Caledonian

Caledonian Offshore & Marine Cables

BS 6883 STANDARD
(Flame Retardant)
BS 7917 STANDARD
(Fire Resisitant)

www.caledonian-cables.co.uk
www.addison-cables.com

Caledonian, established in 1978, offers one of the most


complete lines of ber and copper cabling system solutions with
over hundreds of different cabling system products. Our superior
products provide leading edge within every cable series and for
every application.
Among the national and international standards with which
our cables could comply are: BS - British Standard; LPCB Fire
Performance Standard, ISO Standard etc. Caledonian Cables
offers a comprehensive stock of cables and cabling products
through its nationwide network of resellers and distributors.
Caledonian Cables has continually expanded its global presence
in Europe and Asia.
Caledonian & Addison, produces a wide range of cables for
communication, power and electronics in its primary plants in UK,
Italy and Spain. To stay in front, we continually keep expanding
our manufacturing capabilities in more low cost region such as Romania, Taiwan, Malaysia
etc. This low-cost manufacturing facilities enable us provide a exible, scalable global system
that delivers superior operational performance and optimal results for our customers.
Our extensive global network of manufacturing facilities gives us significant scale and
the exibility to fulll our customer requirements. This global presence provides design and
consultancy solutions that are combined with core cable manufacturing, logistic services, and
vertically integrated with our E commerce technologies, to optimize customer operations by
lowering costs and reducing time to market.
Caledonian & Addison has been respected for its high standards of quality, excellent
service level, competitive pricing and a unique and innovative spirit. With our latest
technologies, we are both inspired and well-positioned to meet the changing needs of our
customers. We have the resources to diversify and to enhance our product lines and services.
We understand the need for change and with our accurate planning, we are ready for the
future and the promise of new marketing opportunities. Our tradition of growth through
excellence is assured.
Our Design Centers work closely with customers to constantly improve its standard
range of products and technologies and to develop customized, country and industryspecific solutions. Caledonian & Addison has established an extensive network of design,
manufacturing, and logistics facilities in the worlds major markets to serve the growing
outsourcing needs of both multinational and regional customers.

CONTENT
MV Flame Retardant Power & Control Cables
1.9/3.3kV, 3.3/3.3kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Flame Retardant Power &
Control Cables ......................................................................................................................................3
3.8/6.6kV, 6.35/11kV, 8.7/15kV HF-EPR Insulated, SW2/SW4 Sheathed Unarmoured Flame
Retardant Power & Control Cables (Radial Field) .................................................................................6
3.8/6.6kV, 6.35/11kV, 8.7/15kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Flame Retardant
Power & Control Cables (Radial Field) ..................................................................................................9
3.8/6.6kV, 6.6/6.6kV, 6.35/11kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Flame Retardant
Power & Control Cables (Non Radial Field) ........................................................................................12

MV Fire Resistant Power & Control Cables


1.9/3.3kV, 3.3/3.3kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Fire Resistant Power &
Control Cables ....................................................................................................................................15

LV Flame Retardant Power & Control Cables


0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Unarmoured Flame Retardant Power & Control
Cables .................................................................................................................................................18
0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Flame Retardant Power & Control Cables
.............................................................................................................................................................21

LV Fire Resistant Power & Control Cables


0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Unarmoured Fire Resistant Power & Control Cables
.............................................................................................................................................................24
0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Fire Resistant Power & Control Cables
.............................................................................................................................................................27

Flame Retardant Instrumentation & Control Cables


150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually Screened Unarmoured Flame
Retardant Instrumentation & Control Cables ......................................................................................30

www.addison-cables.com

ADDISON

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Content
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively Screened Unarmoured Flame


Retardant Instrumentation & Control Cables ......................................................................................32
150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually Screened Armoured Flame Retardant
Instrumentation & Control Cables .......................................................................................................34
150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively Screened Armoured Flame Retardant
Instrumentation & Control Cables .......................................................................................................36

Fire Resistant Instrumentation & Control Cables


150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually Screened Unarmoured Fire Resistant
Instrumentation & Control Cables .......................................................................................................38
150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively Screened Unarmoured Fire Resistant
Instrumentation & Control Cables .......................................................................................................40
150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually Screened Armoured Fire Resistant
Instrumentation & Control Cables .......................................................................................................42
150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively Screened Armoured Fire Resistant
Instrumentation & Control Cables .......................................................................................................44

Technical Information
Cores Identication ..............................................................................................................................46

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

1.9/3.3kV, 3.3/3.3kV HF-EPR Insulated, SW2/SW4 Sheathed


Armoured Flame Retardant Power & Control Cables
Application
These medium voltage elastomeric insulated cables are designed for xed wiring in ships
and on mobile offshore units, suitable for use in power and control applications.

Standards
BS 6883
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 607542 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


HF-EPR GP5 Insulation
SW2/SW4 Inner Sheath
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP5 according to BS 7655 1.2.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core).
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD
Temperature Range: -40 ~ +90

www.addison-cables.com

ADDISON

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


1.9/3.3kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
110
116
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
310
316
325
335
350
370
395
3120
3150
3185
3240
3300

2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.4
2.4
2.4
2.4
2.4
2.6
2.8
2.8
2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.4
2.4
2.4
2.4
2.4

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.1
1.2
1.2
1.3
1.3
1.4
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.2
2.3
1.5
1.6
1.8
1.8
1.9
2.1
2.3
2.4
2.6
2.7
3.0
3.2

10.2
11.4
13.0
14.1
15.3
17.2
19.4
21.3
22.8
24.8
27.5
30.0
33.8
37.6
41.2
20.4
22.8
26.6
28.4
31.2
35.3
40.2
44.0
47.6
51.7
57.7
63.1

11.9
13.1
14.8
15.9
17.2
19.2
21.9
23.8
25.4
27.4
30.3
33.2
37.1
41.1
45.2
22.9
25.3
29.3
31.2
34.4
38.7
44.1
48.1
51.8
56.4
62.9
68.6

Nominal
Armour
Wire
Diameter
mm

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

1.3
1.3
1.4
1.4
1.5
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.3
2.5
2.6
1.7
1.8
2.0
2.1
2.2
2.4
2.6
2.7
2.9
3.0
3.3
3.5

14.2
15.4
17.1
18.2
19.6
21.7
24.2
26.0
28.4
30.6
33.5
36.2
40.3
44.5
48.4
25.1
27.7
32.6
34.6
37.6
42.1
47.4
51.4
55.3
59.6
66.2
72.0

16.2
17.6
19.5
20.6
22.4
24.6
27.2
29.1
31.6
34.3
37.3
40.1
44.8
49.2
53.6
28.2
30.8
36.3
38.5
41.6
46.7
52.1
56.7
60.8
65.7
72.6
79.0

398
499
675
793
970
1269
1623
1983
2423
2917
3654
4428
5416
6726
8562
1052
1357
2032
2382
2936
3877
4995
6118
7284
8750
11118
13531

Nominal
Armour
Wire
Diameter
mm

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

0.3
0.3
0.3
0.3
0.3

1.4
1.4
1.5
1.5
1.6

16.1
17.1
19.1
19.9
21.5

18.4
19.4
21.5
22.8
24.4

483
579
774
885
1082

3.3/3.3kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
110
116
125
135
150

3.0
3.0
3.0
3.0
3.0

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.2
1.2
1.3
1.3
1.4

12.0
13.0
14.7
15.6
17.0

www.addison-cables.com

13.7
14.7
16.7
17.6
19.0

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
170
195
1120
1150
1185
1240
1300
1400
1500
1630
310
316
325
335
350
370
395
3120
3150
3185
3240

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.2
3.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.5
1.5
1.6
1.7
1.7
1.8
1.9
2.1
2.2
2.4
1.7
1.8
1.9
2.0
2.1
2.2
2.4
2.5
2.7
2.8
3.1

18.9
20.6
22.5
24.1
26.0
28.7
31.2
34.7
38.4
42.2
24.1
26.5
30.1
32.1
34.9
38.9
42.9
46.7
50.3
54.4
60.4

21.0
23.1
25.0
26.8
28.6
31.8
34.4
38.1
41.9
46.2
26.7
29.2
33.2
35.4
38.3
42.7
46.9
50.9
54.9
59.2
65.7

Nominal
Armour
Wire
Diameter
mm

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.5
2.6
1.9
2.0
2.1
2.2
2.3
2.5
2.7
2.8
3.0
3.2
3.4

23.4
25.3
27.4
30.0
32.0
34.8
37.6
41.3
45.3
49.4
29.9
32.5
36.3
38.5
41.5
45.8
50.2
54.2
58.2
62.7
69.1

26.4
28.4
30.5
33.6
35.7
38.7
41.5
45.8
50.0
54.6
33.6
36.2
40.2
42.9
46.0
50.5
55.5
59.7
64.2
68.9
76.0

1377
1699
2081
2550
3032
3780
4563
5514
6807
8691
1404
1738
2314
2701
3278
4226
5297
6442
7631
9158
11526

www.addison-cables.com

ADDISON

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

3.8/6.6kV, 6.35/11kV, 8.7/15kV HF-EPR Insulated, SW2/SW4


Sheathed Unarmoured Flame Retardant Power & Control Cables
(Radial Field)
Application
These medium voltage elastomeric insulated cables are designed for xed wiring in ships
and on mobile offshore units, suitable for use in power and control applications.

Standards

Stranded Tinned Copper Conductor

BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Conductor Screen
HF-EPR GP5 Insulation
Insulation Screen
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Conductor Screen: Semiconducting layer or tape.
Insulation: HF-EPR GP5 according to BS 7655 1.2.
Insulation Screen: Semiconducting layer or tape +Tinned copper tape.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 15OD (single core); 20OD (three core)
Temperature Range: -40 ~ +90

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


3.8/6.6kV
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
116
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
316
325
335
350
370
395
3120
3150
3185
3240

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.2
3.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

Nominal Outer
Sheath Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.3
1.3
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.1
2.3
2.4
1.8
2.0
2.0
2.2
2.3
2.5
2.6
2.7
2.9
3.1

16.0
17.6
18.7
19.9
21.8
23.7
25.4
27.0
29.0
31.7
34.3
37.6
41.4
45.1
32.7
36.5
38.4
41.3
45.3
49.3
53.1
56.5
60.8
66.6

18.0
19.7
20.8
22.3
24.3
26.3
28.0
29.8
32.1
35.0
37.6
41.1
45.5
49.2
36.0
39.9
41.9
45.3
49.4
53.9
57.8
61.4
66.1
72.2

492
658
776
942
1229
1546
1890
2242
2713
3427
4177
5145
6408
8134
1482
2031
2359
2918
3788
4776
5868
6933
8401
10616

Nominal Outer
Sheath Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.3
1.4
1.4
1.5
1.5
1.6
1.7
1.7
1.8
1.9

16.8
18.6
19.4
20.8
22.6
24.4
26.3
27.8
29.8
32.5

18.8
20.7
21.9
23.3
25.1
27.1
29.0
30.6
32.9
35.8

524
704
813
994
1272
1592
1956
2294
2769
3487

6.35/11kV
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
116
125
135
150
170
195
1120
1150
1185
1240

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

www.addison-cables.com

ADDISON

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
1300
1400
1500
1630
316
325
335
350
370
395
3120
3150
3185
3240

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

Nominal Outer
Sheath Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

2.0
2.1
2.3
2.4
1.9
2.0
2.1
2.2
2.4
2.5
2.7
2.8
3.0
3.2

35.0
38.4
41.8
45.5
34.5
38.2
40.2
43.0
47.1
51.0
55.0
58.4
62.7
68.5

38.4
41.9
45.8
49.6
37.9
41.6
44.1
47.0
51.3
55.6
59.8
63.3
68.1
74.1

4242
5208
6442
8176
1601
2139
2497
3040
3949
4919
6055
7132
8613
10848

Nominal Outer
Sheath Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
Mm

Approx. Weight
kg/km

1.5
1.5
1.5
1.6
1.7
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.5
2.2
2.3
2.4
2.6
2.7
2.9
3.0
3.2

20.9
21.7
22.9
24.9
26.7
28.6
30.1
32.1
34.8
37.3
40.7
44.1
47.8
43.1
45.2
47.9
52.1
55.9
59.9
63.3
67.6

23.4
24.3
25.5
27.5
29.5
31.4
33.3
35.3
38.2
40.8
44.6
48.2
52.0
47.1
49.2
52.1
56.7
60.7
64.9
68.7
73.2

808
921
1110
1396
1726
2099
2445
2929
3661
4429
5390
6638
8415
2458
2832
3395
4336
5334
6500
7602
9116

8.7/15kV
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
325
335
350
370
395
3120
3150
3185

ADDISON

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

3.8/6.6kV, 6.35/11kV, 8.7/15kV HF-EPR Insulated, SW2/SW4


Sheathed Armoured Flame Retardant Power & Control Cables
(Radial Field)
Application
These medium voltage elastomeric insulated cables are designed for xed wiring in ships
and on mobile offshore units, suitable for use in power and control applications.

Standards
BS 6883
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 607542 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

SW2/SW4 Inner Sheath


Stranded Tinned Copper Conductor
Conductor Screen
HF-EPR GP5 Insulation
Insulation Screen
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Conductor Screen: Semiconducting layer or tape.
Insulation: HF-EPR GP5 according to BS 7655 1.2.
Insulation Screen: Semiconducting layer or tape +Tinned copper tape.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core).
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 15OD (single core); 20OD (three core)
Temperature Range: -40 ~ +90
www.addison-cables.com

ADDISON

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


3.8/6.6kV
Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

116
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
316
325
335
350
370
395
3120
3150
3185
3240

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.2
3.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

6.35/11kV
Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

116
125
135
150
170
195
1120
1150

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

10

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.3
16.0
18.0
1.3
17.6
19.7
1.4
18.7
20.8
1.4
19.9
22.3
1.5
21.8
24.3
1.6
23.7
26.3
1.6
25.4
28.0
1.7
27.0
29.8
1.8
29.0
32.1
1.9
31.7
35.0
2.0
34.3
37.6
2.1
37.6
41.4
2.3
41.4
45.4
45.1
49.2
2.4
1.8
32.7
36.0
2.0
36.5
39.9
2.0
38.4
41.9
2.2
41.3
45.3
2.3
45.3
49.4
2.5
49.3
53.9
2.6
53.1
57.8
2.7
56.6
61.4
2.9
60.8
66.1
3.1
66.6
72.2

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.4
1.5
1.5
1.6
1.7
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.5
2.7
2.1
2.2
2.3
2.4
2.6
2.8
2.9
3.1
3.2
3.5

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.3
16.8
18.8
1.4
18.6
20.7
1.4
19.4
21.9
1.5
20.8
23.3
1.5
22.6
25.1
1.6
24.4
27.1
1.7
26.3
29.0
1.7
27.8
30.6

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.5
1.5
1.6
1.6
1.7
1.8
1.9
2.0

www.addison-cables.com

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

20.2
21.9
23.0
24.4
26.5
28.6
30.2
32.8
35.0
37.9
40.6
44.4
48.4
52.4
38.9
42.9
44.9
48.1
52.4
56.8
60.8
64.6
69.1
75.5

23.0
24.9
26.0
27.4
29.6
31.8
33.9
36.6
38.9
41.9
45.1
49.0
53.6
57.8
43.3
47.5
49.6
53.3
57.4
62.4
67.0
70.9
76.0
82.6

790
950
1060
1320
1610
1930
2260
2760
3210
3960
4660
5470
6610
8230
2610
3220
3700
4360
5410
6710
7770
9160
10430
12840

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

21.1
22.9
24.0
25.3
27.3
29.3
32.1
33.8

24
25.9
27.0
28.4
30.4
33.0
35.9
37.6

810
980
1110
1360
1660
1970
2360
2810

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

1185
1240
1300
1400
1500
1630
316
325
335
350
370
395
3120
3150
3185
3240

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

8.7/15kV
Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
325
335
350
370
395
3120
3150
3185

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.8
29.8
32.9
1.9
32.5
35.8
38.4
2.0
35.0
2.1
38.4
41.9
2.3
41.8
45.8
2.4
45.5
49.6
1.9
34.5
37.9
2.0
38.2
41.6
2.1
40.2
44.1
2.2
43.0
47.0
2.4
47.1
51.3
2.5
51.0
55.6
2.7
55.0
59.8
2.8
58.4
63.3
3.0
62.7
68.1
3.2
68.5
74.1

Nominal
Armour
Wire
Diameter
mm
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
2.0
2.2
2.3
2.4
2.5
2.7
2.1
2.3
2.4
2.5
2.7
2.8
3.0
3.1
3.3
3.6

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.5
20.9
23.4
1.5
21.7
24.3
1.5
22.9
25.5
1.6
24.9
27.5
1.7
26.7
29.5
1.8
28.6
31.4
1.8
30.1
33.3
1.9
32.1
35.3
2.0
34.8
38.2
2.1
37.3
40.8
2.2
40.7
44.6
2.4
44.1
48.2
2.5
47.8
52.0
2.2
43.1
47.1
2.3
45.2
49.2
2.4
47.9
52.1
2.6
52.1
56.7
2.7
55.9
60.7
2.9
59.9
64.9
3.0
63.3
68.7
3.2
67.6
73.2

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.2
2.4
2.5
2.6
2.8
2.5
2.6
2.7
2.9
3.0
3.2
3.3
3.5

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

35.8
38.9
41.6
45.1
48.8
52.8
40.7
44.7
47.0
50.0
54.4
58.5
62.9
66.5
71.2
77.5

39.7
43.3
46.1
49.8
54.0
58.2
45.2
49.4
51.7
55.2
59.9
64.5
69.1
72.8
78.1
85.2

3260
4020
4760
5610
6820
8480
2660
3310
3960
4570
5610
6820
8070
9260
10960
13390

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

25.4
26.4
27.6
29.8
32.6
34.6
36.3
38.3
41.2
44.1
47.6
51.3
55.3
50.1
52.3
55.3
59.8
63.8
68.2
71.8
76.5

28.5
29.6
30.8
33.4
36.3
38.5
40.2
42.3
45.7
48.7
52.4
56.6
60.8
55.4
57.7
60.8
65.9
70.1
75.1
78.8
83.7

1150
1260
1510
1770
2270
2730
3020
3490
4260
4810
6160
7330
8800
3610
4510
5210
6390
7660
8810
10070
11420

www.addison-cables.com

ADDISON

11

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

3.8/6.6kV, 6.6/6.6kV, 6.35/11kV HF-EPR Insulated, SW2/SW4


Sheathed Armoured Flame Retardant Power & Control Cables
(Non Radial Field)
Application
These medium voltage elastomeric insulated cables are designed for xed wiring in ships
and on mobile offshore units, suitable for use in power and control applications.

Standards
BS 6883
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 607542 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


Conductor Screen
HF-EPR GP5 Insulation
SW2/SW4 Inner Sheath
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Conductor Screen: Semiconducting layer or tape.
Insulation: HF-EPR GP5 according to BS 7655 1.2.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core).
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 12OD
Temperature Range: -40 ~ +90
12

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


3.8/6.6kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
116
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
316
325
335
350
370
395
3120
3150
3185
3240

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

6.6/6.6kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
125
135
150
170
195
1120
1150
1185

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.3
13.9
15.7
1.3
15.5
17.5
1.4
16.6
18.6
1.4
17.8
19.8
1.5
19.7
22.1
1.6
21.6
24.1
1.6
23.2
25.8
1.7
24.9
27.6
1.8
26.9
29.6
1.9
29.6
32.8
2.0
32.1
35.4
2.1
35.5
38.9
2.2
38.7
42.6
42.6
46.6
2.4
1.8
28.1
30.9
2.0
31.9
35.2
2.0
33.8
37.1
2.2
36.8
40.2
2.3
40.7
44.6
2.5
44.7
48.8
2.6
48.6
53.1
2.7
51.9
56.6
2.9
56.2
61.1
3.1
62.0
67.4

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.4
1.5
1.5
1.6
1.7
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.5
2.7
2.1
2.2
2.3
2.4
2.6
2.8
2.9
3.1
3.2
3.5

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.5
19.9
22.4
1.5
20.8
23.3
1.6
22.2
24.7
1.7
24.1
26.7
1.7
25.8
28.5
1.8
27.7
30.4
1.9
29.3
32.5
1.9
31.1
34.3

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.7
1.7
1.8
1.9
2.0
2.0
2.1
2.2

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

18.0
19.8
20.9
22.3
24.4
26.5
28.1
30.7
32.9
35.8
38.5
42.2
45.7
49.9
34.3
38.3
40.4
43.5
47.9
52.3
56.3
60.1
64.6
70.9

20.4
22.7
23.8
25.2
27.4
29.6
31.3
34.4
36.7
39.7
42.9
46.8
50.4
55.2
38.2
42.3
44.9
48.2
52.7
57.7
61.8
66.2
70.8
77.9

703
899
1029
1223
1547
1903
2266
2760
3282
4059
4872
5844
7113
9093
2109
2747
3133
3772
4771
5900
7098
8304
9895
12358

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

24.6
25.5
27.1
29.9
31.8
33.7
35.5
37.5

27.7
28.6
30.2
33.6
35.5
37.5
39.4
41.5

1211
1338
1565
2017
2383
2794
3213
3737

www.addison-cables.com

ADDISON

13

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
1240
1300
1400
1500
1630
325
335
350
370
395
3120
3150
3185
3240

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

6.35/11kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
335
350
370
395
3120
3150
3185

14

6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
2.0
33.8
37.2
2.1
36.4
39.8
43.8
2.3
39.9
2.4
43.2
47.2
2.5
46.8
51.0
2.3
41.2
45.1
2.4
43.3
47.3
2.5
46.1
50.2
2.7
50.2
54.8
2.8
54.0
58.8
3.0
58.0
63.0
3.1
61.4
66.8
3.3
65.7
71.3
3.5
71.5
77.6

Nominal
Armour
Wire
Diameter
mm
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
2.3
2.4
2.6
2.7
2.8
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.6
3.9

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.6
22.9
25.5
1.7
24.3
26.9
1.7
26.0
28.7
1.8
27.9
30.7
1.9
29.8
32.9
1.9
31.2
34.5
2.0
33.3
36.5
2.1
36.0
39.4
2.2
38.5
42.3
2.4
42.0
46.0
2.5
45.3
49.4
2.6
48.9
53.5
2.6
47.8
52.0
2.7
50.6
55.2
2.8
54.5
59.3
3.0
58.6
63.5
3.1
62.4
67.8
3.3
66.0
71.5
3.4
70.1
76.1

Nominal
Armour
Wire
Diameter
mm
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.8
1.9
2.0
2.1
2.1
2.2
2.3
2.4
2.5
2.6
2.8
2.9
2.9
3.0
3.2
3.3
3.5
3.6
3.8

www.addison-cables.com

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

40.4
43.1
47.0
50.5
54.3
48.4
50.6
53.6
58.1
62.1
66.5
70.1
74.8
81.2

44.9
47.7
51.8
55.8
59.8
53.6
55.9
59.0
64.1
68.3
72.9
77.0
81.9
89.0

4548
5392
6384
7689
9709
3746
4204
4872
5992
7130
8486
9723
11448
14038

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

27.8
30.1
32.0
34.1
36.0
37.6
39.8
42.7
45.4
49.2
52.8
56.6
55.5
58.5
62.8
67.0
71.3
75.0
79.5

31.0
33.8
35.8
37.9
39.9
41.6
44.3
47.3
50.1
54.4
58.2
62.2
61.1
64.6
69.0
73.4
78.2
82.2
87.2

1514
1751
2201
2600
3021
3427
3987
4814
5674
6637
7986
10057
4793
5489
6612
7829
9182
10498
12218

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

1.9/3.3kV, 3.3/3.3kV HF-EPR Insulated, SW2/SW4 Sheathed


Armoured Fire Resistant Power & Control Cables
Application
These fire resistant medium voltage elastomeric insulated cables are designed for fixed
wiring in ships and on mobile offshore units, suitable for use in power and control applications
where re integrity is essential.

Standards
BS 7917
IEC 60331-31 Fire
resistant
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 60754-2 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


Mica Tape+HF-EPR GP5 Insulation
SB1 Inner Sheath
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP5 according to BS 7655 1.2.
Inner Sheath: Halogen free thermosetting compound SB1 according to BS 7917.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core).
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD
Temperature Range: -40 ~ +90

www.addison-cables.com

ADDISON

15

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


1.9/3.3kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
125
135
150
170
195
1120
1150
1185
1240
1300
1400
1500
1630
325
335
350
370
395
3120
3150
3185
3240
3300

2.2
2.2
2.2
2.2
2.4
2.4
2.4
2.4
2.4
2.4
2.6
2.8
2.8
2.2
2.2
2.2
2.2
2.4
2.4
2.4
2.4
2.4
2.4

3.3/3.3kV
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
125
135
150
170
195
1120
1150
1185
1240

16

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.2
13.4
15.2
1.3
14.4
16.4
1.3
15.6
17.6
1.4
17.6
19.6
1.5
19.8
22.3
1.6
21.7
24.2
1.6
23.2
25.8
1.7
25.2
27.8
1.8
27.9
30.7
1.9
30.4
33.6
2.0
34.1
37.5
2.2
38.0
41.5
2.3
41.6
45.6
27.4
30.1
1.8
1.8
29.3
32.4
1.9
32.1
35.3
2.1
36.2
39.6
2.3
41.0
44.9
2.4
44.9
48.9
2.6
48.4
53.0
2.7
52.5
57.2
3.0
58.5
63.8
3.2
64.0
69.4

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.4
1.4
1.5
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.3
2.5
2.6
2.0
2.1
2.2
2.4
2.6
2.7
2.9
3.0
3.3
3.5

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.3
15.1
17.1
1.3
16.0
18.0
1.4
17.4
19.4
1.5
19.3
21.7
1.5
21.0
23.5
1.6
22.9
25.4
1.7
24.5
27.2
1.7
26.3
29.0
1.8
29.0
32.2

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.5
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.1

www.addison-cables.com

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

17.5
18.6
20.0
22.1
24.5
26.4
28.8
31.0
33.9
36.6
40.7
44.9
48.8
33.4
35.5
38.4
42.9
48.2
52.2
56.2
60.5
67.0
72.8

19.9
21.0
22.8
25.0
27.6
29.5
32.0
34.7
37.7
40.5
45.2
49.6
54.0
37.2
39.3
42.8
47.5
53.4
57.6
61.7
66.6
73.4
79.9

687
806
983
1283
1637
1997
2439
2933
3671
4446
5435
6746
8583
2072
2422
2977
3920
5041
6165
7333
8800
11172
13587

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

19.4
20.3
21.9
23.8
25.7
27.8
30.3
32.3
35.2

22.3
23.2
24.8
26.8
28.8
30.9
34.0
36.1
39.1

789
900
1097
1392
1715
2097
2568
3050
3798

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
1300
1400
1500
1630
325
335
350
370
395
3120
3150
3185
3240
3300

3.0
3.0
3.2
3.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.9
31.6
34.8
2.1
35.1
38.5
42.6
2.2
38.7
2.4
43.6
46.6
1.9
30.9
34.1
2.0
33.0
36.2
2.1
35.8
39.1
2.2
39.7
43.5
2.4
43.7
47.7
2.5
47.5
51.7
2.7
51.1
55.7
2.8
55.2
60.0
3.1
61.2
66.6
3.3
66.6
72.2

Nominal
Armour
Wire
Diameter
mm
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
2.2
2.3
2.5
2.6
2.1
2.2
2.3
2.5
2.7
2.8
3.0
3.2
3.4
3.6

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

37.9
41.7
45.7
49.7
37.1
39.4
42.3
46.6
51.1
55.1
59.0
63.5
69.9
75.7

41.9
46.2
50.4
55.0
41.1
43.8
46.9
51.4
56.4
60.6
65.1
69.8
76.8
82.9

4582
5533
6828
8712
2358
2747
3325
4274
5347
6493
7684
9213
11583
14031

www.addison-cables.com

ADDISON

17

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Unarmoured Flame


Retardant Power & Control Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in power and control applications.

Standards
BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor

HF-EPR GP4 Insulation


SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD (OD>25mm); 4OD (OD 25mm)
Temperature Range: -40 ~ +90

18

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Single core cables
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
14
16
110
116
125
135
150
170
195
1120
1150
1185
1240
1300

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.0
1.0
1.0
1.1
1.2
1.2
1.3
1.3
1.4
1.5
1.6
1.7
1.8
1.9

6.3
6.8
7.7
8.9
11.1
12.0
13.7
15.5
17.7
19.6
21.6
24.0
27.1
30.0

7.6
8.1
9.1
10.3
12.8
13.7
15.5
17.4
19.8
22.0
24.2
26.6
29.9
33.2

85
120
165
230
345
445
600
810
1100
1360
1650
2070
2670
3340

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.0
1.1
1.1
1.2
1.2
1.3
1.4
1.5
1.6
1.7
1.9
2.1
2.2
1.1
1.1
1.1
1.2
1.2
1.3
1.4

7.5
8.2
9.0
11.0
12.1
14.1
16.3
20.4
22.4
25.7
29.6
34.1
37.7
8.2
8.7
9.6
11.7
12.9
15.0
17.4

8.8
9.6
10.4
12.7
13.8
15.9
18.3
22.9
24.9
28.4
32.7
37.4
41.1
9.5
10.1
11.0
13.4
14.7
17.0
19.4

100
125
160
235
300
415
590
890
1150
1570
2140
2930
3600
110
150
190
280
370
505
750

Multicore cables
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
21
21.5
22.5
24
26
210
216
225
235
250
270
295
2120
31
31.5
32.5
34
36
310
316

0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
0.8
1.0
1.0
1.0
1.0

www.addison-cables.com

ADDISON

19

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
325
335
350
370
395
3120
3150
3185
3240
3300
41
41.5
42.5
44
46
410
416
425
435
450
470
495
4120
4150
4185
4240
51.5
71.5
121.5
191.5
271.5
371.5
52.5
72.5
122.5
192.5

20

ADDISON

1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.6
1.7
1.8
2.0
2.2
2.3
2.5
2.7
2.9
3.2
1.1
1.1
1.1
1.2
1.3
1.4
1.5
1.7
1.8
1.9
2.1
2.3
2.5
2.7
2.9
3.2
1.1
1.2
1.3
1.4
1.6
1.7
1.2
1.2
1.4
1.5

22.0
24.1
27.7
31.8
36.7
40.5
44.9
50.1
56.7
63.1
8.9
9.5
10.5
12.9
14.4
16.7
19.4
24.5
26.8
30.8
35.4
40.8
45.2
50.1
55.8
63.4
10.4
11.5
15.2
18.0
21.9
24.7
11.7
12.7
17.1
20.2

24.6
26.7
30.5
35.1
40.1
44.4
49.0
54.6
61.5
68.6
10.3
10.9
12.1
14.6
16.2
18.7
21.8
27.1
29.5
34.0
38.8
44.7
49.3
54.7
60.7
68.9
12.0
13.2
17.2
20.1
24.5
27.3
13.3
14.4
19.1
22.7

1150
1490
2030
2790
3820
4710
5710
7180
9310
10860
140
175
225
340
465
640
960
1550
1920
2600
3570
4900
6070
7360
9260
12030
200
255
405
600
850
1120
270
335
550
830

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Flame


Retardant Power & Control Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in power and control applications.

Standards
BS 6883
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 607542 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


HF-EPR GP4 Insulation
SW2/SW4 Inner Sheath
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core). Copper
wire braid can be offered upon request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD (OD>25mm); 4OD (OD 25mm)
Temperature Range: -40 ~ +90

www.addison-cables.com

ADDISON

21

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Single core cables
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
14
16
110
116
125
135
150
170
195
1120
1150
1185
1240
1300

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

Multicore cables
Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
21
21.5
22.5
24
26
210
216
225
235
250
270
295
2120
31
31.5
32.5
34
36

22

0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
0.8
1.0
1.0

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.0
6.3
7.6
1.0
6.8
8.1
9.1
1.0
7.7
1.1
8.9
10.3
1.2
11.1
12.8
1.2
12.0
13.7
1.3
13.7
15.5
1.3
15.5
17.4
1.4
17.7
19.8
1.5
19.6
22.0
1.6
21.6
24.2
1.7
24.0
26.6
1.8
27.1
29.9
1.9
30.0
33.2

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.1
1.1
1.2
1.2
1.3
1.4
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.1

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.0
7.5
8.8
1.1
8.2
9.6
1.1
9.0
10.4
1.2
11.0
12.7
1.2
12.1
13.8
1.3
14.1
15.9
1.4
16.3
18.3
1.5
20.4
22.9
1.6
22.4
24.9
1.7
25.7
28.4
1.9
29.6
32.7
2.1
34.1
37.4
2.2
37.7
41.1
1.1
8.2
9.5
1.1
8.7
10.1
1.1
9.6
11.0
1.2
11.7
13.4
1.2
12.9
14.7

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3

Nominal
Outer
Sheath
Thickness
mm
1.2
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.8
2.0
2.1
2.3
2.5
1.2
1.2
1.3
1.3
1.4

www.addison-cables.com

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

9.8
10.4
11.5
12.7
15.0
16.1
17.9
19.8
22.2
24.3
26.5
29.8
33.1
36.2

11.7
12.2
13.4
14.6
17.3
18.4
20.2
22.6
25.2
27.3
29.7
33.5
36.9
40.1

220
250
310
400
570
660
870
1110
1460
1770
2110
2720
3410
4180

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

11.3
12.0
12.8
15.0
16.3
18.2
20.6
25.2
27.3
31.7
35.8
40.7
44.6
11.9
12.5
13.5
15.7
17.0

13.1
13.9
14.7
17.2
18.5
20.6
23.5
28.2
30.4
35.5
39.7
45.2
49.3
13.8
14.4
15.5
17.9
19.4

230
270
320
430
530
660
840
1310
1600
2240
2900
3860
4650
250
305
360
495
600

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm
310
316
325
335
350
370
395
3120
3150
3185
3240
3300
41
41.5
42.5
44
46
410
416
425
435
450
470
495
4120
4150
4185
4240
51.5
71.5
121.5
191.5
271.5
371.5
52.5
72.5
122.5
192.5

1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.3
15.0
17.0
1.4
17.4
19.4
1.6
22.0
24.6
1.7
24.1
26.7
1.8
27.7
30.5
2.0
31.8
35.1
2.2
36.7
40.1
2.3
40.5
44.4
2.5
44.9
49.0
2.7
50.1
54.6
2.9
56.7
61.5
3.2
63.1
68.6
1.1
8.9
10.3
9.5
10.9
1.1
1.1
10.5
12.1
1.2
12.9
14.6
1.3
14.4
16.2
1.4
16.7
18.7
1.5
19.4
21.8
1.7
24.5
27.1
1.8
26.8
29.5
1.9
30.8
34.0
2.1
35.4
38.8
2.3
40.8
44.7
49.3
2.5
45.2
2.7
50.1
54.7
2.9
55.8
60.7
3.2
63.4
68.9
1.1
10.4
12.0
1.2
11.5
13.2
1.3
15.2
17.2
1.4
18.0
20.1
1.6
21.9
24.5
1.7
24.7
27.3
1.2
11.7
13.3
1.2
12.7
14.4
1.4
17.1
19.1
1.5
20.2
22.7

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3

Nominal
Outer
Sheath
Thickness
mm
1.5
1.6
1.8
1.9
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.5
1.2
1.3
1.3
1.4
1.5
1.6
1.7
1.9
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.5
1.3
1.3
1.5
1.6
1.8
1.9
1.3
1.4
1.6
1.7

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

19.4
21.9
26.9
29.9
33.7
38.2
43.5
47.7
52.5
58.0
65.0
72.0
12.6
13.5
14.4
17.0
18.7
21.3
24.1
30.3
32.8
37.2
42.2
47.9
52.8
58.1
64.1
72.3
14.3
15.4
19.6
22.5
26.8
30.5
15.6
16.8
21.6
24.9

22.2
24.8
30.1
33.6
37.5
42.2
48.1
52.5
57.8
64.0
71.3
79.0
14.6
15.4
16.4
19.3
21.1
24.1
27.1
34.0
36.6
41.2
46.7
52.7
58.2
64.1
70.4
79.3
16.3
17.7
22.4
25.5
30.0
34.2
17.8
19.1
24.5
28.0

810
1070
1620
2130
2750
3660
4740
5950
7120
8820
11280
13640
280
350
410
570
730
990
1330
2150
2600
3410
4530
5940
7390
8700
10780
13840
395
460
680
930
1270
1740
480
570
880
1220

www.addison-cables.com

ADDISON

23

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Unarmoured Fire


Resistant Power & Control Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in power and control applications where re integrity
is essential.

Standards
BS 7917
IEC 60331-31 Fire resistant
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor

Mica Tape+HF-EPR GP4 Insulation


SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD (OD>25mm); 4OD (OD 25mm)
Temperature Range: -40 ~ +90

24

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Single core cables
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
14
16
110
116
125
135
150
170
195
1120
1150
1185
1240
1300

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.0
1.0
1.0
1.1
1.2
1.2
1.3
1.3
1.4
1.5
1.6
1.7
1.8
1.9

6.7
7.2
8.1
9.3
11.5
12.3
14.1
15.8
18.1
20.0
22.0
24.4
27.5
30.4

8.0
8.5
9.5
10.7
13.2
14.1
15.9
17.8
20.2
22.4
24.6
27.0
30.3
33.6

90
135
180
315
550
715
830
1110
1470
2130
2475
2870
3120
4060

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.1
1.1
1.2
1.2
1.3
1.4
1.5
1.6
1.7
1.9
2.1
2.2
1.1
1.1
1.2
1.2
1.3
1.4
1.6
1.7

9.0
9.8
11.8
12.9
14.9
17.1
21.2
23.1
26.5
30.3
34.9
38.4
9.6
10.4
12.6
13.8
15.9
18.2
22.9
24.9

10.4
11.4
13.5
14.6
16.8
19.1
23.7
25.7
29.2
33.5
38.2
42.2
11.0
12.1
14.3
15.5
17.8
20.3
25.4
27.6

145
180
260
325
445
630
930
1210
1630
2210
3010
3690
170
210
310
395
590
830
1270
1540

Multicore cables
Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
21.5
22.5
24
26
210
216
225
235
250
270
295
2120
31.5
32.5
34
36
310
316
325
335

0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2

www.addison-cables.com

ADDISON

25

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm
350
370
395
3120
3150
3185
3240
41.5
42.5
44
46
410
416
425
435
450
470
495
4120
51.5
71.5
121.5
191.5
271.5
371.5
52.5
72.5
122.5
192.5

26

ADDISON

1.4
1.4
1.6
1.6
1.8
2.0
2.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

1.8
2.0
2.2
2.3
2.5
2.7
2.9
1.1
1.1
1.2
1.3
1.4
1.5
1.7
1.8
1.9
2.1
2.3
2.5
1.1
1.2
1.3
1.4
1.6
1.7
1.2
1.2
1.4
1.5

28.5
32.7
37.5
41.3
45.8
50.9
57.5
10.5
11.4
13.8
15.3
17.7
20.3
25.5
27.7
31.8
36.3
41.7
46.2
11.4
12.6
16.8
19.9
24.3
27.4
12.7
13.9
18.7
22.1

31.3
35.9
41.0
45.3
49.9
55.5
62.4
12.1
13.1
15.6
17.3
19.7
22.8
28.1
30.5
35.0
39.7
45.7
50.3
13.1
14.4
18.8
22.4
26.9
30.4
14.4
15.6
20.8
24.7

2100
2870
3910
4800
5810
7290
9440
200
250
375
495
740
1050
1580
1960
2570
3530
4850
5990
220
285
465
680
960
1260
310
375
610
895

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

0.6/1kV HF-EPR Insulated, SW2/SW4 Sheathed Armoured Fire


Resistant Power & Control Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in power and control applications where re integrity
is essential.

Standards
BS 7917
IEC 60331-31 Fire
resistant
IEC 60332-3A Flame
retardant
IEC 60754-1; IEC 60754-2 Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


Mica Tape+HF-EPR GP4 Insulation
SB1 Inner Sheath
Galvanized Steel Wire/Tinned Bronze Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Inner Sheath: Halogen free thermosetting compound SB1 according to BS 7917.
Armour: Galvanized steel wire braid or tinned bronze wire braid (single core). Copper
wire braid can be offered upon request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 6OD
Temperature Range: -40 ~ +90

www.addison-cables.com

ADDISON

27

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Single core cables
Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

14
16
110
116
125
135
150
170
195
1120
1150
1185
1240
1300

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4

Multicore cables
Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

21.5
22.5
24
26
210
216
225
235
250
270
295
2120
31.5
32.5
34
36
310
316

0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
1.0
1.0
1.0
1.0

28

ADDISON

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.0
6.7
8.0
1.0
7.2
8.5
1.0
8.1
9.5
1.1
9.3
10.7
1.2
11.5
13.2
1.2
12.3
14.1
1.3
14.1
15.9
1.3
15.8
17.8
1.4
18.1
20.2
1.5
20.0
22.4
1.6
22.0
24.6
1.7
24.4
27.0
1.8
27.5
30.3
1.9
30.4
33.6

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45

Nominal
Outer
Sheath
Thickness
mm
1.1
1.1
1.2
1.2
1.3
1.4
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.1

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.1
9.0
10.4
1.1
9.8
11.4
1.2
11.8
13.5
1.2
12.9
14.6
1.3
14.9
16.8
1.4
17.1
19.1
1.5
21.2
23.7
1.6
23.1
25.7
1.7
26.5
29.2
1.9
30.3
33.5
2.1
34.9
38.2
2.2
38.4
42.2
1.1
9.6
11.0
1.1
10.4
12.1
1.2
12.6
14.3
1.2
13.8
15.5
1.3
15.9
17.8
1.4
18.2
20.3

Nominal
Armour
Wire
Diameter
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3
0.3

Nominal
Outer
Sheath
Thickness
mm
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.8
2.0
2.1
2.3
2.5
1.2
1.3
1.3
1.4
1.5
1.6

www.addison-cables.com

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

10.2
10.8
11.9
13.1
15.4
16.5
18.2
20.2
22.6
24.7
26.9
30.2
33.5
36.6

12.1
12.6
13.8
15.0
17.7
18.8
20.6
23.0
25.6
27.7
30.1
33.9
37.3
40.5

245
275
355
440
600
720
910
1170
1510
1830
2160
2790
3530
4280

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

12.7
13.6
15.7
17.0
19.0
21.4
25.9
28.0
32.5
36.5
41.4
45.4
13.3
14.4
16.5
17.9
20.2
22.8

14.7
15.5
18.0
19.3
21.4
24.3
29.0
31.2
36.3
40.5
46.0
50.1
15.3
16.4
18.8
20.2
23.0
25.7

310
355
475
580
750
980
1380
1710
2370
3100
4020
4870
345
405
540
660
910
1200

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


LV Fire Resistant Power & Control Cables
www.caledonian-cables.co.uk

Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

325
335
350
370
395
3120
3150
3185
3240
41.5
42.5
44
46
410
416
425
435
450
470
495
4120
51.5
71.5
121.5
191.5
271.5
371.5
52.5
72.5
122.5
192.5

1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

Nominal
Minimum Maximum
Inner
Diameter
Diameter
Sheath
Over Inner Over Inner
Thickness
Sheath
Sheath
mm
mm
mm
1.6
22.9
25.4
1.7
24.9
27.6
1.8
28.5
31.3
2.0
32.7
35.9
2.2
37.5
41.0
2.3
41.3
45.3
2.5
45.8
49.9
2.7
50.9
55.5
2.9
57.5
62.4
1.1
10.5
12.1
1.1
11.4
13.1
1.2
13.8
15.6
1.3
15.3
17.3
19.7
1.4
17.7
1.5
20.3
22.8
1.7
25.5
28.1
1.8
27.7
30.5
1.9
31.8
35.0
2.1
36.3
39.7
2.3
41.7
45.7
2.5
46.2
50.3
1.1
11.4
13.1
1.2
12.6
14.4
1.3
16.8
18.8
1.4
19.9
22.4
1.6
24.3
26.9
1.7
27.4
30.4
1.2
12.7
14.4
1.2
13.9
15.6
1.4
18.7
20.8
1.5
22.1
24.7

Nominal
Armour
Wire
Diameter
mm
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3
0.3
0.45
0.45
0.45
0.45
0.45
0.45
0.3
0.3
0.3
0.3
0.3
0.45
0.3
0.3
0.3
0.3

Nominal
Outer
Sheath
Thickness
mm
1.8
1.9
2.0
2.2
2.4
2.6
2.8
3.0
3.2
1.3
1.3
1.4
1.5
1.6
1.7
1.9
2.0
2.2
2.4
2.6
2.8
1.3
1.3
1.5
1.6
1.8
1.9
1.3
1.4
1.6
1.7

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

27.8
30.7
34.5
39.0
44.3
48.5
53.3
58.8
65.8
14.4
15.4
17.9
19.6
22.2
25.0
31.3
33.7
38.1
43.1
48.9
53.7
15.4
16.6
21.2
24.4
29.2
33.2
16.6
18.0
23.2
26.8

30.9
34.4
38.4
43.5
48.9
53.7
58.7
64.9
72.2
16.4
17.6
20.3
22.5
25.1
28.1
35.0
37.5
42.1
47.7
54.1
59.2
17.6
18.9
24.0
27.5
32.8
37.0
18.9
20.3
26.2
30.0

1760
2260
2880
3800
4890
6070
7270
8970
1350
395
465
640
790
1070
1460
2140
2670
3630
4740
6290
7670
455
530
790
1080
1460
1990
560
650
970
1360

www.addison-cables.com

ADDISON

29

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually


Screened Unarmoured Flame Retardant Instrumentation & Control
Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in instrumentation, lighting and control circuits.

Standards

Stranded Tinned Copper Conductor

BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

HF-EPR GP4 Insulation


Aluminium/Polyester Tape + Drain Wire
SW4/SW2 Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples, quads.
Individual Screen: Aluminium/polyester tape + drain wire tinned copper.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

30

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

7.3
12.6
16.9
21.2
27.0
30.8
35.9
7.7
13.5
18.0
22.8
28.8
32.8
38.5

9.0
14.5
19.0
23.7
29.8
33.9
39.3
9.5
15.5
20.1
25.4
31.6
36.0
42.3

90
200
390
630
1010
1320
1560
100
240
470
780
1230
1630
2180

7.7
14.2
19.7
24.4
8.4
15.0
21.0
26.2

9.4
16.2
22.1
27.1
10.1
17.2
23.5
28.9

100
250
500
830
120
300
610
1020

8.6
16.4
22.1
9.1
17.5
23.6

10.4
18.5
24.7
10.9
19.6
26.2

120
310
620
140
360
740

Multipair
120.75
320.75
720.75
1220.75
2020.75
2720.75
3720.75
121
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.0
1.2
1.4
1.6
1.9
2.0
2.2
1.0
1.3
1.4
1.7
1.9
2.1
2.3

130.75
330.75
730.75
1230.75
131
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.0
1.3
1.5
1.7
1.1
1.3
1.5
1.8

140.75
340.75
740.75
141
341
741

0.8
0.8
0.8
0.8
0.8
0.8

1.1
1.4
1.6
1.1
1.4
1.6

Multitriple

Multiquad

www.addison-cables.com

ADDISON

31

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively


Screened Unarmoured Flame Retardant Instrumentation & Control
Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in instrumentation, lighting and control circuits.

Standards

Stranded Tinned Copper Conductor

BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

HF-EPR GP4 Insulation


Aluminium/Polyester Tape + Drain Wire
SW4/SW2 Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples.
Collective Screen: Aluminium/polyester tape + drain wire tinned copper.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

32

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

12.6
16.6
21.7
27.3
31.1
34.4
13.3
17.6
23.1
29.1
33.3
36.9

14.5
18.7
24.2
30.1
34.2
37.7
15.3
19.8
25.7
31.9
36.6
40.3

175
330
530
830
1070
1430
185
360
590
920
1220
1630

14.2
19.4
24.2
15.1
20.9
25.8

16.2
21.9
26.8
17.1
23.4
28.5

230
440
730
260
510
840

Multipair
320.75
720.75
1220.75
2020.75
2720.75
3720.75
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.2
1.4
1.6
1.8
1.9
2.1
1.2
1.4
1.6
1.8
2.0
2.2

330.75
730.75
1230.75
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8

1.3
1.4
1.7
1.3
1.5
1.7

Multitriple

www.addison-cables.com

ADDISON

33

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually


Screened Armoured Flame Retardant Instrumentation & Control
Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in instrumentation, lighting and control circuits.

Standards
BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


HF-EPR GP4 Insulation
Aluminium/Polyester Tape + Drain Wire
SW2/SW4 Inner Sheath
Galvanized Steel Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples, quads.
Individual Screen: Aluminium/polyester tape + drain wire tinned copper.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid. Tinned bronze wire braid can be offered upon
request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

34

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

Dimensions and Weight


Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

120.75
320.75
720.75
1220.75
2020.75
2720.75
3720.75
121
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

130.75
330.75
730.75
1230.75
131
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

140.75
340.75
740.75
141
341
741

0.8
0.8
0.8
0.8
0.8
0.8

Nominal
Minimum Maximum
Nominal
Inner
Diameter
Diameter
Armour
Sheath
Over Inner Over Inner
Wire
Thickness
Sheath
Sheath
Diameter
mm
mm
mm
mm
Multipair
1.0
7.3
9.0
0.3
1.2
12.6
14.5
0.3
1.4
16.9
19.0
0.3
1.6
21.3
23.7
0.3
1.9
27.0
29.8
0.45
2.0
30.8
33.9
0.45
2.2
35.9
39.3
0.45
1.0
7.7
9.5
0.3
1.3
13.5
15.5
0.3
1.4
18.0
20.1
0.3
1.7
22.8
25.4
0.45
1.9
28.8
31.6
0.45
32.8
36.0
0.45
2.1
2.3
38.5
42.3
0.45
Multitriple
1.0
7.7
9.4
0.3
1.3
14.2
16.2
0.3
1.5
19.7
22.1
0.3
1.7
24.4
27.1
0.45
1.1
8.4
10.1
0.3
1.3
15.0
17.2
0.3
1.5
21.0
23.5
0.3
1.8
26.2
28.9
0.45
Multiquad
1.1
8.6
10.4
0.3
1.4
16.4
18.5
0.3
1.6
22.1
24.7
0.3
1.1
9.1
10.9
0.3
1.4
17.5
19.6
0.3
1.6
23.6
26.2
0.45

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

1.2
1.4
1.6
1.8
2.1
2.3
2.5
1.2
1.4
1.6
1.9
2.2
2.4
2.6

11.1
16.7
21.4
26.1
33.2
37.3
42.9
11.5
17.6
22.5
28.6
35.2
39.5
45.7

12.9
19.0
24.3
29.2
37.0
41.3
47.5
13.4
20.0
25.4
31.8
39.0
44.0
50.4

250
440
730
1090
1750
2190
2780
260
490
810
1370
2010
2570
3290

1.2
1.5
1.7
2.0
1.2
1.5
1.7
2.0

11.5
18.6
24.4
30.4
12.1
19.4
25.7
32.2

13.3
20.9
27.4
34.1
14.0
22.3
28.8
36.0

270
540
910
1500
290
600
1030
1740

1.2
1.5
1.7
1.2
1.6
1.8

12.4
20.9
27.0
12.9
22.0
29.4

14.3
23.8
30.2
14.8
24.9
32.0

290
610
1060
330
680
1290

www.addison-cables.com

ADDISON

35

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively


Screened Armoured Flame Retardant Instrumentation & Control
Cables
Application
These elastomeric insulated cables are designed for fixed wiring in ships and on mobile
offshore units, suitable for use in instrumentation, lighting and control circuits.

Standards
BS 6883
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


HF-EPR GP4 Insulation
Aluminium/Polyester Tape + Drain Wire
SW2/SW4 Inner Sheath
Galvanized Steel Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples.
Collective Screen: Aluminium/polyester tape + drain wire tinned copper.
Inner Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.
Armour: Galvanized steel wire braid. Tinned bronze wire braid can be offered upon
request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

36

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flame Retardant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

Dimensions and Weight


Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

320.75
720.75
1220.75
2020.75
2720.75
3720.75
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

330.75
730.75
1230.75
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8

Nominal
Minimum Maximum
Nominal
Inner
Diameter
Diameter
Armour
Sheath
Over Inner Over Inner
Wire
Thickness
Sheath
Sheath
Diameter
mm
mm
mm
mm
Multipair
1.2
12.6
14.5
0.3
1.4
16.6
18.7
0.3
1.6
21.7
24.2
0.3
1.8
27.3
30.1
0.45
1.9
31.1
34.2
0.45
2.1
34.4
37.7
0.45
1.2
13.3
15.3
0.3
1.4
17.6
19.8
0.3
1.6
23.1
25.7
0.3
1.8
29.0
31.9
0.45
2.0
33.3
36.6
0.45
2.2
36.9
40.3
0.45
Multitriple
1.3
14.2
16.2
0.3
1.4
19.4
21.9
0.3
1.7
24.2
26.8
0.45
1.3
15.1
17.1
0.3
1.5
20.9
23.4
0.3
1.7
25.8
28.5
0.45

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

1.4
1.5
1.7
2.0
2.2
2.3
1.4
1.6
1.8
2.1
2.2
2.4

16.7
20.9
26.4
33.3
37.4
41.0
17.4
22.1
28.0
35.3
39.7
43.7

19.0
23.8
29.5
37.1
41.4
45.5
19.8
25.1
31.2
39.2
44.2
48.3

390
620
930
1460
1810
2270
410
680
1010
1600
2000
2540

1.4
1.6
1.9
1.5
1.7
2.0

18.3
24.0
29.3
19.4
25.6
31.8

20.7
27.0
32.9
22.2
28.7
35.5

480
780
1320
530
890
1480

www.addison-cables.com

ADDISON

37

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Fire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually


Screened Unarmoured Fire Resistant Instrumentation & Control
Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in instrumentation, lighting and control circuits where
re integrity is essential.

Standards

Stranded Tinned Copper Conductor

BS 7917
IEC 60331-31 Fire resistant
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Mica Tape+HF-EPR GP4 Insulation


Aluminium/Polyester Tape + Drain Wire
SW4/SW2 Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples, quads.
Individual Screen: Aluminium/polyester tape + drain wire tinned copper.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

38

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

8.1
14.0
19.0
23.8
30.4
34.6
40.5
8.5
15.0
20.0
25.4
32.1
36.8
43.0

9.8
16.0
21.1
26.4
33.5
37.9
44.3
10.3
17.0
22.5
28.0
35.3
40.2
47.0

97
227
449
740
1183
1555
1846
108
264
522
865
1377
1814
2432

8.1
15.0
20.8
25.8
8.7
15.8
22.0
27.5

9.8
17.0
23.3
28.5
10.5
17.9
24.5
30.2

104
269
527
880
124
310
622
1032

9.1
17.4
23.5
9.6
18.4
24.9

10.9
19.5
26.1
11.4
20.6
27.6

137
366
725
148
413
843

Multipair
120.75
320.75
720.75
1220.75
2020.75
2720.75
3720.75
121
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.0
1.2
1.4
1.6
1.9
2.0
2.2
1.0
1.3
1.4
1.7
1.9
2.1
2.3

130.75
330.75
730.75
1230.75
131
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.0
1.3
1.5
1.7
1.1
1.3
1.5
1.8

140.75
340.75
740.75
141
341
741

0.8
0.8
0.8
0.8
0.8
0.8

1.1
1.4
1.6
1.1
1.4
1.6

Multitriple

Multiquad

www.addison-cables.com

ADDISON

39

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Fire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively


Screened Unarmoured Fire Resistant Instrumentation & Control
Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in instrumentation, lighting and control circuits where
re integrity is essential.

Standards

Stranded Tinned Copper Conductor

BS 7917
IEC 60331-31 Fire resistant
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Mica Tape+HF-EPR GP4 Insulation


Aluminium/Polyester Tape + Drain Wire
SW4/SW2 Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples.
Collective Screen: Aluminium/polyester tape + drain wire tinned copper.
Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

40

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Dimensions and Weight


Construction
Nominal Insulation
No. of coresCross
Thickness
section(mm)
mm

Nominal Sheath
Thickness
mm

Minimum Overall
Diameter
mm

Maximum Overall
Diameter
mm

Approx. Weight
kg/km

14.0
18.6
24.4
30.8
35.0
38.8
14.8
19.6
25.8
32.6
37.3
41.3

16.0
20.7
27.0
34.0
38.4
42.6
16.8
22.0
28.5
35.8
40.8
45.2

202
383
615
841
1265
1707
208
413
683
1070
1421
1912

15.0
20.5
25.6
15.8
21.9
27.1

17.0
23.0
28.3
17.8
24.4
29.8

244
457
758
270
521
857

Multipair
320.75
720.75
1220.75
2020.75
2720.75
3720.75
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.2
1.4
1.6
1.8
1.9
2.1
1.2
1.4
1.6
1.8
2.0
2.2

330.75
730.75
1230.75
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8

1.3
1.4
1.7
1.3
1.5
1.7

Multitriple

www.addison-cables.com

ADDISON

41

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Fire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Individually


Screened Armoured Fire Resistant Instrumentation & Control
Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in instrumentation, lighting and control circuits where
re integrity is essential.

Standards
BS 7917
IEC 60331-31 Fire resistant
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


Mica Tape+HF-EPR GP4 Insulation
Aluminium/Polyester Tape + Drain Wire
SB1 Inner Sheath
Galvanized Steel Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples.
Individual Screen: Aluminium/polyester tape + drain wire tinned copper.
Inner Sheath: Halogen free thermosetting compound SB1 according to BS 7917.
Armour: Galvanized steel wire braid. Tinned bronze wire braid can be offered upon
request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

42

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

Dimensions and Weight


Construction
No. of
coresCross
section(mm)

Nominal
Insulation
Thickness
mm

120.75
320.75
720.75
1220.75
2020.75
2720.75
3720.75
121
321
721
1221
2021
2721
3721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

130.75
330.75
730.75
1230.75
131
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

140.75
340.75
740.75
141
341
741

0.8
0.8
0.8
0.8
0.8
0.8

Nominal
Minimum Maximum
Nominal
Inner
Diameter
Diameter
Armour
Sheath
Over Inner Over Inner
Wire
Thickness
Sheath
Sheath
Diameter
mm
mm
mm
mm
Multipair
1.0
8.1
9.8
0.3
1.2
14.0
16.0
0.3
1.4
19.0
21.1
0.3
1.6
23.8
26.4
0.3
1.9
30.4
33.5
0.45
2.0
34.6
37.9
0.45
2.2
40.5
44.3
0.45
1.0
8.5
10.3
0.3
1.3
15.0
17.0
0.3
1.4
20.0
22.5
0.3
1.7
25.4
28.0
0.45
1.9
32.1
35.3
0.45
40.2
0.45
2.1
36.8
2.3
43.0
47.0
0.45
Multitriple
1.0
8.1
9.8
0.3
1.3
15.0
17.0
0.3
1.5
20.8
23.3
0.3
1.7
25.8
28.5
0.45
1.1
8.7
10.5
0.3
1.3
15.8
17.9
0.3
1.5
22.0
24.5
0.3
1.8
27.5
30.2
0.45
Multiquad
1.1
9.1
10.9
0.3
1.4
17.4
19.5
0.3
1.6
23.5
26.1
0.3
1.1
9.6
11.4
0.3
1.4
18.4
20.6
0.3
1.6
24.9
27.6
0.45

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

1.2
1.4
1.6
1.8
2.1
2.3
2.5
1.2
1.4
1.6
1.9
2.2
2.4
2.6

11.9
18.1
23.5
28.7
36.5
41.2
47.4
12.3
19.1
24.5
31.2
38.5
43.6
50.2

13.7
20.5
26.4
31.9
40.5
45.7
52.2
14.2
21.5
27.6
34.9
42.9
48.2
55.5

270
500
840
1280
2050
2580
3290
280
540
900
1520
2250
2860
3670

1.2
1.5
1.7
2.0
1.2
1.5
1.7
2.0

11.9
19.3
25.5
31.8
12.5
20.1
26.7
33.5

13.7
22.1
28.6
35.6
14.4
23.0
29.8
37.3

280
580
960
1590
300
620
1050
1760

1.2
1.5
1.7
1.2
1.6
1.8

12.8
21.9
28.4
13.3
22.9
30.8

14.8
24.8
31.6
15.3
25.9
34.0

330
720
1240
350
780
1470

www.addison-cables.com

ADDISON

43

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Fire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

150/250V HF-EPR Insulated, SW2/SW4 Sheathed, Collectively


Screened Armoured Fire Resistant Instrumentation & Control
Cables
Application
These re resistant elastomeric insulated cables are designed for xed wiring in ships and
on mobile offshore units, suitable for use in instrumentation, lighting and control circuits where
re integrity is essential.

Standards
BS 7917
IEC 60331-31 Fire resistant
IEC 60332-3A Flame retardant
IEC 60754-1; IEC 60754-2
Corrosivity
IEC 61034-2 Smoke density
Cold bend and impact (-40C) (on request)
CSA C22.2 No. 38-95 (on request)

Stranded Tinned Copper Conductor


Mica Tape+HF-EPR GP4 Insulation
Aluminium/Polyester Tape + Drain Wire
SB1 Inner Sheath
Galvanized Steel Wire Braid
SW2/SW4 Outer Sheath

Construction
Conductor: Tinned copper wire stranded circular cl. 2 BS 6360/IEC 60228.
Insulation: Mica tape + HF-EPR GP4 according to BS 7655 1.2.
Lay-up: Pairs, triples.
Collective Screen: Aluminium/polyester tape + drain wire tinned copper.
Inner Sheath: Halogen free thermosetting compound SB1 according to BS 7917.
Armour: Galvanized steel wire braid. Tinned bronze wire braid can be offered upon
request.
Outer Sheath: Halogen free thermosetting compound SW4 according to BS 7655 2.6 or
reduced halogen thermosetting compound SW2 according to BS 7655 2.6.

44

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Flire Resistant Instrumentation & Control Cables
www.caledonian-cables.co.uk

Mechanical and Thermal Properties


Minimum Internal Bending Radius: 8OD
Temperature Range: -40 ~ +90

Dimensions and Weight


Construction Nominal
No. of
Insulation
coresCross Thickness
section(mm)
mm

Nominal
Minimum Maximum
Nominal
Inner
Diameter
Diameter
Armour
Sheath
Over Inner Over Inner
Wire
Thickness
Sheath
Sheath
Diameter
mm
mm
mm
mm
Multipair
1.2
14.0
16.0
0.3
1.4
18.6
20.7
0.3
1.6
24.4
27.0
0.3
1.8
30.8
34.0
0.45
1.9
35.0
38.4
0.45
2.1
38.8
42.6
0.45
1.2
14.8
16.8
0.3
1.4
19.6
22.0
0.3

Nominal
Outer
Sheath
Thickness
mm

Minimum
Overall
Diameter
mm

Maximum
Overall
Diameter
mm

Approx.
Weight
kg/km

1.4
1.5
1.7
2.0
2.2
2.3
1.4
1.6

18.1
22.9
29.1
36.8
41.4
45.4
18.9
24.1

20.5
25.8
32.7
40.7
45.9
50.1
21.3
27.1

450
720
1080
1480
2140
2710
460
780

320.75
720.75
1220.75
2020.75
2720.75
3720.75
321
721

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1221

0.8

1.6

25.8

28.5

0.3

1.8

30.7

34.4

1170

2021
2721
3721

0.8
0.8
0.8

1.8
2.0
2.2

32.6
37.3
41.3

0.45
0.45
0.45

2.1
2.2
2.4

38.8
43.7
48.1

43.2
48.3
53.3

1860
2330
2980

330.75
730.75
1230.75
331
731
1231

0.8
0.8
0.8
0.8
0.8
0.8

1.3
1.4
1.7
1.3
1.5
1.7

15.0
20.5
25.6
15.8
21.9
27.1

35.8
40.8
45.2
Multitriple
17.0
23.0
28.3
17.8
24.4
29.8

0.3
0.3
0.45
0.3
0.3
0.45

1.4
1.6
1.9
1.5
1.7
2.0

19.1
25.1
31.4
20.1
26.6
33.1

21.5
28.1
35.1
22.9
29.7
36.9

510
810
1370
550
910
1510

www.addison-cables.com

ADDISON

45

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


Technical Information
www.caledonian-cables.co.uk

Cores Identification
Insulation Colour Scheme
MV cables
Single core

Natural colour of the compound

Three core

Coloured tape or thread (e.g.: red - yellow - blue)

0.6/1 kV Power and Control Cables


1 core

According to BS 6883/BS 7917


Red or Black

Alternatives
White and numbered

2 cores

Red - Black

White and numbered

3 cores

Red - Yellow - Blue

White and numbered

4 cores

Red - Yellow - Blue - Black

White and numbered

Above 4 cores

black numbers on white background

150/250 V Instrumentation Cables


Pair

Black - White

Triple

Black - White - Red

Quad

Black - White - Red - Blue

Pairs/Triples/Quads are numbered with numbers printed directly on the insulated conductors (1-1; 2-2; ) or buy numbered
tape

Outer Sheath Standard Colours


MV power and control

Red

LV power and control

Black

Instrumentation and control

Grey

Other colours available on request

46

ADDISON

www.addison-cables.com

BS 6883&BS 7917 Caledonian Offshore & Marine Cables


MV Flame Retardant Power & Control Cables
www.caledonian-cables.co.uk

UNITED KINGDOM

HONG KONG

Marchants Industrial Centre,


Mill Lane, Laughton, Lewes,
East Sussex, BN8 6AJ, UK
Tel: 44 (0) 207 419 5087
Fax: 44 (0) 207 831 9489
Email: sales@caledonian-cables.co.uk
www.caledonian-cables.co.uk