When the supply voltage falls below 85% of the rated value, the PLC stops and
the output goes OFF.
When a momentary power failure is detected, the CPU stops operating and the
output goes OFF.
Automatic Restart
When the supply voltage recovers to a value higher than 85% of the rated
value, operations resumes automatically.
Unde
r Over
Duration of power 10 ms (2 ms)
interrupt
(Below 85% of rated
voltage)
Operatio
Normal
n
operatio
may
n
stop
All outputs go OFF
when
Operations stop.
Note The PLC may repeat stop/start operations if the supply voltage of less than 85%
of the rated value gradually goes up or down.
If this affects the equipment, etc., provide a protection circuit which shuts off
the output if the supply voltage is not above the rated value.
The time from when the power supply is turned on to when the operation starts
varies depending on the operation conditions such as power supply voltage,
configuration, ambient temperature, etc. The minimum time is approximately
300 ms.
8-1
8. INSTALLATION AND WIRING CONSIDERATIONS
Panel/Cabinet Installation
Consider PLC operation, maintenance, and surrounding conditions when
installing the PLC in a panel or cabinet.
Overheating
The operation temperature range for the PLC is 0°C to 55°C. Be sure that there
is adequate ventilation for cooling.
Control
Panel Fa
n
CPM
1
Air
Vent
Electrical Noise
Power lines and high-voltage equipment can cause electrical noise in the PLC.
• Do not install the PLC in a panel or cabinet with high-voltage equipment.
• Allow at least 200 mm between the PLC and nearby power lines.
200 mm
min.
CPM*A
200 mm
min.
8-2
8. INSTALLATION AND WIRING CONSIDERATIONS
Handing Ducts
Leave at least 300 mm between the power cables and the I/O or control wiring,
as shown in the following diagram.
300 mm min
Control cables
and
CPM*A power
lines
300 mm min
Power
cables
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in
the following diagram. Control cables
and
CPM*A I/O Cpm*A power Mental plate
lines Power cables
lines (iron)
200 mm
min
Conduit
Separate the CPM*A I/O lines, power and control lines, and power cables, as
shown in the following diagram.
8-3
8. INSTALLATION AND WIRING CONSIDERATIONS
Grounding
Be sure to ground the functional earth and protective earth terminals together
to less than 100Ω in order to protect against electric shock and incorrect
operation from electrical noise. Be sure to sue a wire of at least 2 mm2 for
grounding.
Ground to 100Ω
max.
Crimp Connectors
Always use crimp connectors for the CPM*A’s power lines and I/O lines or else
use a single-wire line (instead of a stranded wire). Stray wire strands could
accidentally short out.
Use M3 terminal screws and tighten the screws securely (0.5 to 0.6 N-m).
Wire a separate circuit for the CPM*A’s power supply circuit so that there isn’t a
voltage drop from the inrush current that flows when other equipment is turned
on.
When several CPM*A PLCs are being used, it is recommended to wire the PCs
on separate circuits to prevent a voltage drop from the inrush current or
incorrect operation of the circuit breaker.
Use twisted power supply wires to prevent noise from the power supply lines.
Adding a 1:1 isolating transformer reduces electrical noise even further.
Isolation
AC transfor
powe mer
Twist the wires. The cross-sectional area
r of each wire must be 2 mm2 min.
suppl
y Breaker
8-4
8. INSTALLATION AND WIRING CONSIDERATIONS
8-5
8. INSTALLATION AND WIRING CONSIDERATIONS
varistor. There is time lag
between the moment the
load is reset.
If the supply voltage is 24
or 48V, insert the varistor
in parallel with the load. If
the supply voltage is 100
to 200V, insert the varistor
between the contacts.
When switching a load with a high inrush current such as an incandescent lamp
suppress the inrush current as shown below.
Countermeasure Countermeasure
1 2
R
OUT L OUT L
+ +
R
COM COM
8-6