Академический Документы
Профессиональный Документы
Культура Документы
P/N 300-005-849
REV A04
Environmental requirements:
- Temperature
- Humidity
- Altitude
- Physical space
- AC power
Package dimensions and clearance requirements
Environmental Requirements
+15o C to +32o C (59o F to 89.6o F) site temperature*
Environmental Requirements
You must provide adequate clearance for the installation process and to
service and cool your system.
When fully extended, a drawer will sit 25 in. (.625 m) outside of the cabinet.
You must provide adequate clearance beyond this 25 in. to provide room for
servicing your system; some component upgrade/replacements may require 42
in. (1.1 m) to accommodate a standard mechanical lift.
Once configured, the 44U cabinet dimensions will be: 82.44 in. H (2.1 m) x
43.3 in. D (1.1 m) x 24.0 in. W (.61 m).
Width
24.0 in.
Depth
43.3 in.
Height
82.44 in.
25.0 in.
CL4439
Environmental Requirements
The weight of the system must be split over four floor tiles. The front two tiles
will each hold approximately 673 pounds (305.3 kg). The rear two tiles will
each hold approximately 508 pounds (230.4 kg).
CL3784
If you intend to secure stabilizer brackets to your site floor, prepare the
location for the mounting bolts.
0.63 in.
0.47 in.
1.13 in.
16.92 in.
8.46 in.
23.25 in.
Rear
44.16 in.
46.16 in.
CL3992
Power Requirements
The cabinet requires receptacles that will match one of the receptacles shown
below.
Power
cord
connector
Operating
voltage/
frequency
Service type
Site
200-240 V AC
50/60 Hz
North America,
Japan
200-240 V AC
50/60 Hz
International
240 V AC
50/60 Hz
Australia
NEMA L6-30P
IEC-309332P6
56PA332
Right Angle
Each AC circuit in the 44U cabinet requires three source connections that can
support a minimum of 4800 VA of single phase, 200-240 V AC input power.
Highly available performance configurations require a second discreet power
circuit with another three connections to the cabinet.
All source power feeds are routed through the cabinet bottom.
Contact your EMC representative if you are uncertain about your systems
power requirements.
90 in.
(2.3 m)
52 in.
(1.3 m)
42 in.
(1.1 m)
CL3793
96 in.
(2.43 m)
EMC2840
The 44U Dense Storage Cabinet Unpacking and Setup Guide (which is
attached to the outside of the unit) provides instructions for: