Академический Документы
Профессиональный Документы
Культура Документы
TECHNOLOGY
DEPARTMENT OF ELECTRICAL
ENGINEERING
FUNDAMENTAL OF AC CIRCUIT ANALYSIS (EEU
07105)
LECTURER: J. MUSHI
PARTICIPANTS
NAMES
1. BAKARI .H.ABDALLAH
2. JUMA GANIYU
ADM.NO.
110333261669
110333231691
3. ABBAS S BINDE
4. JAMES MATINDE
5. ABUBAKAR HAMAD
110333221709
110333271679
110333241687
A two phase system is produced by a generator consisting of two coils placed perpendicular to
each other so that the voltage generated by one lags the other by 90o .
The diagram showing two phase three wire system;
The circuit shown is a star connection system. The power measured by two
wattmeter method is equal to the instantaneous power absorbed by the
three loads(Z1, Z2 and Z 3),as shown bellow;
W1 + W2= iR(VRN-VBN) + iY(VYN-VBN)
=i RVRN-iRVBN+iYVYN-iYVBN
=i RVRN+iYVYN-VBN(iR +iY)
But,i R + iY +iB=0, there fore
iR +iY =-iB
=P1 + P2 +P3 =P3-
Where;
P1=Power(instantaneous power) absorbed by 1st load.
P2=Instantaneous power absorbed by the 2nd load.
P3=Instantaneous power absorbed by the 3rd load.
Therefore this shows that the power measured is equal to the instantaneous
power absorbed by three loads.
3-Wattmeter method.
In this method there are three(3) watt meters (W1,W2 and W3) and connected
to the phases(R,Y and B) with neutral respectively.
Consider the diagram bellow;
POWER FACTOR
The power factor is the cosine of the phase difference between voltage and
current.
It is also the cosine of the angle of the load impedance or the ratio of the real
power to the apparent power.
Determination of the power factor from the two wattmeter method
Recall that each line voltage leads the corresponding phase voltage by 300.
Average power read by wattmeter 1 is;
W1=VLILcos(300-),
And the average power read by wattmeter t 2 is;
W2=VLILcos(300+)
From above;
W1-W2=VLILsin.(1)
W1+W2=3ILcos(2)
Divide eqn.(1) by eqn.(2)
W1 W2 VL I L sin 1
W1 W2 VL I L cos 3
W1 W2
W1 W2
tan 3
W W2
cos cos tan 1 3 1
W1 W2
fund that there are both reactive power and active power components, but in case of three phase
power expression the instantaneous power is constant. Actually in three phase system, the
reactive power in each individual phase is not zero but sum of them at any instant is zero
NOTE:
The total power of a balanced star or delta connected load is given by
P= 3 VL IL Cos
Where,
VL = line voltage
IL = line current
Cos= power factor of any phase
= phase angle between phase voltage and phase current
If the neutral point in a star-connected system is accessible, the power may be
calculated from the readings of one wattmeter whose current coil has to carry the
phase current and the voltage coil the phase voltage of the same phase. The total
Power is three times the power in one line.
P= 3. P3
In a delta or star connected system with no access to neutral point, the power may
be calculated from the readings of two watt meters whose current coils are carrying
line currents & the voltage coil are connected between the same lines and the third
line. The total power is the algebraic sum of the two-wattmeter readings.
P=P1 +P2