Вы находитесь на странице: 1из 13

______________________________________________________________________________

blank
blank

Hussaini New Design GF


blank
blank
Tel:
Fax:
3/17/2016

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
1

______________________________________________________________________________

1. Material List
.

Picture

Rated
Total
Cooling Cooling
Power Type
Capacity( Capacity(
kW)
kW)

Model

Memo

Unit

Qty.

Unit
Price($)

Sum
Price($)

AB382MCERA

Indoor
unit

set

12

1,220230,50/60

11.2

134.4

AV48IMVESA

Outdoor
Unit

set

3,380400,50/60

135

135

PB-950JB

Panel

set

12

FQG-B1350A

Branch
Pipe

set

FQG-B730A

Branch
Pipe

set

FQG-B506A

Branch
Pipe

set

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
2

______________________________________________________________________________

Picture

Rated
Total
Cooling Cooling
Power Type
Capacity( Capacity(
kW)
kW)

Model

Memo

Unit

Qty.

Unit
Price($)

Sum
Price($)

FQG-B335A

Branch
Pipe

set

HZG-30A

Gather
Pipe

set

YR-E14

Wired
Controlle
r

set

12

Pipe-12.7

Copper
Pipe

18

Pipe-38.1

Copper
Pipe

20

Pipe-19.05

Copper
Pipe

32

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
3

______________________________________________________________________________

Picture

Total

Rated
Total
Cooling Cooling
Power Type
Capacity( Capacity(
kW)
kW)

Model

Memo

Unit

Qty.

Unit
Price($)

Sum
Price($)

Pipe-31.8

Copper
Pipe

Pipe-15.88

Copper
Pipe

53.5

Pipe-9.52

Copper
Pipe

51.5

Pipe-28.58

Copper
Pipe

28

Oil-9.52

Oil Pipe

R410A

Refrigera
nt

Kg

26

269.4

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
4

______________________________________________________________________________

2. Room List
.

Name

Area(m)

Type

Cooling
Design
Load(kW)

Cooling
Actual
Load(kW)

Heating
Design
Load(kW)

Heating
Actual
Load(kW)

Qty.

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
5

______________________________________________________________________________

3. System Construction
3.1 System1--ODU1
3.1.1 ODU

AV48IMVESA

Running Condition

Max. Combination

100%

Temperature

Actual Combination

99%

Cooling

Cooling Capacity
(Corrected/Rated)

117.13/135kW

Ind.WB

19C

Ind.DB

20C

Heating Capacity
(Corrected/Rated)

145.04/150kW

Out.DB

46C

Out.WB

6.5C

53m

Max.Drop

Power Supply

3,380400,50/60

Length And Drop

Dimensions

Max.Len.

Width

/mm

Height

/mm

Depth

/mm

Weight

1104Kg

Picture

Heating

0m

Model

Width(mm)

Height(mm)

Depth(mm)

MCA(A) MFA(A)

AV16IMVESA

1390

1808

750

33.3

40

AV16IMVESA

1390

1808

750

33.3

40

AV16IMVESA

1390

1808

750

33.3

40

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
6

______________________________________________________________________________
3.1.2 IDU

Picture

Name

Model

Cooling
Capacity(Co
rrected/Rate
d)(kW)

Heating
Capacity(Co
rrected/Rate
d)(kW)

Lab
IDU12

AB382MC
ERA

10.8/11.2

12.5/12.5

840*840*2
95

Lab
IDU6

AB382MC
ERA

10.8/11.2

12.5/12.5

Lab
IDU7

AB382MC
ERA

10.8/11.2

Lab
IDU8

AB382MC
ERA

Lab
IDU9

Size_WDH Weight(
Kg)
(mm)

Controller

MCA(A)

MFA(A)

38

YR-E14

1.38

4.4

840*840*2
95

38

YR-E14

1.38

4.4

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

AB382MC
ERA

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

Lab
IDU10

AB382MC
ERA

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

Lab
IDU11

AB382MC
ERA

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

Room

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
7

______________________________________________________________________________

Picture

Name

Model

Cooling
Capacity(Co
rrected/Rate
d)(kW)

Heating
Capacity(Co
rrected/Rate
d)(kW)

Lab
IDU1

AB382MC
ERA

10.8/11.2

12.5/12.5

840*840*2
95

Lab
IDU2

AB382MC
ERA

10.8/11.2

12.5/12.5

Lab
IDU3

AB382MC
ERA

10.8/11.2

Lab
IDU4

AB382MC
ERA

Lab
IDU5

AB382MC
ERA

Size_WDH Weight(
Kg)
(mm)

Controller

MCA(A)

MFA(A)

38

YR-E14

1.38

4.4

840*840*2
95

38

YR-E14

1.38

4.4

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

10.8/11.2

12.5/12.5

840*840*2
95

38

YR-E14

1.38

4.4

Room

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
8

______________________________________________________________________________
3.1.3 Piping

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
9

______________________________________________________________________________

Pipes Length and Drop


Length Piping Rules

Current

Max

Max.Length between ODU and frist branch pipe

20 m

135 m

Max.Length between the frist branch pipe and each IDU

32 m

40 m

Max.Length between ODU and furthest IDU

52 m

175 m

103.5 m

300 m

Current

Max

Max.Drop between ODU and IDU(ODU higher)

50 m

Max.Drop between ODU and IDU(IDU higher)

40 m

0m

15 m

Total Length of all pipes

Height Piping Rules

Max.Drop between IDUS


Max.Drop between Valve Box

Refrigerant Charged
Initial Refrigerant Charged:

30 Kg

To be Provided:

26 Kg

Total

56 Kg

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
10

______________________________________________________________________________

3.1.4 Wiring

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
11

______________________________________________________________________________

3.1.5 Dip Switch


3.1.5. IDU(0:OFF, 1:ON)
When YR-E14 used in group control system , the first unit of group control connection is set as master unit;
Name

Name

Model

SW01

SW02/CN4144

SW03

SW07

SW08

ODU1

Lab IDU12

AB382MCERA

00001010

0000

10000000

11111111

11111111

ODU1

Lab IDU6

AB382MCERA

00001010

0000

10000001

11111111

11111111

ODU1

Lab IDU7

AB382MCERA

00001010

0000

10000010

11111111

11111111

ODU1

Lab IDU8

AB382MCERA

00001010

0000

10000011

11111111

11111111

ODU1

Lab IDU9

AB382MCERA

00001010

0000

10000100

11111111

11111111

ODU1

Lab IDU10

AB382MCERA

00001010

0000

10000101

11111111

11111111

ODU1

Lab IDU11

AB382MCERA

00001010

0000

10000110

11111111

11111111

ODU1

Lab IDU1

AB382MCERA

00001010

0000

10000111

11111111

11111111

ODU1

Lab IDU2

AB382MCERA

00001010

0000

10001000

11111111

11111111

ODU1

Lab IDU3

AB382MCERA

00001010

0000

10001001

11111111

11111111

ODU1

Lab IDU4

AB382MCERA

00001010

0000

10001010

11111111

11111111

ODU1

Lab IDU5

AB382MCERA

00001010

0000

10001011

11111111

11111111

3.1.5. ODU (0:OFF, 1:ON)


The 1st & 2nd bit of BM1 of master unit should be set 0(Off position) before power on , after power on and finishing searching indoor and
outdoor address ,set 1st & 2nd bit of BM1 to 1 (On position).
Name

Model

BM1

BM2

BM3

BM4

BM5

ODU1--AV48IMVESA

AV16IMVESA

11000000

00000000

00000101

00000000

11000011

AV16IMVESA

11000001

00000000

00000101

00000000

11000011

AV16IMVESA

11000010

00000000

00000101

00000000

11000011

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
12

______________________________________________________________________________

4.Central Control

______________________________________________________________________________________________________________
The Haier Project Express is property of Haier Air-Con Elec.Corp.Ltd. Only the data published in the official documents is exactly correct.All the
data used in this program is just for your information.
13