Universal Annunciator Setup for MCM3320

Preliminary/Confidential/Proprietary

Product:

Universal Annunciator Control

Author:

Mike Hartley

Date:

1/23/2017 6:16 AM

Document:

Universal Annunciator Setup for MCM3320.doc

Document Version:

Comments:

This version shall take precedence over all


previous versions of this document.

Onan Corporation assumes no responsibility for any errors which may appear in this document nor does it make a commitment to update the information contained herein.
On retains the right to make changes to these specifications at any time without notice. No part of this document may be reproduced, translated, or transmitted in any form, or
disclosed to others without authorization from Onan Corporation.

Universal Annunciator Setup for MCM3320


Preliminary/Confidential/Proprietary

1 Introduction
Universal Annunciator versions 1.07 and higher have the functionality of accepting configuration
commands over the PCCNet network. Older versions must be configured manually by using the push
buttons on the back of the annunciator.
MCM3320 versions 1.24 and higher have the functionality of configuring annunciators over the network.

2 Testing for Automatic Configuration Functionality


You can test if your MCM3320 and annunciator can automatically perform the configuration by using
either the HMI display for the MCM3320 or by using Inpower.
Using the HMI Display:
Go to the Adj Config Annun screen
Select the Perform Config menu selection
Set PERFORM CONFIG to either Basic Status or to Ld Add Shed.
The CONFIG STATUS parameter will display Annun Not Ready. Press the Silence button on
the Annunciator that you would like to configure.
The CONFIG STATUS will change to Configuring for a few seconds.
The CONFIG STATUS will then change to either Config Error or to Success.
If CONFIG STATUS is set to Success then your annunciator has been properly configured. If
set to Config Error then the annunciator will have to be manually set-up.
Using Inpower:
Set Perform Annunciator Configuration to either Config to Basic Statuses or to Config to Load
Add Shed.
The Annunciator Configuration Status parameter will display Annun Not Ready for Config.
Press the Silence button on the Annunciator that you would like to configure.
The Annunciator Configuration Status parameter will change to Performing Configuration for a
few seconds.
The Annunciator Configuration Status parameter will then change to either Error Occurred While
Configuring or to Annun Successfully Configured.
If the Annunciator Configuration Status parameter is set to Annun Successfully Configured then
your annunciator has been properly configured. If set to Error Occurred While Configuring then
the annunciator will have to be manually set-up.

3 Manually Setting-up the Annunciator


The annunciator can be configured via push buttons. The following defines how to set-up the
annunciator using 3 momentary buttons, 3 LEDs located on the back of the board and the 20 status LEDs
on the front panel. The buttons function as follows:
S1: enter or leave configuration mode at any time.
S1: cycle through the configuration functions.
S2: used in certain configurations to cycle through each of the 20 inputs/LEDs.
S3: used to select possible configurations.
NOTE: This document is intended to be used only for manually setting up the annunciator for use with
the MCM3320. Refer to the Universal Annunciator Operators Manual for further annunciator information.

page 2 of 6
Cummins Proprietary and Confidential

Universal Annunciator Setup for MCM3320


Preliminary/Confidential/Proprietary
The 3 LEDs on the back panel are used to display which configuration function is presently being edited.
If Config LED 3 (N3) is flashing at 1 Hz then the annunciator is in Running mode, otherwise, the
annunciator is in Configuration Mode. When in Configuration Mode the 3 Configuration LEDs indicate
which Configuration Function is being edited.

3.1

Modifying Configurations

Press and hold the S1 button for 5 seconds to enter configuration mode.

LEDs N1:Off, N2:Off, N3:Off should be displayed.


Press the S3 button until the first LED on the front panel is Red. This sets all entries to known
configurations.
Press the S1 button.
LEDs N1:On, N2:Off, N3:Off should be displayed.
Press the S3 button until green LEDs are active on the front panel.
Press the S1 button TWICE.
LEDs N1:On, N2:On, N3:Off should be displayed.
The next step depends on whether the annunciator is being set-up for Basic Configurations or for
Load Add Shed.
o If setting-up for Basic Configurations then press the S3 button until the second LED on
the front panel LEDs is green.
o If setting-up for the Load Add Shed Configurations then press the S3 button until the
third LED on the front panel LEDs is green.
Press the S1 button.
LEDs N1:Off, N2:Off, N3:On should be displayed.
The color and flash can now be set-up. Using either the Basic Configuration Table or the Load
Add Shed Configuration Table (both below) set the color and flash for each of the 20 LEDs.
o Press the S3 button to cycle through the color and flash.
o Press the S2 button to cycle through the 20 LEDs.
Press the S1 button.
LEDs N1:On, N2:Off, N3:On should be displayed.
The audible alert configuration of each LED can now be set-up. Using either the Basic
Configuration Table or the Load Add Shed Configuration Table (both below) set the audible alert
configuration for each of the 20 LEDs.
o Press the S3 button to select the audible alert configuration for each LED. Select Red to
Enable the alert or Green to Disable it.
o Press the S2 button to cycle through the 20 LEDs.

Press and hold the S1 button for 5 seconds to exit configuration mode. All changes will be saved
to non-volatile memory.

page 3 of 6
Cummins Proprietary and Confidential

Universal Annunciator Setup for MCM3320


Preliminary/Confidential/Proprietary

Function

Config
LEDs
[N3 N2
N1]
<S1>

Predefined
Configuration
Table

Select
Individu
al Input /
LED
<S2>

Report Battery
Voltage in Status
LEDs 11,12,13

Neg/Pos Input
Select
Network
Configuration
Address

Color and Flash


for Individual
LEDs.

Press
<S2> to
cycle
through
each of
20 LEDs

Audible Alert
with Individual
LEDs.

Invert Active
Signal for
Individual Inputs

Press
<S2> to
cycle
through
each of
20 LEDs
Press
<S2> to
cycle
through
each of
20 LEDs

Global Horn
Enable

Front Panel LED


Selection
[Top LED Bottom LED]
<S3>

Value

><
><
><

No Chg: keep PCCNet


No Chg: keep Modbus
Select:PCCNet Legacy
Select:PCCnet NFPA 1101
Select:Modbus NFPA 110
PCCNet Dont Report 1 3
PCCNet Report 12v. 2
PCCNet Report 24.
PCCNet Report 12v. Hi Low
PCCNet Report 24v. Hi Low
Positive
Negative 1
1 (NFPA 110) 1 2 3 4
2
3
4
Solid Green
Solid Yellow
Solid Red
Flashing Green
Flashing Yellow
Flashing Red
Disabled
Disabled
Enabled

Dont Invert
Invert

Disabled
Enabled-Soft
Enabled-Loud 1

Factory Default
Default when Predefined Configuration Table = PCCNet Legacy
3
Default when Predefined Configuration Table = PCCNet NFPA 110
4
Default when Predefined Configuration Table = Modbus NFPA 110
2

Table 1: Configuration Table

page 4 of 6
Cummins Proprietary and Confidential

Universal Annunciator Setup for MCM3320


Preliminary/Confidential/Proprietary

Description

Color

Horn

Flash

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Utility Available
Utility Connected
Genset Available
Genset Connected
Auto/Manual Switch
Common Warning
Fail to Sync Fault
Genset 1 Available
Genset 2 Available
Genset 3 Available
Genset 4 Available
Test Start
Extended Parallel
Genset Bus Under frequency
Load Demand Enable
Configurable LED 16
Configurable LED 17
Configurable LED 18
Configurable LED 19
Configurable LED 20

Green
Yellow
Yellow
Green
Red
Red
Red
Green
Green
Green
Green
Yellow

No
No
No
No
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No

No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Yellow
Red
Yellow
Yellow
Yellow
Yellow
Yellow

Table 2: MCM 3320 Basic Configuration Table

Description

Color

Horn

Flash

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Add Load 1
Add Load 2
Add Load 3
Add Load 4
Add Load 5
Add Load 6
Shed Load 1
Shed Load 2
Shed Load 3
Shed Load 4
Shed Load 5
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used

Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow

No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No

Table 3: MCM 3320 Load Add Shed Configuration Table

page 5 of 6
Cummins Proprietary and Confidential

Universal Annunciator Setup for MCM3320


Preliminary/Confidential/Proprietary

4 Revision History
Revision
A
B

Date
5/15/2007
8/13/2007

Description
Document Creation.
Added configuration table

page 6 of 6
Cummins Proprietary and Confidential