EXERCISE 7+8

Using ATPDraw program make the model of the 400 kV (model Clarke-distributed
parameters) 180 km long transmission line supplied from both sides as shown in Fig.1.
Task to do:
- simulate the A-G and A-B-G faults in the middle of the line. Show the current
and voltage waveforms in the fault location and at the busbar A for each fault.
- make the MODELS program block to calculate the zero sequence current . Use
the block to determine the zero sequence current waveforms at the fault location
and at the busbar B.
- show the vector diagrams of voltages and currents (including the zero sequence
currents) at fault location at time instants t1=0.04s and t2=0.18s for each fault.

Fig 1. The system diagram

Modeling parameters:
- Fault resistance - Rf=5
.
- System parameters;
Z0SA=2,3+j 26,4
, Z1SA=1,3+j15,0
, ESA= 415ej0 kV
Z0SB=2,65+j 32,8
, Z1SB=1,81+j20,5 , ESB =415e -j20 kV.
- Line parameters:
r1=0.0276 /km, r0=0.275 /km,
l1=1.0031 mH/km, l0=3.2675mH/km,
c1=0.013 F/km, c0=0.0085 F/km.
Assume that output signals are sampled at the rate fs= 5,0 kHz.