Академический Документы
Профессиональный Документы
Культура Документы
299
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
8.7.1General.
All requirements of Section8.5 shall apply to sidewall standard spray sprinklers except as
modified in Section8.7.
BK-NFPA-13HB16-150270-Chp08-P1.indd 299
11/20/2015 3:56:25 PM
. ..
300
8.7.2.1.2 The protection area of the sprinkler shall be established by multiplying the S dimension by the L dimension, as follows:
As = S L
[8.7.2.1.2]
Ordinary Hazard
Noncombustible
or Limited-
Combustible
Ceiling Finish
Combustible
Ceiling
Finish
Noncombustible
or LimitedCombustible
Ceiling Finish
14 [4.3]
14 [4.3]
10 [3.0]
10 [3.0]
12 [3.7]
14 [4.3]
10 [3.0]
10 [3.0]
120 [11.1]
196 [18.2]
80 [7.4]
100 [9.3]
8.7.2.2.2 In any case, the maximum area of coverage of a sprinkler shall not exceed 196ft2
(18.2m2).
Protection areas for sidewall sprinklers differ from those of standard spray upright and pendent sprinklers.
Because of the characteristic horizontal or sideways travel of the sprinkler discharge, the water spray pattern of sidewall sprinklers has a greater tendency of being obstructed or otherwise impacted by furniture
and other objects near the floor. The discharge of standard spray sprinklers is not normally as adversely
affected by furniture and other objects on the floor. In addition, the discharge patterns of sidewall spray
sprinklers are less uniform than those of standard spray sprinklers.
Table 8.7.2.2.1 indicates the maximum allowable protection areas. Table 8.7.2.2.1 also indicates
sprinkler protection areas that are not affected by the building construction above the ceiling. The
sprinkler system is intended to control the fire below the ceiling if properly designed and installed.
Paragraph 8.15.1.2 identifies the concealed spaces above ceilings that are not required to be protected
with sprinklers.
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
HISTORICAL NOTE
The 2010 edition of NFPA13
revised the column headings to clarify that only
the combustibility of the
exposed surfaces is considered when determining the
maximum allowable distance between sprinklers
and the maximum sprinkler protection area.
BK-NFPA-13HB16-150270-Chp08-P1.indd 300
11/20/2015 3:56:26 PM
. ..
8.7.3.1.4 Sidewall spray sprinklers shall not be installed back-to-back without being separated by a continuous lintel or soffit.
8.7.3.1.4.1 The maximum width of the lintel or soffit shall not exceed 16in. (400mm).
8.7.3.1.4.2 The maximum width of the lintel or soffit can exceed 16in. (400mm) when a
pendent sprinkler is installed under the lintel or soffit.
8.7.3.1.5 Where sidewall spray sprinklers are installed on two opposite walls or sides of bays,
the maximum width of the room or bay shall be permitted to be up to 24ft (7.3m) for light
hazard occupancy or 20ft (6.1m) for ordinary hazard occupancy, with spacing as required by
Table 8.7.2.2.1.
Due to the spacing limitations of sidewall sprinklers, only certain size rooms can be effectively protected. Paragraph 8.7.3.1.5 permits sidewall sprinklers to be used in larger rooms under certain conditions, including a maximum room width dimension and the use of two lines of sprinklers on opposite
walls.
Extended coverage sidewall sprinklers provide better coverage for wide rooms and should be used
for rooms over 24 ft (7.3 m) wide.
301
FAQ
8.7.3.1.6 Sidewall spray sprinklers shall be permitted to be installed on opposing or adjacent walls, provided no sprinkler is located within the maximum protection area of another
sprinkler.
Testing has determined the minimum required distance to prevent cold soldering from an adjacent
sidewall sprinkler when both sprinklers are located along the same wall. However, no testing has been
done to determine the minimum distance when sprinklers are located on opposite or adjacent walls (see
8.7.3.1.6). Placing sidewall sprinklers outside the protection area of the adjacent sprinklers is probably
conservative, but it eliminates the potential for the discharge from one sprinkler wetting the thermal element of another.
HISTORICAL NOTE
The maximum room width
allowed for light hazard occupancies when standard sidewall sprinklers are located on
opposite walls was reduced
from 30 ft (9.1 m) to 24 ft
(7.3 m) beginning with the
1996 edition of NFPA 13.
8.7.3.1.7 Where sidewall standard spray sprinklers are installed to protect areas below overhead
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
doors within ordinary hazard occupancy spaces or rooms, protection area and maximum sprinkler spacing for light hazard as specified in Table 8.7.2.2.1 shall be permitted under the overhead
doors.
Sprinkler protection is required under overhead doors so that protection is provided when the doors are
open and the ceiling sprinklers are obstructed. In ordinary hazard areas, this provision permits larger doors
to be protected by a single sidewall sprinkler, reducing the installation costs while not significantly impacting the protection of the space.
8.7.3.2 Maximum Distance from Walls. The distance from sprinklers to the end walls shall
not exceed one-half of the allowable distance permitted between sprinklers as indicated in
Table 8.7.2.2.1.
8.7.3.3 Minimum Distance from Walls.
8.7.3.3.1 Sprinklers shall be located a minimum of 4in. (100mm) from an end wall.
8.7.3.3.2 The distance from the wall to the sprinkler shall be measured perpendicular to the
wall.
The dead-air space described in the FAQ following 8.6.3.3 can also have a detrimental effect on sidewall sprinklers. Exhibit 8.28 shows the correct placement of a sidewall sprinkler adjacent to an end
wall.
BK-NFPA-13HB16-150270-Chp08-P1.indd 301
11/20/2015 3:56:26 PM
. ..
302
Legend
1
Wall
Finished floor
3
2
4 in
(100 .
mm)
min.
8.7.3.4 Minimum Distance Between Sprinklers. Sprinklers shall be spaced not less than
6ft (1.8m) on center unless required by 8.7.4.1.3.1 or unless the sprinklers are separated by
baffles that comply with the following:
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
(1) Baffles shall be arranged to protect the actuating elements.
(2) Baffles shall be of solid and rigid material that will stay in place before and during sprinkler operation.
(3) Baffles shall be not less than 8in. (200mm) long and 6in. (150mm) high.
(4) The tops of baffles shall extend between 2in. and 3in. (50mm and 75mm) above the
deflectors.
(5) The bottoms of baffles shall extend downward to a level at least even with the deflectors.
The reference to 8.7.4.1.3.1 clarifies that the minimum distance rule does not apply to pendent sprinklers
installed immediately adjacent to sidewall sprinklers under soffits deeper than 8 in. (200 mm). Exhibit 8.29
shows an example of compliant pendent and sidewall sprinklers in the same soffit.
8.7.4 Deflector Position from Ceilings and Walls (Standard Sidewall Spray
Sprinklers).
8.7.4.1 Distance Below Ceilings and from Walls.
8.7.4.1.1Ceilings.
8.7.4.1.1.1 Unless the requirements of 8.7.4.1.1.2 are met, sidewall sprinkler deflectors shall
be located not more than 6in. (150mm) or less than 4in. (100mm) from ceilings.
8.7.4.1.1.2 Horizontal sidewall sprinklers shall be permitted to be located in a zone 6in. to
12in. (150mm to 300mm) or 12in. to 18in. (300mm to 450mm) below noncombustible
and limited-combustible ceilings where listed for such use.
BK-NFPA-13HB16-150270-Chp08-P1.indd 302
11/20/2015 3:56:27 PM
. ..
303
Legend
1
Finished ceiling
Finished soffit
4
EXHIBIT 8.29 Pendent and Sidewall Sprinklers in the Same Soffit: (left) shown in a photo (Courtesy of
American Fire Sprinkler Association) and (right) illustrated (Courtesy of Stephan Laforest).
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
Sidewall sprinklers should not be located in the dead-air space at the junction of the ceiling and the wall
(see 8.7.4.1.1.2). The desirable sprinkler location is 4 in. to 6 in. (100 mm to 150 mm) from the ceiling to
optimize performance. As the sprinkler is lowered to more than 6 in. (150 mm) from the ceiling, it is likely
to take longer to operate. In addition, the ceiling has an impact on the discharge of a sidewall sprinkler,
causing the spray pattern to change as the sprinkler is lowered. The sprinkler may be lowered as much as
18 in. (450 mm) when specifically tested and listed for such use.
8.7.4.1.2Walls.
8.7.4.1.2.1* Vertical sidewall sprinkler deflectors shall be located not more than 6 in.
(150mm) or less than 4in. (100mm) from the wall from which they are projecting.
A.8.7.4.1.2.1 The 6in. (150mm) as referenced is measured from the wall to the vertical plane
representing the surface of attachment of the deflector. See Figure A.8.7.4.1.2.1.
8.7.4.1.2.2 Horizontal sidewall sprinkler deflectors shall be located no more than 6 in.
(150mm), and shall be permitted to be located with their deflectors less than 4in. (100mm),
from the wall on which they are mounted.
The requirement in 8.7.4.1.2.2 permits horizontal sidewall sprinklers to be installed less than 4 in. (100 mm)
from the wall to which they are mounted. This requirement is similar to the requirement in 8.6.4.1.1.2 for
flush and concealed pendent sprinklers with respect to the position relative to the ceiling and allows the
sprinkler to be mounted on the surface of a wall or soffit.
BK-NFPA-13HB16-150270-Chp08-P1.indd 303
11/20/2015 3:56:29 PM
. ..
304
X
Where X is 6 in.
(150 mm) or less
Ceiling
Top of sprinkler
deflector
Ceiling
Soffit
Top of sprinkler
deflector
Soffit
Allowable
deflector-toceiling distance
Wall
Wall
Minimum
deflector-toceiling distance
Maximum
deflector-toceiling distance
BK-NFPA-13HB16-150270-Chp08-P1.indd 304
11/20/2015 3:56:33 PM
. ..
305
A.8.7.4.1.4 The requirements in 8.7.4.1.4 were developed from years of experience with
NFPA13 obstruction requirements and an additional test series conducted by the National
Fire Sprinkler Association with the help of Tyco International(Valentine and Isman, Kitchen
Cabinets and Residential Sprinklers,National Fire Sprinkler Association, November 2005),
which included fire modeling, distribution tests, and full-scale fire tests. The test series showed
that pendent sprinklers definitely provide protection for kitchens, even for fires that start under
the cabinets. The information in the series was less than definitive for sidewall sprinklers, but
distribution data show that sprinklers in the positions in this standard provide adequate water
distribution in front of the cabinets and that sidewall sprinklers should be able to control a
fire that starts under the cabinets. When protecting kitchens or similar rooms with cabinets,
the pendent sprinkler should be the first option. If pendent sprinklers cannot be installed, the
next best option is a sidewall sprinkler on the opposite wall from the cabinets, spraying in the
direction of the cabinets. The third best option is the sidewall sprinkler on the same wall as
the cabinets, on a soffit flush with the face of the cabinet. The last option should be putting
sprinklers on the wall back behind the face of the cabinet because this location is subject to
being blocked by items placed on top of the cabinets. It is not the intent of the committee to
require sprinklers under kitchen cabinets.
8.7.4.1.4.1 Where soffits exceed more than 8in. (200mm) in width or projection from the
wall, pendent sprinklers shall be installed under the soffit.
8.7.4.1.4.2 Sidewall sprinklers shall be permitted to be installed in the face of a soffit located
directly over cabinets, without requiring additional sprinklers below the soffit or cabinets,
where the soffit does not project horizontally more than 12in. (300mm) from the wall.
8.7.4.1.4.3 Where sidewall sprinklers are more than 36 in. (900 mm) above the top of
cabinets, the sprinkler shall be permitted to be installed on the wall above the cabinets where
the cabinets are no greater than 12in. (300mm) from the wall.
8.7.4.2 Deflector Orientation.
8.7.4.2.1 Deflectors of sprinklers shall be aligned parallel to ceilings or roofs.
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
8.7.4.2.2 Sidewall sprinklers, where installed under a sloped ceiling with a slope exceeding
FAQ
2 in 12, shall be located at the high point of the slope and positioned to discharge downward
along the slope.
8.7.5.1.3 The distance between light fixtures or similar obstructions located more than 4ft
(1.2m) from the sprinkler shall be in conformity with Table 8.7.5.1.3 and Figure 8.7.5.1.3.
BK-NFPA-13HB16-150270-Chp08-P1.indd 305
11/20/2015 3:56:33 PM
. ..
306
Ceiling or roof
Maximum
Allowable Distance of Deflector
Above Bottom
of Obstruction
(B) [in. (mm)]
Distance from
Sidewall Sprinkler to
Side of Obstruction (A)
Less than 4 ft (1.2 m)
4 ft (1.2 m) to less than 5 ft (1.5 m)
5 ft (1.5 m) to less than 5 ft 6 in. (1.7 m)
5 ft 6 in. (1.7 m) to less than 6 ft (1.8 m)
6 ft (1.8 m) to less than 6 ft 6 in. (2.0 m)
6 ft 6 in. (2.0 m) to less than 7 ft (2.1 m)
7 ft (2.1 m) to less than 7 ft 6 in. (2.3 m)
7 ft 6 in. (2.3 m) to less than 8 ft (2.4 m)
8 ft (2.4 m) to less than 8 ft 6 in. (2.6 m)
8 ft 6 in. (2.6 m) or greater
Not allowed
1 (25)
2 (50)
3 (75)
4 (100)
6 (150)
7 (175)
9 (225)
11 (275)
14 (350)
Obstruction
Wall
Elevation View
Paragraph 8.7.5.1.3 is analogous to the provisions for solid continuous obstructions for upright and
pendent spray sprinklers (see 8.6.5.1.2) and is intended to ensure that sprinkler discharge falls below
the obstruction. Table 8.7.5.1.3 is based on the discharge pattern falling away from the ceiling in a descending
trajectory pattern. The farther the ceiling obstruction is from the wall, the higher the deflector can be
positioned with respect to the ceiling. However, the sprinkler must be located at least 4 ft (1.2 m) from an
obstruction to allow the patterns to develop.
8.7.5.1.4 Obstructions projecting from the same wall as the one on which the sidewall sprinkler is mounted shall be in accordance with Table 8.7.5.1.4 and Figure 8.7.5.1.4.
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
Table 8.7.5.1.4 Positioning of Sprinklers to Avoid
Obstructions Along Wall (Standard Sidewall Spray Sprinklers)
Distance from
Sidewall Sprinkler to
Side of Obstruction (A)
4 in.(100 mm) to less than 6 in. (150 mm)
6 in. (150 mm) to less than 1 ft (300 mm)
1 ft (300 mm) to less than 1 ft 6 in. (450 mm)
1 ft 6 in. (450 mm) to less than 2 ft (600 mm)
2 ft (600 mm) to less than 2 ft 6 in. (750 mm)
2 ft 6 in. (750 mm) to less than 3 ft (900 mm)
3 ft (900 mm) to less than 3 ft 6 in. (1.1 m)
3 ft 6 in. (1.1 m) to less than 4 ft (1.2 m)
4 ft (1.2 m) to less than 4 ft 6 in. (1.4 m)
4 ft 6 in. (1.4 m) to less than 5 ft (1.5 m)
5 ft (1.5 m) to less than 5 ft 6 in. (1.7 m)
5 ft 6 in. (1.7 m) to less than 6 ft (1.8 m)
6 ft (1.8 m) to less than 6 ft 6 in. (2.0 m)
6 ft 6 in. (2.0 m) to less than 7 ft (2.2 m)
7 ft (2.2 m) to less than 7 ft 6 in. (2.3 m)
Ceiling
Sidewall
sprinkler
on wall
B
Obstruction
A
Elevation View
BK-NFPA-13HB16-150270-Chp08-P1.indd 306
11/20/2015 3:56:36 PM
. ..
307
Sidewall sprinkler spray distribution is adversely affected by obstructions projecting out from the same wall
on which the sprinkler is mounted. The effect is similar to the problems caused by a beam parallel to the
wall on which the sprinkler is mounted (see 8.7.5.1.3). The obstruction prevents the sprinkler discharge from
reaching the hazard on the other side of the obstruction. Because the sprinkler throw along the wall on
which it is mounted is shorter than the throw outward, the sprinkler can be located closer to the obstruction.
8.7.5.1.4.1 Isolated obstructions projecting from the same wall as the one on which the sidewall
sprinkler is mounted shall be located a minimum of 4 in. (100mm) from the sidewall sprinkler.
In addition to meeting the obstruction rules in 8.7.5.1.4, the sidewall sprinkler must be located at least
4 in. (100 mm) from the obstruction to avoid the dead-air space along the obstruction. This requirement is
similar to 8.7.3.3.1, which requires the sprinkler to be located away from an end wall.
8.7.5.1.5 Sprinklers shall be permitted to be spaced on opposite sides of obstructions less than
4ft (1.2m) in width where the distance from the centerline of the obstruction to the sprinklers
does not exceed one-half the allowable distance between sprinklers.
As in the case of upright and pendent sprinklers, when the sprinkler cannot be located such that the
discharge will spray under the obstruction, sprinklers are permitted to be placed on opposite sides of
an obstruction less than 4 ft (1.2 m) in width, provided that the distance between the sprinkler and the
centerline of the obstruction does not exceed one-half the allowable distance between sprinklers.
8.7.5.1.6* Obstructions on the wall opposite from the sidewall sprinkler shall be permitted
where the obstruction is up to 2ft (600mm) deep and 2ft (600mm) wide.
A.8.7.5.1.6 See Figure A.8.7.5.1.6.
2 ft (600 mm)
2 ft
(600 mm)
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
Figure A.8.7.5.1.6 Permitted Obstruction on Wall
Opposite Sidewall Sprinkler.
The purpose of the beam rules found in 8.7.5.1.3 and 8.7.5.1.4 is to make sure that sufficient water gets past
the obstruction to attack the fire on the far side of the obstruction. When the obstruction is against a wall,
the sprinkler spray is not required to get past the obstruction.
8.7.5.2.1General.
8.7.5.2.1.1 Continuous or noncontinuous obstructions less than or equal to 18in. (450mm)
below the sprinkler deflector that prevent the pattern from fully developing shall comply with
this section.
Automatic Sprinkler Systems Handbook 2016
BK-NFPA-13HB16-150270-Chp08-P1.indd 307
11/20/2015 3:56:38 PM
. ..
308
8.7.5.2.1.2 Regardless of the rules of this section, solid continuous obstructions shall meet the
requirements of 8.7.5.1.2 and 8.7.5.1.3.
8.7.5.2.1.3* Unless the requirements of 8.7.5.2.1.4 or 8.7.5.2.1.5 are met, sprinklers shall be
positioned away from obstructions a minimum distance of three times the maximum dimension of the obstruction (e.g., truss webs and chords, pipe, columns, and fixtures) in accordance
with Figure 8.7.5.2.1.3(a) and Figure 8.7.5.2.1.3(b).
Ceiling
D
A
Sprinkler
Obstruction
C
Obstruction
A
Wall
Wall
Plan View of Column
(Obstruction in vertical orientation)
A 3C or 3D
(Use dimension C or D, whichever is greater)
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
(A)The maximum clear distance required to obstructions in the horizontal orientation
(e.g., light fixtures and truss chords) shall be 24 in. (600mm).
(B) The maximum clear distance shall not be applied to obstructions in the vertical orientation (e.g., columns).
A.8.7.5.2.1.3 The rules of 8.7.5.2.1.3 (known as the Three Times Rule) have been written
to apply to obstructions where the sprinkler can be expected to get water to both sides of the
obstruction without allowing a significant dry shadow on the other side of the obstruction.
This works for small noncontinuous obstructions and for continuous obstructions where the
sprinkler can throw water over and under the obstruction, such as the bottom chord of an open
truss or joist. For solid continuous obstructions, such as a beam, the Three Times Rule is ineffective since the sprinkler cannot throw water over and under the obstruction. Sufficient water
must be thrown under the obstruction to adequately cover the floor area on the other side of the
obstruction. To ensure this, compliance with the rules of 8.7.5.1.2 is necessary.
8.7.5.2.1.4 The requirements of 8.7.5.2.1.3 shall not apply to sprinkler system piping less
than 3in. (80mm) in diameter.
8.7.5.2.1.5 The requirements of 8.7.5.2.1.3 shall not apply where sprinklers are positioned
with respect to obstructions in accordance with 8.7.5.1.2, 8.7.5.1.3, and 8.7.5.1.4.
8.7.5.2.1.6* Sprinklers shall be permitted to be placed without regard to the blades of ceiling fans
less than 60in. (1.5m) in diameter, provided the plan view of the fan is at least 50percent open.
2016 Automatic Sprinkler Systems Handbook
BK-NFPA-13HB16-150270-Chp08-P1.indd 308
11/20/2015 3:56:41 PM
. ..
309
Just as for upright and pendent sprinklers, the blades on small fans less than 60 in. (1.5 m) in
diameter are not considered obstructions if they are 50 percent open. See the commentary following
8.6.5.2.1.10.
A.8.7.5.2.1.6 The housing unit of the ceiling fan is expected to be addressed by the Three
Times Rule.
8.7.5.2.2Suspended or Floor-Mounted Vertical Obstructions.The distance from
sprinklers to privacy curtains, free-standing partitions, room dividers, and similar
obstructions in light hazard occupancies shall be in accordance with Table 8.7.5.2.2 and
Figure 8.7.5.2.2.
Table 8.7.5.2.2 Suspended or Floor-Mounted Obstructions
(Standard Sidewall Spray Sprinklers) in Light Hazard
Occupancies Only
Ceiling
Minimum Vertical
Distance Below
Deflector (B) [in. (mm)]
Obstruction
3 (75)
4 (100)
6 (150)
Wall
8 (200)
912 (240)
Floor
12 2 (315)
1
Elevation View
{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
1512 (390)
18 (450)
For SI units, 1 in. = 25.4 mm. Note: For A and B, refer to Figure 8.7.5.2.2.
The distances specified in Table 8.7.5.2.2 were derived from NBSIR 802097.
8.7.5.2.2.1* In light hazard occupancies, privacy curtains, as shown in Figure 8.7.5.2.2, shall
not be considered obstructions where all of the following are met:
(1) The curtains are supported by fabric mesh on ceiling track.
(2) Openings in the mesh are equal to 70percent or greater.
(3) The mesh extends a minimum of 22in. (550mm) down from ceiling.
A.8.7.5.2.2.1 Testing has shown that privacy curtains supported from the ceiling by mesh fabric do not obstruct the distribution pattern in a negative way as long as the mesh is 70percent
or more open and extends from the ceiling a minimum of 22in. (550mm).
RESEARCH NOTE
A report of tests conducted by NIST in July 2004, The Effect of Privacy Curtains on Sprinkler Spray, confirmed that privacy curtains
supported by mesh that is at least 70 percent open and that extends
down at least 22 in. (550 mm) allows as much water to reach the
opposite side of the curtain as arrangements that meet the requirements of 8.7.5.2.2. This finding is recognized in 8.7.5.2.2.1.
BK-NFPA-13HB16-150270-Chp08-P1.indd 309
11/20/2015 3:56:42 PM
. ..
310
FAQ
8.8.1General.
All requirements of Section8.5 shall apply to extended coverage upright and pendent sprin{2FC84572-0B19-4D3C-B16A-15DE6BAFE1FD}
klers except as modified in Section8.8.
8.8.2 Protection Areas per Sprinkler (Extended Coverage Upright and Pendent
Spray Sprinklers).
8.8.2.1* Determination of Protection Area of Coverage.
A.8.8.2.1 The protection area for extended coverage upright and pendent sprinklers is defined
in the listing of the sprinkler as a maximum square area. Listing information is presented in
even 2ft (0.6m) increments up to 20ft (6.1m). When a sprinkler is selected for an application, its area of coverage must be equal to or greater than both the length and width of the
hazard area. For example, if the hazard to be protected is a room 13ft 6in. (4.1m) wide and
17ft 6in. (5.3m) long as indicated in Figure A.8.8.2.1, a sprinkler that is listed to protect an
area of 18ft 18ft (5.5m 5.5m) must be selected. The flow used in the calculations is then
selected as the flow required by the listing for the selected coverage.
8.8.2.1.1 The protection area of coverage (As) for extended coverage sprinklers shall be not
less than that prescribed by the listing.
8.8.2.1.2 Listing dimensions shall be even-numbered square protection areas as shown in
Table 8.8.2.1.2.
Restrictions are placed on the allowable spacing of upright and pendent EC sprinklers to promote interchangeability. As stated in 8.8.2.1.2, the protection area must be uniform that is, a square pattern
so that the sprinkler can be installed without regard to the orientation of the frame arms. Limiting the
spacing to even-numbered increments allows a variety of protection areas and promotes interchangeability among models from different manufacturers.
2016 Automatic Sprinkler Systems Handbook
BK-NFPA-13HB16-150270-Chp08-P1.indd 310
11/20/2015 3:56:42 PM