Вы находитесь на странице: 1из 6

InteliLiteNT

SINGLE SET GEN-SET CONTROLLER

Description
The InteliLiteNT range offers a wide choice
of integrated control solutions for gen-sets
operating in single standby mode. Based
on the field proven InteliLite architecture,
the family of controllers fulfills every
requirement from simple to complex and
AMF to MRS applications with specific
models providing modem and Internet
control, user configuration and complete
gen-set monitoring and protection.

All InteliLiteNT controllers are easy to use


with an intuitive user interface and graphic
display. All of these models also feature a
built-in event and performance log. Some
incorporate a backed-up real time clock and
others with running hours reference which
makes troubleshooting even simpler.

The new design brings seamless


integration with the latest breed of
EFI engines, which include Caterpillar,
Cummins, Detroit Diesel, Deutz, GM, Isuzu,
Iveco, John Deere, MAN, MTU, Perkins,
Scania, Sisu, VM Motori, Volvo Penta
and others. This offers a higher level of
functionality with users able to display a
comprehensive range of values from the
EFI engine on standard analog gauges and
AirGate true RMS measurement of electric values.
Modern communications made simple. ComAps powerful AirGate technology is provided
in a range of our controllers and makes remote Internet connection to the ComAp controller
easy. Just register the AirGate enabled controller on our website and from then on let ComAps
unique system locate and maintain contact with the controller, no need to worry about VPNs,
static IP addresses or corporate firewalls, simple! AirGate Simply connected. Benets
WebSupervisor Less wiring and components
The WebSupervisor system, a secure cloud-based remote monitoring system which allows
equipment fitted with various types ComAp units to be monitored via the Internet from a remote Less engineering and programming
PC or other web enabled device such as smartphone, webbook, etc. It operates in any Internet
browser and needs no special software to be installed. User can view recorded data from their
Remote monitoring helps reduce
equipment, receive email alerts on alarms and control the remote units. Dedicated applications for call-out costs of service engineers
iPhone and Android provide a truly mobile constant connection with the monitored equipment.
Optional additional 8 binary
LOCATE inputs/outputs
ComAps LOCATE system uses the power of mobile communications technology to provide
users peace of mind that the monitored asset is where it should be. LOCATE provides location Optional Internet with control and
data to the WebSupervisor system without the need for costly GPS positioning equipment and
works anywhere there is a mobile phone signal, even indoors. Not only will WebSupervisor monitoring over web pages
show the position of the monitored equipment, it will also maintain a track history and show Support of wireless Internet
route of the movement on a map. LOCATE Simply here!
Active SMS / emails
Direct communication with EFI engines
Perfect price / performance ratio
History log easy troubleshooting
and warranty claim handling
ComAp is a member of ComAp products meet the highest The product has the
AMPS (The Association of standards, with every stage of production UL Certification.
Manufacturers of Power undertaken in accordance with the ISO * UL Certification is available
generating Systems). certification obtained in 1998. for InteliLiteNT AMF 25.
Features
3 phase AMF function1) Buttons with mechanical feedback Communication interfaces
Over/Under frequency Customized front facia on request Optional RS232, RS485 (including
Over/Under voltage Modem support) or USB plug-in interface
Voltage asymmetry Inputs and outputs Modbus RTU/ TCP (requires
6/71) or up to 14/151) RS485 interface/IB-Lite)
3 phase generator protections (with IL-NT BIO8) binary inputs SNMP (requires IB-Lite)
Over/Under frequency 6/71) or up to 14/151) Optional Internet connection
Over/Under voltage (with IL-NT BIO8) binary outputs with Ethernet via IB-Lite
Current/Voltage asymmetry 3 configurable analog inputs with Online control and monitoring over web
Overcurrent/Overload wide list of predefined senders pages (embedded web server) via IB-Lite
Additional inputs/outputs Optional GSM modem/wireless
True RMS voltage measurement available2) via IG-IOM or IGS-PTM Internet via IL-NT GPRS
3 phase generator and Magnetic pickup input
mains1) voltages D+ pre-excitation terminal Mechanical and operation parameters
Voltage range 277 V p-n, 480 V p-p Optional 8 analog gauge Unit dimension 120 180 mm
Maximal measured drive outputs, compatible Sealed front face rated for IP65
voltage 300 V p-n with VDO-style gauges Hard plexiglass LCD cover
PT ratio range 0.1500 Operation temperature:
EFI engine support -20C to +70C standard version
True RMS current measurements Cummins Modbus -40C to +70C low temperature version
3 generator phase currents Engine specific J1939 for all major Power supply voltage 836 V
Current range 5 A manufacturers (see table below) Voltage drops shorter than
Maximal measured current 10 A Diagnostic messages in plain text 50 ms do not affect operation
CT ratio range 15000
SMS/Emails ANSI codes
Power measurements SMS commands
Active/Reactive Power and Emails4) ANSI code Protection
Power Factor per phase Alarm and event SMS 59 Overvoltage
Gen-set Active and Reactive
Energy counter Miscellaneous features 27 Undervoltage
Mains Active and Reactive Support of telecom applications 47 Voltage asymmetry
Energy counter1) with special firmware
81H Overfrequency
Apparent power Integrates with UPS systems5)
Fuel theft protection 81L Underfrequency
Event and performance log + RTC Mutual stand-by system 50+51 Overcurrent*
Flexible event based history Automatic temperature
46 Current unbalance
with up to 119 events based cooling/heating
Reason, running hours + all Load shedding, dummy load 32 Overload
important values are stored3) Customer logo screen 47 Phase rotation**
Reason, date and time + all Two multipurpose timers
71 Gas (Fuel) level
important values are stored2) Alternative configuration
Battery backed-up RTC2) (50Hz/60Hz) 50N + 64 Earth fault current***
Test run scheduler1) * For MRS 10, MRS 11 and AMF 20 models shortcurrent only
** Fixed setting
*** For MRS 15, MRS 16 and AMD 25 models
User interface
Graphic 128 64 pixels display
2 languages, user InteliLiteNT controllers support J1939 for all major brands:
changeable from PC Caterpillar GM MAN Sisu
Wide range of languages in package Cummins Isuzu MTU VM Motori
Setpoints adjustable via Detroit Diesel Iveco Perkins Volvo Penta
controller buttons or PC Deutz John Deere Scania and others
Large font in user interface

Accessories Order codes


IL-NT RS232 RS232 Extension board IGS-PTM2) Analog/Binary Product Order code
IL-NT RS232-485 Dual input/output module InteliLite NT
MRS 10 IL-NT MRS10
port extension board IG-IOM2) Analog/Binary
IL-NT S-USB Service USB module input/output module InteliLiteNT MRS 11 IL-NT MRS11
IB-Lite Internet/Ethernet plug-in IGL-RA152) Remote Annunciator InteliLite NT
MRS 15 IL-NT MRS15
module including Web server InteliLiteNT MRS 16 IL-NT MRS16
IL-NT GPRS GSM modem/ KEY
wireless Internet module MRS manual and remote start controller
InteliLite NT
AMF 20 IL-NT AMF20
IL-NT AOUT8 Analog outputs AMF automatic mains failure start controller InteliLite NT
AMF 25 IL-NT AMF25
for PWM gauges module 1) Only for AMF models
IL-NT BIO8 Binary input/output module 2) Only for MRS 15, MRS 16 and AMF 25 models
IC-NT CT-BIO7 2) Hybrid current input & 3) Only for MRS 10, MRS 11 and AMF 20 models
binary input/output extension module 4) Emails only for IB-Lite
IL-NT RD (SW) Remote display 5) Detail information available on request
software for InteliLiteNT controllers

InteliLite NT
Schematic diagram
or

+24V 85
S232-4
IL-NT R
S232
IL-NT R

PRS C
IL-NT G
SUPPLY

AL A
POWER VDC
8 to 36 ION
- UNICAT LE

RM
+ COMM MODU

STO
PLUG-IN

P
5
UP TO OUTPUTS
Y )
BINAR OLLECTOR
C
7 (OPEN or
UP TO INPUTS M
Y IGS-PT
SION BINAR
EXTEN MODULE IG-IOM

t eNT
PLUG-IN

InteliLi MAINS

M EA
ATOR CAN -
J1939
UT8 GENER ON B

VOL
TENSI

SUR
IL-NT AO I/O EX

M EA
5

TAG
IGL-RA1

EM E
VOL
CUR

SUR
G
ANALO

E
E
ENGIN

NT
TAG
INPUTS

REN

EM E
Y
BINAR
OUTPU
TS models

E
r AMF

NT
y fo
(OPEN TOR) A Onl , MRS
16
MRS 15
T BIO8 COLLEC Models

GEN
IL-N Only on 25

MAIN
D+ B M F
an d A

ERA
or
t:

SC
connec RD (SW),
sible to

TOR
T
C Pos ODEM, IL-N NET

RPM

.B. C
Oil P

3ph
2 PC, M R
Start

LC, INTE
Fue

/P

C.B
SC A D A

ONT
ress
Aux xcitatio
Pre

er

MAINS
l

3ph

. CO
3ph
Sole

ure

ROL
e
Alte

NTR
BIO7
noid

-NT CT- A
rnato

IC

OL
B
n
r

LOAD

1
odes
+ Fault C
Values
ATOR
GENER uest
eed Req J1939
E top - Sp
ENGIN Start/S
L/GAS
DIESE

1 ECU

Available models

MRS 10 MRS 11 AMF 20


MANUAL AND REMOTE START CONTROLLER MANUAL AND REMOTE START CONTROLLER AUTOMATIC MAINS FAILURE
START CONTROLLER

3 configurable analog inputs 3 configurable analog inputs 3 configurable analog inputs


Magnetic pickup input Magnetic pickup input Magnetic pickup input
D+ preexcitation terminal D+ preexcitation terminal D+ preexcitation terminal
6 binary inputs / 6 binary outputs 6 binary inputs / 6 binary outputs 7 binary inputs / 7 binary outputs
Automatic GCB control Automatic and manual GCB control Automatic and manual
Running hours event and Running hours event and GCB and MCB control
performance log performance log CAN with J1939 support
Running hours event and performance log

MRS 15 MRS 16 AMF 25


MANUAL AND REMOTE START CONTROLLER MANUAL AND REMOTE START CONTROLLER AUTOMATIC MAINS FAILURE START
WITH SUPPORT FOR EFI ENGINES WITH SUPPORT FOR EFI ENGINES CONTROLLER WITH SUPPORT FOR EFI ENGINES

3 configurable analog inputs 3 configurable analog inputs 3 configurable analog inputs


Magnetic pickup input Magnetic pickup input Magnetic pickup input
D+ preexcitation terminal D+ preexcitation terminal D+ preexcitation terminal
6 binary inputs / 6 binary outputs 6 binary inputs / 6 binary outputs 7 binary inputs / 7 binary outputs
Automatic GCB control Automatic and manual GCB control Automatic and manual
CAN with J1939 support CAN with J1939 support GCB and MCB control
RTC event and performance log RTC event and performance log CAN with J1939 support
RTC event and performance log
Dual AMF/Mutual stand-by system

InteliLite NT
Typical applications
PRIME POWER SYSTEM
REMOTE MONITORING VIAINTERNET

Description:

Manual and remote start of


gen-set with electronic engine.
INTERNET

IB-Lite
InteliLiteNT MRS 16 starts, controls and
monitors the gen-set and controls the
J1939 circuit breaker to supply the load.
ite M
NT RS 16 Service provider can monitor and control
InteliL

L
gen-set operation remotely via Internet.
HOTE
The controller sends active
GEN
-SET E-mails upon alarm event.
M
The generator is protected by a
INE ROO
ENG
built in over/under voltage and
frequency protections as well as
IDMT overcurrent protection.
The controller communicates with
INT
ERN
ET
engine management unit by a CAN
J1939 bus. Engine values and alarms
VIDE
R are visible on a graphical LCD screen
PRO
VICE
SER in plain language no need to learn
cryptic ashing or numeric error codes.

Scope of supply:

1 InteliLiteNT MRS 16
1 IB-Lite

S
MAIN

PRS
IL-NT G

TRANSM
ITTER
S J193
9
STANDBY SYSTEM
MAIN
NT AM F 25
Inte liLite REMOTE MONITORING VIAINTERNET
PRS
IL-NT G
S
Description:
MAIN TER INE
NSMIT ENG
TV TRA ROO
M

25
J193
9
Stand-by gen-set with electronic engine.
NT MF
ite A
PRS GEN
-S ET InteliL InteliLiteNT AMF 25 continuously monitors
IL-NT G
a mains supply and automatically starts
R
9
an engine and switches load to a standby
J193 INE
NT
ite AMF
25 ENG
ROO
M generator set in case of mains failure.
InteliL
viso
r, The service provider can monitor the gen-
per VIDER
-SET bSu O
GEN We E PR set operation remotely via GPRS modem.
VIC
SER

INE
The operator can use LiteEdit for a
ENG
M
ROO single gen-set view or WebSupervisor
-SET INT
ER NET for total eet management.
GEN or,
TheebSgenerator
rvis
upe OVIDE
R
R is protected by a
W
IC EP
built
SER in over/under voltage and
V

frequency protections as well as


,
isor R
IDMT overcurrent protection.
NEpTerv E
TeEbRSu ROVID
INW
V IC EP The controller communicates with
SER
engine management unit by a CAN
J1939 bus. Engine values and alarms
ER NET are visible on a graphical LCD screen
INT
in plain language no need to learn
cryptic ashing or numeric error codes.

Scope of supply:

1 InteliLiteNT AMF 25
1 IL-NT GPRS

InteliLite NT
Functions chart
InteliLiteNT InteliLiteNT InteliLiteNT InteliLiteNT InteliLiteNT InteliLiteNT
Product
MRS 10 MRS 11 MRS 15 MRS 16 AMF 20 AMF 25

Order code IL-NT MRS10 IL-NT MRS11 IL-NT MRS15 IL-NT MRS16 IL-NT AMF20 IL-NT AMF25

Binary inputs/outputs 6/6 6/6 6/6 6/6 7/7 7/7

Analog inputs 3 3 3 3 3 3

Input configuration l l l l l l

Output configuration l l l l l l

Magnetic pickup l l l l l l

D+ battery charging alternator


l l l l l l
circuit

AMF function/MRS function / l / l / l / l l/l l/l

GCB/MCB control with feedback l 1)/ l/ l 1)/ l 2)/ l/l l/l

Voltage measurement Gen./Mains 3 ph / 3 ph / 3 ph / 3 ph / 3 ph / 3 ph 3 ph / 3 ph

3 ph, 3 ph, 3 ph,


Current measurement 3 ph 3 ph 3 ph
IDMT overcurrent IDMT overcurrent IDMT overcurrent

kW/kVAr/ kVA/kWh/kVArh
l/l/l/l/l l/l/l/l/l l/l/l/l/l l/l/l/l/l l/l/l/l/l l/l/l/l/l
measurement

Generator protections l l l l l l

Earth fault current protection O O O

Full history file/Running hours


/l /l l/ l/ /l l/
history

RTC with battery l l l

Engine hours l l l l l l

Internet support with Web server with IB-Lite with IB-Lite with IB-Lite with IB-Lite with IB-Lite with IB-Lite

Internet support over GPRS with IL-NT GPRS with IL-NT GPRS with IL-NT GPRS with IL-NT GPRS with IL-NT GPRS with IL-NT GPRS

Active SMS/emails O O O O O O

Remote communication interface3) O O O O O O

Remote display O O O O O O

Modbus interface O O O O O O

CAN-J1939 interface l l l

Cummins Modbus O O O

IGL-RA15, IG-IOM, IGL-RA15, IG-IOM, IGL-RA15, IG-IOM,


CAN extension modules
IGS-PTM IGS-PTM IGS-PTM

Dummy load/Load shedding l l l l l l

Auto. temperature based


l l l l l l
heating/cooling

Louver control l l l l l l

Manual idle l l l l l l

UL Certification l

KEY Legend:
l included IG-IOM/IGS-PTM: Analog/binary input/output modules
excluded IGL-RA15: Remote annunciator
O optional plug-in module required GCB: Generator circuit breaker
1) Automatic GCB control MCB: Mains circuit breaker
2) Automatic and manual GCB control
3) RS232, RS485, USB, Internet, GPRS/GSM

InteliLite NT
References

Poland
USING COMAP POWER
CONTROLLERS IS A HUGE
ADVANTAGE
EPS SYSTEM produces power generators in Poland, using
mostly IVECO, VOLVO-PENTA, PERKINS and MTU engines.
Besides the production of generators, company provides and
integrates power supply systems, including installation.

During 12 years of service, we have been handling various


tasks in monitoring and control of power supply systems and
generators. The technologies in this branch are continuously
evolving which makes us resolve new and unusual
requirements given by our clients. Using ComAp power
controllers is a huge advantage not only for typical applications,
but also in executing individual requests and demands. The
vast majority of power generators we produce is equipped
with an electronically controlled fuel injection combined
with ComAp controllers and CAN interface. This simplifies
production and maintenance and also helps with diagnostics.

Norbert Szymon Broniek


Sales Manager
www.epssystem.pl

USA
STAND-BY POWER FOR
MANUFACTURING FACILITY

Our customers site had more than 10 gensets of various


makes and vintages spread out over as many buildings. As
we were commissioning a new genset on their campus, we
identified an opportunity to retrofit their existing fleet with
InteliLiteNT, giving them the ability to monitor all their sets
remotely. The remote communications flexibility has allowed
our service department torespond to our customers needs
in an instant and provide them with great service. This has
saved our customer an incredible amount of time and money.

Larry Davis
Sales Manager
www.acfstandbysystems.com

MANUFACTURER: LOCAL DISTRIBUTOR / PARTNER:

ComAp a.s.

Czech Republic
Phone: + 420246012111
Fax: + 420266316647
E-mail: info@comap.cz
Internet: www.comap.cz

Customer satisfaction is our mission. We continuously develop our people to be the best to succeed in our mission.

ComAp. Features and specification are subject to change without prior notice. 2015-02/CPLEINT

Вам также может понравиться