INSTALLATION AND OPERATING MANUAL

ITYS

1-10 kVA

IOMITYTWXX00-GB_00 - 03.2008

Downloaded from www.Manualslib.com manuals search engine

Thank you for choosing ITYS, a SOCOMEC UPS product.


You have purchased a high professional UPS to provide you protection against black-outs and electrical impurities. The ITYS range has been designed specifically for the protection of critical electronics and I.T. consumers
such as servers, UNIX workstations or networking peripherals which could suffer hardware damage and data
losses as a result of the disturbance deriving from the electrical mains.

ITALIANO
ENGLISH

For correct use and to obtain the best performance from this product, please read and follow carefully the
instructions contained within. Keep this manual at hand for rapid and easy consultation.
Reproduction of any part of this manual is forbidden without the manufacturers consent. The information and
drawings contained herein may be changed without prior notice and are not binding upon the manufacturer.
SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document.
All reproduction, modification, dissemination of this document whether in part or whole and by any manner
are expressly prohibited except upon Socomecs express prior written consent.
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without
prior notice.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ITYS

INDEX

1-10 kVA

1. CERTIFICATE AND CONDITIONS OF WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


2. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4. UNPACKING AND INSTALLATION . . . . . . . . . . . . . .


4.1 Environmental requirements for installation.
4.2 Unpacking of the UPS . . . . . . . . . . . . . . .
4.2.1 ITYS 1 kVA, 2 kVA, 3 kVA . . . . . . . . .
4.2.2 ITYS 6 kVA, 10 kVA . . . . . . . . . . . .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

10
10
11
11
11

5. FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6. REAR VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7. CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. EXTERNAL BATTERY CABINET CONNECTION (for LB models only)
8.1 Important. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 External battery cabinet connection . . . . . . . . . . . .
8.3 Modular battery cabinet . . . . . . . . . . . . . . . . . . . .
8.4 Battery cabinet specific for Itys . . . . . . . . . . . . . . . .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

17
17
17
18
18

9. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1 Battery recharging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Start-up and shutdown ITYS 1 kVA, 2 kVA, 3 kVA . . . . . . . . . . . . . . . . . . . .
10.2.1 Start-up with mains present . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.2 Start-up without mains present . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.3 Shutdown with mains present. . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.4 Shutdown without mains present . . . . . . . . . . . . . . . . . . . . . . . .
10.3 Start-up and shutdown ITYS 6 kVA, 10 kVA . . . . . . . . . . . . . . . . . . . . . . . .
10.3.1 Start-up with mains present . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3.2 Start-up without mains present . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3.3 Shutdown with mains present. . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3.4 Shutdown without mains present . . . . . . . . . . . . . . . . . . . . . . . .
10.4 Operation with manual by-pass (ITYS 6 kVA, 10 kVA only) . . . . . . . . . . . . . .
10.5 Operation from manual by-pass to normal operation (ITYS 6 kVA, 10 kVA only).
10.6 Battery test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

20
20
20
20
20
21
21
22
22
22
23
24
24
25
25

11. VISUAL AND ACOUSTIC SEGNALISATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26


12. COMMUNICATION. . . . . . . . . . . . . . . . .
12.1 Communication solutions . . . .
12.2 RS232 interface . . . . . . . . . . .
12.3 NetVision card . . . . . . . . . . . .
12.4 Use of signalling rrelay interface

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

28
28
29
29
29

13. MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
13.1 Troubleshooting for minor problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
14. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ENGLISH

3. GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

ITALIANO
Downloaded from www.Manualslib.com manuals search engine

CERTIFICATE AND CONDITIONS


OF WARRANTY

ITYS

1-10 kVA

The period of validity of the warranty is calculated from the date of purchase of the new product, by the final
user, from an official reseller (the date shown on the purchase receipt is used as proof).
The warranty is of the carry-in type: free supply of parts and labour for repairs, with return of a product to be
replaced to SOCOMEC UPS, or authorized centres, at the customers cost and risk.

In order to use the warranty service, the user must respect the following rules:
t 5IFQSPEVDUNVTUCFSFUVSOFEFYDMVTJWFMZJOJUTPSJHJOBMQBDLBHJOH"OZEBNBHFDBVTFEEVSJOHTIJQQJOHJO
packaging other than the original is not covered by the warranty;
t 5IFQSPEVDUNVTUCFBDDPNQBOJFECZQSPPGPGQVSDIBTFBEPDVNFOU CJMM JOWPJDF SFDFJQU
TIPXJOHUIFEBUF
of purchase and the information necessary to identify the product (model, serial number). The number of the
authorization for return for repairs must also be attached, with a detailed description of the defect found in
the product. If any of these elements is missing, the warranty is invalid. The return authorization number is
issued by the service centres by telephone on receiving notification of the malfunction;
t *GJUJTOPUQPTTJCMFUPQSPWJEFQSPPGPGQVSDIBTF UIFTFSJBMOVNCFSBOEEBUFPGQSPEVDUJPOXJMMCFVTFEUP
calculate expiry of the warranty, which may lead to a reduction in the products warranty period.

The product is not covered by warranty for damage caused by negligence (use outside the tolerance ranges:
electric power supply, lightning, humidity, temperature, bad ventilation, etc.), tampering or any unauthorized
intervention.
During the warranty period, SOCOMEC UPS may, at its discretion, decide to repair the product or replace the
defective parts with new parts or with used parts that are equivalent to new parts in terms of functions and
performance.
In the case of the battery, the warranty is valid if periodic recharging has been effected within the terms indicated on the packaging. It is advisable, therefore, after purchase, to check that the date of the next recharging
has not passed.

Optionals.
Warranty for the optionals is 12 months and is of the carry-in type.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ENGLISH

This SOCOMEC UPS uninterruptible power system is guaranteed against manufacturing and material defects,
for a period of 12 months from the date of purchase (local warranty condition apply in addition to the general
one). This certificate of warranty must NOT be sent back, but must be kept by the customer together with the
purchase receipt, to be used if the product should require interventions while under warranty.

CERTIFICATE AND CONDITIONS


OF WARRANTY

ITYS

1-10 kVA

ITALIANO
ENGLISH

Software products.
Warranty for the software is 90 days. The software is guaranteed to function in compliance with the manual
and the written material accompanying the product. Hardware accessories or supports (e.g. disks, cables, etc.)
attached are guaranteed from material and manufacturing defects under normal use and service, for a period
of 12 months from the date of purchase.

Under no circumstances will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earnings, interruption of activity, loss of data or other economic losses) deriving from the use of
this product.
The present conditions are subject to Italian law. All disputes to be heard by the Court of Vicenza.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

SAFETY STANDARDS

ITYS

1-10 kVA

t *GZPVS*5:4NPEFMIBTYFEDPOOFDUJPOT UFSNJOBMT
electrical installation must be effected EXCLUSIVELY
by qualified personnel, scrupulously following the instructions contained in this manual.
t Before starting, the unit must be provided with an equipotential connection as established by the
safety standards in force. The earth cable of the UPS is to be connected to an efficient earthing point.
t If the earth connection is not made, all devices connected to the UPS will be without equipotential
connection. In this case the manufacturer declines all responsibility for damage or accidents caused by nonobservance of the said standard.
t In case of mains failure (battery mode), do not disconnect the input cable from mains so to ensure the
earth connection to the loads supplied.
t All subsequent maintenance operations must be carried out solely and exclusively by authorised personnel. Inside the system high electric voltages are generated which may endanger maintenance personnel
who are not sufficiently prepared and trained for such tasks.
t If at any time during use a hazard condition is created, remove the mains power supply (if possible through the
distribution panel upstream of the unit) and switch the UPS off completely following the appropriate procedure.
t The UPS contains an internal power source that is the batteries. The UPS output may be powered even
when the UPS is not connected to the mains power supply.
t Do not force, break or try to open the batteries. They are sealed and do not require any maintenance.
Inside they contain substances that are toxic to health and that pollute the atmosphere. Do not switch
the UPS on if there is any leak of liquid, or if a residual white powder is noted.
t Avoid contact of the UPS unit with water or liquids in general. Do not introduce foreign bodies.
t If the unit needs to be scrapped, it is essential to entrust the equipment solely and exclusively to specialist
disposal companies. These are obliged to break up and dispose of the various components in accordance
with the legal provisions in force nationally.
t Only for ITYS 1-2-3 kVA: as the mains cable of the UPS is considered a disconnecting device, the mains socket to
which the UPS is connected and/or the rear of the UPS must be accessible and easy to disconnect.
t Only for ITYS 1-2-3 kVA: the UPS generates a leakage current of approximately 3 mA. In order to guarantee the maximum limit on leakage current of 3.5 mA, ensure that the load has a maximum leakage current
of 2 mA. If the load leakage current exceeds this limit, qualified personnel should connect the UPS to an
industrial-type mains power supply, compliant with IEC 309, dimensioned for a current that is appropriate for
the systems power rating.
IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ENGLISH

This manual must be kept in the vicinity of the UPS, so that the operator may consult it at any time for clarifications on the correct use of the UPS. Read the manual carefully before connecting the unit to the general mains
power supply and to the devices to be powered. Before putting the UPS (Uninterruptible Power Supply) into
operation, the operator must be fully aware of the functions and positions of all the controls and of the technical and functional characteristics of the system, in order to avoid risks to persons and to the equipment.

ITYS

SAFETY STANDARDS

1-10 kVA

ITALIANO
ENGLISH

t 5IFQSPEVDUZPVIBWFDIPTFOJTEFTJHOFEGPSDPNNFSDJBMBOEJOEVTUSJBMVTFPOMZ*OPSEFSUPCFVTFEGPS
particular critical applications such as life support systems, medical applications, commercial transportation,
nuclear facilities or any other application or systems where product failure is likely to cause substantial harms
to person or property, the products may have to be adapted. For such uses we would advise you to contact
SOCOMEC UPS beforehand to confirm the ability of these products to meet the requested level of safety,
performance, reliability and compliance with applicable laws, regulations and specifications.
t 6TFUIF614JOBDDPSEBODFXJUITQFDJDBUJPOTTIPXOJOUIFUFDIOJDBMEBUB DIBQUFS

t Only for ITYS 3-6-10 kVA: in order to comply with the requirements for emergency shutdown (ESD), a relay
card with remote ESD function is available. Should the card not be present, the output line must be equipped
with a disconnecting switch to interrupt the continuous power supply to the load in any operation mode of
the UPS.
t Only for ITYS 6-10 kVA: If the UPS does not have an automatic protection device against current back-feed, the
operator/installer must:
- add warning labels to all the mains power disconnecting switches installed at a distance from the
UPS area; this serves to remind technicians of the
fact that the circuit is connected to a UPS.
- install an external isolating device as shown in figure 2-1.

ISOLATE THE UPS BEFORE


OPERATING ON THIS CIRCUIT

2-1
External distribution
panel.
Q

UPS.

Legend.
B Coil.
Q Magneto-thermal input main switch.
T 90 A AC1 remote contactor 2-pole; 230 V coil.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ITYS

GENERAL DESCRIPTION

1-10 kVA

3.1 OPERATION.
ITYS is based on the on-line, double conversion, VFI (Voltage and Frequency Independent) technology to guarantee the highest level of electrical protection.
With this principle of operation, the voltage and the frequency at the input of the UPS are completely regenerated via a first AC/DC conversion followed by a DC/AC conversion in order to provide the consumer a stable
waveform that is exempt of noise or distortions, and therefore completely independent of the input mains. In
this double conversion process, the UPS also becomes a filter element in relation to the electrical network thus
preventing the distorting absorption (typical of IT users) from being reflected on the power supply line.
In the event of a black-out, ITYS provides for generation of the output voltage without any disturbance, even
transient, drawing the power from the internal batteries. During normal operation with the mains line present,
ITYS recharges the batteries fully automatically and independently.

3.1-1

Wiring diagram.

I
Legend.

A UPS.
B Mains input.
C Power output for consumer lines.
D AC/DC rectifier.
E DC/AC inverter.
F Automatic internal by-pass.
G Battery-charger.
H Batteries.
I Manual by-pass
(6 kVA and 10 kVA only).

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ENGLISH

The main purpose of the UPS is to protect sensitive and critical equipment items from the electrical disturbances that can compromise operation. Black-outs, brown-outs, variations of voltage and frequency, lightning,
electrostatic discharges and rapid overvoltages are phenomena found in all office and industrial environments
and which cause hardware damage and data losses.

ITALIANO
ENGLISH

UNPACKING AND INSTALLATION

ITYS

1-10 kVA

4.1 ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION.


Install the UPS after first checking the following:
t *5:4IBTCFFOEFTJHOFEGPSVTFJODMPTFEFOWJSPONFOUT
t 1MBDFUIF614POBBUBOETUBCMFTVSGBDF JOBWFOUJMBUFEFOWJSPONFOUBXBZGSPNIFBUTPVSDFTBOEFYQPTVSF
to direct sunlight.
t ,FFQBNCJFOUUFNQFSBUVSFCFUXFFO$BOE$BOEIVNJEJUZMFTTUIBO OPODPOEFOTJOH
UIFCFTU
UFNQFSBUVSFUPHVBSBOUFFMPOHFTUQPTTJCMFCBUUFSZMJGFJT$
t &OTVSFUIBUUIFFOWJSPONFOUXIFSFUIF614XJMMCFJOTUBMMFEJTOPUEVTUZ
t -FBWFBTQBDFPGBUMFBTUDNBSPVOEJUUPBMMPXGPSBEFRVBUFWFOUJMBUJPOBOEBDDFTTUPUIFSFBSQBOFM
t .BLFTVSFOPUUPQMBDFUIF614PSBOZPUIFSIFBWZPCKFDUPOUIFDBCMFT
t $IFDLUIBUUIFWPMUBHFBOEGSFRVFODZQSFTFUGPSPQFSBUJPOJTSJHIUGPSZPVSFMFDUSJDBMQPXFSTVQQMZMPPLJOHUIF
data can be found on the data plate.
t 6TFPOMZUIFNBOVGBDUVSFSTVQQMJFEPSSFDPNNFOEFEDBCMFTBOEBDDFTTPSJFTGPSDPOOFDUJPOTUPUIF34
serial interface.
t *UJTSFDPNNFOEFEUIBUUIFCBUUFSJFTCFMFGUUPDIBSHFGPSIPVSTUIFSTUUJNFUIFVOJUJTVTFE
CAUTION IF DAMAGED.
BATTERIES, NON SPILLABLE.
Packages, crushed, punctured, or torn such that contents are revealed must be set aside in an
isolated area and inspected by a qualified person. If the package is deemed to be not shippable, the contents must be promptly collected, segregated, and either the consignor or consignee
contacted.

10

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

ITYS

UNPACKING AND INSTALLATION

1-10 kVA

4.2 UNPACKAGING OF THE UPS.


4.2.1 ITYS 1 kVA, 2 kVA, 3 kVA.
4.2.1-2

4.2.1-3

4.2.2-2

4.2.2-3

ENGLISH

4.2.1-1

4.2.2 ITYS 6 kVA, 10 kVA.


4.2.2-1

4.2.2-4

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

11

ITYS

FRONT VIEW

1-10 kVA

ITALIANO
ENGLISH

Mimic panel.

OFF
button

6 kVA
10 kVA

12

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

2 kVA
3 kVA

ON button
and silence
buzzer

1 kVA

ITYS

REAR VIEW

1-10 kVA

1 kVA

2 kVA

Legend.

A RS232 serial port (JBUS protocol)


G

B Fan
C Input protection

D ADSL/modem/telephone line protection


H
C

E Input socket (IEC 320)


F Slot for optional communication boards

G Output sockets (IEC 320)


H Output terminals

3 kVA

I Output socket for external battery cabinet


connection (LB models only)

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

13

ENGLISH

ITYS

REAR VIEW

1-10 kVA

Legend.
A
F

A RS232 serial port (JBUS protocol)


B Fan

ITALIANO
ENGLISH

B1 Fan (10 kVA only)


C Input protection
(magneto-thermal)

D Input and output terminal board


E Cable couplings
F Slot for optional communication
boards
G Manual by-pass

B1

H Wheels with safety locking system


I
C
G

6 kVA
10 kVA

14

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

Output socket for external battery


cabinet connection (LB models only)

ITYS

CONNECTIONS

1-10 kVA

ENGLISH

Connection to the mains supply and the load should be effected by using cables of an appropriate thickness
and which conform to the standards in force.
A distribution panel must be set up (if there is not one already) which can be used to isolate the mains upstream
of the UPS. This panel must have an automatic switch of sufficient capacity for the current absorbed at full load
and a differential breaking device.

OUT 230 V~
6 x IEC320
OUT 230 V~
4 x IEC320

1 kVA

2 kVA

IN 230 V~
Use the servers supply cord
(IEC 320).

IN 230 V~
Use the servers supply cord
(IEC 320).

OUT 230 V~
4 x IEC320

3 kVA

IN 230 V~
Use power cord
provided (IEC 320 16 A).

IN 230 V~
Use the power
cord provided
(IEC 320 16 A).

3 kVA
OUT 230 V~
3 x 2,5 mm2

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

15

ITYS

CONNECTIONS

The installation and the system must comply with national plant regulations. If a differential switch is installed on the mains power switch (optional), it must be inserted upstream from the distribution panel.

UPS
Mains

ITALIANO
ENGLISH

CAUTION!
Use selective type differentials. Any current dispersed by
the loads will be summed to that of the UPS. The differential protection must be regulated in cases of loads with
high current dispersion.

7-4

INPUT
7-5
6 kVA
10 kVA

16

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

JP2

(mm2)

6
10

7-3

JP1

UPS

7-2

Output

(mm2)

7-1

1-10 kVA

OUTPUT
7-6

6 kVA
10 kVA

JP1

JP2

6
10

EXTERNAL BATTERY CABINET CONNECTION


(for LB models only)

ITYS

1-10 kVA

8.1 IMPORTANT.
t #FGPSFDPOOFDUJOHUIFFYUFSOBMCBUUFSZDBCJOFU DIFDLUIBUUIJTJTGVMMZDPNQBUJCMFXJUIUIFNPEFMPG614
t 5IFVTFPGFYUFSOBMCBUUFSZDBCJOFUTOPUTVQQMJFECZUIFNBOVGBDUVSFSTJTOPUSFDPNNFOEFE

t 5IF CBUUFSJFT BSF DPOTJEFSFE BT UPYJD XBTUF *G UIFZ BSF SFQMBDFE  FOUSVTU UIF VTFE CBUUFSJFT TPMFMZ BOE
exclusively to specialist disposal companies. As provided for by the local laws in force, batteries must not be
disposed of with other industrial or domestic waste.
WARNING!
It is very dangerous to touch any part of the batteries as there is no isolation between the
batteries and the mains power source.

8.2 EXTERNAL BATTERY CABINET CONNECTION.


WARNING!
Before carrying out any operation, ensure that:
t UIFCBUUFSZGVTFTMPDBUFEJOTJEFUIFCBUUFSZDBCJOFUBSFPQFO
t UIF614JTOPUMJWFBOEBMMNBJOTPSCBUUFSZTXJUDIFTBSFPQFO
t UIFTXJUDIFTVQTUSFBNPGUIF614BSFPQFO
Use the cable supplied with the unit to connect the UPS to the Battery cabinet.
Cabling errors with inversion of the battery polarity may cause permanent damage to the
equipment.
If using cabinets not supplied by the manufacturers of the UPS, it is the installers responsibility
to check the electrical compatibility and the presence of appropriate protection devices
between the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect
the cables from the UPS to the battery cabinet).
t 5IF614JTUPCFQPTJUJPOFEBTTIPXOPOQBSBHSBQITPS
t $POOFDUUIFDPOOFDUPSPGUIFDBCMFQSPWJEFEPOUIFi&YUFSOBM#BUUFSZwTPDLFUMPDBUFEPOUIFSFBSPGUIF614
t $POOFDUUIFDBCMFTUPUIFCBUUFSZDBCJOFUUFSNJOBMT SFTQFDUJOHQPMBSJUZWFSZDBSFGVMMZ
t $POOFDUUIFCBUUFSZDBCJOFUUPHSPVOE

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

17

ENGLISH

WARNING!
Danger of explosion if the batteries are replaced with others of the wrong type.

ITYS

EXTERNAL BATTERY CABINET CONNECTION


(for LB models only)

8.3 MODULAR BATTERY CABINET.

ITALIANO
ENGLISH

6-10 kVA

2-3 kVA

8.4 BATTERY CABINET SPECIFIC FOR ITYS.

1-2-3 kVA

+
6-10 kVA

+
18

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

1-10 kVA

ITYS

MIMIC PANEL

1-10 kVA

The mimic panel located on the front of the UPS provides all the information relating to the units operating
status.

Legend.

ENGLISH

A Yellow LED.
By-pass mode.
B Yellow LED.
Power supply from battery (battery
mode).
C Green LED.
Inverter mode (continuity).

H
C

D Red LED.
General alarm (fault or failure).

E ON button and silence buzzer.


F LED bar.
Depending on the situation, this shows
the charge level (figure 9.1-1) or the
battery capacity (figure 9.1-2).
G OFF button.
H Green LED.
Mains present.

9.1-1

Indication of load level.

9.1-2

Indication of battery capacity.

035%

020%

3655%

2140%

5675%

4160%

7695%

6180%

96105%

81100%

LED ON

LED OFF

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

19

10

ITYS

MODES OF OPERATION

1-10 kVA

ITALIANO
ENGLISH

10.1 BATTERY RECHARGING.


Connect the UPS to the mains voltage for approx. 8 hours to recharge the internal batteries.
The UPS can also be used with batteries that are not fully charged, but back-up time will be reduced if there is
a mains power failure.

10.2 START-UP AND SHUTDOWN ITYS 1 kVA, 2 kVA, 3 kVA.


10.2.1 Start-up with mains present.
10.2.1-1

10.2.1-2

10.2.1-3

Normal operation.

10.2.2-3

Operation on battery mode.

> 1 sec

TEST

Start-up all the loads, one at a time.

10.2.2 Start-up without mains present.


10.2.2-1

10.2.2-2

> 1 sec

TEST

Start-up all the loads, one at a time.

20

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

10

ITYS

MODES OF OPERATION

1-10 kVA

10.2.3 Shutdown with mains present.


10.2.3-1

10.2.3-2

10.2.3-3

t 5VSOPGGBMMUIFMPBET POFBGUFS
the other.
t 3FNPWFUIFNBJOTQPXFS
supply for full shutdown.

> 1 sec

10.2.3-4

10.2.4 Shutdown without mains present.


10.2.4-1

10.2.4-2

10.2.4-3

> 1 sec

TEST

Turn off all the loads, one after the other.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

21

ENGLISH

t 5IF614JTTXJUDIFEP

10

ITYS

MODES OF OPERATION

1-10 kVA

10.3 START-UP AND SHUTDOWN ITYS 6 kVA, 10 kVA.


10.3.1 Start-up with mains present.

ITALIANO
ENGLISH

10.3.1-1

10.3.1-2

10.3.1-3

ON

> 1 sec

TEST

10.3.1-4

10.3.1-5

Normal operation.

10.3.2-3

Operation on battery mode.

TEST

Start-up all the loads, one at a time.

10.3.2 Start-up without mains present.


10.3.2-1

10.3.2-2

> 1 sec

TEST

Start-up all the loads, one at a time.

22

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

10

ITYS

MODES OF OPERATION

1-10 kVA

10.3.3 Shutdown with mains present.


10.3.3-2

10.3.3-3

ENGLISH

10.3.3-1

> 1 sec

TEST

t 5IF614JTTXJUDIFEPGG UIFMPBETBSFQPXFSFECZUIFCZQBTTNBJOT
t 5VSOPGGBMMUIFMPBET POFBGUFSUIFPUIFS

10.3.3-4

10.3.3-5

10.3.3-6

OFF

TEST

Remove the mains power supply for full shutdown.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

23

10

ITYS

MODES OF OPERATION

1-10 kVA

10.3.4 Shutdown without mains present.


10.3.4-2

10.3.4-3

ITALIANO
ENGLISH

10.3.4-1

> 1 sec

TEST

Turn off all the loads, one after the other.

10.4 OPERATION WITH MANUAL BY-PASS (ITYS 6 kVA, 10 kVA only).


If the maintenance bypass is activated using the appropriate procedure, the load is powered directly from the
maintenance by-pass, while the UPS is separated from the power supply.
WARNING!
In this mode continuity is not guaranteed in the event of a mains power failure.
This operating mode can be selected for maintenance to be
carried out on the system so that
the necessary actions can be
performed by service personnel
without having to disconnect the
power supply to the load.

24

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

10.4-1

10.4-2

10.4-3

10.4-4

10

ITYS

MODES OF OPERATION

1-10 kVA

10.5 OPERATION FROM MANUAL BY-PASS TO NORMAL OPERATION (ITYS 6 kVA, 10 kVA only).
10.5-2

10.5-3

ENGLISH

10.5-1

10.5-4

10.6 BATTERY TEST.


The battery test can be activated manually or via the SW (as long as the conditions are right).
The automatic test checks the efficiency of the batteries so that, if necessary, the user can be informed when
they need to be replaced in order to guarantee sure service of the UPS. If the test fails, a specific alarm condition
is displayed.
For a manual test, press the
button for more than 3 seconds (with the UPS in normal conditions); the test
lasts for about 10 seconds with the LED flashing to indicate that the test is in progress. It is advisable to perform
the test with batteries fully charged.

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

25

11

ITYS

VISUAL AND ACOUSTIC SEGNALISATIONS

LED ON

LED OFF

1-10 kVA
LED flashing

Indication of load level (normal operation).

035%

ITALIANO
ENGLISH

3655%
5675%
7695%
96105%

Indication of battery capacity (operation on battery mode).

Bypass mode.
Other optical signals that may be
present are due to other reasons.

every 2 minutes

Irregular mains voltage.


Other acoustic and/or optical signals that may be
present are due to other reasons

26

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

020%

every second

2140%

every 4 seconds

4160%

every 4 seconds

6180%

every 4 seconds

81100%

every 4 seconds

Overload in operation from


mains with UPS in Inverter
mode

every second

Overload in operation on
battery mode, first report signal. every second
Other optical signals that may be
present are due to other reasons.

Overload in operation from


mains with UPS in By-pass
mode

Overload in operation on
battery mode, load blocked.
Other optical signals that may be
present are due to other reasons.

every second

continuous

11

ITYS

VISUAL AND ACOUSTIC SEGNALISATIONS

LED ON

Very high temperature.

Irregular inverter operation.


continuous

Other optical signals that may be


present are due to other reasons.

LED flashing

Output short-circuit.
continuous

Other optical signals that may be


present are due to other reasons.

continuous

ENGLISH

Other optical signals that may be


present are due to other reasons.

LED OFF

1-10 kVA

Irregular BUS voltage.


Other optical signals that may be
present are due to other reasons.

continuous

Irregular fan operation.


Other optical signals that may be
present are due to other reasons.

Battery charger and battery


faulty.
Other optical signals that may be
present are due to other reasons.

BAT SCR faulty.


every second

INV RLY faulty.


every second

Other optical signals that may be


present are due to other reasons.

Other optical signals that may be


present are due to other reasons.

continuous

Irregular communication.
continuous

Other optical signals that may be


present are due to other reasons.

continuous

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

27

12

COMMUNICATION

ITYS

1-10 kVA

ITALIANO
ENGLISH

Communication software and accessories to enable the device status to be monitored are available to optimize
UPS operation and for the correct management of shutdown due to end of back-up time. The applications allow all mains power failures and any battery depletion to be recorded in order to be able to activate an orderly
automatic procedure to close programs and shut down the system.
The ITYS UPSs come with RS232 serial communication interfaces and slots for the NetVision card.

12.1 COMMUNICATION SOLUTIONS.


t Uni Vision local management software (RS232 interface) for local shutdown of Windows & Linux systems.
Free on www.socomec.com (CD included in some models).
t Uni Vision Pro network management software (RS232 interface) for local and remote shutdown: supports
the major operating systems through Java Shutdown Client technology.
t NetVision Web/SNMP manager (Web/SNMP card) for UPS control over LAN with TCP/IP protocol. Allows
remote shutdown through Java Shutdown Client technology.
t BMS (JBUS protocol): possibility to integrate the UPS with BMS (Building Management Systems).

BAUD RATE SERIAL LINK:


t Baud Rate parameter setting (see the operating manual of the software):
- UniVision:
Menu: SW Setup

4 Communication4 RS232 Speed 4 set the Baud Rate value

- UniVision Pro:
File: Univision.cfg
- NetVision:
Page: Mgm MENU

4 ProtocolSpeed = Baud Rate 4 set the Baud Rate value


4 Configuration4 Baudrate (bps) 4 set the Baud Rate value

t #BVE3BUFWBMVFUPCFTFU
- 1 kVA:
9600 b/s
- 2 kVA:
9600 b/s
- 3 kVA:
9600 b/s
- 6 kVA:
2400 b/s
- 10 kVA:
2400 b/s

28

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

12

ITYS

COMMUNICATION

1-10 kVA

12.3 NETVISION CARD.


NetVision permits direct connection of the UPS to a LAN (RJ45 Ethernet) and remote control of the UPS through
TCP/IP using a WEB browser. For a complete description, refer to the Net Vision documentation.

12.4 USE OF SIGNALLING RELAY INTERFACE.


Optional card (available for insertion in the slot) which is able to handle 5 isolated contact signals to remote
relay UPS status information.
The maximum voltage that can be applied to the contacts is 24 Vdc and the maximum current is 500 mA.
12.4-1

12.4-2
5

1 Internal fault
9

2 General alarm

6 By-pass mode
Legend - pin DB9
1 Internal fault
2 General alarm
3 Return for ESD
4 Positive for ESD
5 Relay common

7 Batteria almost out


6
7
8
9

Operation from by-pass


Batteria almost out
Operation from inverter
Mains missing

Where required, it is also possible to switch off the


UPS via a remote external contact. The command is
received by leaving the contact closed for 3 consecutive seconds. The external contact must be closed between pin 3 and pin 4 (figure 12.4-3).
The external contact MUST be dedicated
BOEBU[FSPQPUFOUJBMJGUIJTDPOEJUJPOJT
not respected, permanent damage may
be caused to the UPS.

8 Inverter mode
9 Mains missing
5
Relay common

12.4-3

ESD

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

29

ENGLISH

12.2 RS232 INTERFACE.


Communication with the server can take place directly via the RS232 interface.
In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters
regarding battery status and the automatic programming of the UPS start-up and shutdown procedures.
For a complete description of the software features, refer to the UniVision and UniVision Pro documentation.

13

ITYS

MAINTENANCE

1-10 kVA

ITALIANO
ENGLISH

WARNING!
DANGEROUS electrical voltages are generated inside the UPS. All maintenance operations to
be performed SOLELY AND EXCLUSIVELY by authorized personnel.
t 0QUJNBMPQFSBUJPOPGUIFVOJUJTPCUBJOFECZLFFQJOHJUDPOTUBOUMZQPXFSFE IPVSTBEBZ
5IJTHVBSBOUFFT
correct maintenance of the battery charge.
t *GUIFSFJTUPCFBMPOHQFSJPEXIFOUIFFRVJQNFOUJTOPUJOVTF XBJUVOUJMUIFCBUUFSJFTBSFGVMMZDIBSHFE
before switching the UPS off completely (mains present for eight hours consecutively).
t 8IJMFUIFVOJUJTOPUJOPQFSBUJPO UIFCBUUFSJFTTIPVMECFSFDIBSHFEGPSIPVSTBUMFBTUFWFSZXFFLT

13.1 TROUBLESHOOTING FOR MINOR PROBLEMS.


IMPORTANT!
If after following the indications in this chapter, the problems persist or are repeated frequently, you should call the technical service centre providing a full description of the
problem.
Troubleshooting for minor problems
Problem

Possible cause

The main switch is not inserted.


The MAINS LED does not come on,
Mains voltage is missing.
the acoustic alarm sounds at intervals.
Input protection device triggered.
UPS broken.
ALARM LED on
and fault signal active.
The batteries are not fully charged.
Battery back-up time less than
indicated.
The batteries are faulty.
The battery-charger is defective.
Overload
on the UPS output.
Overload LED indicator lit.
No communication between UPS
and PC
Overtemperature signalisation

30

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

Serial connection cable error.


The PC interface is busy with
another process or defective
Interference on the data cable.
Overtemperature signal.

Solution
Insert the main switch.
Have an electrician check the mains.
Input protection device restored.
Contact the customer support service.
Charge the batteries for at least 8 hours
consecutively.
Contact the customer support service.
Contact the customer support service.
Reduce the load connected to within
the nominal value.
Use the cable provided.
Check that other SW applications
are not interfering.
Change position of the cable.
Reduce the ambient temperature.

14

ITYS

TECHNICAL SPECIFICATIONS

1-10 kVA

Models
Power (VA)
Power (W)

ITY-TW010B / LB
1000
700

ITY-TW020B / LB
2000
1400

ITY-TW030B / LB
3000
2100

ITY-TW060B / LB
6000
4200

ITY-TW100B / LB
10000
7000

ITY-TW010B / LB

ITY-TW020B / LB ITY-TW030B / LB
230 Vac
7BDVQUP7!PGUIFMPBE

50/60 Hz
0,98

Mains voltage

Frequency (nominal)
Power factor

ITY-TW060B / LB ITY-TW100B / LB
230 Vac
7BD

Electrical specifications - Output


ITY-TW010B / LB

ITY-TW020B / LB ITY-TW030B / LB ITY-TW060B / LB ITY-TW100B / LB


230 Vac (selectable 220 / 240 Vac)
50/60 Hz
 

sync interval
sync interval
4654 Hz
4654 Hz
(50 0,2 Hz in battery mode)
(50 0,05 Hz in battery mode)
6QUPGPSTFDPOET
6QUPGPSNJOVUFT
6QUP
3:1
RS232 with DB9 connector
45 dB
55 dB

Output voltage (Vout)


Frequency (nominal)
3FHVMBUJPOPGNBJOTWPMUBHF
Output frequency stability
(for 50 Hz)
0WFSMPBE XJUINBJOTQSFTFOU

&GGJDJFODZ
Peak factor
Communication interface
Noise level

Batteries
Typical back-up time (minutes)
!PGOPNJOBMMPBE
BU$XJUIFDJFOUCBUUFSJFT

ITY-TW010B / LB
10 / *


ITY-TW020B / LB
17 / *


ITY-TW030B / LB
9/*


ITY-TW060B / LB
13 / *


ITY-TW100B / LB
9/*


ITY-TW020B / LB

ITY-TW030B / LB
EN 62040

ITY-TW060B / LB

ITY-TW100B / LB

* Back-up time depends on the configuration of the external battery cabinet.

Standards
ITY-TW010B / LB
Standard
Product certification
Safety
EMC
Protection level

(EN) IEC 62040-1-1


EN 50091-2, IEC 62040-2
IP20 (compliant with a IEC 60529)

Mechanical characteristics
Dimensions WxDxH (mm)
Weight B (kg) / Weight LB (kg)

ITY-TW010B / LB
145x400x220
14 / 7

ITY-TW020B / LB
192x460x350
34 / 15

ITY-TW030B / LB
192x460x350
35 / 16

ITY-TW060B / LB
260x570x715
84 / 35

ITY-TW100B / LB
260x570x715
93 / 38

IOMITYTWXX00-GB_00

Downloaded from www.Manualslib.com manuals search engine

31

ENGLISH

Electrical specifications - Input

FRANAIS

ITALIANO