is detected.
All off
Displayed when
error is detected.
All off
Displayed when
error is detected.
All off
Displayed when
error is detected.
Not
displayed
Operation
continues
Outdoor P.C.
board
Others
(including
compressor)
Outdoor P.C.
board
Operation
continues
Displayed when
error is detected.
Displayed when
error is detected.
1. Trouble on compressor
2. Trouble on wiring of compressor
(Missed phase)
Discharge temp.
exceeded 117C
All off
Displayed when
error is detected.
Break down of
compressor
All off
Displayed when
error is detected.
72
Operation
Measures
NO
Item by symptoms
NO
NO
Remote controller is defective.
Is fuse (F01)
of indoor control
board blown?
YES
NO
NO
Is voltage
(DC12V or 5V)
indicated on rear of
indoor control
board normal?
YES
Microcomputer
is defective.
Replace main
P.C. board
Be sure to disconnect the motor connector CN31 after shut off the power supply, or it will be a cause of
damage of the motor.
NO
Does OPERATION indicator flash?
YES
NO
Correct wiring.
YES
To item of
Power supply is not turned on.
73
Operation
Check Item
Considerable principle cause
Turn off power supply once, and
5 second later, turn it on again.
Measures
NO
Item by symptoms
NO
NO
Remote controller is defective.
Is fuse (F01)
of indoor control
board blown?
YES
Does fan
YES
motor connector
between CN10 1
3 short-circuit?
NO
NO
Is voltage
(DC12V or 5V)
indicated on rear of
indoor control
board normal?
Is DC310340V
supplied between
CN10 1 3 ?
NO
NO
YES
Microcomputer
is defective.
Replace main
P.C. board
YES
Replace fan
motor.
Be sure to disconnect the motor connector CN31 after shut off the power supply, or it will be a cause of
damage of the motor.
NO
Does OPERATION indicator flash?
YES
NO
Correct wiring.
YES
To item of
Power supply is not turned on.
74
YES
Control P.C. board failure
Start to operate
indoor unit in cooling
operation at airflow
level LOW.
Does indoor
fan operate?
Dose AC120V or
ligher voltage apply to
NO
NO
Replace main
P.C. board.
of the motor?
YES
YES
Is it possible to
rotate cross-flow fan by
hand properly?
NO
Replace
bearing.
YES
Is it possible to
change airflow level
to HIGH?
NO
YES
When rotating the
cross-flow fan by hand
at the operation stopNO
NO
condition, is the rotation signal
(DC+12V 0V) detected between
2 (Purple lead) and 3
(Blue lead) of the motor
connector (CN33)
(1 pulse / 1 revolutio).
YES
Fan motor
operates normally.
75
Is it possible to detect
YES DC
1V or more between
NO
5 + and 3 of
Peplace indoor
fan motor.
NO
YES
Start to operate
indoor unit in cooling
operation at airflow
level LOW.
Does indoor
fan operate?
NO
YES
Is it possible to detect
DC 310340V between
1 + and 3 of motor
connector (CN31).
NO
YES
(Motor connection condition)
Is it possible to detect DC 15V
between 4 + and 3 of
motor connector (CN31).
NO
YES
Is it possible to detect
DC 15V between 4 +
and 3 of motor
connector (CN31).
NO
Peplace main
P.C. board.
YES
Start to operate the
indoor unit in except
heating operation.
NO
At this time, is it possible to
detect DC 1V or more between
5 + and 3 of motor
connector (CN31)?
YES
Is it possible to
change airflow level
to HIGH?
NO
YES
NO
YES
Is it possible to
rotate cross-flow fan by
hand properly?
NO
Peplace
bearing.
YES
Fan motor
operates normally.
NO
YES
76
6 (Blue)
Yellow
Measure voltage between 3 (GND : BLACK)
and 5 (V line : YELLOW) of motor connector (CN31)
while indoor fan motor is rotating.
5 (Yellow)
4 (White)
Black
3 (Black)
2
1 (Red)
DC 1.0V or more
Under DC 1.0V
DC
Motor is defective.
Replace motor.
77
5
CN31
WHI
BLK
RED
BLK
3 3
WHI
2 2
RED
1 1
BLK
WHI
RED
BLU
3
CN33 2 PUR
1 GRY
BLU
3 3
PUR 2 2
GRY 1 1
BLU
PUR
GRY
3
1
P.C. board
(Black) -
(Red)
Between
(Black) -
(White)
Between
(Red) -
(White)
Resistance value
74 15
100 20
174 35
78
Is transmission
mark indicated?
YES
Is receiver
on indoor unit
exposed to
direct sunlight?
NO
YES
Is there any
thyristor
fluorescent light
nearby?
NO
NO
YES
YES
Batteries are
exhausted.
Is transmission
mark indicated?
YES
NO
YES
NO
NO
YES
Remote controller
is defective.
P.C. board
is defective.
Avoid direct
sunlight.
Replace
P.C. board.
Replace
batteries.
79
Normal
operation
Replace
remote controller.
S5277G
White
Terminal block
Tester
Normal time
: Voltage swings between DC15 and 60V. ...................Inverter Assembly check (11-8-1.)
Abnormal time : Voltage does not vary.
Gas shortage
Gas leak
Pipe clogging
2) If the unit stops once, it does not operate until the power will be turned on again.
3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)
Gas leak
P.M.V. is defective.
80
1C
1E
Gas leakage,
disconnection of TS/TC
sensors (Check code 02, 1C)
NO
Set it correctly.
YES
NO
Set it correctly.
YES
NO
YES
NO
Set it correctly.
YES
Check the operating pressure from service port, and add gas if pressure is low.
81
YES
Replace valve.
Add gas.
Item
Contents
Preparation
Remove connector
of compressor.
Check
NG
OK
Replace fuse.
Check
electrolytic
capacitor, diode
block (DB01),
etc.
OK
Discharging position
(Discharging period
10 seconds or more)
NG
NO
Operation
YES
Measurement
Remove connector
CN300 of outdoor fan
motor, and using a
tester, check resistance
value between every
phases at motor side.
Check
Stop
OK
Check
Measurement
Replace
outdoor
fan motor.
Plug of
soldering
iron
Check
electrolytic
capacitor, diode
(DB01),
etc.
Does outdoor
fan rotate?
NG
Check
Check
terminal voltage
of electrolytic
capacitor.
Summary
OK if 500F or 760F
DC280 to 380V
Remove CN300 while
pushing the part indicated
by an arrow because CN300
is a connector with lock.
82
Resistance between
phases should be
approx. 55 to 77
Should be 10M or
more.
Item
Contents
Check
Replace control
board assembly.
Check
compressor
winding
resistance.
NG
Is not grounded.
OK if 10M or more
Is not short-circuited
between windings.
OK if 0.51 0.57
(Check by a digital tester.)
OK
Replace
control board.
Summary
Operation
Replace
compressor.
83
Procedure
Check points
84
Causes
Table 11-8-1
No.
Procedure
Check points
Causes
85
Table 11-8-1
No.
Procedure
86
Table 11-8-1
No.
7
Procedure
Check points
Causes
87
+5V
+12V
100
Resistance value (k )
90
80
TD
70
60
50
40
30
20
TA, TC, TO, TE, TS
10
0
0
10
20
30
40
50
Temperature (C)
88
TD
TA
TC
TO
TE
TS
GND
+12V
+5V
100
Resistance value (k )
90
80
TD
70
60
50
40
30
20
TA, TC, TO, TE, TS
10
0
0
10
20
30
40
50
Temperature (C)
89
TD
TA
TC
TO
TE
TS
Part name
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Temperature
Sensor
TA, TC (k)
10C
20C
25C
30C
40C
20.7
12.6
10.0
7.9
4.5
Remote controller
Louver motor
MP24Z3T
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25C)
White
Yellow
Yellow
Yellow
Yellow
1
2
3
4
5
1
2
3
4
5
Position
Resistance value
1 to 2
1 to 3
1 to 4
1 to 5
250 20
Part name
Compressor
(Model : DA111A1F-20F1)
Checking procedure
Position
38NYV035H, 38NYV045H,
38NYV045M
(Model : DA89X1C-23FZ)
38NYV025H, 38NYV035M
White
Black
0.88 to 0.98
1.04 to 1.16
Under 20C
White
Red - White
White - Black
Black - Red
Resistance value
DA111A1F-20F1 DA89X1C-1F-23FZ
Black
Position
Resistance value
Red - White
20 to 22
White - Black
20 to 22
Black- Red
20 to 22
Under 20C
4
6 GR
COM
Y R BL
COM 2
Position
Resistance value
Gray - White
43 to 49
Gray - Orange
43 to 49
Red- Yellow
43 to 49
Red- Blue
43 to 49
Under 20C
5
Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)
Temperature
10C
20C
25C
30C
40C
50C
TD (k )
100
64
50
41
27
18
TO,TS,TE (k )
20.7
12.6
10.0
7.9
4.5
Sensor
90
Electrolytic capacitor
(For boost, smoothing)
Checking procedure
1.
2.
3.
4.
5.
6.
No.
C12
C13
C14
MCC-5009
Soldered
surface
Diode block
Tester rod
+~~
1 2 3 4
(DBO1)
~2
~3
+1
~2
~3
Resistance value
in good product
91
NO
CN300
YES
If the resistance value between
1 (Red lead)
2 (White lead)
2 (White lead)
3 (Black lead)
3 (Black lead)
1 (Red lead)
of the connector
(CN300 : Motor winding)
is 17 to 25, it is normal.
NO
YES
Fan motor is normal.
NOTE :
However, GND circuit error inside of the motor may be accepted in some cases when the above check is
performed.
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.
92
Part name
Front panel
Procedures
1) Stop operation of the air conditioner and
turn off its main power supply.
2) Open the air inlet grille, push the arm
toward the outside, and remove the grille.
3) Remove the left and right air filters.
93
Remarks
Part name
Front panel
Procedures
4) Press "PUSH" part under the front panel
and remove hooks of the front panel from
the installation plate.
Remarks
Installation plate
Front panel
Press
2 Screws
Three hooks
94
Part name
Electric parts
box assembly
Procedures
Remarks
Electric part
box cover
TC sensor
Earth Screw
Fan motor
connector
Fixing screw
AC fan motor
connector
(42NQV025H,
42NQV035H,
Louver motor 42NQV035M)
connecto
95
Part name
Procedures
Remarks
Horizontal louver
Evaporator
(Heat exchanger)
2 screws
Screw
96
Part name
Bearing
Procedures
Remarks
Two screws
97
Bearing
Bearing base
Part name
Fan motor
Procedures
Remarks
Set screw
Motor cover
Two screws on
motor band
Two Screws
98
Part name
Procedures
<Caution at reassembling>
1) To incorporate the fan motor, remove the fan
motor rubber (at shaft core side), incorporate
the motor into the position in the following
figure, and then install the fan motor.
U groove
99
Remarks
5 mm
Part name
Common procedure
Procedure
Remarks
R01
CN31
R02
CN33
C01
FUSE
L01
C02
C03
IC12
CN51
C121
T01
100
C133
GND
+12V
101
+5V
Part name
Common
procedure
Remarks
Procedure
1. Detachment
Upper cabinet
NOTE
Wear gloves for this job.
Otherwise, you may injure your
hands on the parts, etc.
Waterproof cover
Valve cover
2. Attachment
1) Attach the water-proof cover.
NOTE
The water-proof cover must be
attached without fail in order to
prevent rain water, etc. from entering
inside the indoor unit.
2) Attach the upper cabinet.
(ST1T4 10L 5 pcs.)
3) Perform cabling of connecting cable,
and attach the cord clamp.
Fix the cord clamp by tightening
the screws (ST2T 4 x 14L 3 pcs.),
fitting 2 concave parts of the cord
clamp to each connecting cables.
4) Attach the valve cover.
(ST1T 4 x 10L 2 pcs.)
Insert the upper part into the square
hole of the side cabinet, set hook
claws of the valve cover to square
holes (at three positions) of the main
unit, and attach it pushing upward,
102
These 2 bending
parts shall be
put inside of a unit
by bending
these 2 ports.
This part shall be
put on
the side cabinet.
Part name
Procedure
Front cabinet
1. Detachment
1) Perform step 1 in .
2) Remove the fixing screws (ST1T4 10L
2 pcs.) used to secure the front cabinet
and inverter cover, the screws (ST1T4
10L 4 pcs.) used to secure the front
cabinet at the bottom, and the fixing
screws (ST1T4 10L 2 pcs.) used to
secure the motor base.
The front cabinet is fitted into the side
cabinet (left) at the front left side so
pull up the top of the front cabinet to
remove it.
2. Attachment
1) Insert the claw on the front left side into
the side cabinet (left).
2) Hook the bottom part of the front right
side onto the concave section of the
bottom plate. Insert the claw of the side
cabinet (right) into the square hole in the
front cabinet.
3) Return the screws that were removed
above to their original positions and
attach them.
Remarks
Front cabinet
Claw
Square
hole
Concave section
103
Part name
Inverter
assembly
Procedure
1) Perform work of item 1 in .
2) Remove screw (ST1T4 10L 2 pcs.) of the
upper part of the front cabinet.
If removing the inverter cover in this
condition, P.C. board can be checked.
If there is no space above the unit, perform
work of 1 in .
Remarks
Inverter cover
P.C. board
(Soldered surface)
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering
iron
Requirement
As each connector has a lock mechanism, avoid to remove the connector by
holding the lead wire, but by holding the
connector.
104
Part name
Procedure
Control board
assembly
Remarks
CN603
CN601
CN600
CN701
CN700 CN602
CN300
NOTE
These connectors have a disconnect prevention
mechanism: as such, the lock on their housing
must be released before they are disconnected.
2. Remove the control board assembly from the P.C.
board base. (Remove the heat sink and control
board assembly while keeping them screwed
together.)
NOTE
Disengage the four claws of the P.C. board base,
hold the heat sink, and lift to remove it.
3. Remove the two fixing screws used to secure the
heat sink and control board assembly.
4. Mount the new control board assembly.
NOTE
When mounting the new control board assembly,
ensure that the P.C. board is inserted properly
into the P.C. board support groove.
105
Part name
Side cabinet
Procedure
Remarks
Detail A
Fan motor
Detail B
106
Detail C
Propeller fan
Fan motor
Flange nut
Part name
Procedure
Compressor
Reactor
Remarks
107
Partition
board
Compressor
Valve
fixing
plate
Reactor
Part name
Electronic
expansion valve
coil
Procedure
1. Detachment
1) Perform step 1 in , all the steps in
and 1 in .
2) Remove the coil by rotating it at 90
toward either direction.
Remarks
Lead
connecting part
Notch
2. Attachment
1) Insert a valve coil in a volve body to the
bottom, and fix it by rotating at 90 toword
either direction. And confirm to fix it surely.
e
tat
Ro 0
9
Coil inserting
position
Fan guard
1. Detachment
1) Perform work of item 1 of .
2) Remove the front cabinet, and put it down
so that fan guard side directs downward.
Coil fixing
position
Fixing hole
for coil
Minus screwdriver
Hooking claw
108
Part name
Procedure
Remarks
Arrow D
Detail B
Detail C
Detail A
12
13
14
Detail A
TS sensor
Detail B
TD sensor
Arrow D
TO sensor
TO sensor
holder
CAUTION
During the installation work (and on its completion), take care not to damage the coverings of
the sensor leads on the edges of the metal plates or other parts. It is dangerous for these
coverings to be damaged since damage may cause electric shocks and/or a fire.
CAUTION
After replacing the parts, check whether the positions where the sensors were installed are the
proper positions as instructed. The product will not be controlled properly and trouble will result
if the sensors have not been installed in their proper positions.
109
Location
No.
Part
No.
201
202
43T21397
43T21399
202
203
204
205
206
43T21371
43T22312
43T70313
43T20325
43T11301
206
43T11320
207
208
209
211
212
213
214
215
216
217
218
219
43T83003
43T60382
43T82310
43T19333
43T09408
43T03360
43T39327
43T39328
43T39329
43T09409
43T79313
43T44402
219
43T44403
Description
Location
No.
Part
No.
221
43T00491
221
43T00490
222
223
224
43T80321
43T80322
43T09412
224
43T09413
224
43T09414
224
43T09415
226
227
43T62328
43T69649
227
43T69618
227
43T69649
LOUVER MOTOR
FAN MOTOR ASSEMBLY(42NQV035H)
(42NQV035M),(42NQV025H)
FAN MOTOR(42NQV045H,42NQV045M)
MOLD BEARING ASSEMBLY
DRAIN HOSE
CROSS FLOW FAN ASSEMBLY
PIPE SHIELD(42NQV035H)
(42NQV035M),(42NQV025H)
PIPE SHIELD(42NQV045H),
(42NQV045M)
REMOTE CONTROL HOLDER
MOTOR CORD
INSTALLATION PLATE
SENSOR FIX PLATE
PIPE HOLDER
BACK BODY ASSEMBLY
BEARING BASE
MOTOR BAND (LEFT)
MOTOR BAND (RIGHT)
HORIZONTAL LOUVER
DRAIN CAP
REFRIGERANT CYCLE ASSEMBLY
(42NQV035H),(42NQV035M),
(42NQV025H)
REFRIGERANT CYCLE ASSEMBLY
(42NQV045H),(42NQV045M)
110
Description
PANEL SERVICE ASSEMBLY
(42NQV035H),(42NQV025H),
(42NQV045H)
PANEL SERVICE ASSEMBLY
(42NQV045M),(42NQV035M)
AIR FILTER (R)
AIR FILTER (L)
GRILLE OF AIR INLET (ORIGINAL,
SILVER)(42NQV035H)
(42NQV025H),(42NQV045H)
GRILLE OF AIR INLET (ORIGINAL,
WHITE)(42NQV045M),(42NQV035M)
GRILLE OF AIR INLET (OPTIONAL,
WHITE)(42NQV035H)
(42NQV025H),(42NQV045H)
GRILLE OF AIR INLET (OPTIONAL,
SILVER)(42NQV035M)
TERMINAL COVER
WIRELESS REMOTE
CONTROL(42NQV035H)
WIRELESS REMOTE CONTROL
(42NQV035M),(42NQV045M)
WIRELESS REMOTE CONTROL
(42NQV025H),(42NQV045H)
Location
No.
Part
No.
401
402
403
404
405
43T69319
43T60002
43T50318
43T62003
43T69634
Description
TC SENSOR
TERMINAL BLOCK; 3P
TEMPERATURE SENSOR
CORD CLAMP
PC BOARD ASSY,WRS-LED
(42NQV025H),(42NQV035H),
(42NQV045H)
Location
No.
Part
No.
405
43T69633
406
406
406
406
406
43T69635
43T69636
43T69637
43T69638
43T69639
111
Description
PC BOARD ASSY,WRS-LED
(42NQV035M),(42NQV045M)
PC BOARD(42NQV045M)
PC BOARD(42NQV045H)
PC BOARD(42NQV035M)
PC BOARD(42NQV025H)
PC BOARD(42NQV035H)
19 : BIMETAL THERMO
29 : DRAIN NIPPLE
31 : HOLDER,SENSOR(TE) (FOR PIPE O.D. 6.35)
32 : HOLDER,SENSOR(TD) (FOR PIPE O.D. 8.0)
33 : HOLDER,SENSOR(TS) (FOR PIPE O.D. 9.52)
112
Location
No.
Part
No.
1
2
3
4
5
6
7
8
43T00468
43T00459
43T42336
43T00452
43T19332
43T19330
43T62325
43T41358
43T41401
43T43410
43T43411
43T43412
10
11
43T46332
43T46331
11
43T46335
12
13
43T47331
43T47332
Description
Location
No.
Part
No.
13
43T47333
14
15
16
17
18
19
21
22
23
24
25
26
27
28
29
30
31
32
33
34
43T00448
43T00451
43T46342
43T63314
43T58306
43T50316
43T20319
43T21375
43T47001
43T47354
43T49335
43T46343
43T63315
43T63319
43T79305
43T39317
43T63318
43T63317
43T63316
43T19331
FRONT CABINET
LEFT CABINET
ASM-BASE
UPPER CABINET
FAN GUARD
PACKED VALVE COVER
ELECTRIC PART COVER
COMPRESSOR(Made in China)
(38NYV025H,38NYV035M)
COMPRESSOR(38NYV035H,
38NYV045H,38NYV045M)
CONDENSER ASSEMBLY
(38NYV025H,38NYV035M)
CONDENSER ASSEMBLY
(38NYV035H,38NYV045M)
CONDENSER ASSEMBLY
(38NYV045H)
VALVE;PACKED 6.35 DIA
VALVE;PACKED 9.52 DIA
(38NYV025H,38NYV035H,38NYV035M)
VALVE;PACKED 12.7 DIA (H4)
(38NYV045H,38NYV045M)
BONNET, 6.35 DIA
BONNET, 9.52 DIA(38NYV025H
,38NYV035H,38NYV035M)
113
Description
BONNET, 12.70 DIA(38NYV045H,
38NYV045M)
FIXING PLATE VALVE
RIGHT CABINET ASSEMBLY
BODY-PMV
COIL-PMV
REACTOR
BIMETAL THERMO
PROPELLER FAN
FAN-MOTOR
NUT FLANGE
BOLT COMPRESSOR (M6)
RUBBER CUSHION
4 WAY VALVE
4WAY VALVE COIL ASSEMBLY
HOLDER,SENSOR
DRAIN NIPPLE
MOTOR BASE CONNECTION PLATE
HOLDER,SENSOR
HOLDER,SENSOR
HOLDER,SENSOR
FIN GUARD
Location
No.
Part
No.
701
43T62320
701
43T62321
702
702
702
702
43T69630
43T69631
43T69656
43T69632
Description
HEATSINK(38NYV025H,
38NYV035H,38NYV035M)
HEATSINKA(38NYV045H,
38NYV045M)
PC BOARD(38NYV025H)
PC BOARD(38NYV035H)
PC BOARD(38NYV035M)
PC BOARD(38NYV045H)
114
Location
No.
Part
No.
702
703
704
705
706
707
43T69657
43T60384
43T60326
43T60377
43T50304
43T62313
Description
PC BOARD(38NYV045M)
TERMINAL BLOCK,6P
FUSE
TEMPERATURE SENSOR
SENSOR;HEAT EXCHANGER
BASE-PLATE-PC
56