Академический Документы
Профессиональный Документы
Культура Документы
I. INTRODUCTION
ART I of this paper [1] analyzes the problem of transformer differential protection and summarizes the existing
methods for discriminating internal faults from inrush and
overexcitation conditions. Most transformer differential relays
use only current signals. These relays use the harmonics of the
operating current to restrain [2] or to block [3] relay operation.
These methods ensure security for most of the inrush and
overexcitation cases but fail for cases with very low harmonic
content in the operating current. Common harmonic restraint
or blocking [4] increases relay security but could delay operation for internal faults combined with inrush currents in the
nonfaulted phases. Wave-shape recognition techniques [5] represent another major group of methods. By themselves, these
methods fail to identify transformer overexcitation conditions.
This paper describes a new approach for transformer differential protection using current-only inputs. The approach ensures
security for external faults, inrush, and overexcitation conditions and dependability for internal faults. It combines harmonic
restraint and blocking methods with a wave-shape recognition
technique. The new method uses even harmonics for restraint
and also blocks operation using the dc component and the fifth
harmonic. We also compare, in the paper, the behavior of some
traditional transformer protection methods to that of the new
method for real cases of magnetizing inrush conditions.
II. NEW APPROACH FOR TRANSFORMER PROTECTION
The evaluation of existing harmonic restraint/blocking
methods makes it clear that independent restraint/blocking
Manuscript received January 20, 2000; revised February 14, 2002.
The authors are with the Schweitzer Engineering Laboratories, Pullman, WA
99163 USA
Digital Object Identifier 10.1109/TPWRD.2002.803736
(2)
GUZMN et al.: SOLUTION FOR TRANSFORMER PROTECTION PART II: RELAY DESCRIPTION
887
with an
ratio of greater than 40, the delay will increase
slightly without sacrificing dependability.
The response of this dc blocking method depends on the dc
signal information apart from the harmonic content of the differential current. For example, the method ensures dependability
for internal faults with CT saturation and maintains its security
during inrush conditions with low even-harmonic content.
D. Additional Even-Harmonic Restraint Based on dc Content
Another alternative solution for inrush detection is to calculate the ratio of the dc component to the fundamental component
of the differential current and use this ratio information to boost
the even-harmonic restraint quantity. Calculate the dc compofrom the following:
nent
(9)
The extreme case of dc offset for an internal fault is a completely asymmetrical sine-wave current. In this case, the dc component equals the peak value of the fundamental component of
the current, or
(10)
(4)
is the number
where represents the current samples, and
of samples per cycle.
of the negative current examples is given by
The sum
(11)
(5)
(6)
(12)
(7)
(13)
This solution applies a multiplying factor to the even-harmonic restraint quantity in (1) when (13) is true
(14)
(8)
Relay tripping requires the fulfillment of (1), but neither (2)
nor (8).
DCRF is an internal relay setting. Selecting a value for DCRF
means deciding on a compromise between security and speed. A
high value of DCRF (approximately one) affords high security
but is detrimental to speed. From tests, we defined a value of 0.1
as a good solution. The delay for internal faults is practically
ratios as great as 40. For systems
negligible for system
888
Fig. 2.
DC blocking logic.
Fig. 6.
Fig. 3.
GUZMN et al.: SOLUTION FOR TRANSFORMER PROTECTION PART II: RELAY DESCRIPTION
889
Fig. 10. Transformer energization while A phase is faulted and the transformer
is loaded.
Fig. 11. Element 1 inrush currents from the high- and low-side transformer
windings after relay scaling.
890
Fig. 12.
Fig. 13. Second, third, and fourth harmonic as percentages of fundamental for
the Fig. 12 current.
Fig. 14.
Fig. 15.
GUZMN et al.: SOLUTION FOR TRANSFORMER PROTECTION PART II: RELAY DESCRIPTION
891
Fig. 16.
cycle.
Fig. 17.
Fig. 18.
892
TABLE I
INRUSH DETECTION METHODS PERFORMANCE DURING INRUSH CONDITIONS.
C. Case 3
Fig. 15 shows a field case of energization during commissioning of a three-phase, 180-MVA, 230/138-kV autotransformer. The autotransformer connection is wye-wye; CTs at
both sides of the autotransformer are connected in delta.
Fig. 16 shows the secondary currents from the autotransformer high side. These currents result from autotransformer
energization with the low-side breaker open. The currents are
typical inrush waves with a relatively small magnitude. Note
that the signal low current intervals last less than one-quarter
cycle.
Fig. 17 shows the harmonic content of the inrush current. Note
that the inrush current has a relatively small second-harmonic
percentage, which drops to approximately 9%. As in previous
cases, Fig. 18 shows that the dc content of the inrush current
exceeds the rms value of fundamental.
All differential elements except the low-current detector
operate correctly for this case. The low current zone in this
case lasts less than the one-quarter cycle required to determine
blocking conditions.
Table I summarizes the performance of the different inrush
detection methods discussed earlier. The all-harmonic restraint
method and the additional even-harmonic restraint method perform correctly for all three cases. The former sacrifices relay
dependability during symmetrical CT saturation conditions, and
the latter sacrifices speed when the dc content is greater than the
rms value of fundamental during fault conditions. Combining
the even-harmonic restraint method and the dc ratio blocking
method provides a good compromise of speed and reliability.
In addition to the presented cases, the proposed approach has
been tested with satisfactory results during such multiple conditions as internal faults, internal faults during energization, and
external faults.
V. CONCLUSIONS
1) A new approach combining harmonic restraint and blocking
methods with a wave-shape recognition technique adds security to the independent harmonic restraint element without
sacrificing dependability. This new method uses even harmonics for restraint, plus dc component and a fifth harmonic
for blocking.
2) Using even-harmonic restraint ensures security for inrush
currents with low second-harmonic content and maintains
dependability for internal faults with CT saturation. The use
of fifth-harmonic blocking guarantees an invariant relay response to overexcitation. Using dc offset blocking ensures
security for inrush conditions with very low total harmonic
distortion.
REFERENCES
[1] A. Guzmn, S. Zocholl, G. Benmouyal, and H. J. Altuve, A currentbased solution for transformer differential protection. Part I: problem
statement, IEEE Trans. Power Delivery., vol. 16, pp. 485491, Oct.
2001.
[2] C. D. Hayward, Harmonic-current-restrained relays for transformer
differential protection, AIEE Trans., vol. 60, pp. 377382, 1941.
[3] R. L. Sharp and W. E. Glassburn, A transformer differential relay with
second-harmonic restraint, AIEE Trans., pt. III, vol. 77, pp. 913918,
Dec. 1958.
[4] C. H. Einval and J. R. Linders, A three-phase differential relay for
transformer protection, IEEE Trans. Power App. Syst., vol. PAS-94, pp.
19711980, Nov. 1975.
[5] A. M. Dmitrenko, Semiconductor pulse-duration differential restraint
relay (in Russian), Izvestiya Vysshikh Uchebnykh Zavedenii, Elektromekhanika, no. 3, pp. 335339, Mar. 1970.
[6] L. F. Kennedy and C. D. Hayward, Harmonic-current-restrained relays for differential protection, AIEE Trans., vol. 57, pp. 262266, May
1938.
GUZMN et al.: SOLUTION FOR TRANSFORMER PROTECTION PART II: RELAY DESCRIPTION
893
Stanley Zocholl received the B.S.E.E. and M.S.E.E. degrees from Drexel University, Philadelphia, PA, in 1958 and 1973, respectively.
Currently, he is a Distinguished Engineer at Schweitzer Engineering
Laboratories, Pullman, WA, where he has been since 1991. He was Director
of Protection Technology at ABB Power T&D Co., (formerly ITE, Gould,
BBC) Allentown, PA, from 1947 to 1991.
Mr. Zocholl received the Best Paper Award at the 1988 Petroleum and
Chemical Industry Conference and the Power System Relaying Committees
Distinguished Service Award in 1991.
Hctor J. Altuve (SM95) received the B.S.E.E. degree from Central University
of Las Villas (UCLV), Santa Clara, Cuba, in 1969, and the Ph.D. degree from
Kiev Polytechnic Institute, Kiev, Ukraine, in 1981.
Currently, he is a Research Engineer with Schweitzer Engineering Laboratories, Pullman, WA. From 1993 to 2001, he was a Professor in the Ph.D. program
with the Mechanical and Electrical Engineering School, Autonomous University of Nuevo Leon, Monterrey, Mexico. He was also a Professor in the School
of Electrical Engineering at UCLV from 1969 to 1993.
Dr. Altuve is a member of the Mexican National Research System.