Installation & programming instructions

Compact wireless control panel with built-in digital communicator

EKZ004400f

DOMONIAL
800++ Range

(Issue October 2002)


Product meets the requirements of CEM provisions on electrical safety and compatibility.
Product meets the requirements of R&TTE specifications

EKZ004400F

CONTENTS
1/

2/

3/

4/

5/

6/

7/
8/

9/

INTRODUCTION

INSTALLATION

PROGRAMMING

SYSTEM

TESTING

DIAGNOSTICS

OPERATION

TECHNICAL

APPENDICES

SPECIFICATIONS

CONFORMITY

1-1/

General

1-2/

Control panel

1-3/

Communication function

2-1/

Preliminary precautions

2-2/

Securing the control panel

2-3/

LED indicator lights

3-1/

Introduction to programming keypad TB550

10

3-2/

Registering wireless peripherals

11

3-3/

Deleting wireless peripherals

12

3-4/

Altering wireless peripherals

12

3-5/

Adjusting the built-in siren

12

3-6/

Programming radio receivers

13

3-7/

List of the output functions

14

3-8/

Programming the control panel

15

3-9/

Programming the digital communicator

15

3-10/

Programming installer code, date and time

18

3-11/

Beep adjustment

19

3-12/

Descriptive list of audible signals

19

4-1/

Radio tests

20

4-2/

Sounder tests

20

4-3/

Wireless receiver tests

20

4-4/

GSM level indicator

21

4-5/

Event log look-up

21

4-6/

Changing the language

21

5-1/

Wireless peripherals

21

5-2/

Battery and mains

22

5-3/

Transmission intended stop

22

5-4/

Transparent mode manual test

22

6-1/

Transmission to a DTMF telephone set

23

6-2/

Using the optional wireless keypad

23

6-3/

DTMF remote controls

24

7-1/

Knowledge of the various protocols

25

7-2/

List of associated wireless peripherals

26

8-1/

Functional

27

8-2/

Physical

27

8-3/

Electrical

27

8-4/

Radio

27
27

DECLARATION

Domonial 800++ Installation Manual - 10/2002

www.secom.tm.fr

EKZ004400F

1 - INTRODUCTION
1-1 General
The CRT800++ (or PCT800++) is a wireless control panel with a built in siren and digital communicator.
The CRI800++ (or PCI800++) is a wireless control panel with a built in siren, digital communicator and audio verification.
The radio link between the various components of the system facilitates easy installation without the need for most cabling.
Arming and disarming can be controlled by both wireless keypads and wireless keyfobs from the SCURIT COMMUNICATIONS 800
range.
Programming of the control panel and digital communicator can be carried out locally via the TB550 terminal or a PC running Windows 95 or
98. Programming is also possible via the PSTN network and a Domocom (1) modem.
A 500-event log file can be browsed through using the TB550 or a PC.
The CRT/CRI800++ has an built in mains supply and a 4V 3.5A/h back-up battery (included).
System setting are saved in the case of total power loss (mains and battery).

Mimic diagram

DETECTION

ANALYSIS

SIGNALLING
Wireless receivers.

Maximum :
4*

.
.
.

Wireless peripherals from the


800 Secom range (keypads,
keyfobs, PIR detectors,
door/window contacts,
technical detectors)

Maximum :
20 detectors
2 keypads
4 keyfobs (4 buttons)
+ 1 response keyfob
2 LCD keypad

Wireless siren from the


Secom 800 range

Maximum :
4* sirens (internal or
external).

Control panel
800++

Local audio verification


(CRI/PCI800++ only)

Built in siren

DTMF remote control

Telephone transmission by
PSTN Network or
GSM Network (optional)

(*) :Up to 4 devices of


these type

Special model of modem used for Domonial Range

Domonial 800++ Installation Manual - 10/2002

www.secom.tm.fr

EKZ004400F

1-2 Control panel


The control panel, depending of the programming, covers:
-

1 Total "zone" (or Main)

1 Part "zone"

1 Annex or Perimeter "zone"

P
A

Arming / Disarming
The surveillance of the zones can be controlled as follows :
Zones
Total ARMING
Partial ARMING
Annex ZONE ARMING
Total DISARMING
Annex zone DISARMING

Keypad

Keyfob

Y
Y
Y
Y
Y

Y
Y
Y
Y
Y

Remote DTMF
Code by phone
Y(1)
Y(1)
Y(1)
N
N

By DOMOSTATION software
Y(1)
Y(1)
Y(1)
Y(1)
Y(1)

Users :
The control panel allows up to 10 users (including master) ; The keyfobs/keypads and the codes (except CLI800HF) are assigned
by the user :
Functions \ Users
Master
1
2
3
4
5
6
7
8
9
Allocate user TCX04HF / TC805HF
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Allocate code on keypad CLBX00HF
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Supervised user
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
The users name is stored in the event log and actions of the supervised user are reported to the monitoring station by a code.

Alarm detection: The triggering of wireless detectors and of certain internal inputs (refer to records table on 3.14) can be subordinated
to the arming status.

The detectors can be programmed :


with a entry/exit delay programmable from 0 to 90 seconds (for total, part or annex zone).
hybrid (delay or instant trigger depending on which input is activated first) = Mixed.
direct trigger (Total, partial, annex or 24/24)

Each zone can be armed from a remote multifrequency telephone set(1) (via PSTN or GSM(2)
network).
Several sounder operating modes are available:
standard sounder.
sounder activated upon intrusion or loss of PSTN line.
Sounding duration can be programmed from 0 to 240 seconds.
Activation of the sounder can also be postponed until after the alarm signal has been transmitted.

(1)
(2)

These functions can be disabled, depending on the country rules.


Only when using the optional GSM unit

Domonial 800++ Installation Manual - 10/2002

www.secom.tm.fr

EKZ004400F

1-3 Transmitter function


The Domonial 800++ control panel includes a digital communicator designed to send information, via the PSTN or GSM (optional) network to:
an Alarm Receiving Center using the following formats: Secom3, Surtec, Cesa, Stratel, Contact ID (3).
a telephone set.
The Domonial 800++ control panel can receive and integrate a full set of parameters from a remote position via the PSTN network. Specific
software and a Domocom modem are necessary (depending of country rules).

Digital Alarm Receiver


(at monitoring station)

CRI / PCI model only

Alarm
Receiving
Center
(ARC)

GSM
network

Optional GSM unit

PSTN
network

DOMONIAL800++

Tone dialling
telephone set

Remote maintenance
station

Six call numbers (designated: A, B, C, D, E, F) each containing a maximum of 17 digits can be programmed (* for pause).
The call sequences are as follows:

Mode

The Domonial 800++ makes 15 attempts dialling A tel. N (2 times) then B tel. N (2 times) then C tel. N (2 times) then E etc
Telephone number D is used only for connection to an automated maintenance host.
The telephone number D must not be an alarm receiver telephone number.
The telephone numbers E and F are used for transmission by GSM network
A dialling prefix (within the maximum of 17 digits ) can be programmed when a telephone exchange or a telephone card is used
The call sequence can be modified by programming the Domonial 800++ via the PC software.

LINE
PROTECT.

DTMF
TELECOM.

Listen.

6 CALL NUMBERS

AABBCCEEFFABCEF (4)

The PCI or CRI800++ model includes a audio verification system.

It is possible to activate automation functions and surveillance arming (as it is programmed) via of a DTMF telephone set.

The telephone line interface has built-in voltage surge protection and phone line failure detection.

(3) For others formats : please, consult us.


(4) Depending on software versions
Domonial 800++ Installation Manual - 10/2002

www.secom.tm.fr

EKZ004400F

2 INSTALLION

2-1 Preliminary precautions

Warning : Any work inside the CRT/CRI800++ control panel


enclosure must be carried out by qualified personnel :

ELECTRIC SHOCK HAZARD

The circuit board uses advanced technology CMOS circuits, as with any other electronic devices, these circuits are sensitive to
electrostatic shocks.

Before touching the board or its circuits, discharge the electrostatic current by touching the
earthed box base.
Characteristics of a radio transmission
Like light, radio waves are propagated in a straight line. They can be
attenuated when sent through certain materials (wood, Artex, brick,
concrete, steel reinforcements) and even reflected by metal surfaces
(mirror, steel sheeting, aluminium steam-arrestor, fine-mesh wirenetting).

Low attenuation

Medium attenuation

It is therefore obvious that the quality and range of radio links


between the various components largely depends on the existing
environmental characteristics (nature and thickness of the
neighbouring materials).
In the open (without any obstructions) the radio transmitter range is
more than 150 m. Indoors, the range is reduced (by 30 to 50% as an
average) by the various obstructions.
The four diagrams (opposite) show radio wave behaviour as a function
of the interfering material:

Checks before installation


The above paragraph demonstrates that radio wave behaviour is not
necessarily identical in every premise therefore, before securing the
various components of the system, the following tests should be
made :
test the radio link by positioning each peripheral unit and the
control panel in their anticipated final locations (use the "radio
recept." caption in the main menu). It is not necessary to record the
peripheral at this stage.
using the field meter, check the received radio signal strength for
each peripheral. For a reliable radio communication a minimum level of
2 boxes is recommended.
If such a signal strength cannot be obtained, move the device a few
inches or slightly move the control panel.

Domonial 800++ Installation Manual - 10/2002

Built-in field meter


To help you find the best position for the system
components, the Domonial 800++ control panel has a
radio field meter of the RSSI type. This enables you
to check the strength of the received radio signal.
Scaled from 1 to 10, this information is delivered
during the test and record phases. Therefore, to
make the best use of this function, it must be carried
out when the transmitter is in its final location.

www.secom.tm.fr

EKZ004400F

2-2 Securing the control panel CRT/CRI800++ and connections


The control panel has 4 securing points.
The base can be used as a template for holes marking.
Detach the various cut outs before securing the panel and use to plug holes as
required.

Pre-cut caps for :


- cover wires passage (under the battery)
- programming connector (under the
sounder)

Do not use the base as a drilling template.


Wire passage

Built-in
Speaker

*
PNV : Phone Network Voltage
SELV : Security Elecrtical Low Voltage

Velcro straps
for securing
battery
MAINS + EARTH
connection (1.5mm2 minimum)
Warning
230V~

Connection to Client's
phone line

PNV(*)

SELV(*)

4 pin
Stocko
connector

4 holes for 3.5


screws

Tamper

Programming
tool connector

Mains: (Terminal block J1)


The control panel is supplied from the mains, 230V with earth. A built-in transformer ensures supply to the control panel and for
battery charging. The mains is protected by a fuse integrated into the circuit board. This protects the electrical system and it is
not removable.
A fused switch /spur (depending on country) must be used for connecting the CRT/CRI800++ to the mains.

230V~
230V~

Warning : This Class I system


must be earthed

Transformer

J1

Telephone line (Terminal block: J2)


Connect the telephone line using the "Stocko" connector (included). Terminals "L1, L2" and "P1, P2" are marked and correspond to
telephone line input and return to set respectively. (If youre using an ADSL line, please visit our web site for information)

The control panel must be connected so as to override any other call.


Transmitter
Line
(L1, L2)

Terminal block:
Return to Phone
(P1, P2)

Incoming
PSTN line

Domonial 800++ Installation Manual - 10/2002

Telephone set
connection

www.secom.tm.fr

EKZ004400F

Serial port (J3)


A serial port is available to connect the programming tool or a personal computer (with optional cord) via an RJ45 connector.
Cable reference : CAB550PC (or CAB550PALM for the connection with a PDA computer). The serial cable/PDA is not included

Battery connection: (Red wire + and Black wire - with lugs)


The power supply must be backed up by a 4V-3.5Ah battery (included) to maintain system operation in case of mains failure.
Once the battery has been connected the system will not be initialised until mains connection.

o Do not leave the battery connected to the control panel without the mains being connected
(e.g. storage before installation). In this case power used would be 1mA. System parameter back up by
EEPROM requires no power supply.
2-3 LED indicator lights
5 LED indicators show the control panel & transmitter status.

State / Indicator
Off

Mains Power

Arm/Disarm

Perimeter fault

Alarm memory

Technical alarm

No mains power

No zone armed

No fault

No alarm

No technical alarm

Slow Flashing
(2s-2s)

Cover tamper opened

Annex or partial zone


armed

One or more
perimeter detectors
are open

Alarm memory in
annex or partial zone

One or more
technical or system
alarm in memory

Quick Flashing
(1/4s-1/2s)

Cover tamper
opened and
transmission
in course

Alarm memory in
total zone

One or more
technical detector
alarms in progress

On steady

Mains Power On

Domonial 800++ Installation Manual - 10/2002

Total zone armed

www.secom.tm.fr

EKZ004400F

3 - PROGRAMMING
3-1 Introduction to programming terminal TB550
The terminal TB500 is only to be used for programming. It must not be left connected when not being used for this purpose. To
enter the programming mode, once the control panel has been connected to the mains and the Total and Part zones have been
disarmed:
open the control panel cover (tamper protection contact open)
connect the terminal cord to socket RJ45 on the control panel board (connector J3).
-

the home page is displayed after a few


seconds and you are required to enter
the control panel password.

When programming has been completed


carefully go through the sequence described
opposite so as to confirm and save
the programmed parameters

Keys activating a
function displayed
on the screen
(soft keys)

Tab key :
To change to
next entry
zone
To change
entry values

Alphanumeric
keys to enter
values (and *
key for pause
during
dialling)

o
o

6&6(&20

VHFXULWH
FRPPXQLFDWLRQV !

'2<28:$1772(;,7
7+(352*5$0"

6$9 (;,7(;,7 !

Wait

&5;1b
9(56,219[[[
&RGH
5(6(7',$* !

 
$&7,21
,1352&(66
 

(1'2)&211(&7,21
6$9,1*'21(
'2127)25*(7
7+(',$*1267,&

Wait


7%

SCURIT

COMMUNICATIONS

Control panel
serial number

&5;1b
9HUVLRQ9[[[
&RGH
5(6(7',$* !

Software
version
PROG

QUIT

&

To change to next
screen or function

>

<

Screen
brightness

111

33

55

66

Back to the previous


screen (or quit for
current screen)

TB550 connection

RJ11/RJ11 cable

Warning :

TB550 does not check the consistency of the programmed parameters.


The Technician must check the suitable operation of the system before leaving.
During programming with the terminal, the control panel cannot transmit.

Domonial 800++ Installation Manual - 10/2002

www.secom.tm.fr

EKZ004400F

3-2 Recording wireless peripherals


Each peripheral unit of control panel CRx800++ has a specific built-in code. Recording the device consists of having its code
recognised and logged by the control panel. The control panel emits a beep to confirm recording.
Get access to the recording menu as follows:

Shortcuts for direct access to menus from home page

&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

then e1

352*5$00,1*
!(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

e1

5HFRUGLQJ
Trigger the tamper contact on the peripheral
device being recorded (or the Alert key for
CLI800/CLB800 keypad or TC804 remote
control box or "init" button for sounders or
DFO)
Enter the designation applicable to this
peripheral device as well as its operating mode

For detectors :

352*(48,30(176
!5$',2(48,30(17
%8,/7,16,5(1
5$',25(&(,9(5


 !

e1

(48,30(173523(57,(6
gggggggg00
'HWHFWRU')(
 !

e =>
3(48,5$'5(&'(7
%$6(0(17,00('
$/$50727$/
 !

e =>

For keyfobs :

3(48,5$'5(&7(/
/$%%$%<6,77(5
)21&!212))3$
'(/(7(3/86

86(57(/
/$%%$%<6,77(5
86(586(5
1(;786(5 !

352*(48,35$',2
!5(&25',1*
;02',),&$7,21
;'(/(7(


 !

e =>

(48,30(175(&25',1*
!!!5(&(37,21!!!
!!!5$',2!!!


 !

e1

Received radio signal strength, peripheral device type


(detector, remote control box, sounder or keypad) as
well as its serial n are then displayed.

Press => key to go on.

p The minimum recording level for a suitable


operation must be more than 2 boxes out of 10

Use the alphanumeric keys to enter the designation, >


for next character (12 maximum).
A list of predefined designations is made available by
pressing * key, then *,*,*
Choose triggering mode:
Immediate , Delay or Mixt (access path).
Alarm , Technical, Perimeter, Counter, Prealarm
Total , Part, Annex or24/24h,

Press => key to go on.

Use the alphanumeric keys to enter the designation, >


for next letter (12 maximum). A list of predefined
designations is made available by pressing * key, then
*,*,*
Choose triggering mode:
Arm/Disarm Total, Arm Part, Alert 1 (mute) or
Arm/Disarm Total, Arm Part, Alert 3 (audible) or
Arm/Disarm Total, Arm/Disarm Annex or.
Arm/Disarm with receiver remote functions.

Press PLUS

(software >B version only).


Choose the keyfob user by pressing next user key

Press PLUS

(software >B version only).


Choose the receiver to be associated with the kf

Press => key to go on

e =>

Use the alphanumeric keys to enter the designation, >


for next letter (12 maximum).
A list of predefined designations is made available by
pressing * key, then *,*,*
Choose triggering mode:
Arm/Disarm Total or Arm/Disarm Annex (for CLI)
Alert key inactive , Alert 1,2,3 or Chime

3(48,5$'5(&6,5
/,%&25,'25
7<3(,1'225
1(;7'(/(7(025(

Use the alphanumeric keys to enter the designation, >


for next letter (12 maximum)

For keypads :
3(48,5$'5(&.(<
/$%(175$1&(
!727$/$/(57
 !

For sounders :

3(48,5$'5(&6,5
/,%&25,'25
/(9(/gggg00
7(67 !

3(48,5$'5(&6,5
/,%&25,'25
%((36gggg00
7(67 !

e =>

Press => key to go on

Type, MORE key can be used to select sound


strength (7 levels + one gradual ) and remote acknowledgement (beeps): select using "<, >" keys

Press => key to go on

p A beep from the built-in sounder confirms recording. Highlighted text = default values
Domonial 800++ Installation Manual - 10/2002

10

www.secom.tm.fr

EKZ004400F
The detector operating modes are:
24/24 : of the 24/24 type (not depending of Arming status)
Delay: inhibited when the surveillance is not armed and:
upon Exit, it becomes active only after the Arming delay has elapsed,
upon Entry, it triggers the entry delay at the end of which the alarm is activated if the system has not been disarmed.
Mixt: inhibited when the surveillance is being disarmed; delayed (access path) if it is triggered after a delay entry and instant if it
is triggered beforehand. Delay entry for the Part zone.
Counting: makes it possible to trigger the alarm or the transmission only after the second activation of the detector concerned
within a period of 3 minutes.

3-3 Deleting wireless peripherals


Any wireless peripheral of the control panel CRx800++ can be deleted from the system. This function is accessible only if at least
one wireless peripheral is recorded.

p Remote keyfob stolen or lost:

Follow the procedure described below selecting the relevant remote control box. Access to "delete" menu is as follows:

&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

352*5$00,1*
!(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

then e1

352*(48,30(176
!5$',2(48,30(17
%8,/7,16,5(1
5$',25(&(,9(5


 !

e1

'(/(7(
Pressing keys " w " and " 8 " selects the type
of peripheral.
Press "NEXT" to select the next peripheral .

e1

3(48,35$',2'(/(7(
',$7<3('(7(&7
/$%%$6(0(17
1(;7'(/(7( !

e DEL

352*(48,35$',2
5(&25',1*
02',),&$7,21
!'(/(7(


 !

e3

In confirmation, the display reads :


" PERIPHERAL DELETED"

Press => key to go on

3-4 Altering wireless peripherals


The operating mode of control panel CRx800++ wireless peripherals can be altered. This function is accessible only if at least one
wireless peripheral is recorded. Access to "MODIFICATION" menu is as follows:
&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

352*5$00,1*
!(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

then e1

352*(48,30(176
!5$',2(48,30(17
%8,/7,16,5(1
5$',25(&(,9(5


 !

e1

02',),&$7,21
The display gives access to peripheral device
designation and operating mode alteration.
Press "NEXT" to select the next peripheral

e1

3(48,5$'02''(7
%$6(0(17,00('
$/$50727$/
1(;7'(/(7( !

e =>

352*(48,35$',2
5(&25',1*
!02',),&$7,21
'(/(7(


 !

e2

3(48,35$',202',)
!'(7(&725
.(<)2%
.(<3$'
6,5(1

 !

e1,2,3 ou 4

Using the "


" key to move within the display
and alter the values as required

Press => key to go on

3-5 Adjusting the built-in sounder


The built-in sounder has 7 levels of sound strength, used as an alarm deterrent and for confirmation beeps. The sounder can also
be programmed to gradually increase in strength via the sounder mode.
&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

352*5$00,1*
!(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

then e1

6,5(1/(9(/
The display gives access to sound level
adjustment for the control panel sounder (alarm
and beeps).
Select the beep adjustment via key "NEXT"
Domonial 800++ Installation Manual - 10/2002

352*(48,30(176
5$',2(48,30(17
!%8,/7,16,5(1
5$',25(&(,9(5


 !

e1

e2

3(48,%8,/7,16,5

/(9(/gggg00
7(67 !

Change to the desired values by moving through the


display using keys "<" and ">

3(48,%8,/7,16,5

%((3gggg00
7(67 !

Press => key to go on

11

www.secom.tm.fr

EKZ004400F

3-6 Programming the radio receiver


The control panel can manage 4 radio receiver controllers. There is 2 different type :
RS800HF : remote mains plug in DIN format including 1 output
WR800HF : wireless module with 1 output (relay) and 2 inputs (detection and tamper). This module has to be powered by an
external 12V source.
Access the recording menu as follows:
&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

352*5$00,1*
!(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

then e1

5HFRUGLQJ
Trigger the tamper contact on the
WR800HF or the button on the
RS800HF

352*(48,30(176
!5$',2(48,30(17
%8,/7,16,5(1
5$',25(&(,9(5


 !

e1

e1

(48,30(173523(57,(6
gggggggg00
5;')(
 !

e =>

352*(48,35$',2
!5(&25',1*
;02',),&$7,21
;'(/(7(


 !

(48,30(175(&25',1*
!!!5(&(37,21!!!
!!!5$',2!!!


 !

e1

Received radio signal strength, peripheral device type


(detector, remote control box, sounder or keypad) as well as
its serial n are then displayed.

Press => key to go on.

p The minimum recording level for a suitable operation must


be more than 2 boxes out of 10

33(5,35$'(155;
/$%)/$6+(;7
!$872)/$6+
)81&025(

e MORE
33(5,5$'3$5$05;
)81&'(/$<('6
'85$67<3(12
 !

Use the alphanumeric keys to enter the designation, > for


next character (12 maximum).
A list of predefined designations is available by
pressing * key, then *,*,*
Choose the different mode :
Auto (driven by a control panel function) or Pilot (driven by
a peripheral) see 3.11 for the functions definition
Choose the trigger method by touching FUNCTION

Press Plus key to go on

Select :
the value of the output delay (in seconds, 240s max)
the value of the output duration (in seconds, 240s max)
the mode Normally Open or Normally Close of the output

e =>

Press Quit key to go on

Configuration of the wired


input for the WR800HF

5(&25',1*2)
(;7(51$/6(1625
5$',25(&(,9(5
 !

e =>

The input has to be programmed as 3.2

Press Quit key to go on

(48,30(173523(57,(6
gggggggg00
5;')(
 !

e =>

3(48,5$'5(&'(7
%$6(0(17,00('
$/$50727$/
 !

e Quit

Domonial 800++ Installation Manual - 10/2002

12

www.secom.tm.fr

EKZ004400F

3-7 List of the output functions


PILOT Output*
BISTABLE
MONO TRIGGER

Time t

I
O

MONOSTABLE

Mode

I
O

1 to 240s
+ ...

1 to 240s

O
MONO DTMF
TELERUPTOR

1 to 240s
-

Output action
Follows the status of the associated peripheral.
Follows the status of the associated peripheral for a maximum of
the programmed time. Re triggerabled

Follows the status of the associated peripheral for a maximum of


the programmed time. Not Re triggerabled
Follows the status of the associated peripheral for a maximum of
the programmed time, but only within 10mins following an alarm.
The first action activate the output. The following action will
deactivate it.

AUTO Output

Mode

FOLLOW DIALER
PCI CRI panels only

EAVESDROPPING
SIREN

Time t
1 to 240s
t = t1+t2

SIREN PSTN
PART STATUS
TOTAL STATUS

Input
Siren
1 Off
0
1 Off

t
On

1 to 240s
-

1 Off
0

Activated during the eavesdropping (listening or talking) phase


For Siren mode. This ouput will be restored during the
eavesdropping phase
Siren triggered only after an alarm and in case of
PSTN line failure
Reports the Partial zone status.
(NO to activate the output during the armed time)

On

Reports the Main zone status.


(NO to activate the output during the armed time)

On

Reports the Annex zone status.


(NO to activate the output during the armed time)

0
ANNEX STATUS

Activated during the transmitter hang up

ALARM MEMORY

Follows the control panel LED status for the alarm memory.

FLASHLIGHT

It operates similar to the siren mode except for :


- 0 value : in this case, the output will be restored when the
system is disarmed.
- This output will not be deactivated during the eavesdropping
phase

0 to 240s

You can only switch Pilot mode outputs with DTMF remote controls.

Domonial 800++ Installation Manual - 10/2002

13

www.secom.tm.fr

EKZ004400F

3-8 Programming the alarm control panel


Access to the control panel programming menu is as follows:
&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

then e1

352*5$00,1*
(48,30(176
!&21752/3$1(/
75$160,77(5
6<67(0
2873876
 !

e2

727$/(175<'(/$<
Total zone Entry and Exit delays

352*&21752/3$1(/
!727$/'(/$<
$11(;'(/$<
237,216


 !

e1
33$1(/727$/'(/$<
(QWU\GHOD\6
([LWGHOD\6
 !

e =>

$11(;(175<'(/$<
Annex zone Entry and Exit delays

33$1(/$11(;'(/$<
(QWU\GHOD\6
([LWGHOD\6
 !

e =>
$11(;/,1.
Arming surveillance of the total zone also arms
surveillance of the Annex zone. Disarming of
each zone is independent.

'(/$<('(;,7
All the intrusion detectors in the relevant
zone correspond to an exit delay.
They
will
become active only when zone surveillance has
been armed and the exit delay has expired.

$50,1*&21',7,21
Arming is impossible if a perimeter security
wireless device shows a fault.

(;7(51$/7$03(5
Running External Tamper on optional board
(future function).

33$1(/237/,1.
$QQH[7RWDO/LQN
!12
 !

e =>
33$1(/237(;'(/$<
([LWDOZD\VGHOD\
!12
 !

Enter TOTAL zone Entry and Exit delays

Press => key to go on


Enter ANNEX zone Entry & Exit delays

Press => key to go on


Enter value YES or NO

Press => key to go on


Enter value YES or NO

Press => key to go on

e =>
33$1(/237$50('
/RFNHGRQ)DXOW
!12
 !

e =>
33$1(/2377$03(5
([WHUQDOWDPSHU
!12
 !

Enter value YES or NO

Press => key to go on


Enter value YES or NO

Press => key to go on

e =>

3-9 Programming the transmitter


The built-in telephone transmitter (communicator) makes it possible to send protocol-coded information to an Alarm Receiving
Center (ARC) describing the status of the alarm system.
Access to the control panel programming menu is as follows:
&5[1b
&57;9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

then e1

352*5$00,1*
(48,30(176
&21752/3$1(/
!75$160,77(5
6<67(0
2873876
 !

e3

352*75$160,77(5
!5(027($&&(66
75$160,66,21
&/,(17180%(5
3+21(180%(56
35(),;
)250$7
&<&/,&7(67
+($5,1*
$/$50&2'(6
 !

e1

Domonial 800++ Installation Manual - 10/2002

14

www.secom.tm.fr

EKZ004400F

180%(52)5,1*6
Select number of rings before CRX800++
control panel transmitter picks up the call.

75$160,77(5
CRT800++ control panel transmission activation
/ deactivation

&/,(17180%(5
To enter the client code for site Identification
by ARC

e =>
375$16$&&(665,1*
1XPEHURIULQJV

 !

e =>
375$1602'(
7UDQVPLVVLRQ
!(1$%/(
 !

e =>

375$16&/,(17180%
&OLHQW1XPEHU

'(/(7( !

e =>

Audio
verification

375$165(027(&200
5HPRWH$FFHVV
!(1$%/(
 !

Choose one of the


following options for remote
access to CRT/CRI++:

Remote
commands

e =>

Press key => to go on


Remote
programming

Select remote access mode to the control panel


CRT/CRI800++ transmitter
The answerer by-pass mode is always active
(pick up on first ring of 2nd call coming in within
30 seconds of the first one)
Remote control and remote programming
inhibition over 2 minutes if the sequence has
not properly been completed within 30 secs
(wrong code or not)

352*75$165(027(
!5(027(&21752/
5,1*6180%(5
 !

Hang-up

5(027($&&(6602'(

Y
Y
Y
Y

Y
Y
Y
Y

N
Y
Y
Y

N
N
Y
(*)

DISABLED
ENABLED
ACTIVE (WITH AUDIO V.)
ACTIVE (NO AUDIO V.)

(*) only within a period of 10mn after an alarm


Enter a value between 1 and 12

Press key => to go on

Enter value DISABLE, PSTN, GSM only or PSTN+GSM

Press key => to go on

Enter the site identifier code. The number of


characters depends on the protocol in use. Use * to
adjust length
e.g.: 00*12345 for 12345 using Cesa.(***12345 to
reverse Arming/Disarming using)

Press key => to go on

3+21(180%(56
phone numbers of ARC

375$160,73+21(
$
%
1(;7'(/(7( !

e NEXT

phone numbers of ARC

o Warning : phone "D" is reserved for calls to


remote maintenance station
Dialing prefix

',$/,1*35(),;(

375$160,73+21(
&
'
1(;7'(/(7( !

e NEXT
352*75$1635(),;
',$/,1*35(),;(

'(/(7( !

e =>
&20081,&$7)250$7
Select the transmitter format associated with
the ARC telephone numbers

3(5,2',&7(67
Cyclic test or periodic test 1 report
The second cyclic test (2) cant be modidied
by this programming tool.
$8',29(5,),&7,0(
Select the listening-in time

e =>

375$16&<&/,&7(67
67$57K,1+,%1
3(5,2'MKPQ
 !

e =>
375$16/,67(1,1*
/LVWHQLQJWLPH
VHFRQGV
 !

e =>

6<67(05(3&2'(6
Transmission / System input reporting codes
(See next page for description)

01 RESET
02 MAIN BATTERY
03 MAIN POWER
04 PHONE LINE
05 EQUIPMENT TAMPER
06 C. PANEL TAMPER
07 BATTERY EQUIPMENT
08 JAMMING
09 SUPERVISION
10 VAT MODE
11 CYCLIC TEST (PSTN)
12 CYCLIC TEST (GSM)

375$16)250$7
)RUPDW
!6(&20
 !

13 REMOTE TEST
14 THREE WRONG CODES
15 DURESS CODE
16 RESPONSE
17 GSM NETWORK
18 SYNTHESIS ALARM
19 ALARM MEMORY
20 CONFIRMATION
21 EJECTION
22 TOTAL ARMED
23 PART ARMED
24 ANNEX ARMED

Domonial 800++ Installation Manual - 10/2002

375$16&'(6<67(0
/$%5(6(7
!$/$50!$33
1(;7 !

e NEXT

Enter the phone numbers (17 digits max,* for a 2


second pause). Multi-frequency dialing

Press key => to go on

Enter the phone numbers (17 digits max,* for a 2


second pause). Multi-frequency dialing

Press key => to go on

Enter the dialing prefix n(s) (17 digits max, * for a 2


second pause).
Leave blank if no prefix is necessary (direct line)

Press key => to go on

Choose the protocol used by the ARC in the list


proposed.

Press key => to go on

Enter start time of 1st test, after control panel


switching on, frequency (30 days max) and inhibition:
Inhibited = test only if control panel in total
surveillance

Press key => to go on

Choose the time for listening/speaking by the central


station operation (CRI-PCI800++ only) 1s to 240s

Press key => to go on

Select the internal system inputs to be transmitted


ALARM : Only transmitted when fault appears
ALARM/END : transmitted when appears+disappears
NO TRANS : not to be transmitted.
APP/DIS : Enter the following code transmitted when
alarm appears and disappears (if DIS. Code not
modified, it will be identical to the one for APP.)

Press NEXT to go on
Press key => to quit
15

www.secom.tm.fr

EKZ004400F
$/(57
Transmission / "Alert" key codes

'(7(&7256
Transmission / "Detectors" codes
This function is available only if at least 1
wireless detector is registred

375$16&2'($/(57
/$%6,/(17$/(57
!1275$16!$33
1(;7 !

e NEXT
375$16&2'('(7(&
/$%%$6(0(17 5$ 
!$/$50!$33
1(;7 !

e NEXT

Select the Alert/Detector inputs to be transmitted


ALARM : Only transmitted when fault appears
ALARM/END : transmitted when appears+disappears
NO TRANS : not to be transmitted.
APP/DIS : Enter the following code transmitted when
alarm appears and disappears (if DIS. Code not
modified, it will be identical to the one for APP.)

Press NEXT to go on
Press key => to quit

System inputs list

Operation

RESET
MAIN BATTERY
MAINS POWER

Code sent at the end of a reprogramming session or upon power being restored
Code sent by a run-down battery and when back to normal
Code sent upon mains power failure/restoration
Activation delay : 30 mins - Restore delay : 10 mins
Code sent in event of PSTN failure / restoration.
Activation delay : 30 secs - Restore delay : 10 secs
Code sent in event of attempted opening or wrenching-off of a device within the system
Code sent in event of attempted opening of CRT/CRI800++ control panel.
Activation with 0.1 second integration and de-activation with 5 seconds integration
Code sent in case of a wireless peripheral power supply failure
Code sent to inform that a radio transmission of more than 10 seconds has been detected on the
same frequency band as that used by control panel CRT/CRI800++
Code sent when a wireless peripheral (detector or sounder) has not answered the daily test sent
by the control panel
Code for transmission in transparent mode from CTR800++ Diagnosis menu. This information must
be activated (ALARM/END) to enable the transparent mode (IST Server needed)
Codes sent at programmable intervals to report to the monitoring station (via several networks)
Code sent in return to a call (as programmed). e.g.: if "operative", every call picked-up will be
followed by the remote testing code
Code sent to inform that connection to CRT800++ control panel has been attempted (locally or
remotely: programming or remote control). Such code is sent after 3 wrong codes received.
Code sent to inform that the code increased by 1 has been entered on the keypad 'e.g.: 1235
instead of 1234)
The person sent to the site by the monitoring station carries an "Agent" remote control box
automatically identified by CRT800++ control panel (recording such a box is not necessary). When
the control panel is armed and within one (1) hour after an alarm event, depressing this remote
control box will transmit a code confirming the agents arrival on site. This information is also
stored in the event log.
Code sent to report to the ARC the GSM networks status.
Code sent when one of the networks (PSTN or GSM) is restored, if an alarm occurred when the
networks were not working.
Code sent when main zone is disarmed following an alarm activation
Code sent to indicate a wrong operation if Total surveillance is disarmed within one (1) minute
following alarm activation.
Code transmitted upon surveillance arming when a door contact or a wireless peripheral detector
programmed for perimeter security is not secured and is "by-passed"
Codes transmitted upon Total surveillance arming / disarming
Codes transmitted upon Part surveillance arming / disarming
Codes transmitted upon Annex zone surveillance arming / disarming

PHONE LINE FAILURE


EQUIPMENTS TAMPER
CONTROL PANEL TAMPER
EQUIPMENT BATTERY FAILURE
RADIO JAMMING
SUPERVISION
VAT MODE
CYCLIC TEST (PSTN or GSM)
REMOTE TEST
3 WRONG CODES
DURESS CODE
RESPONSE CODE

GSM NETWORK
SYNTHESIS ALARM
ALARM MEMORY
CONFIRMATION (FALSE ALARM)
DETECTOR EJECTION
TOTAL SURVEILLANCE ARMING
PART SURVEILLANCE ARMING
ANNEX ZONE SURVEIL. ARMING

Domonial 800++ Installation Manual - 10/2002

16

www.secom.tm.fr

EKZ004400F

3-10 Programming engineer code, date and time, optional GSM unit, Users codes
Access to applicable menus is as follows:
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

&57[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

Enter code
(001234 factory default values)

then e1

352*5$00,1*
(48,30(176
&21752/3$1(/
75$160,77(5
!6<67(0
2873876
 !

e4

,167$//(5&2'(
Remote control and programming access codes
changing.

02',)'$7( 7,0(
The display modification date & time changing.
Date & time are used by the event log file for
message dating

*60&2'(3,1
To set the PIN code for the optional GSM
Network unit

0(02
This display allows a 16-digit text.

'70)5(027(&2'(
Remote DTMF code for user

352*6<67(0
!,167$/&2'(
'$7($1'7,0(
6(5,$/$33/,&
*603,1&2'(
0(02
86(56
 !

e1
36<67(1*(1((5&2'(
,167$//(5&2'(

'(/(7( !

e =>

Enter new 6-digit code using the numeric keys.

Press => to go on
Enter new date & time using the numeric keys For the

36<67'$7(7,0(
'$7(''00<<
7,0(++K00
 !

time press "

e =>

" key

Press => to go on

36<673,1&2'(
*60&2'(3,1

9$/,''(/(7( !

e =>

Enter the PIN code of the SIM card (often 0000,


depending on provider)

Press => VALID

Wait for the correct code message

Press => to go on

352*6<67(00(02
0(02

'(/(7( !

e =>

Enter memo using the numeric keys. Key > for next
character (16 maximum).

Press => to go on

Enter new 6-digit code using the numeric keys.

36<677(/(&&2'(
.H\SDGFRGH
!
 !

Press => key to go on

e =>

For security reason, the installer must ask the customer to change this code
86(5&2'(6
This display allows user codes to be change via
the CLB800 keypad.

352*6<6786(5
0$67(55(325712
02',)&/%12
1(;7'(/(7(025(
352*6<67025(&2'(
0$67(5
&RGH
'(/(7( !

e =>
Functions \ Users
Label (8 characters)
Supervised user
(REPORT)
Displayed on CLBX00HF for modification
(MODIF CLB)

Domonial 800++ Installation Manual - 10/2002

MASTER: to change the code label (8 char. max)


REPORT: Y/N for transmission Arming and disarming
information to the monitoring station
MODIF CLB: Y/N to allow changing code on CLB
keypad (if NO is selected, this user will not be showed
on the CLB800 changing codes menu)
MORE: to change the code (4 numbers)

Press => to go on

Master
Y
Y/N

1
Y
Y/N

2
Y
Y/N

3
Y
Y/N

4
Y
Y/N

5
Y
Y/N

6
Y
Y/N

7
Y
Y/N

8
Y
Y/N

9
Y
Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

17

www.secom.tm.fr

EKZ004400F

3-11 Beep adjustment


Access to the beep programming menu is as follows:
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&57[9[[[
!352*5$00,1*
7(67
(9(17/2*

 !

(001234 factory default values)

then e1

352*5$00,1*
(48,30(176
&21752/3$1(/
75$160,77(5
6<67(0
!2873876
 !

e5

%((36
Programming of audible confirmations given by
the built-in sounder and indoor sounder SI800
(if any).

352*287387
352*5$00,1*
3,/27,1*
!6281'6,*1$/
 !

e3
32873876281'6,*1
$/(57!<(67(&+!<(6

 !


e =>

32873876281'6,*1
6859!<(6'(/$<!(6
%((3(5!<(6
 !


e =>

Choose the desired confirmation beeps as per table


below.

Press key => to go on


Choose the desired confirmation beeps as per table
below. For delay beeps, choice is as follows: No, Entry
only, Exit only or Entry + Exit.
In the "pre-alarm" mode a detector triggers Beeps
only (no alarm transmission).

Press => to quit.

3-12 Descriptive list of audible signals


24h/24
Alert 1
Alert 2
Alert 3
Chime
Prealarm
Sounder with delay
Technical mode
Mains power or battery failure, Alarm memo
Access violated

Surveillance disarmed
Alarm mode
Prealarm mode
Perimeter security mode
Total surveillance arming
Part or Annex zone surveillance armed
Radio jamming, transmission network defective
Control panel & system tamper protect.

Surveillance armed
Alarm mode
Prealarm mode
Perimeter security mode
Total surveillance disarming
Annex zone surveillance disarming
Entry delay
Exit delay
Radio jamming, transmission network defective
Control panel & system tamper protect.

Domonial 800++ Installation Manual - 10/2002

Beeps from SI800 sounder &


built-in sounder
4 beeps
N
N
1 series of 2 beeps
1 series of 2 beeps
1 series of 2 beeps
2 series of 7 beeps
2 series of 7 beeps
N

Indoor
Siren

Outdoor
Siren

5s
90s

5s
90s

After delay

After delay

90s

Beeps from SI800 sounder & built-in


sounder

90s

Indoor
Siren

Outdoor
Siren

Transmission
Y/N
Y/ N
Y/N

Y/N
Y/N
Y/N

Transmission

1 series of 2 beeps
3 modulated tones: 4s
2 modulated tones: 2.5s
2 series of 7 beeps

Beeps from SI800 sounder & built-in


sounder

Y/N
Y/N
Y/N

Indoor
Siren

Outdoor
Siren

Transmission

90s

90s

Y
N

90s

90s

Continuous tone: 2.5s


2 continuous tones: 4s
1 beep/second 15s before delay expiry
1 beep/second 15s before delay expiry

Y/N
Y/N

90s

18

90s

Y/N

www.secom.tm.fr

EKZ004400F

4 - SYSTEM TESTING
In normal service conditions, the main circuit board LED must keep flashing at the rate of 1.5 second. If
it is off, the board power supply must be checked. The software version can be read from TB550 when
programming is initiated.

4-1 Radio tests


Access to the radio test menu is as follows:
&5[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&5[9[[[
352*5$00,1*
!7(67
(9(17/2*
/$1*8$*(

 !

(001234 factory default values)

then

7(67
!5$',2/(9(/
5$',25(&(37
6,5(1623(5$
5$',25(&(,9(
*60/(9(/
 !

e2

Test the ambient radio level on the same


frequency as CRT800++ and its peripherals

$0%,(17/(9(/

e1

p The minimum recording level to

secure suitable performance is 2


boxes out of 10.

7(675$',2/(9(/
5$',2/(9(/
gg0000000000
 !


e =>

Test peripherals reception level.

5(&(37,21/(9(/

5(&(37,215$',2!!
gggggg0000
.(<)2%$'
/$%%$%<6,77(5 !


e =>

The ambient level must not be higher than 4


permanent boxes to ensure secure operation of the
system

Press => to go on.

This menu enables the radio level to be tested and the


system wireless peripherals to be positioned

Press => to go on

4-2 Sounder tests


Access to the sounder test menu is as follows:
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&57[9[[[
352*5$00,1*
!7(67
(9(17/2*
/$1*8$*(

 !

(001234 factory default values)

then e2

7(67
5$',2/(9(/
5$',25(&(37
!6,5(1623(5$
5$',25(&(,9(
*60/(9(/
 !

e3

Test of the wireless and built-in sounders of


the system.

7(676,5(1
7(67$//7+(
5(&25'('6,5(16
212)) !


e =>

6,5(17(67

Press "ON" to trigger the sounders and "OFF" to


silence them.

Press => to go on

4-3 Radio Receiver test


The control panel logs 500 date-stamped events. The event log readout is as follows:
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&57[9[[[
352*5$00,1*
!7(67
(9(17/2*
/$1*8$*(

 !

(001234 factory default values)

then e2

7(67
5$',2/(9(/
5$',25(&(37
6,5(1623(5$
!5$',25(&(,9(
*60/(9(/
 !

e4

5$',25(&(,9(57(67

7(675$',25(&(,9(
:,5(/(665(/$<
/$%:5
212)) !

Domonial 800++ Installation Manual - 10/2002

e NEXT

19

Press keys "ON" and "OFF" to activate the radio relay.


-

Press => to quit.

www.secom.tm.fr

EKZ004400F

4-4 GSM Network level


&57[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&57[9[[[
352*5$00,1*
!7(67
(9(17/2*
/$1*8$*(

 !

(001234 factory default values)

then e2

7(67
5$',2/(9(/
5$',25(&(37
6,5(1623(5$
5$',25(&(,9(
!*60/(9(/
 !

7(67*60/(9(/
*60/(9(/
gggggggggggg000
 !

e5

*601(7:25./(9(/

e NEXT

Read the displayed level

Press => to quit.

4-5 Event log look up


The control panel logs 500 date-stamped events. Event log readout is as follows:
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

&57[9[[[
352*5$00,1*
7(67
!(9(17/2*
/$1*8$*(

 !

Enter code

(001234 factory default values)


+'(6$50('

35(91(;7 !

then e3

(9(176/2*5($'287

e NEXT

Press keys "NEXT" and "BACK" to read the Event log.


Readout is as follows :
date and time
designation & serial number
event type (activation or deactivation)

Press => to quit.

4-6 Changing language


The control panel includes 2 languages. To switch between languages during programming :
&57[1b
&57[9[[[
&RGH
5(6(7',$* !

Enter code

&57[9[[[
352*5$00,1*
7(67
(9(17/2*
!/$1*8$*(

 !

(001234 factory default values)

3&75/(237/$1*
/DQJXDJHFKRLFH
!(1*/,6+
 !

then e4

e NEXT

&+$1*(/$1*8$*(

Switch the language with the >, < keys

Press => to quit.

5 DIAGNOSTICS
5-1 Wireless peripheral diagnostics
This mode enables the system wireless peripherals to be diagnosed (battery low, tamper protection and monitoring).
Access to the diagnostics menu is authorised without a password.
&57[1b
&57[9[[[
&RGH
5(6(7',$*

eDIAG

',$*1267,&6
!5$',2,7(06
6<67(0
672375$16
75$163$5(1702'(
 !

',$*5$',2(48,30
!%$77(5<
7$03(5)$8/7
683(59,6,21)$8/7

 !


e1

Battery low diagnostics for system wireless


peripherals.

%$77(5<)$8/7

e1
or

',$*(48,30%$77(5<
!!12)$8/7!!
!!%$77(5<!!
 !
',$*(48,30%$77(5<
)$8/71%
/$%%$6(0(17
7<3('(7(&725 !

e =>
Domonial 800++ Installation Manual - 10/2002

20

The screen displays the number of faults, the


peripheral(s)
concerned
with
corresponding
designation and type. A beeps sounds if a fault has
been found on the completion of the diagnostics.

Press => to go on

www.secom.tm.fr

EKZ004400F

Tamper fault diagnostics for system wireless


peripherals.

',$*(48,307$03(5
!!12)$8/7!!
!!7$03(5!!
 !

7$03(5)$8/7

or

',$*(48,307$03(5
)$8/71%
/$%&25,'25
7<3(6,5(1 !

e =>

Monitoring fault diagnostics for system wireless


peripherals.
(Detectors and sounders)

683(59,6,21)$8/7

',$*(48,30683(59,6

!!12)$8/7!!
!!683(59,6,21!!

or

',$*(48,30683(59,6

)$8/71%
/$%&25,'25

The screen displays the number of faults, the


peripheral(s)
concerned
with
corresponding
designation and type. A beeps sounds if a fault has
been found on completion of the diagnostics.

Press => to go on

The screen displays the number of faults, the


peripheral(s)
concerned
with
corresponding
designation and type. A beeps sounds if a fault has
been found on completion of the diagnostics.

Press => to go on

e =>

In the case of several faults arising, they will be displayed consecutively at the rate of one per second and a beep will sound on
TB550 upon completion diagnostics.
',$*(48,307$03(5
)$8/71%
/$%&25,'25
7<3(6,5(1 !

',$*(48,307$03(5
)$8/71%
/$%%$6(0(17
7<3('(7(&725

Bip

',$*(48,307$03(5
)$8/71%
/$%&25,'25
7<3(6,5(1 !

',$*(48,307$03(5
)$8/71%
/$%%$6(0(17
7<3('(7(&725

Bip

These displays being dynamic displays, a fault being corrected modifies the beeps rate or even causes them to stop. These beeps
being repeated by the sounder, the technician can, easily and by himself, correct possible faults on the system.

5-2 Battery and mains diagnostics


This mode allows battery and mains faults to be diagnosed.
&5[1b
&5[9[[[
&RGH
5(6(7',$*

',$*1267,&6
5$',2,7(06
!6<67(0
672375$16
75$163$5(1702'(
 !

eDIAG

7DPSHU2.
%DWWHU\2.2.




Control panel tamper protection status (KO = Open)


Battery status (KO = voltage low)
230V Mains power (KO = no power or fuse blown)

e2

6<67(0',$*

5-3 Transmission intended stop


This mode allows the current transmission to be stopped.
&57[1b
&7[9[[[
&RGH
5(6(7',$* !

',$*1267,&6
5$',2,7(06
6<67(0
!672375$16
75$163$5(1702'(
 !

eDIAG

e3

',$*672375$16
!!672375$16!!
!!,1352*5(66!!

The above screen is displayed for about 3 seconds

&$//6723

5-4 Transparent mode manual test (Scurit communications-Vat mode)


This allows the technical host to be called in order to test the transparent mode.
The action is confirmed by a beep from TB550 and can be cancelled by "CANCEL"
&5[1b
&5[9[[[
&RGH
5(6(7',$*

',$*1267,&6
5$',2,7(06
6<67(0
672375$16
!75$163$5(1702'(
 !

',$*75$16302'(
,1352*5(66

 &$1&(/

association with PE1500 Alarm receiver


and IST Scurit communications server.

eDIAG

p This function is only available in

e4

75$163$5(1702'(7(67

Domonial 800++ Installation Manual - 10/2002

21

www.secom.tm.fr

EKZ004400F

6 OPERATION
6-1 Transmission to a DTMF telephone set

Once programmed Domonial++ can send information to a telephone set.


When a call is received and the handset is picked up the identification music is played
Type 1 (by default)
Type 2
followed by a number of beeps corresponding to the triggered input. When several
Music 1
Music 2
devices have been triggered, only the first one is indicated.
+ bip
+ bip
After the message has been listened to an acknowledgement is made by pressing the #
key .
Then (on the CRI/PCI version only), if there is audio programmed, the site can be listened to remotly.
The call is terminated by hanging up.
If the above configuration does not exist or in the case of a decimal telephone, the message will be repeated using the
programmed sequence.
The identification music can be changed by means of PC software.

Mimic diagram

Press key :

Music 1
or music 2

#
CRI/PCI800++ only

Ringing

Pick-up

Identification

Beeps

Acknowledge

Listen (CRI)

Hang-up

6-2 Using the CLI800HF optional wireless keypad


How to use the keypad
Total Arming :

Press

key (then enter your code : see How to program the ON key).

Partial Arming :

Press

key then entre your secret code.

Disarming :

Press

key then entre your secret code.

Alert (panic) :

Press

to trigger an alert. The operation will have been pre-programmed


during registration of the keypad on the system.
How to modify the codes

To modify the code Master User


User code
(1234 by
default)

New
code

To modify the Service 1 code

New
code

To modify the Service 2 code


New
code

Service 1 code
(1234 by
default)

New
code

Service 2 code
(1234 by
default)

New
code

New
code

How to program the ON key


To arm an alarm system, use the On button without entering a code.
However, for improved safety, you can set the condition that requires a secret code to be entered.
To arm the system with a code :

To return to the previous command mode (without a code) :

User code
(1234 by default)

Domonial 800++ Installation Manual - 10/2002

User code
(1234 by default)

22

www.secom.tm.fr

EKZ004400F

6-3 DTMF Remote controls


1/ Call the control panel from a
DTMF telephone set

1000Hz beep for 1.5 second


then
5 seconds silence (waiting for carrier)

Arpeggio..

Invitation music : "Arpeggio"

2/ Enter password. After 30 secs


without a further entry the
communicator hooks up

001234

Beep for 2 seconds high/low-pitched

(factory default)

Low-pitched
Password wrong

High-pitched
Password correct

(1)

*16

Activate Relay 1

*17

Activate Relay 2

*18

Activate Relay 3

*19

Activate Relay 4

*21

Total zone arming

*22

Part zone arming

*23

*4

Remote test

Annex zone arming

*6
Audio

*8

*#

Changing
Phone N

Hang up

Communicator hang
up and sends a
remote test

Hang up

Dial actual
number

Speaking
Arms and hang up after the
melody

Confirmation by high beep

(Optional Wireless
Remote Plug or Relay)

Dial new
number

Listening
Confirmation by high beep

Dial new
number

Hang up

> To enable remote control via phone, the control panel pick up mode must not be programmed to "No".
(1) Please consult us for the available software version
Domonial 800++ Installation Manual - 10/2002

23

www.secom.tm.fr

EKZ004400F

7 - TECHNICAL APPENDIXES
7-1 : Knowledge of the various formats

Secom 3:

Secom 3 is a DTMF Format. Used in conjunction with control panel CRx800++ it features :
- Identifier code ( 8 Numeric digits ).
- Numeric codes from 0 to 98.
- Checksum verifying the received and transmitted data frame integrity.
- Information to the ARC as to the period of time elapsed between alarm activation and surveillance
arming.
- Zone surveillance status upon cyclic testing.
- Listening duration between 1 and 240 seconds (option not available on CRT/PCT800++)
- Changing to Modem mode (owner) for switching to Scurit communications-Vat protocol (remote
parameter setting and maintenance)
- Digital communicator time setting from the alarm receiver.
- Option of automated scripts possibility via a Technical Service Integrator IST.

This format is supported by the alarm receiver Scurit communications PE1500.

Formats codes :
The following table shows the codes corresponding to each format.
Some are dedicated ones and are programmed as default codes in CRx800++.
Communication format
Client number
Alarm (disappearance)
Low battery (appearance)
Low battery (disappearance)
Cyclic test
Remote test
Reset
Total arming
Total disarming

Domonial 800++ Installation Manual - 10/2002

Secom3

Surtec

Cesa

Contact ID

9
91
90
92
93
03
94
95

Numeric
(5 Char.)
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99

Numeric only
(4 char.)
100 - 199
302
302
602
601
305
400
400

Numeric
(8 char.)
9
91
90
0 to 98
0 to 98
0 to 98
94
95

24

www.secom.tm.fr

EKZ004400F

7-2 List of the associated wireless peripherals

IR800

IR800PI Passive infrared motion

Passive infrared motion detector

detector pet-imune

Detection range ~10m


Radio range ~50m on site depending on local
environment
Opening tamper protection and wall tamper
(depending on model)
Supervised : yes
Power requirement: 1 battery CR123 - 3V with low
battery indication transmission
Battery life ~5 years

Detection range ~10m


Radio range ~50m on site depending on local
environment
Opening tamper protection and wall tamper
(depending on model)
Supervised : yes
Power requirement: 1 battery CR123 - 3V with low
battery indication transmission
Battery life ~5 years

DOD800 Door/Window detector with offfitted contact possibility

BVA800

Glass-break detector

WR800

Wireless Remote

RS800

Remote Mains Plug (DIN


format)

Radio range ~50m on site depending on local


environment
Opening and wall tamper
Supervised: yes
Power requirement: 1 battery CR123 - 3V with low
battery indication transmission
Battery life ~5 years

DFO800

Smoke detector

SI800

Indoor Siren

CLB800

Detection area ~50m


Radio range ~50m on site depending on local
environment
Opening tamper protection
Supervised: yes
Power requirement: 1 battery SL761 - 3.6V with low
battery indication transmission
Battery life ~5 years

Power 85 to 115dB
Radio range ~50m on site depending on local
environment
Opening and wrenching tamper protection
Supervised: yes
Power requirement: 4 batteries CR123 - 3V with low
battery indication transmission
Battery life ~4 years

CSK800 Keypad with built-in proximity

keypad with LCD display (10


codes + 1 duress code)

fob reader (10 users)

Radio range ~50m on site depending on local


environment
Opening and wall tamper
Power requirement: 1 battery CR123 - 3V with
low battery indication transmission
Battery life ~ 100,000 operations

Control keypad (3 codes + 1


duress code)

CLI810

Control keypad (10 users)

TC805

4-buttons keyfob / 5 functions

Radio range ~50m on site depending on local


environment
Opening and wrenching tamper protection
Power requirement: 1 battery CR123 - 3V with low
battery indication transmission
Battery life ~ 100,000 operations

TC804

4-buttons keyfob
Radio range ~50 m in the open
Power requirement 1 battery (included)
Battery life ~ 150,000 operations
Weight 30 grams

Domonial 800++ Installation Manual - 10/2002

1 relay output
1 detection input
1 tamper input
Radio range ~50 m in the open
Mains Powered by 12V=
Output Status Saving by batteries CR123
Opening and wrenching tamper protection for in
box model

Radio range ~50 m in the open


Powered by mains
1500W switched

Radio range ~50m on site depending on local


environment
Opening and wrenching tamper protection
Power requirement: 1 battery 3,6V with low
battery indication transmission
Battery life ~ 3 years

CLI800

Detection area 360 - 7,50m


Radio range ~50m on site depending on local
environment
Opening tamper
Supervised: yes
Power requirement: 1 battery SL761 - 3.6V with
low battery indication transmission
Battery life ~5 years

25

Radio range ~50m on site depending on local


environment
Opening and wrenching tamper protection
Power requirement: 1 battery CR123 - 3V with
low battery indication transmission
Battery life ~ 100,000 operations

Radio range ~50 m in the open


Power requirement 1 battery (included)
Battery life ~ 150,000 operations
Weight 30 grams
Wireless devices operating capabilities

www.secom.tm.fr

EKZ004400F

8-1 Functional

4 zone surveillance (Total, Part, Annex and 24hours)


Management of wireless peripherals of the Scurit communications 800 range
Numeric transmission format : Secom3, Cesa, Surtec, contact ID (5)
Other format : phone
Built-in siren
Built-in audio half-duplex system (CRI/PCI800++ only)
4 phones numbers (of which one reserved for remote maintenance) + 2 phones numbers for GSM Network use
Event log for 500 events
Remote parameter feeding from PC and Domocom Modem; locally from TB500 or PC

8-2 Physical
z Dimensions

Height :
Width :
Max Depth :
Operating :
Storage :

183mm
235mm / 295mm(6)
50mm / 56mm(5)
5 <-> 40C
-40 <-> 70C
< 85%
1280 g (2822 lb)

z Power requirement
z Battery

typique (Ut) :
Type :
Fault :

z Typical consumption (Ut)

Normal :
Calling :

230V~ 50Hz, fused (200mA)


4V 3,5Ah max.
appear
: 3,5 V
disappear :
4V
25 mA
85 mA

z Temperature (CSEI - 11- 10 Standard)


z Relative humidity (CSEI - 11- 10 Standard)
z Weight (with battery)

8-3 Electrical

8-4 radio
z Radio frequency
z Number of channels

z Monitoring
z Radio jamming detection

FM narrow band
Detection (IR, DO )
Control keypad
Keyfob
Other
bi-directionnal
peripherals (siren, remote
mains plug, wireless relay)
Detectors and sirens

868,25MHz
20
2CLI + 2CLB
4 (+ 1 response)
4 (including the number of CLBs)

Once per 4 h
Detection of a 868.25Mhz transmission
for more than 10s over a period of 20s

Note:

This product is in compliance with the applicable provisions of R&TTE.


This equipment can be connected anywhere to the Pan-European PSTN.
However, as there are some differences in the PSTN from a country to another, this compliance is not an inherent absolute
guarantee of optimal performance irrespective of the connection point to the Pan-European PSTN.
Should any problem arise, contact your dealer first.
The connection to the mains supply and phone line must be made in conformity with the local authoritys rules and regulation.

5
6

For Contact ID, the client number is only on 4 numeric characters (not hexa) ; others formats : please, consult us.
Depending on cover model.

Domonial 800++ Installation Manual - 10/2002

26

www.secom.tm.fr

---------------------------- For product and user interest, the specifications may be subject to change without notice ------------------------------------------------------

8 - SPECIFICATIONS

EKZ004400F

9 CONFORMITY DECLARATION

Domonial 800++ Installation Manual - 10/2002

27

www.secom.tm.fr

EKZ004400F

A
ADSL
Alert

G
10
13, 21, 24, 29

GSM Network

Battery4, 10, 11, 21, 24, 27, 28, 32, 33, 34, 35
Beeps
13, 14, 16, 24, 25, 28
Bistable
17
Built-in sounder
14, 15, 24, 26

Hybrid

11
7, 19, 32, 35
13, 24
23, 35
19
7, 32, 35

J
21

13, 15, 34
3, 5, 13, 16, 21, 23, 29, 33, 35

L
D
Date & time
Delay
Deleting
Diagnosis
Diagnostics
Dialing prefixe
DTMF
Duress code

23
5, 15, 16, 18, 21, 24, 25
3, 15
27, 28
27, 28, 28
19
3, 5, 7, 17, 23, 29, 31, 32
21

Language
LED
Level
Listening time

3, 27
3, 11, 17, 26
3, 9, 15, 26, 27
19

17
4, 5, 21, 23, 26

Recording
3, 13
Remote
5, 15, 16, 19, 23, 31, 32, 33, 35
Remote access
19
Reset
21
Response
21

Secom 3
Serial port
Sounder
Status
Stocko
Supervised
Supervision
Surtec
Synthesis Alarm

M
Mains power
Master
Memo

21
23
23, 24

Tamper
TB550
Telephone
Teleruptor
Tests
Transparent mode

Flashlight
Format

18, 28
3, 4, 12, 26, 28
3, 5, 7, 8, 10, 18, 19, 29
17
3, 9, 26
21, 28

N
Number of rings

19

U
Users

32
11, 13, 16, 27
3, 6, 24, 26
17
10
5, 23, 33
21
7, 32, 35
21

E
Eavesdropping
Event log

13, 24
4, 5, 6, 7, 17, 19, 21, 36

K
Keyfob
Keypad

Prealarm
PSTN Network

Jamming

C
CAB550PC
Cesa
Chime
CLB800
Client code
Contact ID

3, 5, 7, 19, 21, 23, 27, 35

5, 33

P
17
16, 19, 32, 33, 35

Domonial 800++ Installation Manual - 10/2002

PE1500 Receiver
Periodic test
Phone numbers
PIN Code

32
19
19
23

28

V
VAT Mode

21

www.secom.tm.fr

EKZ004400F

Domonial 800++ Installation Manual - 10/2002

29

www.secom.tm.fr

EKZ004400F

Domonial 800++ Installation Manual - 10/2002

30

www.secom.tm.fr

EKZ004400F

Securite Communications - Registered Office and Clients Services


Route des Dolines - BP 41
06901 SOPHIA-ANTIPOLIS Cedex
FRANCE
Tl : (33) 492 942 950 - Fax : (33) 492 942 960
Web : http://www.secom.tm.fr
E.mail : support@secom.tm.fr

Domonial 800++ Installation Manual - 10/2002

31

www.secom.tm.fr