Purifier Purge

The Most Trusted Purge in the Industry

The Trane Purifier purge is designed to help


owners manage refrigerant losses.

The Purifier purge is microprocessorbased, so it stores the kind of


information you need to know how
much, where, and when a chiller is
leaking. This monitoring of the chillers
purging characteristic helps to detect
leaks, helps to speed repair, and helps to
keep owners compliant with todays
refrigerant management laws.
Refrigerant is saved through the
Purifier Purges highly efficient operation.
It combines low separation temperatures
and the Purifier Plus accessory to
reduce purge refrigerant losses to zero.
Enhanced safeties are also included to
protect the chillers refrigerant in the case
of a large chiller leak or operator error.
The added adaptive mode of
operation allows the purge to run only

2003 American Standard Inc. All rights reserved

when air is present in the chiller. This


added feature reduces the run time of
the purge, thereby saving energy. In the
case of a purge malfunction, the Purifier
purge communicates the problem
source to the servicer through a two-line,
16-character clear language display.
These diagnostics improve purge
servicing by reducing the time it takes
to identify the problem.
Tranes 55 years of low-pressure chiller
experience, high quality standards, and
pre-ship run testing make it the mosttrusted purge in the industry. In fact,
more than 40,000 Trane Purifier purges
are in operation today.

ECTV-SLB020-EN

PRG00099
CFC-11/HCFC-123 Purifier Purge
WITH Human Interface
The Purifier purge can be applied to
50- or 60-cycle, low-pressure CFC11/HCFC-123 centrifugal chillers without
Unit Control Panel (UCP2).
PRG00100
CFC-113 Purifier Purge
WITH Human Interface
The Purifier purge can be applied to
50- or 60-cycle, low-pressure CFC-113
centrifugal chillers without Unit Control
Panel (UCP2).
PRG00101
CFC-11/HCFC-123 Purifier Purge
WITHOUT Human Interface
The Purifier purge can be applied to
50- or 60-cycle, low-pressure CFC11/HCFC-123 centrifugal chillers with
UCP2. In this case, the purge will utilize
the UCP2 chiller display for purge to
operator communication.
Not included with any unit: customized
purge mounting brackets (if needed),
electrical conduit or connectors, 14 in. and
5
8 in. copper refrigerant tubing, copper
couplings, flare nuts, tees, and insulation
for the 58 in. vapor line. A 58 in. OD ball
valve (required for units with heat
recovery or auxiliary condensers only) is
also not included. See the purge
installation manual for details.

ECTV-SLB020-EN

Chiller operators and owners will welcome the ease with w


receive fault diagnostics, and view purge and chiller operat
Design and Features
The Trane Purifier purge is a highly
efficient separation system that
removes air, moisture, and other
non-condensables from low-pressure
chillers using refrigerants CFC-11,
CFC-113, and HCFC-123. The system
significantly reduces the amount of
refrigerant lost to the atmosphere during
normal purge operation and protects the
chillers complete charge from accidental
pump out. The design maintains reliable
operation within a range from 40F to
120F chiller-condenser saturation
temperatures. The CFC-11 and HCFC-123
Purifier purges are Underwriters
Laboratory (UL) listed.
The patented design eliminates the need
for troublesome purge compressors,
water connection, and tank float valves.
The free-flow design utilizes a CFC-free,
integrated refrigeration system that is
completely isolated from the chillers
refrigerant. This refrigeration system
is optimized to supply separation
temperatures as low as -5F and enables
the purge to run when the chiller is either
operating or idle. The microprocessorbased control system enables superior
refrigerant protection and provides
significant energy conservation.
Microprocessor-Based Controls
The Purifier purge has microprocessorbased controls that enhance its
capabilities. These controls provide
current purge and chiller operational
data pertinent to managing chiller leaks.
The Purifier purge automatically
measures, stores, and displays purging
measurements of purge exhaust time,
condenser run time, and chiller run time
for the last 30 days and/or for the last
24 hours.

ECTV-SLB020-EN

which they can adjust set points, select operating modes,


ting and purging information.
Clear-Language Human Interface
All retrofit Purifier purges use a clear
language human interface. The human
interface is used to control purge
operations and to view stored purging
and/or chiller data. The human interface
has eight keys and a two-line backlit
display. The information displayed on
the human interface is continuously
updated by the purge microprocessor.

Advanced Diagnostic Capability


In the event of unusual purge
operation or failure, the Purifier purge
communicates the problem source
through the human-interface display.
Below are examples of the Purifier purge
diagnostics. These helpful messages will
save the service technician the time it
takes to identify the problem source.

Adaptive Purifier Purge Operation


The Purifier purge has four operating
modes: Stop, On, Auto, and Adaptive.

2. Liquid Level Too High

Stop manually shuts down the


purge. In this mode, the purge will
remain off until it is manually started.

4. Liquid Temp Sensor Fail

On manually turns the purge on. It


will operate continuously until it is
manually changed.
Auto will signal the purge to run
whenever the chiller is on and shut
down whenever the chiller is off.
Adaptive allows non-continuous (or
adaptive) purging whether the chiller
is on or off. While operating in this
mode, power to the purge
refrigeration system is activated only
when purging is necessary, thus
saving energy.
When in the Adaptive mode, the Purifier
purge can also identify when and where
a chiller is leaking. It accomplishes this
by separately tracking and displaying
purge activity when the chiller is on and
off. With this feature, chiller operators
and owners can determine if a chiller
leak is occurring on the high side or low
side of a chiller.

ECTV-SLB020-EN

1. Max Pumpout Rate Exceeded


3. Suction Temp Sensor Fail
5. Lost Communication
Gravity Free-Flow Design:
Trane Exclusive
Tranes patented gravity free-flow
design is exclusive to the Purifier purge.
It returns liquid refrigerant to the chiller
condenser, eliminating the liquid return
components such as float valves, float
switches, orifice restrictors, and solenoid
valves that are required on designs
that return refrigerant to the chiller
evaporator. When such components fail
or are fouled, the purge, and ultimately
the chiller, will fail. By eliminating these
components, Trane Purifier purge has
provided unequalled reliability for the
40,000 chillers on which it is installed.

Conforms to Canadian Environmental


Standards
When used in combination with the
Trane Purifier Plus carbon canister,
Trane certifies that purge emissions for
R-11, R-123, or R-113, when tested in
accordance with ARI Standard 580, will
be 0.0019 kg/kg air or lower. This is 98%
better than the 0.1 kg/kg air maximum
purge-emissions limit, effective 2003,
set in the Canadian National Action
Plan for the Environmental Control of
Ozone-Depleting Substances and their
Halocarbon Alternatives approved by the
Canadian Council of Ministers of the
Environment (CCME), May 1, 2001.
Exclusive Filter-Drier Technology
Advanced filter technology improves
chiller reliability and speeds service.
The nominal 96-cubic-inch capacity
filter-drier is easier to service than the
replaceable core type canisters. The
filter drier is packed with o-ring seal
threaded fittings on each end for easy
serviceability. Plastic end caps are
shipped on the drier assembly and can
be used to seal the saturated filter-drier
canister, which will keep refrigerant
leakage to a minimum when properly
discarding the saturated canister.

ARI 580 Rated


Trane Purifier purge efficiency
performance is rated in accordance with
ARI Standard 580-2001. An ARI listing
provides assurance that Purifier purge
performance conforms to industry
criterion such as those published in
ASHRAE Guideline 3-1996. Refer to the
ARI Directory of Certified Products at
http://www.ARI.org for the Trane Purifier
purge listing.

Purifier Purge Accessories


TNK00858
Purifier Plus Carbon Canister
The Purifier Plus is an optional, activatedcarbon canister designed to be installed
on the exhaust line of Trane Purifier
purges to obtain near-zero purge
emissions. The Purifier Plus accessory
can be sold with new Purifier purges,
sold as a Purifier Purge upgrade, or sold
separately for the replacement of an
existing canister.
Existing Trane Model PRGA, PRGB, and
PRGC Purifier purges on low-pressure
chillers using CFC-11, HCFD-123, OR
CFC-113, and not having Purifier Plus
carbon canisters, have emissions
exceeding 2003 Canadian 0.1 kg/kg air
emissions limits. For Canadian Purifier
Purges, the retrofit of a Purifier Plus
carbon canister is recommended. In such
retrofits, Trane certifies that purge
emissions for R-11, R-123, or R-113 will
be 0.0019 kg/kg air or lower when tested
per ARI Standard 580.
Specifications:
Weight (Including brackets): 50 lb.
Overall size (Including brackets):
21 in. H x 12 in. W x 14 in. L
Connection Sizes
Inlet: 38 in. Male Flare
Outlet: 38 in. Male Flare
Temperature Range
Operating 40 to 120F
Shipping and Storage: -40 to 150F
SEP00017
Liquid-Refrigerant Separator
The purge liquid-refrigerant separator is
intended for use with the Purifier purge
in applications where, for clearance or
other reasons, the purge cannot be
mounted on the chiller condenser.
The liquid separator allows the purge
to be mounted on top of the chiller
evaporator. See the purge liquidrefrigerant separator installation manual
for further details.

ECTV-SLB020-EN

KIT08067
Bracket Kit for Purifier Plus
The purge bracket kit is intended to be
used when installing a Purifier Plus
Carbon Canister for the first time. The kit
includes a holding bracket, mounting
brackets, and hardware.
KIT08014
Purge Valve Kit
The purge valve kit is an option that
includes piping fittings and valves
needed in a typical purge installation. If
this kit is not ordered, the following parts
must be field provided.
14 in. NPS Tee
14 in. C Ball Valve
78 in. fitting x 5/8 in. C Bushing
78 in. fitting x 7/8 in. Elbow
Coupling
58 in. C x 1.2 in. NPTE Adapter
12 in. NPS Elbow
58 in. ODS Ball Valve
KIT02586
Purge Human-Interface Kit
This kit converts an existing PRGC that
was originally part of a chiller UCP2
control system to a stand-alone Purifier
purge having its own human interface.
In other words it will convert a PRG00101
(CFC-11/HCFC-123 Purifier Purge without
Human Interface) to PRG00099 (CFC11/HCFC-123 Purifier Purge with Human
Interface). This kit includes a new display,
mounting bracket, necessary control
modules, and hardware.

ECTV-SLB020-EN

Literature Order Number

ECTV-SLB020-EN

Date

January 2003

Supersedes

E/CTV-GS-6

Stocking Location

La Crosse - Inland

Trane
A business of American Standard Companies
www.trane.com
For more information, contact your local Trane
office or e-mail us at comfort@trane.com

Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice.

Вам также может понравиться