Al Bayan, Dubai Investment Park
Project
Building
Al Bayan
Date
April 2016
Carelabs, Dubai, Phone : 00971 4 5149730, Email : info@carelabs.ae
Table of Content
Project details
Report summary
Table of Panels inspected
Index of Fault Findings
Reports
Company Details
Project Details
Project Name
Client
: Al Bayan
Conducted by
: Carelabs
Location
Executive Summary
This report has been created after a thorough investigation carried out on site
consisting of a detailed condition survey using physical verification, thermography imaging
and measurement of electrical parameters from the MDB panel to the Sub Main Distribution
Boards within Al Bayan
The report has been categorized into two priorities Critical & Urgent as per the following
parameters
Priority 1- Critical issues that need immediate action and rectification
Priority 2- Urgent issues that are based on electrical compliance of local and international
authorities
The purpose of this report is to identify the electrical related issues that can impact the
operation of the building, affect the end users/ tenants of the building. The aim of this report is
to address the issues based on priorities and ensure the electrical systems are risk free.
The detailed report illustrates our findings and points of action required to restore the healthy
status of the building.
Type
Location
LV Panel
Electrical Room
Capacitor Bank
Electrical Room
SMDB
PME Room
MDB 1
SMDB 11
Cap Machine 1
Control Panel
PME Room
Cap Machine 2
Control Panel
PME Room
SDB 3
SMDB
Plant
SDB 4
SMDB
Plant
SDB 2
SMDB
Ware house
SDB 1
SMDB
Ware house
10
Control panel
Plant
11
MDB-2
MDB
Electrical Room
12
Capacitor Bank
Electrical Room
13
SDB 5
SMDB
Office
14
SDB 7
SMDB
Plant
15
SMDB 13
SMDB
Cooler Plant
16
Granulator
Control Panel
Grinding Area
17
Isolator Panel
Grinding Area
18
MDB-3
LV Panel
Electrical Room
19
Capacitor Bank
Electrical Room
20
SDB-6
SMDB
Plastic Division
21
SMDB-9
SMDB
PME Room
22
Control panel
Plastic Division
23
MDB-4
LV Panel
Outside-Electrical Room
24
Capacitor Bank
Electrical Room
25
SMDB 12
SMDB
Plastic Division
26
SMDB 10
SMDB
PME Room
27
SDB 8
SMDB
Plant
28
Control panel
Plant
Location
Equipment
Date
April 2016
Priority 1
S. N
Equipment
MDB-1
Fault findings
Recommendation
Recommended to
service/replace capacitor bank
75KVAR
Capacitor Bank
Recommended to
service/replace capacitor bank
SMDB-11
SDB-3
SDB-4
Recommended to
replace/service it
10
11
12
Recommended to
service/replace capacitor bank
Recommended to
service/replace capacitor bank
13
MDB-2
75KVAR
Capacitor bank 2
Page
no.
14
SMDB-13
15
Granulator
16
17
High temperature
Showed at incomer side
blue phase busbar
18
19
Recommended to
service/replace capacitor bank
Recommended to
service/replace capacitor bank
22
23
24
25
High temperature
showed at incoming
busbar and outgoing
cables of 250A MCCB
MDB-3
20
75KVAR
Capacitor Bank 3
21
SDB-6
SMDB-9
MDB-4
26
27
SMDB-10
28
NPAS Control
panel
Priority 2
S. N
Equipment
Fault findings
Recommendation
Recommended to provide
earthing for panel door
Recommended to replace it
with new door handle
External handle is
damaged
Recommended to replace it
with new lock
MDB-1
75KVAR
Capacitor Bank 1
Cap machine 1
Cap machine 2
Recommended to provide
proper shroud cover
10
11
Recommended to provide
load schedule
12
Recommended to do proper
cable dressing
13
14
Recommended to remove if
not required
15
SDB-3
Page
no.
30-33
S. N
Equipment
Fault findings
Recommendation
16
Recommended to fix it
properly
17
18
SDB-4
19
Recommended to provide
suitable glands
20
21
Recommended to provide
load schedule
22
23
24
Recommended to do proper
cable dressing
25
Recommended to provide
proper shroud cover
26
Recommended to remove if
not required
27
Recommended to do proper
cable dressing
29
30
Recommended to provide
proper shroud cover
31
Recommended to provide
load schedule
SDB-2
28
SDB-1
Page
no.
34-38
39-42
43-47
S. N
Fault findings
Recommendation
32
Recommended to provide
suitable trunking
33
34
Recommended to provide
suitable glands
35
External handle is
damaged
Recommended to replace it
with new
36
Recommended to replace it
with new
37
38
Recommended to fix
capacitor suitably
40
Recommended to remove if
not required
41
Recommended to replace it
with new contactor
42
43
44
Recommended to do proper
cable dressing
45
Recommended to provide
suitable glands
46
No shrouding cover
Recommended to provide
proper shrouding cover
47
Disconnected
present
48
Recommended to connect
glands with ECC cables
49
Recommended to provide
load schedule
50
39
Equipment
UAT/PLC
Control panel
75kvar Capacitor
Bank
SDB-5
SDB-7
cables
Page
no.
52-55
60-65
S. N
Fault findings
Recommendation
51
52
External handle is
damaged
Recommended to replace it
with new
Recommended to connect
glands with ECC cables
54
No door earthing
Recommended to provide
proper earthing
55
56
Recommended to rearrange
the connected load
57
Recommended to connect
glands with ECC cables
58
Independent loads
connected to single isolator
Recommended to use
separate isolator
Recommended to provide
suitable glands
60
61
Recommended to do proper
cable dressing
62
63
Recommended to provide
busbar links
Recommended to provide
suitable glands
65
Recommended to replace it
with new
66
53
59
64
Equipment
SMDB 13
Granulator
MDB-3
Page
no.
72-78
87-91
67
Comb busbar is in
damaged condition
Recommended to replace
comb busbar with new
68
Improper termination of
incoming cable to 63A TP
MCB
Recommended to do proper
cable termination
69
Recommended to provide
load schedule
70
Recommended to remove if
not required
71
Recommended to remove
damaged ELCB
72
Recommended to provide
suitable glands
73
Improper fixing of
shrouding cover
Recommended to provide
proper shrouding cover
74
75
Recommended to do proper
cable dressing
76
77
No shrouding cover
Recommended to provide
proper shrouding cover
78
No labelling on shrouding
cover
Recommended to provide
proper identification in the
panel
79
80
Recommended to provide
proper trunking cover
Panel is mounted on
exterior wall of the
building
Dust precipitation in the
panel
Improper wire joints found
in the panel
SDB-6
SMDB-9
81
Automa Control
panel
82
83
84
85
MDB-4
92-97
98102
103106
107111
86
Recommended to fix it
properly in the panel
87
Panel is mounted on
exterior wall of the
building
Recommended to replace it
with new
89
90
91
92
93
Recommended to connect
glands with ECC cables
94
Recommended to do proper
cable dressing
95
Recommended to remove if
not required
96
Recommended to provide
load schedule
97
Recommended to connect
glands with ECC cables
98
Recommended to replace it
with new indicator
88
60KVAR
Capacitor Bank 4
SMDB 12
SDB 8
99
Panel Name
Recommendations
MDB-1
Transformer
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
MCCB
400A TP 36KA
Incomer
MCCB
63A TP 25KA
SDB 3
MCCB
63A TP 25KA
SDB 2
MCCB
160A TP 36KA
Capacitor Bank
MCCB
125A TP 25KA
CAP Machine
MCCB
63A TP 25KA
SDB 1
MCCB
160A TP 25KA
SDB 4
MCCB
125A TP 25KA
Bottling Machine
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
196.6
165.1
B phase
Neutral
203
17.5
Feeder
Incomer
Value (Volts)
Status
0.020 V
OK
Earth Resistance
Stakeless earth testing could not be completed because main ecc cable is in disconnected condition
MDB-1
Unused openings are present in the door and inside of the panel. This will degrade the
degree of ingress protection of Enclosure
Recommended to close all the unused openings with Suitable grommets to maintain the
ingress protection
Check List
Panel: MDB-1
Location: LV Room1
Incomer
400A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
Ok
OK
OK
OK
NIL
NA
NIL
OK
OK
NIL
OK
NIL
NIL
NIL
OK
OK
OK
Room Temperature
Good
Dry
MDB-1
Total Breakers
Details of Breakers
S.N
Breaker
Description
Quantity
Isolator
160A TP
1(Incomer)
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
Check List
Panel: 75KVAR Capacitor Bank-1
400A TP MCCB.
General Status
Good
Fair
Inspection
Poor
Comments
Ok
OK
OK
NIL
OK
NIL
OK
OK
NIL
OK
NIL
Ok
NIL
OK
Ok
OK
OK
Room Temperature
Good
Dry
SMDB-11 CAP
Name Plate: SMDB-11 CAP
MDB 1
Total Breakers:
Details of Breakers
S.N
Breaker
Description
QTY
MCCB
200A TP 36KA
Incomer 1QTY
MCCB
60A TP 25KA
MCCB
40A TP 25kA
MCCB
100A TP 25kA
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
62.3
34.4
B phase
Neutral
35.4
8.6
Feeder
Incomer
Value (Volts)
Status
0.15V
OK
Value (mA)
Status
Feeder
Incomer
8.9mA
OK
SMDB-11 CAP
Check List
Panel: SMDB 11 CAP
Good
Fair
Inspection
Poor
Comments
OK
OK
OK
OK
NIL
OK
NIL
OK
OK
NIL
NIL
NIL
OK
NIL
OK
OK
OK
OK
Room Temperature
Good
Dry
Cap Machine 1
Name Plate: Cap Machine 1
SDB 11
Total Breakers
Details of Breakers
S.N
Breaker
Description
QTY
MCCB
150A TP
1(Incomer )
Contactor
22kW
MCB
20A TP
MCCB
150A TP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer 2
R phase
Y phase
B phase
33.8
34
33.7
Neutral
-
Cap Machine 1
Check List
Panel: Cap Machine 1
Good
Fair
Poor
Inspection
Comments
Ok
No label
OK
OK
NIL
OK
NIL
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
Cap Machine 2
Name Plate: Cap Machine 2
SDB 11
Total Breakers
Details of Breakers
S.N
Breaker
Description
QTY
MCCB
60A TP
1(Incomer )
MCB
60A TP
MCCB
150A
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer 2
R phase
13.01
Y phase
14.8
B phase
13.9
Neutral
-
Cap Machine 2
Check List
Panel: Cap Machine 2
60A MCCB
General Status
Good
Fair
Poor
Inspection
Comments
Ok
No label
OK
OK
NIL
OK
NIL
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SDB-3
Name Plate: SDB-3
Location: Plant
Feed from
MDB-1
Total Breakers
26
Details of Breakers
S.N
Breaker
Description
Qty
Isolator
4P 63A
1(Incomer)
ELCB
40A 100mA 4P
ELCB
40A 30mA 4P
MCB
45A TP
MCB
40A TP
MCB
25A TP
MCB
32A TP
MCB
6A SP
MCB
10A SP
10
MCB
40A SP
11
MCB
20A SP
13
Contactor
40A
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
41.3
27.9
27.3
13.5
Feeder
Incomer
Value (Volts)
Status
0.4V
OK
Value (mA)
Status
Feeder
Incomer
0.72mA
OK
SDB-3
Disconnected cables are present in the panel, recommended to provide the tag plate with
reason for disconnecting on the cable
No load schedule is available with the panel, recommended to provide updated load
schedule with the panel.
Check List
Panel: SDB 3
Location: Plant
Incomer
63A 4P Isolator
General Status
Good
Fair
Poor
Inspection
Comments
No load schedule
OK
NIL
NA
Ok
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
OK
Ok
Room Temperature
good
Dry
SDB 4
Location: Plant
Feed from
MDB-1
Total Breakers
36
Details of Breakers
S.N
Breaker
Description
Qty
Isolator
200A TP
1(Incomer)
ELCB
40A 100mA
10
ELCB
63A 100mA
ELCB
40A 30mA
Isolator
63A
MCB
32A TP
MCB
20A TP
MCB
40A TP
MCB
25A TP
10
MCB
16A TP
11
MCB
20A SP
12
MCB
10A SP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
60
70.2
B phase
Neutral
61.7
7.8
Feeder
Incomer
Value (Volts)
Status
0.18V
OK
SDB 4
No load schedule:
No load schedule is available with the panel,
Recommended to provide updated load schedule with the panel.
Check List
Panel: SDB 4
Location: Plant
Incomer
200A Isolator
General Status
Good
Fair
Poor
Inspection
Comments
No load schedule
Unused openings
OK
OK
NIL
NA
NIL
OK
NIL
NIL
NIL
OK
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SDB 2
MDB-1
Number of breakers:
19
Details of Components
S.N
Components
Description
QTY
Isolator
63A 4P
Incomer
ELCB
40A 100mA 4P
MCB
16A SP
MCB
20A SP
10
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
8.3
7.7
B phase
Neutral
9.1
2.5
Feeder
Incomer
Value (Volts)
Status
1.3 V
OK
Value (mA)
Status
Feeder
Incomer
0.5 mA
OK
SDB 2
No shrouding cover:
No shrouding cover is fixed on the panel
Recommened to provide proper shrouding cover on the panel
Check List
Panel: SDB 2
63A Isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
Unused openings
OK
Not available
NIL
NA
NIL
OK
NIL
OK
NIL
Ok
NIL
OK
Ok
Status of Capacitors
NA
Room Temperature
Good
Dry
SDB 1
Name Plate: SDB 1
MDB 1
Total Breakers
32
Details of components
S.N
Breaker
Description
Qty
Isolator
63A 4P
1 Nos. (Incomer)
Isolator
63A 4P
ELCB
63A 100mA 4P
ELCB
40A 100mA 4P
ELCB
40A 30mA 4P
MCB
10A SP
MCB
20A SP
15
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
14
Y phase
B phase
Neutral
14
14.4
3.6
SDB 1
No shrouding cover:
No shrouding cover is fixed on the panel
Recommened to provide proper shrouding cover on the panel
No load schedule:
Load schedule is not provided on the panel.
Recommended to provide load schedule on the panel.
Check List
Panel: SDB 1
63A Isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
OK
No shrouding
NIL
NA
NIL
OK
NIL
OK
NIL
OK
NIL
OK
OK
OK
Status of Capacitors
NA
Room Temperature
Good
Dry
Location: Plant
Feed from:
MDB 1
Total Breakers
Details of Breakers
S.N
Breaker
Description
Qty
Isolator
Not available
MCB
32A
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
11.9
Y phase
12.4
B phase
31.8
Neutral
-
Check List
Inspection Date: 17/04/2016
Location:
Incomer
General Status
Good
Fair
Inspection
Poor
Comments
Ok
OK
NIL
NA
NIL
Ok
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
MDB-2
Transformer
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
MCCB
400A TP 36KA
Incomer
MCCB
125A TP 36KA
Grinder 1&2
MCCB
160 TP 36KA
SDB 5
MCCB
100A TP 25KA
MCCB
160A TP 36KA
Capacitor Bank
MCCB
250A TP 36KA
SMDB 7
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
308.2
275.2
B phase
Neutral
262.3
58.6
Feeder
Incomer
Value (Volts)
Status
0.047 V
OK
Earth Resistance
Stakeless earth testing could not be completed because main ecc cable is in disconnected condition
MDB-2
Under sized busbar used for outgoing feeders. Recommended to use busbar of proper size as
per standard.
Recommended check the connection between main ECC cable and earth pit.
Recommended to replace panel door handle and external handle of MCCB with new.
Recommended to use suitable glands for cable entry.
Dust precipitation found on the panel, recommended to clean the panel periodically by
qualified technicians.
Check List
Panel: MDB-2
400A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
OK
Ok
OK
NIL
NA
NIL
OK
OK
NIL
NIL
NIL
OK
NIL
OK
Disconnected
Ok
OK
Room Temperature
Good
Dry
MDB 2
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
Isolator
160A TP
Incomer (1 Nos)
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
B phase
Neutral
Check List
Panel: 75KVAR Capacitor Bank 2
Isolator 160A TP
General Status
Good
Fair
Inspection
Poor
Comments
Ok
OK
OK
Ok
NIL
Ok
NIL
OK
OK
NIL
OK
NIL
NIL
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SDB 5
Location: Office
Feed from
MDB 2
Total Breakers
Details of Breakers
S.N
Breaker
Description
QTY
Isolator
160A TP
1(Incomer)
ELCB
40A 100mA 2P
ELCB
40A 30mA 4P
ELCB
40A 100mA 4P
ELCB
63A 30mA 4P
MCB
32A SP
23
MCB
40A TP
MCB
10A SP
MCB
20A SP
10
MCB
16A SP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
40.3
25.1
B phase
Neutral
29.2
25.1
Feeder
Incomer
Value (Volts)
Status
0.7V
OK
SDB 5
No shrouding cover:
No shrouding cover is fixed on the panel
Recommended to provide proper shrouding cover on the panel
Neutral current is high:
Neutral current is high due to unbalanced load.
Recommended to rearrange the connected load.
Neutral current is high due to unbalanced load, recommended to rearrange the connected
load.
Recommended to close all the unused openings with suitable grommets to maintain the
ingress protection.
Recommended to clean the panel periodically by qualified technicians.
Recommended to provide proper shrouding cover on the panel
Check List
Panel: SDB 5
160A isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
OK
Not available
NIL
NA
OK
Disconnected cables
OK
NIL
OK
NIL
OK
OK
OK
Status of Capacitors
NA
Room Temperature
Good
Dry
SDB 7
Location: Plant
Feed from
MDB-2
Total Breakers
28
Details of Breakers
S.N
Breaker
Description
Qty
MCCB
300A TP 36KA
1(Incomer)
MCCB
40A TP 25KA
MCCB
30A TP 25KA
MCCB
150A TP 25KA
MCCB
80A TP 25KA
ELCB
40A 100mA 4P
ELCB
40A 100mA 2P
MCB
25A TP
MCB
32A SP
10
MCB
20A SP
11
Contactor
40A TP
12
Contactor
20A TP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
178
175.4
177.9
12.04
Feeder
Incomer
Value (Volts)
Status
0.54 V
OK
SDB 7
Check List
Panel: SDB 7
Location: Plant
Incomer
300A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
OK
Ok
OK
OK
Ok
OK
NIL
OK
OK
Disconnected wires
Dust precipitation
NIL
OK
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SMDB 13
Location: Cooler
Feed from
MDB 2
Total Breakers
14
Details of components
S.N
Breaker
Description
QTY
Isolator
350A TP
Incomer
ELCB
100A 100mA 4P
ELCB
40A 100mA 4P
MCB
10A SP
MCB
32A TP
MCB
20A SP
MCB
16A SP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
19.1
1.9
B phase
Neutral
3.2
17.1
Feeder
Incomer
Value (Volts)
Status
0.2V
OK
SMDB 13
Check List
Panel: SMDB 13
Location: Cooler
Incomer
350A Isolator.
General Status
Good
Fair
Inspection
Poor
Comments
OK
Unused openings
NIL
Ok
NIL
NA
NIL
OK
OK
NIL
OK
NIL
Ok
NIL
OK
Ok
Status of Capacitors
NA
Room Temperature
Good
Dry
Granulator
Name Plate: Granulator
MDB-2
Total Breakers
Details of Breakers
S.N
Breaker
Description
Qty
Isolator
200A TP
1(Incomer)
Isolator
63A 4P
MCB
SP 10A
Contactor
LC1D80
Contactor
LC1D25
Contactor
LC1D32
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
25.0
25.3
B phase
Neutral
29.6
3.7
Feeder
Incomer
Value (Volts)
Status
0.051 V
OK
Granulator
Check List
Panel: Granulator
Location: Grinder
Incomer
200A Isolator
General Status
Good
Fair
Poor
Inspection
Comments
Ok
Ok
OK
OK
NIL
NA
Ok
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
OK
Room Temperature
good
Dry
Name Plate:
Location: Grinder
Feed from
MDB-2
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
Isolator
100A TP
Incomer
Check List
Panel: Isolator box grinder 2
Location: Grinder
Incomer
100A TP Isolator
General Status
Good
Fair
Inspection
Poor
Comments
Dust Precipitation
OK
OK
NIL
NA
NIL
Ok
OK
NIL
NIL
NIL
OK
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
MDB-3
Name Plate: MDB-3
Transformer
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
MCCB
400A TP 36KA
Incomer
MCCB
200A TP 36KA
SMDB 6 - Shaklan
MCCB
63A TP 25KA
SMDB 9 - Shaklan
MCCB
160A TP 36KA
Capacitor Bank
MCCB
320A TP 36KA
Automa Machine
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
232.4
177
205
39.7
Feeder
Incomer
Value (Volts)
Status
0.022V
OK
MDB-3
will
degrade
the
degree
protection of Enclosure.
Recommended to use suitable glands.
of
ingress
Check List
Panel: MDB-3
400A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
Ok
OK
OK
NIL
NA
NIL
OK
OK
NIL
Dust precipitation
NIL
NIL
NIL
OK
OK
OK
OK
Room Temperature
good
Dry
MDB 3
Total Breakers
Details of Breakers
S.N
Breaker
Description
Feeder
Isoaltor
315A TP
Incomer
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
B phase
Neutral
Check List
Panel: 75KVAR Capacitor Bank 3
Isolator 315A
General Status
Good
Fair
Inspection
Poor
Comments
OK
Dust Precipitation
OK
OK
NIL
NA
NIL
OK
OK
NIL
NIL
NIL
OK
NIL
OK
OK
OK
OK
Room Temperature
Good
Dry
SDB 6
Name Plate: SDB 6
MDB-3
Total Breakers
35
Details of Breakers
S.N
Breaker
Description
QTY
Isolator
250A TP
ELCB
40A 100mA 4P
ELCB
40A 30mA 4P
ELCB
63A 500mA 4P
ELCB
63A 100mA 4P
MCB
20A TP
MCB
40A TP
MCB
63A TP
MCB
10A SP
10
MCB
20A SP
11
Contactor
40A
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
80.4
70.2
B phase
Neutral
87.4
21.2
Feeder
Incomer
Value (Volts)
Status
0.24V
OK
Value (mA)
Status
Feeder
Incomer
5.01mA
OK
SDB 6
Check List
Panel: SDB 6
250A Isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
OK
OK
NIL
NA
NIL
OK
Dust precipitation
NIL
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SMDB 9
MDB 3
Total Breakers
Details of Breakers
S.N
Breaker
Description
QTY
MCCB
200A TP 36KA
Incomer 1
MCCB
40A TP 25KA
MCCB
60A TP 25KA
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
22.4
23.6
B phase
Neutral
21.1
Feeder
Incomer
Value (Volts)
Status
0.04V
OK
Value (mA)
Status
Feeder
Incomer
0.5mA
OK
SMDB 9
Check List
Panel: SMDB 9
200A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
Ok
Ok
Not available
NIL
NA
NIL
OK
OK
NIL
OK
NIL
OK
NIL
OK
OK
OK
OK
Room Temperature
Good
Dry
MDB-3
Total Breakers
Details of Breakers
S.N
Components
Description
Qty
MCCB
250A TP 40kA
Incomer
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
128
114
130
14.5
Check List
Panel: Automa Control Panel
250A MCCB.
General Status
Good
Fair
Poor
Inspection
Comments
Ok
Dust preciptation
No trunking cover
OK
Ok
NA
Ok
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
OK
OK
Room Temperature
Good
Dry
MDB 4
Name Plate: MDB 4
Transformer
Total Breakers
Details of Components
S.N
Components
Description
Feeder
MCCB
400A TP 36kA
Incomer
MCCB
250A TP 36KA
SMDB 8
MCCB
100A TP 25KA
SMDB 12
MCCB
160A TP 36KA
SMDB 10
MCCB
125A TP 36KA
Capacitor Bank
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
254
250
B phase
Neutral
249
14.4
Feeder
Incomer
Value (Volts)
Status
0.067 V
OK
Value (Ohms)
Status
0.018
OK
Feeder
Incomer ECC
MDB-4
Check List
Panel: MDB-4
400A MCCB.
General Status
Good
Fair
Inspection
Poor
Comments
OK
OK
OK
NA
OK
NIL
OK
OK
NIL
Dust precipitation
NIL
OK
NIL
OK
OK
Ok
OK
Room Temperature
Hot
Dry
MDB 4
Total Breakers
Details of Breakers
S.N
Components
Description
Feeder
Isolator
200A TP
Incomer
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
B phase
Neutral
Feeder
Incomer
Value (Volts)
Status
0.04V
OK
Louver is removed:
Louver of the panel is in removed condition.
Recommended to replace it with new for proper
ventilation
Check List
Panel: 60 KVAR Capacitor Bank 4
200A Isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
Ok
OK
OK
NA
NIL
OK
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
OK
OK
Room Temperature
Hot
Dry
SMDB-12
Name Plate: SMDB-12
MDB-4
Total Breakers
11
Details of Breakers
S.N
Components
Description
Qty
Isolator
125A TP
MCCB
125A TP 25KA
ELCB
40A 100mA 4P
ELCB
100A 100mA 4P
MCB
40A TP
MCB
20A SP
MCB
10A SP
MCB
25A SP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
43.9
30.1
B phase
Neutral
33.5
10.4
Feeder
Incomer
Value (Volts)
Status
0.27V
OK
SMDB-12
Check List
Panel: SMDB-12
125A Isolator
General Status
Good
Fair
Inspection
Poor
Comments
OK
Ok
OK
OK
OK
NA
NIL
OK
OK
NIL
NIL
OK
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SMDB 10
MDB 4
Total Breakers
Details of Breakers
S.N
Breaker
Description
Qty
MCCB
400A TP 36KA
(1 Nos)Incomer
MCCB
100A TP 25KA
MCCB
200A TP 36KA
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
R phase
Incomer
Y phase
B phase
Neutral
Feeder
Incomer
Value (Volts)
Status
0.067V
OK
Value (mA)
Status
Feeder
Incomer
0.16mA
OK
SMDB 10
Check List
Inspection Date: 14/04/2016
Panel: SMDB 10
Location: PME Room
Incomer
400A MCCB
General Status
Good
Fair
Inspection
Poor
Comments
OK
OK
OK
NA
NIL
NA
NIL
OK
OK
NIL
NIL
NIL
Ok
NIL
OK
OK
Ok
OK
Room Temperature
Good
Dry
SDB 8
Name Plate: SDB 8
Location: Plant
Feed from
MDB 4
Total Breakers
Details of Breakers
S.N
Breaker
Description
Quantity
MCCB
400A TP 50KA
1 Nos
MCCB
160A TP 36KA
MCCB
100A TP 25KA
MCCB
30A TP 25KA
MCCB
160A TP 36KA
MCCB
63A TP 25KA
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
214
221
B phase
Neutral
218
7.3
Feeder
Incomer
Value (Volts)
Status
0.8V
OK
SDB 8
Check List
Panel: SDB 8
Location: Plant
Incomer
400A MCCB
General Status
Good
Fair
Poor
Inspection
Comments
Ok
OK
NA
NIL
NA
NIL
OK
OK
NIL
OK
NIL
NIL
NIL
OK
Ok
Ok
OK
Room Temperature
Good
Dry
Location: Plant
Feed from
SDB 8
Total Breakers
Details of Breakers
S.N
Breaker
Description
QTY
Isolator
100A TP
1 Nos
MCCB
800A TP
Tests
Load Current Measured on the incoming feeders (Ampere)
SN
1
Feeder
Incomer
R phase
Y phase
B phase
Neutral
73.2
70.5
83.7
2.84
Feeder
Incomer
Value (Volts)
Status
0.77 V
OK
Value (mA)
Status
Feeder
Incomer
15.1 mA
OK
Check List
Panel: NPAS Control Panel
Location: Plant
Incomer
Isolator 100A
General Status
Good
Fair
Inspection
Poor
Comments
Ok
Ok
OK
NA
NIL
NA
NIL
OK
Ok
NIL
OK
NIL
NIL
NIL
OK
OK
OK
OK
Room Temperature
Good
Dry