Commercial Electrical Testing Of LV Panels

At
Al Bayan, Dubai Investment Park

Project

Commercial Electrical Testing

Building

Al Bayan

Date

April 2016
Carelabs, Dubai, Phone : 00971 4 5149730, Email : info@carelabs.ae

Table of Content
Project details
Report summary
Table of Panels inspected
Index of Fault Findings
Reports
Company Details

Project Details
Project Name

: Commercial Electrical Testing

Client

: Al Bayan

Conducted by

: Carelabs

Location

: Dubai Investment Park

Executive Summary
This report has been created after a thorough investigation carried out on site
consisting of a detailed condition survey using physical verification, thermography imaging
and measurement of electrical parameters from the MDB panel to the Sub Main Distribution
Boards within Al Bayan
The report has been categorized into two priorities Critical & Urgent as per the following
parameters
Priority 1- Critical issues that need immediate action and rectification
Priority 2- Urgent issues that are based on electrical compliance of local and international
authorities
The purpose of this report is to identify the electrical related issues that can impact the
operation of the building, affect the end users/ tenants of the building. The aim of this report is
to address the issues based on priorities and ensure the electrical systems are risk free.
The detailed report illustrates our findings and points of action required to restore the healthy
status of the building.

Table of Inspected Panels


SI.No.

Panel Name plate

Type

Location

LV Panel

Electrical Room

Capacitor Bank

Electrical Room

SMDB

PME Room

MDB 1

75KVAR Capacitor Bank 1

SMDB 11

Cap Machine 1

Control Panel

PME Room

Cap Machine 2

Control Panel

PME Room

SDB 3

SMDB

Plant

SDB 4

SMDB

Plant

SDB 2

SMDB

Ware house

SDB 1

SMDB

Ware house

10

UAT/PLC Control Panel

Control panel

Plant

11

MDB-2

MDB

Electrical Room

12

75KVAR Capacitor Bank 2

Capacitor Bank

Electrical Room

13

SDB 5

SMDB

Office

14

SDB 7

SMDB

Plant

15

SMDB 13

SMDB

Cooler Plant

16

Granulator

Control Panel

Grinding Area

17

Isolator Panel Grinder 2

Isolator Panel

Grinding Area

18

MDB-3

LV Panel

Electrical Room

19

75KVAR Capacitor Bank 3

Capacitor Bank

Electrical Room

20

SDB-6

SMDB

Plastic Division

21

SMDB-9

SMDB

PME Room

22

Automa Control Panel

Control panel

Plastic Division

23

MDB-4

LV Panel

Outside-Electrical Room

24

60KVAR Capacitor Bank 4

Capacitor Bank

Electrical Room

25

SMDB 12

SMDB

Plastic Division

26

SMDB 10

SMDB

PME Room

27

SDB 8

SMDB

Plant

28

NPAS Control Panel

Control panel

Plant

Index of Fault findings

Index of Fault Findings & Recommendations


Project

Commercial Electrical Testing

Location

Al Bayan, Dubai Investment Park

Equipment

MDB, SMDB, Capacitor Bank, Control Panel

Date

April 2016

Priority 1
S. N

Equipment

MDB-1

Fault findings

Recommendation

Busbar size not suitable


for connected load

Recommended to use busbar


of proper size as per standard.

Main ECC Cable not


showing any continuity

Recommended to check the


connection of ECC cable

Power factor is low

Recommended to
service/replace capacitor bank

75KVAR
Capacitor Bank

Out of Order condition

Recommended to
service/replace capacitor bank

SMDB-11

Cable size not suitable


for connected load

Recommended to change cable


/ breaker as per load

SDB-3

Proper protective device


not provided

Recommended to use proper


protective devices

SDB-4

Proper protective device


not provided

Recommended to use proper


protective devices

Independent loads are


connected from MCCB

Recommended to use separate


breakers

MCCB is in over heated


condition

Recommended to
replace/service it

10

Busbar size not suitable


for connected load

Recommended to use busbar


of proper size as per standard.

11

Main ECC Cable not


showing any continuity

Recommended to check the


connection of ECC cable

12

Power factor is low

Recommended to
service/replace capacitor bank

Out of Order condition

Recommended to
service/replace capacitor bank

13

MDB-2

75KVAR
Capacitor bank 2

Page
no.

14

SMDB-13

Proper protective device


not provided

Recommended to use proper


protective devices

15

Granulator

Proper protective device


not provided

Recommended to use proper


protective devices

16

Busbar size not suitable


for connected load

Recommended to use busbar


of proper size as per standard.

17

High temperature
Showed at incomer side
blue phase busbar

Recommended to check the


termination tightness

18

Main ECC Cable not


showing any continuity

Recommended to check the


connection of ECC cable

19

Power factor is low

Recommended to
service/replace capacitor bank

Out of Order condition

Recommended to
service/replace capacitor bank

Proper protective device


not provided

Recommended to use proper


protective devices

22

High temperature rise


showed across 63A TP
MCB

Recommended to check the


termination tightness of MCB

23

Cable size not suitable


for connected load

Recommended to use cables of


proper size as per standard.

24

Independent loads are


connected from MCCB

Recommended to use separate


breakers

25

Busbar size not suitable


for connected load

Recommended to use busbar


of proper size as per standard.

High temperature
showed at incoming
busbar and outgoing
cables of 250A MCCB

Recommended to check the


termination tightness

MDB-3

20

75KVAR
Capacitor Bank 3

21
SDB-6

SMDB-9

MDB-4
26

27

SMDB-10

Cable size not suitable


for connected load

Recommended to use cables of


proper size as per standard.

28

NPAS Control
panel

High temperature rise


showed at incomer
isolator cable
termination

Recommended to check the


tightness of termination

Priority 2
S. N

Equipment

Fault findings

Recommendation

Door earthing not


provided on panel

Recommended to provide
earthing for panel door

Unused openings are


present

Recommended to close the


opening with suitable
grommets

Door handle is damaged

Recommended to replace it
with new door handle

Dust precipitation in the


panel

Recommended to clean the


panel periodically

External handle is
damaged

Recommended to replace it
with new lock

Dust precipitation in the


panel

Recommended to clean the


panel periodically

MDB-1

75KVAR
Capacitor Bank 1

Cap machine 1

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

Cap machine 2

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

Unused openings are


present

Recommended to close the


opening with suitable
grommets

No shroud cover provided

Recommended to provide
proper shroud cover

10
11

No load schedule available

Recommended to provide
load schedule

12

Improper cable dressing

Recommended to do proper
cable dressing

13

Dust precipitation in the


panel

Recommended to clean the


panel periodically

14

Disconnected cables are


present

Recommended to remove if
not required

15

High temperature rise


showed at R phase
termination of ELCB

Recommended to check the


termination tightness of
ELCB

SDB-3

Page
no.

30-33

S. N

Equipment

Fault findings

Recommendation

16

Improper fixing of comb


busbar

Recommended to fix it
properly

17

Dust precipitation in the


panel

Recommended to clean the


panel periodically

18

Unused openings are


present

Recommended to close the


opening with suitable
grommets

SDB-4
19

Improper Entry of cables

Recommended to provide
suitable glands

20

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

21

No load schedule available

Recommended to provide
load schedule

22

Dust precipitation in the


panel

Recommended to clean the


panel periodically

23

Unused openings are


present

Recommended to close the


opening with suitable
grommets

24

Improper cable dressing

Recommended to do proper
cable dressing

25

No shroud cover provided

Recommended to provide
proper shroud cover

26

Vaccant ELCB is present in


the panel

Recommended to remove if
not required

27

Improper cable dressing

Recommended to do proper
cable dressing

Unused openings are


present

Recommended to close the


opening with suitable
grommets

29

Dust precipitation in the


panel

Recommended to clean the


panel periodically

30

No shroud cover provided

Recommended to provide
proper shroud cover

31

No load schedule available

Recommended to provide
load schedule

SDB-2

28
SDB-1

Page
no.

34-38

39-42

43-47

S. N

Fault findings

Recommendation

32

Trunking cover is removed


condition

Recommended to provide
suitable trunking

33

Unused openings are


present

Recommended to close the


opening with suitable
grommets

34

Improper Entry of ECC


cables

Recommended to provide
suitable glands

35

External handle is
damaged

Recommended to replace it
with new

36

Door lock is damaged

Recommended to replace it
with new

37

Dust precipitation in the


panel

Recommended to clean the


panel periodically

38

Improper fixing of first


capacitor in the panel

Recommended to fix
capacitor suitably

Dust precipitation in the


panel

Recommended to clean the


panel periodically

40

Disconnected cables are


present

Recommended to remove if
not required

41

Humming noise coming


from 40A contactor

Recommended to replace it
with new contactor

42

Dust precipitation in the


panel

Recommended to clean the


panel periodically

43

Unused openings are


present

Recommended to close the


opening with grommets

44

Improper cable dressing

Recommended to do proper
cable dressing

45

Improper Entry of cables

Recommended to provide
suitable glands

46

No shrouding cover

Recommended to provide
proper shrouding cover

47

Disconnected
present

48

Cable glands are not


earthed

Recommended to connect
glands with ECC cables

49

No load schedule available

Recommended to provide
load schedule

50

Dust precipitation in the


panel

Recommended to clean the


panel periodically

39

Equipment

UAT/PLC
Control panel

75kvar Capacitor
Bank

SDB-5

SDB-7

cables

Page
no.

52-55

60-65

are Recommended to remove if


not required
6671,
133

S. N

Fault findings

Recommendation

51

Unused openings are


present

Recommended to close the


opening with suitable
grommets

52

External handle is
damaged

Recommended to replace it
with new

Cable glands are not


earthed

Recommended to connect
glands with ECC cables

54

No door earthing

Recommended to provide
proper earthing

55

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

56

Neutral current is high

Recommended to rearrange
the connected load

57

Cable glands are not


earthed

Recommended to connect
glands with ECC cables

58

Independent loads
connected to single isolator

Recommended to use
separate isolator

Improper Entry of cables

Recommended to provide
suitable glands

60

Earth busbar not provided


in the panel

Recommended to use suitable


earth busbar

61

Improper cable dressing

Recommended to do proper
cable dressing

62

Unused openings are


present

Recommended to close the


opening with suitable
grommets

63

Cables are used instead of


Busbar links from Main
busbar

Recommended to provide
busbar links

Improper Entry of cables

Recommended to provide
suitable glands

65

Door lock is damaged

Recommended to replace it
with new

66

Dust precipitation in the


panel

Recommended to clean the


panel periodically

53

59

64

Equipment

SMDB 13

Granulator

MDB-3

Page
no.

72-78

87-91

67

Comb busbar is in
damaged condition

Recommended to replace
comb busbar with new

68

Improper termination of
incoming cable to 63A TP
MCB

Recommended to do proper
cable termination

69

No load schedule available

Recommended to provide
load schedule

70

Disconnected cables are


present

Recommended to remove if
not required

71

Damaged ELCB is still


existing in the panel

Recommended to remove
damaged ELCB

72

Improper Entry of cables

Recommended to provide
suitable glands

73

Improper fixing of
shrouding cover

Recommended to provide
proper shrouding cover

74

Dust precipitation in the


panel

Recommended to clean the


panel periodically

75

Improper cable dressing

Recommended to do proper
cable dressing

76

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

77

No shrouding cover

Recommended to provide
proper shrouding cover

78

No labelling on shrouding
cover

Recommended to provide
proper identification in the
panel

79

High temperature Showed


at outgoing terminals of
40A MCCB

Recommended to check the


termination tightness

80

Abnormal Humming noise


from transformer

Recommended to test and


service the transformer

Trunking cover is found to


be removed condition

Recommended to provide
proper trunking cover

Dust precipitation in the


panel

Recommended to clean the


panel periodically

Panel is mounted on
exterior wall of the
building
Dust precipitation in the
panel
Improper wire joints found
in the panel

Recommended to keep the


panel inside air conditioned
room
Recommended to clean the
panel periodically
Recommended to use
terminals for wire joints

SDB-6

SMDB-9

81

Automa Control
panel

82
83
84
85

MDB-4

92-97

98102

103106

107111

86

Improper fixing of CBCT

Recommended to fix it
properly in the panel

87

Panel is mounted on
exterior wall of the
building

Recommended to keep the


panel inside air conditioned
room

Louver of the panel is in


removed condition

Recommended to replace it
with new

89

Power factor controller


screen is not visible

Recommended to make the


screen visible properly

90

Dust precipitation in the


panel

Recommended to clean the


panel periodically

91

Nonstandard color coded


cables used

Recommended to use proper


color coded cables

92

Unused openings are


present

Recommended to close the


opening with suitable
grommets

93

Cable glands are not


earthed

Recommended to connect
glands with ECC cables

94

Improper cable dressing

Recommended to do proper
cable dressing

95

Disconnected cables are


present

Recommended to remove if
not required

96

No load schedule available

Recommended to provide
load schedule

97

Cable glands are not


earthed

Recommended to connect
glands with ECC cables

98

Unused openings are


present

Recommended to close the


opening with suitable
grommets

Yellow color Indicator


lamp is not working on the
panel

Recommended to replace it
with new indicator

88

60KVAR
Capacitor Bank 4

SMDB 12

SDB 8

99

Other Important Recommendations


S. N

Panel Name

Recommendations

MDB-1

Name Plate: MDB-1

Inspection Date: 13/04/2016

Location: Electrical Room


Feed from

Transformer

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

MCCB

400A TP 36KA

Incomer

MCCB

63A TP 25KA

SDB 3

MCCB

63A TP 25KA

SDB 2

MCCB

160A TP 36KA

Capacitor Bank

MCCB

125A TP 25KA

CAP Machine

MCCB

63A TP 25KA

SDB 1

MCCB

160A TP 25KA

SDB 4

MCCB

125A TP 25KA

Bottling Machine

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

196.6

165.1

B phase

Neutral

203

17.5

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.020 V

OK

Earth Resistance
Stakeless earth testing could not be completed because main ecc cable is in disconnected condition

MDB-1

Main ECC Cable is disconnected:


During Stakeless earth testing it is found that the main ECC cable is not showing any
continuity with earth.
Recommended to check the connection between main ECC cable and earth pit.
Under sized busbar used:
The busbar used for 125A MCCB is 10x5mm, which are under sized busbar.
Recommended to use busbar of proper size as per standard.
Door earthing not provided:

Panel door earthing is not provided for this MDB.


Recommended to provide proper earthing for panel
door

Door handle is damaged:


Door handle of the panel is in damaged condition.
Recommended to replace it with new door handle.

Unused openings found:

Unused openings are present in the door and inside of the panel. This will degrade the
degree of ingress protection of Enclosure
Recommended to close all the unused openings with Suitable grommets to maintain the
ingress protection

Conclusions & Recommendations:


Recommended to close all the unused openings with Suitable grommets to maintain the
ingress protection
Recommended to provide proper earthing for panel door
Recommended to replace panel door handle with new.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: MDB-1

Inspection Date: 13/04/2016

Location: LV Room1
Incomer

400A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

OK

OK

Shrouding & Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

NIL

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

Door earthing not provided, main ECC


Disconnected

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

75KVAR Capacitor Bank-1


Name Plate: 75KVAR Capacitor Bank-1

Inspection Date: 13/04/2016

Location: Electrical Room


Feed from

MDB-1

Total Breakers

Details of Breakers
S.N

Breaker

Description

Quantity

Isolator

160A TP

1(Incomer)

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

No load at the time of inspection

75KVAR Capacitor Bank-1

Capacitor bank is not working:


Capacitor bank panel is not in working condition.
Recommended to service/replace the capacitor bank panel for proper power factor
correction.

External handle is damaged:

External handle for isolator is in damaged condition.


Recommended to replace it with new external handle
for proper operation of isolator.

Conclusions & Recommendations:


Capacitor bank panel is not in working condition, recommended to service/replace the
capacitor bank panel for proper power factor correction.
Recommended to replace external handle with new for proper operation of isolator.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: 75KVAR Capacitor Bank-1

Inspection Date: 13/04/2016

Location: Electrical Room


Incomer

400A TP MCCB.

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Isolator external handle damaged

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

Ok

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SMDB-11 CAP
Name Plate: SMDB-11 CAP

Inspection Date: 14/04/2016

Location: PME Room


Feed from:

MDB 1

Total Breakers:

Details of Breakers
S.N

Breaker

Description

QTY

MCCB

200A TP 36KA

Incomer 1QTY

MCCB

60A TP 25KA

MCCB

40A TP 25kA

MCCB

100A TP 25kA

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

62.3

34.4

B phase

Neutral

35.4

8.6

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.15V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

8.9mA

OK

SMDB-11 CAP

Under sized cables used:

The connected cable is 4C 6 sqmm PVC Cable


which is undersized with the 40A MCCB & is in
unsafe condition.
Recommended to change the cable / Breaker rating
as per the load.

Conclusions & Recommendations:


The connected cable is 4C 6 sqmm PVC Cable which is undersized with the 40A MCCB & is
in unsafe condition, recommended to change the cable / Breaker rating as per the load.

Check List
Panel: SMDB 11 CAP

Inspection Date: 14/04/2016

Location: PME Room


General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

OK

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

Cap Machine 1
Name Plate: Cap Machine 1

Inspection Date: 17/04/2016

Location: PME Room


Feed from

SDB 11

Total Breakers

Details of Breakers
S.N

Breaker

Description

QTY

MCCB

150A TP

1(Incomer )

Contactor

22kW

MCB

20A TP

MCCB

150A TP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer 2

R phase

Y phase

B phase

33.8

34

33.7

Neutral
-

Cap Machine 1

Nonstandard color coded cables used:

Nonstandard color coded cables used in panel.


Recommended to use proper identification color coded cables
as per standard in the panel.

Conclusions & Recommendations:


Nonstandard color coded cables used in panel, recommended to use proper identification
color coded cables as per standard in the panel.

Check List
Panel: Cap Machine 1

Inspection Date: 17/04/2016

Location: PME Room


Incomer
General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

No label

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Non standard color coded cables used

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

Cap Machine 2
Name Plate: Cap Machine 2

Inspection Date: 17/04/2016

Location: PME Room


Feed from

SDB 11

Total Breakers

Details of Breakers
S.N

Breaker

Description

QTY

MCCB

60A TP

1(Incomer )

MCB

60A TP

MCCB

150A

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer 2

R phase
13.01

Y phase
14.8

B phase
13.9

Neutral
-

Cap Machine 2

Nonstandard color coded cables used:

Nonstandard color coded cables used in panel.


Recommended to use proper identification color coded cables
as per standard in the panel.

Conclusions & Recommendations:


Nonstandard color coded cables used in panel, recommended to use proper identification
color coded cables as per standard in the panel.

Check List
Panel: Cap Machine 2

Inspection Date: 17/04/2016

Location: PME Room


Incomer

60A MCCB

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

No label

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Nonstandard color coded cables used

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB-3
Name Plate: SDB-3

Inspection Date: 16/04/2016

Location: Plant
Feed from

MDB-1

Total Breakers

26

Details of Breakers
S.N

Breaker

Description

Qty

Isolator

4P 63A

1(Incomer)

ELCB

40A 100mA 4P

ELCB

40A 30mA 4P

MCB

45A TP

MCB

40A TP

MCB

25A TP

MCB

32A TP

MCB

6A SP

MCB

10A SP

10

MCB

40A SP

11

MCB

20A SP

13

Contactor

40A

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

41.3

27.9

27.3

13.5

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.4V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

0.72mA

OK

SDB-3

Proper protective device not provided:

Unknown load is connected from the 40A 30mA 4P ELCB,


without any over current/short circuit protection.
Recommended to use proper protective device as per
connected load

Unused openings are present:


Unused openings are present in the panel.
This will degrade the degree of ingress
protection of Enclosure
Recommended to close all the unused
openings with Suitable grommets to maintain
the ingress protection
No shrouding cover:
No shrouding cover is fixed on the panel.
Recommened to provide proper shrouding cover on the panel.
No load schedule:
No load schedule is available with the panel,
Recommended to provide updated load schedule with the panel.

Improper cable dressing:


Improper cable dressing found in the panel.
Recommended to do proper cable dressing in the
panel.

Dust Precipitation in panel:

Dust precipitation is high in the panel.


This may degrade the safe operation of breakers &
Insulation resistance
Recommended to clean the panel periodically by
qualified technicians.

Disconnected cables are present:

Disconnected cables are present in the panel.


Recommended to provide the tag plate with reason
for disconnecting on the cable

Conclusions & Recommendations:


Unknown load is connected from the 40A 30mA 4P ELCB, without any over current/short
circuit protection, recommended to use proper protective device as per connected load
Recommended to close all the unused openings with Suitable grommets to maintain the
ingress protection
Recommended to provide proper shrouding cover on the panel
Recommended to do proper cable dressing in the panel.
Recommended to clean the panel periodically by qualified technicians.

Disconnected cables are present in the panel, recommended to provide the tag plate with
reason for disconnecting on the cable
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel.

Check List
Panel: SDB 3

Inspection Date: 16/04/2016

Location: Plant
Incomer

63A 4P Isolator

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

No load schedule

Unused openings, dust precipitation

OK

Shrouding &Trunking covers

Shrouding cover not available

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

Ok

Improper cable dressing, Disconnected


cables

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

Ok

Room Temperature

good

Condition of Floor: Dry or Wet.

Dry

SDB 4

Name Plate: SDB 4

Inspection Date: 16/04/2016

Location: Plant
Feed from

MDB-1

Total Breakers

36

Details of Breakers
S.N

Breaker

Description

Qty

Isolator

200A TP

1(Incomer)

ELCB

40A 100mA

10

ELCB

63A 100mA

ELCB

40A 30mA

Isolator

63A

MCB

32A TP

MCB

20A TP

MCB

40A TP

MCB

25A TP

10

MCB

16A TP

11

MCB

20A SP

12

MCB

10A SP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

60

70.2

B phase

Neutral

61.7

7.8

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.18V

OK

SDB 4

Improper fixing of comb busbar:


Comb busbar fixed improperly in the panel
Recommended to fix comb busbar properly.

Proper protective device not provided:

Unknown load is connected from the 63A 100mA 4P ELCB,


without any over current/short circuit protection.
Recommended to use proper protective device as per
connected load

Unused openings are present:


Unused openings are present in the panel.
This will degrade the degree of ingress protection
of Enclosure
Recommended to close all the unused openings
with Suitable grommets to maintain the ingress
protection

Improper Entry of cables:


The entry of cables are without proper
glands.
This will degrade the degree of ingress
protection of Enclosure
Recommended to use suitable glands
Nonstandard color coded cables used:

Nonstandard color coded cables used in panel.


Recommended to use proper identification color coded cables
as per standard in the panel.

No load schedule:
No load schedule is available with the panel,
Recommended to provide updated load schedule with the panel.

Conclusions & Recommendations:


Comb busbar fixed improperly in the panel, recommended to fix comb busbar properly.
Unknown load is connected from the 63A 100mA ELCB, without any over current/short
circuit protection, recommended to use proper protective device as per connected load
Recommended to close all the unused openings with Suitable grommets to maintain the
ingress protection
Recommended to use suitable glands for cable entry
Recommended to use proper identification color coded cables as per standard in the panel.
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel.
Dust precipitation is high in the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: SDB 4

Inspection Date: 16/04/2016

Location: Plant
Incomer

200A Isolator

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

No load schedule

Unused openings

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Cable gland not provided

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 2

Name Plate: SDB 2

Inspection Date: 16/04/2016

Location: Ware House


Feed from

MDB-1

Number of breakers:

19

Details of Components
S.N

Components

Description

QTY

Isolator

63A 4P

Incomer

ELCB

40A 100mA 4P

MCB

16A SP

MCB

20A SP

10

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

8.3

7.7

B phase

Neutral

9.1

2.5

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

1.3 V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

0.5 mA

OK

SDB 2

Unused openings are present:


Unused openings are present in the panel, this will
degrade the degree of ingress protection of enclosure.
Recommended to close all the unused openings with
suitable grommets to maintain the ingress protection.

Improper cable dressing:


Improper cable dressing found in the panel.
Recommended to do proper cable dressing in the
panel.

Dust Precipitation in panel:

Dust precipitation is high in the panel.


This may degrade the safe operation of breakers &
Insulation resistance
Recommended to clean the panel periodically by
qualified technicians.

No shrouding cover:
No shrouding cover is fixed on the panel
Recommened to provide proper shrouding cover on the panel

Conclusions & Recommendations:


Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Improper cable dressing found in the panel, recommended to do proper cable dressing in the
panel.
Recommended to clean the panel periodically by qualified technicians.
No shrouding cover is fixed on the panel, recommended to provide proper shrouding cover
on the panel

Check List
Panel: SDB 2

Inspection Date: 16/04/2016

Location: Ware House


Incomer

63A Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Unused openings

OK

Shrouding &Trunking covers

Not available

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Improper cable dressing

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

Ok

Status of Grounding of the Equipment.

Door earthing is not connected

Status of Capacitors

NA

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 1
Name Plate: SDB 1

Inspection Date: 16/04/2016

Location: Ware House


Feed from

MDB 1

Total Breakers

32

Details of components
S.N

Breaker

Description

Qty

Isolator

63A 4P

1 Nos. (Incomer)

Isolator

63A 4P

ELCB

63A 100mA 4P

ELCB

40A 100mA 4P

ELCB

40A 30mA 4P

MCB

10A SP

MCB

20A SP

15

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase
14

Y phase

B phase

Neutral

14

14.4

3.6

SDB 1

Vacant ELCB present:

Unused vacant 63A 100mA 4P ELCB is present in the


panel.
Recommended to remove it if not required.

Improper cable dressing:


Improper cable dressing found in the panel.
Recommended to do proper cable dressing in the
panel.

Unused openings are present:


Unused openings are present in the panel, this
will degrade the degree of ingress protection of
enclosure.
Recommended to close all the unused openings
with suitable grommets to maintain the ingress
protection.

Dust precipitation in the panel:

Dust precipitation is high in the panel.


Recommended to clean the panel periodically by
qualified technicians.

No shrouding cover:
No shrouding cover is fixed on the panel
Recommened to provide proper shrouding cover on the panel
No load schedule:
Load schedule is not provided on the panel.
Recommended to provide load schedule on the panel.

Conclusions & Recommendations:


Unused vacant 63A 100mA 4P ELCB is present in the panel, recommended to remove it if not
required
Improper cable dressing found in the panel recommended to do proper cable dressing in the
panel.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Dust precipitation is high in the panel, recommended to clean the panel periodically by
qualified technicians.
No shrouding cover is fixed on the panel, recommended to provide proper shrouding cover
on the panel
Load schedule is not provided on the panel, recommended to provide load schedule on the
panel.

Check List
Panel: SDB 1

Inspection Date: 16/04/2016

Location: Ware House


Incomer

63A Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Dust precipitation, unused openings

OK

Shrouding &Trunking covers

No shrouding

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Improper cable dressing

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Capacitors

NA

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

UAT/PLC Control Panel

Name Plate: UAT/PLC Control Panel

Inspection Date: 17/04/2016

Location: Plant
Feed from:

MDB 1

Total Breakers

Details of Breakers
S.N

Breaker

Description

Qty

Isolator

Not available

MCB

32A

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase
11.9

Y phase
12.4

B phase
31.8

Neutral
-

UAT/PLC Control Panel

Trunking cover damaged:

Trunking cover is in damaged condition.


Recommended to replace the trunking
cover with new

Unused openings are present:

Unused openings are present in the panel. This


will degrade the degree of ingress protection of
Enclosure.
Recommended to close all the unused openings
with suitable grommets to maintain the ingress
protection.

Conclusions & Recommendations:


Trunking cover is in damaged condition, recommended to replace the trunking cover with
new
Unused openings are present in the panel. This will degrade the degree of ingress protection
of Enclosure, recommended to close all the unused openings with suitable grommets to
maintain the ingress protection.

Panel: UAT/PLC Control Panel

Check List
Inspection Date: 17/04/2016

Location:
Incomer
General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Unused openings present

OK

Shrouding &Trunking covers

Trunking cover damaged

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Ok

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

MDB-2

Name Plate: MDB-2

Inspection Date: 13/04/2016

Location: Electrical Room


Feed from

Transformer

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

MCCB

400A TP 36KA

Incomer

MCCB

125A TP 36KA

Grinder 1&2

MCCB

160 TP 36KA

SDB 5

MCCB

100A TP 25KA

Cooler Welding work shop

MCCB

160A TP 36KA

Capacitor Bank

MCCB

250A TP 36KA

SMDB 7

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

308.2

275.2

B phase

Neutral

262.3

58.6

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.047 V

OK

Earth Resistance
Stakeless earth testing could not be completed because main ecc cable is in disconnected condition

MDB-2

Independent loads are connected from MCCB:


Independent loads are connected to 125A MCCB.
Grinder 1&2 are connected to same MCCB.
Recommended to use separate breakers for each
load as per standard.

Bus bar sleeve is damaged:

The main 30 x 10 Bus bars insulating sleeve is in


damaged condition.
Recommended to provide insulating sleeve on bus
bar.

MCCB is in overheated condition:

125A MCCB feeding to grinder is found to be in


over heated condition
Recommended to do service/Replace the MCCB
for proper working.

Under sized busbar used:


The busbar used for 125A MCCB is 10x5mm, for 160A MCCB and 250A MCCB busbar is
20x5mm, which are under sized busbar.
Recommended to use busbar of proper size as per standard.
Main ECC Cable is disconnected:
During Stakeless earth testing it is found that the main ECC cable is not showing any
continuity with earth pit.
Recommended check the connection between main ECC cable and earth pit.
External handle and door lock damaged:

External handle of MCCB and panel door handle is


in damaged condition.
Recommended to replace door handle and external
handle with new.

Improper entry of ECC cables:

The entry of ECC cables are without proper glands.


This will degrade the degree of ingress protection of
Enclosure.
Recommended to use suitable glands.

Conclusions & Recommendations:


Independent loads are connected to 125A MCCB. Recommended to use separate breakers for
each load as per standard.
Recommended to provide insulating sleeve on bus bar.
125A MCCB feeding to grinder is found to be in over heated condition. Recommended to do
service/Replace the MCCB for proper working.

Under sized busbar used for outgoing feeders. Recommended to use busbar of proper size as
per standard.
Recommended check the connection between main ECC cable and earth pit.
Recommended to replace panel door handle and external handle of MCCB with new.
Recommended to use suitable glands for cable entry.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: MDB-2

Inspection Date: 13/04/2016

Location: Electrical Room


Incomer

400A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Door handle and breaker handle


damaged

Ok

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.

NIL

OK

Mechanical Fitness of the Neutral and Earth


Bars.

OK

Presence of any Unwanted/Disconnected


wires.

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

Disconnected

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

75KVAR Capacitor Bank 2

Name Plate: 75KVAR Capacitor Bank 2

Inspection Date: 13/04/2016

Location: Electrical Room


Feed from

MDB 2

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

Isolator

160A TP

Incomer (1 Nos)

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

B phase

Neutral

No load at the time of inspection

75KVAR Capacitor Bank 2

Capacitor bank not working:


Capacitor bank panel is not in working condition.
Recommended to service/replace the capacitor bank panel for proper power factor
correction.

Improper fixing of capacitor:

Improper fixing of first capacitor in the panel.


Recommended to fix capacitor properly.

Conclusions & Recommendations:


Capacitor bank panel is not in working condition. Recommended to service/replace the
capacitor bank panel for proper power factor correction.
Improper fixing of first capacitor in the panel. Recommended to fix capacitor suitably
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: 75KVAR Capacitor Bank 2

Inspection Date: 13/04/2016

Location: Electrical Room


Incomer

Isolator 160A TP

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

OK

OK

Shrouding &Trunking covers

Ok

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

Ok

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.

NIL

If any discoloration and degradation of


electrical insulations/ Sleeves.

NIL

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 5

Name Plate: SDB 5

Inspection Date: 14 /04/2016

Location: Office
Feed from

MDB 2

Total Breakers

Details of Breakers
S.N

Breaker

Description

QTY

Isolator

160A TP

1(Incomer)

ELCB

40A 100mA 2P

ELCB

40A 30mA 4P

ELCB

40A 100mA 4P

ELCB

63A 30mA 4P

MCB

32A SP

23

MCB

40A TP

MCB

10A SP

MCB

20A SP

10

MCB

16A SP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

40.3

25.1

B phase

Neutral

29.2

25.1

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.7V

OK

SDB 5

Disconnected cables present:

Disconnected cables are present in the panel


Recommended to provide tag plate showing reason
for disconnection or remove it if not required.

Humming noise from contactor:


Humming noise coming from 40A contactor
Recommended to replace it with new contactor
for proper working.

Improper cable dressing & cable entry:


The entry of cables are without proper glands.
Cable dressing also improper in panel.
This will degrade the degree of ingress protection
of Enclosure.
Recommended to use suitable glands and do
proper cable dressing.

Unused openings are present:


Unused openings are present in the panel. This
will degrade the degree of ingress protection of
Enclosure.
Recommended to close all the unused openings
with suitable grommets to maintain the ingress
protection.

Dust precipitation in the panel:

Dust precipitation is high in the panel.


Recommended to clean the panel periodically by
qualified technicians.

No shrouding cover:
No shrouding cover is fixed on the panel
Recommended to provide proper shrouding cover on the panel
Neutral current is high:
Neutral current is high due to unbalanced load.
Recommended to rearrange the connected load.

Conclusions & Recommendations:


Disconnected cables are present in the panel, recommended to provide tag plate showing
reason for disconnection or remove it if not required.
Humming noise coming from 40A contactor, recommended to replace it with new contactor
for proper working.
The entry of cables are without proper glands. Cable dressing also improper in panel,
recommended to use suitable glands and do proper cable dressing.

Neutral current is high due to unbalanced load, recommended to rearrange the connected
load.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Recommended to clean the panel periodically by qualified technicians.
Recommended to provide proper shrouding cover on the panel

Check List
Panel: SDB 5

Inspection Date: 14/04/2016

Location: PME Room


Incomer

160A isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Dust precipitation, unused openings

OK

Shrouding &Trunking covers

Not available

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

Humming noise from contactor

Improper cable dressing

OK

Disconnected cables

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Capacitors

NA

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 7

Name Plate: SDB 7

Inspection Date: 16/04/2016

Location: Plant
Feed from

MDB-2

Total Breakers

28

Details of Breakers
S.N

Breaker

Description

Qty

MCCB

300A TP 36KA

1(Incomer)

MCCB

40A TP 25KA

MCCB

30A TP 25KA

MCCB

150A TP 25KA

MCCB

80A TP 25KA

ELCB

40A 100mA 4P

ELCB

40A 100mA 2P

MCB

25A TP

MCB

32A SP

10

MCB

20A SP

11

Contactor

40A TP

12

Contactor

20A TP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

178

175.4

177.9

12.04

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.54 V

OK

SDB 7

Disconnected cables are present:

Disconnected cables are present in the panel.


Recommended to provide the tag plate with
reason for disconnecting on the cable

Cable glands are not earthed:

Cable glands are not earthed using ECC cables.


Recommended to connect the cable gland with
earth bus bar using suitable ECC cables.

No load schedule available:


No load schedule is available with the panel.
Recommended to provide updated load schedule with the panel.

Conclusions & Recommendations:


Disconnected cables are present in the panel, recommended to provide the tag plate with
reason for disconnecting on the cable
Cable glands are not earthed using ECC cables, recommended to connect the cable gland
with earth bus bar using suitable ECC cables.
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel.
Dust precipitation is high in the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: SDB 7

Inspection Date: 16/04/2016

Location: Plant
Incomer

300A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Ok

OK

Shrouding & Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

Ok

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

Disconnected wires

Contamination of foreign materials inside.

Dust precipitation

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SMDB 13

Name Plate: SMDB 13

Inspection Date: 16/04/2016

Location: Cooler
Feed from

MDB 2

Total Breakers

14

Details of components
S.N

Breaker

Description

QTY

Isolator

350A TP

Incomer

ELCB

100A 100mA 4P

ELCB

40A 100mA 4P

MCB

10A SP

MCB

32A TP

MCB

20A SP

MCB

16A SP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

19.1

1.9

B phase

Neutral

3.2

17.1

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.2V

OK

SMDB 13

Proper protective device not provided:

Unknown load is connected from the 100A 100mA ELCB,


without any over current/short circuit protection.
Recommended to use proper protective device as per
connected load

Unused openings are present:


Unused openings are present in the panel, this will
degrade the degree of ingress protection of enclosure.
Recommended to close all the unused openings with
suitable grommets to maintain the ingress protection.

Neutral current is high:


Neutral current is high due to unbalanced connected load.
Recommended to rearrange the connected load.

Isolator External handle not available:


External handle for isolator is in removed condition.
Recommended to provide new external handle for
proper operation of isolator.

Cable glands are not earthed:


Cable glands are not earthed using ECC cables.
Recommended to connect the cable gland with
earth bus bar using suitable ECC cables.

Door earthing not provided:


Panel door earthing is not provided for this MDB.
Recommended to provide proper earthing for panel
door

Improper color coded cables used:

Improper color coded cables are used for 32A MCB


Recommended to use proper color coded cables as per
standard.

Conclusions & Recommendations:


Unknown load is connected from the 100A 100mA ELCB, without any over current/short
circuit protection recommended to use proper protective device as per connected load
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection
External handle for isolator is in removed condition, recommended to provide new external
handle for proper operation of isolator.
Recommended to connect the cable gland with earth bus bar using suitable ECC cables.
Recommended to provide proper earthing for panel door
Improper color coded cables are used for 32A MCB, recommended to use proper color coded
cables as per standard.
Neutral current is high due to unbalanced connected load, recommended to rearrange the
connected load.

Check List
Panel: SMDB 13

Inspection Date: 16/04/2016

Location: Cooler
Incomer

350A Isolator.

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Unused openings

NIL

Shrouding &Trunking covers

Ok

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

No cable entry glands

Status of Grounding of the Equipment.

Ok

Status of Capacitors

NA

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

Granulator
Name Plate: Granulator

Inspection Date: 17/04/2016

Location: Grinding Area


Feed from

MDB-2

Total Breakers

Details of Breakers
S.N

Breaker

Description

Qty

Isolator

200A TP

1(Incomer)

Isolator

63A 4P

MCB

SP 10A

Contactor

LC1D80

Contactor

LC1D25

Contactor

LC1D32

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

25.0

25.3

B phase

Neutral

29.6

3.7

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.051 V

OK

Granulator

Proper protective device not provided:

Contactor is connected without any overcurrent protection.


63A 4P isolator outgoing is connected to contactor.
Recommended to provide proper over current/Short circuit
protection as per standard.

Cable glands are not earthed:

Cable glands are not earthed using ECC cables


Recommended to connect the cable gland with earth
bus bar using suitable ECC cables

Independent loads connected from Isolator:

Independent loads connected to single isolator.


Recommended to use separate isolator for each feeder

Improper Entry of cables:


The entry of cables are without proper
glands.
This will degrade the degree of ingress
protection of enclosure.
Recommended to use suitable glands.

Earth busbar not provided:


Earth busbar not provided in the panel.
Recommended to use suitable earth busbar for ECC
cable termination

Improper cable dressing:


Improper cable dressing found in the panel.
Recommended to do proper cable dressing in the panel.

Conclusions & Recommendations:


Contactor is connected without any overcurrent protection, recommended to provide proper
over current/Short circuit protection as per standard.
Independent loads connected to single isolator, recommended to use separate isolator for
each feeder
Earth busbar not provided in the panel, recommended to use suitable earth busbar for ECC
cable termination
Recommended to connect the cable gland with earth bus bar using suitable ECC cables
Recommended to use suitable earth busbar for ECC cable termination
Recommended to use suitable glands for cable entry.

Check List
Panel: Granulator

Inspection Date: 17/04/2016

Location: Grinder
Incomer

200A Isolator

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Ok

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

Ok

Improper dressing, no cable entry glands

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

Cable gland not earthed, No earth busbar

Room Temperature

good

Condition of Floor: Dry or Wet.

Dry

Isolator Box Grinder 2

Name Plate:

Inspection Date: 17/04/2016

Location: Grinder
Feed from

MDB-2

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

Isolator

100A TP

Incomer

Isolator Box Grinder 2

Conclusions & Recommendations:


During the testing period the panel was in shut down condition, so thermography tests were
not conducted.
We recommended a Periodic Inspection & Testing yearly to ensure the safe and reliable
operation of panel. Need to conduct Thermography testing, RCCB Trip testing & inspection
of terminations, insulators, Breakers etc.
Recommended to clean the panel periodically by qualified Technicians to keep the panel
neat & tidy.

Check List
Panel: Isolator box grinder 2

Inspection Date: 17/04/2016

Location: Grinder
Incomer

100A TP Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Panel in off condition

Dust Precipitation

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

Ok

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

MDB-3
Name Plate: MDB-3

Inspection Date: 14/04/2016

Location: Electrical Room


Feed from

Transformer

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

MCCB

400A TP 36KA

Incomer

MCCB

200A TP 36KA

SMDB 6 - Shaklan

MCCB

63A TP 25KA

SMDB 9 - Shaklan

MCCB

160A TP 36KA

Capacitor Bank

MCCB

320A TP 36KA

Automa Machine

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

232.4

177

205

39.7

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.022V

OK

MDB-3

Under sized busbar used:


The busbar used for 200A MCCB is 20x5mm, it is under sized as per standard
Recommended to use busbar of proper size as per standard
Main ECC Cable is disconnected:
During Stakeless earth testing it is found that the main ECC cable is not showing any
continuity with earth.
Recommended to check the connection between main ECC cable and earth pit.

Cable tapping from Busbar:


Cables are used instead of Busbar links from Main
busbar to Feeder MCCB connection.
This will degrade the kA rating of the internal
busway system.
Recommended to provide busbar links instead of
cables.

Improper entry of ECC cables:

The entry of ECC cables are without proper


glands.
This

will

degrade

the

degree

protection of Enclosure.
Recommended to use suitable glands.

of

ingress

Unused openings are present:

Unused openings are present in the panel.


This will degrade the degree of ingress protection of
Enclosure.
Recommended to close all the unused openings with
suitable grommets to maintain the ingress protection.

Conclusions & Recommendations:


The busbar used for 200A MCCB is 20x5mm, it is under sized as per standard,
Recommended to use busbar of proper size as per standard
Cables are used instead of Busbar links from Main busbar to Feeder MCCB connection,
recommended to provide busbar links instead of cables.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Recommended to use suitable glands for cable entry.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.
Door lock of the panel is in damaged condition, recommended to replace it with new.

Check List
Panel: MDB-3

Inspection Date: 14/04/2016

Location: Electrical Room


Incomer

400A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Door lock damaged

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

Dust precipitation

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

NIL

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

good

Condition of Floor: Dry or Wet.

Dry

75KVAR Capacitor Bank 3

Name Plate: 75KVAR Capacitor Bank 3

Inspection Date: 14/04/2016

Location: Electrical Room


Feed from

MDB 3

Total Breakers

Details of Breakers
S.N

Breaker

Description

Feeder

Isoaltor

315A TP

Incomer

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

B phase

Neutral

No load at the time of inspection

75KVAR Capacitor Bank 3

Capacitor bank not working:


Capacitor bank panel is not in working condition.
Recommended to service/replace the capacitor bank panel for proper power factor
correction.

Conclusions & Recommendations:

Capacitor bank panel is not in working condition, recommended to service/replace the


capacitor bank panel for proper power factor correction.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: 75KVAR Capacitor Bank 3

Inspection Date: 14/04/2016

Location: Electrical Room


Incomer

Isolator 315A

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Dust Precipitation

OK

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 6
Name Plate: SDB 6

Inspection Date: 18/01/2016

Location: Plastic Division


Feed from

MDB-3

Total Breakers

35

Details of Breakers
S.N

Breaker

Description

QTY

Isolator

250A TP

ELCB

40A 100mA 4P

ELCB

40A 30mA 4P

ELCB

63A 500mA 4P

ELCB

63A 100mA 4P

MCB

20A TP

MCB

40A TP

MCB

63A TP

MCB

10A SP

10

MCB

20A SP

11

Contactor

40A

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

80.4

70.2

B phase

Neutral

87.4

21.2

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.24V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

5.01mA

OK

SDB 6

Comb busbar is damaged:

Comb busbar is in damaged condition for 20A


MCB at the top side of the panel.
Recommended to replace it with new comb busbar.

Improper termination of cables:


Improper termination of incoming cable to 63A
TP MCB
Recommended to do proper cable termination.

Load schedule is not available:


No load schedule is available with the panel
Recommended to provide updated load schedule with the panel

Disconnected cables present:


Some cables are in disconnected condition in the
panel
Recommended to provide tag plate with reason for
disconnecting / remove if it is not required

Proper protective device not provided:


Unknown load is connected from the incomer
side of main isolator without any over current/short
circuit protection
Recommended to use proper protective device as
per connected load

Damaged ELCB is present in the panel:


Damaged ELCB is still existing in the panel
without any connection
Recommended to remove damaged ELCB

Proper protective device not provided:

Unknown load is connected from the 40A 30mA ELCB,


without any over current/short circuit protection.
Recommended to use proper protective device as per
connected load

Improper cable entry:


The entry of cables are without proper glands.
This will degrade the degree of ingress protection
of Enclosure.
Recommended to use suitable glands.

Improper fixing of shrouding cover:

Shrouding cover of the panel is fixed improperly


Recommended to fix it properly on the panel.

Conclusions & Recommendations:


Comb busbar is in damaged condition for 20A MCB at the top side of the panel,
recommended to replace it with new comb busbar.
Recommended to do proper cable termination.
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel
Recommended to provide tag plate with reason for disconnecting / remove if it is not
required
Recommended to use proper protective device as per connected load
Recommended to remove damaged ELCB
Recommended to use suitable glands for cable entry.
Shrouding cover of the panel is fixed improperly, recommended to fix it properly on the
panel.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians
Improper Cable dressing in the panel, recommended to do proper cable dressing

Check List
Panel: SDB 6

Inspection Date: 14/04/2016

Location: Plastic Division


Incomer

250A Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

OK

OK

Shrouding &Trunking covers

Improper Shrouding cover

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.

NIL

Fitness of Wiring, Terminal Connections &


Splices.

Improper cable dressing

Mechanical Fitness of the Neutral and Earth


Bars.
Presence of any Unwanted/Disconnected
wires.

OK

Disconnected cables present

Contamination of foreign materials inside.

Dust precipitation

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

cable entry gland not used

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SMDB 9

Name Plate: SMDB 9

Inspection Date: 14/04/2016

Location: PME Room


Feed from

MDB 3

Total Breakers

Details of Breakers
S.N

Breaker

Description

QTY

MCCB

200A TP 36KA

Incomer 1

MCCB

40A TP 25KA

MCCB

60A TP 25KA

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

22.4

23.6

B phase

Neutral

21.1

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.04V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

0.5mA

OK

SMDB 9

Under sized cables used:

For the 200A incomer MCCB the connected cable is 4C 16


sqmm Cable which is undersized, for the outgoing 40A MCCB 4C 16sqmm PVC cable is connected which is also undersized &
which are unsafe conditions.
Recommended to change the cable / Breaker rating as per the
load.

Independent loads connected from MCCB:


Independent loads are connected 60A TP MCCB
Recommended to use separate MCCB for each load
as per standard.

Improper color coded cables used:


All outgoing feeders are connected with improper color coded cables
Recommended to use proper color coded cables as per standard
No shrouding cover:
No shrouding cover is fixed on the panel
Recommended to provide proper shrouding cover on the panel

No Labelling for outgoing feeders:


No labelling is provided for the outgoing feeders in the panel
Recommended to provide proper identification in the panel

Conclusions & Recommendations:


For the 200A incomer MCCB the connected cable is 4C 16 sqmm Cable which is undersized,
for the outgoing 40A MCCB - 4C 16sqmm PVC cable is connected which is also undersized &
which are unsafe conditions, recommended to change the cable / Breaker rating as per the
load.
Independent loads are connected 60A TP MCCB, recommended to use separate MCCB for
each load as per standard.
All outgoing feeders are connected with improper color coded cables, recommended to use
proper color coded cables as per standard
No shrouding cover is fixed on the panel, recommended to provide proper shrouding cover
on the panel
No labelling is provided for the outgoing feeders in the panel, recommended to provide
proper identification in the panel

Check List
Panel: SMDB 9

Inspection Date: 14/04/2016

Location: PME Room


Incomer

200A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

No labelling for outgoing feeders

Ok

Ok

Shrouding &Trunking covers

Not available

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

Automa Control Panel

Name Plate: Automa Control Panel

Inspection Date: 14/04/2016

Location: Plastic Division


Feed from:

MDB-3

Total Breakers

Details of Breakers
S.N

Components

Description

Qty

MCCB

250A TP 40kA

Incomer

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

128

114

130

14.5

Automa Control Panel

Humming noise from transformer:


Abnormal humming noise produced from transformer.
Recommended to test and service the transformer.
Trunking cover removed:
Trunking cover is found to be removed condition in the
panel.
Recommended to provide proper trunking cover.

Dust Precipitation in panel:

Dust precipitation found on the panel.


This may degrade the safe operation of breakers &
Insulation resistance
Recommended to clean the panel periodically by qualified
technicians.

Conclusions & Recommendations:


Abnormal humming sound produced from transformer, recommended to test and service the
transformer.
Trunking cover is found to be removed condition in the panel, recommended to provide
proper trunking cover
Recommended to clean the panel periodically by qualified technicians.

Check List
Panel: Automa Control Panel

Inspection Date: 17/04/2016

Location: Plastic Division


Incomer

250A MCCB.

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Dust preciptation

No trunking cover

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

Ok

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

Humming sound from transformer

Ok

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

MDB 4
Name Plate: MDB 4

Inspection Date: 17/01/2016

Location: Outside of Electrical Room


Feed from:

Transformer

Total Breakers

Details of Components
S.N

Components

Description

Feeder

MCCB

400A TP 36kA

Incomer

MCCB

250A TP 36KA

SMDB 8

MCCB

100A TP 25KA

SMDB 12

MCCB

160A TP 36KA

SMDB 10

MCCB

125A TP 36KA

Capacitor Bank

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

254

250

B phase

Neutral

249

14.4

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.067 V

OK

Value (Ohms)

Status

0.018

OK

Earth Resistance Testing


S.N
1

Feeder
Incomer ECC

MDB-4

Under sized busbar used:


For 125A TP MCCB & 160A MCCB the busbar used is 15x5mm in size, which are under
sized busbar.
Recommended to use busbar of proper size as per standard.
Panel mounted on exterior wall:

Panel is mounted on exterior wall of the building.


Recommended to keep the panel inside air conditioned room
for efficient working.

Dust precipitation in the panel:


Dust precipitation found on the panel.
Recommended to clean the panel periodically by
qualified technicians.

Improper wire joints:


Improper wire joints found in the panel.
Recommended to use terminals for wire joints

Improper fixing of CBCT:


Improper fixing of CBCT in the panel, cable tie is used
for fixing.
Recommended to fix it properly in the panel.

Conclusions & Recommendations:


For 125A TP MCCB & 160A MCCB the busbar used is 15x5mm in size, which are under
sized busbar, recommended to use busbar of proper size as per standard.
Panel is mounted on exterior wall of the building, recommended to keep the panel inside air
conditioned room for efficient working.
Recommended to clean the panel periodically by qualified technicians.
Recommended to use terminals for wire joints
Improper fixing of CBCT in the panel, cable tie is used for fixing, recommended to fix it
properly in the panel.

Check List
Panel: MDB-4

Inspection Date: 14/04/2016

Location: Outside of Electrical Room


Incomer

400A MCCB.

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Mounted on exterior wall

OK

Shrouding & Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NA

OK

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

Dust precipitation

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Hot

Condition of Floor: Dry or Wet.

Dry

60 KVAR Capacitor Bank 4


Name Plate: 60 KVAR Capacitor Bank 4

Inspection Date: 14/04/2016

Location: Outside of Electrical Room


Feed from:

MDB 4

Total Breakers

Details of Breakers
S.N

Components

Description

Feeder

Isolator

200A TP

Incomer

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

B phase

Neutral

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.04V

OK

60 KVAR Capacitor Bank 4

Panel mounted on exterior wall:

Panel is mounted on exterior wall of the building.


Recommended to keep the panel inside air conditioned room
for efficient working.

Louver is removed:
Louver of the panel is in removed condition.
Recommended to replace it with new for proper
ventilation

Power factor controller screen is not visible:

Power factor controller screen is not visible, dust


contamination is high on the screen.
Recommended to make the screen visible properly.

Dust precipitation in the panel:


Dust precipitation found on the panel.
Recommended to clean the panel periodically by
qualified technicians.

Conclusions & Recommendations:


Panel is mounted on exterior wall of the building, recommended to keep the panel inside air
conditioned room for efficient working.
Recommended to replace the panel louver with new for proper ventilation.
Recommended to make the controller screen visible properly.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.

Check List
Panel: 60 KVAR Capacitor Bank 4

Inspection Date: 14/01/2016

Location: Outside of Electrical Romm


Incomer

200A Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Mounted on exterior wall

Ok

Shrouding &Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

OK

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Hot

Condition of Floor: Dry or Wet.

Dry

SMDB-12
Name Plate: SMDB-12

Inspection Date: 14/04/2016

Location: Plastic Division


Feed from:

MDB-4

Total Breakers

11

Details of Breakers
S.N

Components

Description

Qty

Isolator

125A TP

MCCB

125A TP 25KA

ELCB

40A 100mA 4P

ELCB

100A 100mA 4P

MCB

40A TP

MCB

20A SP

MCB

10A SP

MCB

25A SP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

43.9

30.1

B phase

Neutral

33.5

10.4

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.27V

OK

SMDB-12

Improper color coded cables used:

Improper color coded cables are used for 125A MCCB


Recommended to use proper color coded cables as per
standard.

Unused openings are present:

Unused openings are present in the panel. This will


degrade the degree of ingress protection of Enclosure.
Recommended to close all the unused openings with
suitable grommets to maintain the ingress protection.

Cable glands are not earthed:


Cable glands are not earthed using ECC cables.
Recommended to connect the cable gland with
earth bus bar using suitable ECC cables.

Improper cable dressing:


Improper cable dressing is found in the panel.
Recommended to do proper cable dressing in the
panel.

Disconnected cables present:


Some cables are in disconnected condition in the
panel
Recommended to provide tag plate with reason
for disconnecting / remove if it is not required

Conclusions & Recommendations:


Improper color coded cables are used for 125A MCCB, recommended to use proper color
coded cables as per standard.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection
Recommended to connect the cable gland with earth bus bar using suitable ECC cables.
Improper cable dressing is found in the panel, recommended to do proper cable dressing in
the panel.
Some cables are in disconnected condition in the panel, recommended to provide tag plate
with reason for disconnecting / remove if it is not required
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel.

Check List
Panel: SMDB-12

Inspection Date: 14/04/2016

Location: Plastic Division


Incomer

125A Isolator

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

OK

Ok

OK

Shrouding & Trunking covers

OK

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

OK

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

Disconnected cables present

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

OK

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SMDB 10

Name Plate: SMDB 10

Inspection Date: 14/04/2016

Location: PME Room


Feed from:

MDB 4

Total Breakers

Details of Breakers
S.N

Breaker

Description

Qty

MCCB

400A TP 36KA

(1 Nos)Incomer

MCCB

100A TP 25KA

MCCB

200A TP 36KA

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder

R phase

Incomer

Y phase

B phase

Neutral

No load at the time of inspection

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.067V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

0.16mA

OK

SMDB 10

Under sized cables used:

The connected cable is 4C 6 sqmm PVC Cable


which is undersized with the 100A MCCB & is in
unsafe condition.
Recommended to change the cable / Breaker
rating as per the load.

Conclusions & Recommendations


The connected cable is 4C 6 sqmm PVC Cable which is undersized with the 100A MCCB
rating & is in unsafe condition, recommended to change the cable / Breaker rating as per the
load.

Check List
Inspection Date: 14/04/2016

Panel: SMDB 10
Location: PME Room
Incomer

400A MCCB

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.

OK

Condition of the Exterior of Cubicle, Door,


Door handle, locking Bar & Mechanism.

OK

Mechanical Fitness of the Guide rails &


Racking Mechanism.

OK

Shrouding &Trunking covers

NA

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

OK

NIL

Contamination of foreign materials inside.

NIL

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

Ok

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

SDB 8
Name Plate: SDB 8

Inspection Date: 16/04/2016

Location: Plant
Feed from

MDB 4

Total Breakers

Details of Breakers
S.N

Breaker

Description

Quantity

MCCB

400A TP 50KA

1 Nos

MCCB

160A TP 36KA

MCCB

100A TP 25KA

MCCB

30A TP 25KA

MCCB

160A TP 36KA

MCCB

63A TP 25KA

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

214

221

B phase

Neutral

218

7.3

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.8V

OK

SDB 8

Cable glands are not earthed:

Cable glands are not earthed using ECC cables.


Recommended to connect the cable gland with
earth bus bar using suitable ECC cables.

Unused openings are present:


Unused openings are present in the panel, this will degrade
the degree of ingress protection of enclosure.
Recommended to close all the unused openings with suitable
grommets to maintain the ingress protection.

Indicator lamp not working:


Yellow color Indicator lamp is not working on the panel.
Recommended to replace it with new indicator

Conclusions & Recommendations:


Cable glands are not earthed using ECC cables, recommended to connect the cable gland
with earth bus bar using suitable ECC cables.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Yellow color Indicator lamp is not working on the panel, recommended to replace it with
new indicator

Check List
Panel: SDB 8

Inspection Date: 16/04/2016

Location: Plant
Incomer

400A MCCB

General Status

Good

Fair

Poor

Inspection

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Indicator lamp not working

Ok

OK

Shrouding & Trunking covers

NA

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.
Any Abnormal sound/vibrations produced in
Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

NA

NIL

OK

OK

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

NIL

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

Ok

Status of Grounding of the Equipment.

Ok

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry

NPAS Control Panel


Name Plate: NPAS Control Panel

Inspection Date: 16/04/2016

Location: Plant
Feed from

SDB 8

Total Breakers

Details of Breakers
S.N

Breaker

Description

QTY

Isolator

100A TP

1 Nos

MCCB

800A TP

Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1

Feeder
Incomer

R phase

Y phase

B phase

Neutral

73.2

70.5

83.7

2.84

Neutral Ground Potential


S.N
1

Feeder
Incomer

Value (Volts)

Status

0.77 V

OK

Value (mA)

Status

Leakage Current Measurement


S.N
1

Feeder
Incomer

15.1 mA

OK

NPAS Control Panel

Conclusions & Recommendations:


Thermography tests were conducted & report attached
We recommended a Periodic Inspection & Testing yearly to ensure the safe and reliable
operation of panel. Need to conduct Thermography testing, RCCB Trip testing & inspection
of terminations, insulators, Breakers etc.
Recommended to clean the panel periodically by qualified Technicians to keep the panel
neat & tidy.

Check List
Panel: NPAS Control Panel

Inspection Date: 16/04/2016

Location: Plant
Incomer

Isolator 100A

General Status

Good

Fair

Inspection

Poor

Comments

Labeling of the unit & Warning signs, Sign


Boards for Breaker positions.
Condition of the Exterior of Cubicle, Door,
Door handle, locking Bar & Mechanism.
Mechanical Fitness of the Guide rails &
Racking Mechanism.

Ok

Ok

OK

Shrouding &Trunking covers

NA

Broken Instruments Damaged Relay Cover


and Glass. If any
Working status of Control & Metering
Transformers.

NIL

NA

Any Abnormal sound/vibrations produced in


Breakers, Bus bars, CTS etc.
Fitness of Wiring, Terminal Connections &
Splices.
Mechanical Fitness of the Neutral and Earth
Bars.
Presence of any Unwanted/Disconnected
wires.

NIL

OK

Ok

NIL

Contamination of foreign materials inside.

OK

If any Corrosion, Erosion or Deterioration of


painted surfaces of metallic objects.
If any discoloration and degradation of
electrical insulations/ Sleeves.

NIL

NIL

Cracks, or tracking on the insulators.

NIL

Mechanical stability of Insulators.

OK

Status of ECC cables

OK

Status of Grounding of the Equipment.

OK

Status of Earth Fault protection

OK

Room Temperature

Good

Condition of Floor: Dry or Wet.

Dry