Академический Документы
Профессиональный Документы
Культура Документы
0-1
March 2016
Sheet 41 001
42
43
Eatons Electrical Engineering The Power Systems Automation Expertise on Products from
22 Services & Systems (PSA) group provides full-service
Eaton and Other Manufacturers
systems integration, ensuring
Eatons Electrical Engineering Services that hardware, software and Our experienced Professional
23 & Systems (EESS) group operates communication networks from Engineers, Graduate Engineers, Field
through regional service centers various manufacturers perform Engineers and Technicians are trained
throughout the U.S. and Canada. as a seamless system on products manufactured by Eaton,
24 Service centers are equipped with the Power Breaker Reconditioning as well as other manufacturers. As a
most technologically advanced test and Centers (PBRC) furnish specialized result, EESS services can be applied
diagnostic equipment. With over 1000 services, such as Class 1 recondition- to products manufactured under the
25 Field Service Representatives in North ing of power circuit breakers following brands: Cutler-Hammer,
America, Eaton expertise is available (described later in this section) Powerware, Westinghouse,
where and when customers need it. Square D, General Electric, ITE/BBC/
Division-wide Safety and Quality
26 This integrated team of technical
Programs ensure customer
ABB, Allis-Chalmers/Siemens,
experts, logistics specialists, and Federal Pacific Challenger. With
satisfaction while maintaining
customer support associates provides their extensive industry experience,
27 safety as a first priority
24 hours a day, 7 days a week, factory- our engineers can also provide expert
certified direct service. Eaton has one of the largest teams technical assistance on many models
of Power Systems Engineers in the of obsolete equipment.
28 Within and across these regional
industry, strategically located through-
service centers, specialists
out the world. Many of these
collaborate as cohesive, virtual
professionals have influenced
29 teams. For example:
industry standards and are sought
The Power Systems Engineering after for their expertise. Eaton
group uses industry standard operates a central training facility
30 software with advanced modeling where our team members return
and analysis capabilities to design for continuing education on the
power systems for new construction latest products, system upgrades
31 and facility upgrades and diagnostic tools.
34
35
36 Power System Automation Power System Turnkey Field Equipment Life Extension
Engineering Projects Services and Modernization
37 Protection and
control systems
Power systems studies
Harmonic studies
Modular integrated
transportable
24/7 emergency response
Site acceptance testing
MV and LV power circuit
breaker replacements
Dashboards Load flow analysis substation (MITS) Startup and commissioning Equipment rebuild and
Foreseer and Arc flash and safety studies Project management Maintenance and testing reconditioning
38 Power Xpert Integrated Volt-VAR Engineer, procure and Service contracts Life extension and
Enterprise solutions Control (IVVC) construct (EPC) Embedded service modernization
Power Xpert Energy CYME power Equipment install personnel Bus bracing and gear
Crisis response Training services
39 Optimizer controller
Substation automation
engineering software
NERC compliance Microgrid energy system
evaluation studies
Arc flash mitigation
Distribution automation assistance Grid storage
Selective coordination
40 study
41
42
43
22
23
24
25
26
Newfoundland
27
British
Columbia
Alberta Manitoba Quebec 28
New Brunswick
Saskatchewan Ontario
29
Nova Scotia
District Offices 30
Satellite Operations Centers
Power Breaker Reconditioning Centers 31
Figure 41.0-1. Canadian Service Locations
32
33
ME
AK WA
MT ND
MN
VE 34
NH
MA
OR
WI MI NY
ID SD RI
CT
35
WY
IA PA
CA NJ
NV
NE IN OH DE 36
IL WV MD
UT VA
CO
KS MO KY 37
NC
TN
HI
AZ OK AR
SC 38
NM
MS
GA
AL
39
TX LA
District Offices FL 40
Satellite Operations Centers
Power Breaker Reconditioning Centers 41
Power Breaker Center
Customer Reliability Center
42
Figure 41.0-2. U.S. Service Locations
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
41
42
43
43
39
40
41
42
43
43
35
36
37
Energy Monitoring and
Power Quality Screen Shots
38
39
40
41
42
43
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Arc Flash Safety Solutions Document calculations for the level Operating Cost Efficiencies
of incident energy Reduce or eliminate unplanned 22
An arc flash event releases a tremen- Issue proper personal protective downtime, equipment damage,
dous amount of energy in the form equipment (PPE) for workers fines, lawsuits, injuries and fatalities
of thermal heat, toxic fumes, pressure Training for workers on the hazards through improved system design 23
waves, blinding light, sound waves and of energized electrical work, includ- and safety practices
explosions that can result in serious ing electrocution and arc flash
injury including critical burns, collapsed Best Products. Best Services. 24
Provide appropriate tools for working
lungs, loss of vision, ruptured eardrums, Best Solutions.
on energized electrical equipment
puncture wounds and even death.
Affix arc flash warning labels Eaton offers the industrys widest 25
According to the National Fire on equipment where energized range of arc flash related products and
Protection Association (NFPA), an electrical work could be performed services. Our electrical services group
arc flash occurs when an electric
A conscientious safety program
is comprised of industry-leading 26
current passes through air between engineers who not only understand
ungrounded conductors or between incorporates an arc flash hazard how to properly apply todays safety
ungrounded conductors and grounded analysis, the implementation of standards, but many have been tapped 27
conductors. Temperatures can reach mitigation techniques, and training for their expertise by committees who
35,000F, more than three times hotter for personnel who operate and main- develop the codes that help protect
than the surface temperature of the tain energized electrical equipment. what you value most. 28
sun. These excessive temperatures Eaton can help with all three.
cause the air and metal in the path Our Commitment to Help Companies
of the arc to expand and explode, Total Arc Flash Solutions
Protect What They Value Most 29
creating an arc blast. Eaton understands that arc flash
from the Industry Experts safety is tremendously important to
Throughout the world, arc flash businesses striving to protect their 30
Eatons arc flash solutions stress
threatens personnel safety, and most valuable assetstheir people.
prevention, protection and preparation.
companies face lost man-hours, Thats why weve made a $500,000
Our products, engineering experience
lawsuits, fines, equipment damage,
facility downtime and lost production.
and industry know-how create a contribution to the IEEE and the NFPA 31
total arc flash solution to meet your Arc Flash Phenomena Collaborative
Many companies have already companys needs. We offer a complete Research Project. As a platinum level
established and implemented arc flash hazard analysis focusing on: sponsor of this important initiative, 32
enterprise-wide arc flash compliance we are supporting efforts to improve
Enhanced Safety electrical safety standards, to predict
programs that ensure employees are
safe from arc flash hazards. The 2011
Improve your facilitys overall the hazards associated with arcing 33
arc flash safety through training, faults and accompanying arc
National Electrical Code and the NFPA
labeling, analysis and products blasts, and to provide safeguards
Standard 70E mandate required safety
practices for personnel working on
that reduce or eliminate exposure for employees. 34
to dangerous situations. Meet or
energized electrical equipment.
exceed the latest arc flash related
Compliance with the latest OSHA standards, including NFPA 70E 35
standards involves adherence to Standard for Electrical Safety
a six-point plan: in the Workplace and IEEE 1584
A facility must provide, and be able
Guide for Performing Arc Flash 36
Hazard Calculations
to demonstrate a safety program
with defined processes that address 37
arc flash
38
39
40
41
42
Arc Flash Safety Solutions
43
22 Safety Means The standards are open to interpreta- An important first step to ensure
tion, so its up to you or your staff to the safety of your workplace and
Knowing Your Hazard Level draw conclusions from the general employees is a high-level assessment
guidelines. There may be instances of your companys readiness to deal
23 Ensuring that your facility has the best
possible arc flash safety plan in place
where you think youve achieved with arc flash hazards using the
compliance, when in fact, you havent checklist below. If you answer no or
is vital to the safety of your employees because you misinterpreted the not sure to any of the questions, you
24 and to the continued success of your standards. Eaton has the experience need to address your arc flash safety
business. While current arc flash safety and expertise to help you quantify program immediately. Your business
standards are being enforced ever the level of arc flash hazard in your may be noncompliant with industry
25 more strictly, they may not provide the facility and to optimize your system safety standards and at risk for an
specific attention to detail required for performance and safety program arc flash incident.
a safe work environment, even under accordingly.
26 worst case conditions.
28 All persons who operate/maintain energized electrical equipment Electrical safety training for operators and
are trained for the voltage class equipment they operate/maintain. maintenance personnel.
All persons who operate/maintain energized electrical equipment Arc flash hazard training for operators and
29 have been trained on both shock and arc flash hazards. maintenance personnel.
All persons who operate/maintain energized electrical equipment Arc flash hazard training focusing on selection
have access to the proper personal protective equipment (PPE) and use of the proper PPE.
30 to protect them from both the shock and arc flash hazards.
One-line diagram, including current protective Development of one-line diagram of your facility.
device settings, exists, is legible and accurate.
31 All persons who operate the power system have
easy access to the current one-line diagram.
Electrical safety training.
Equipment is labeled correctly, and in accordance Arc flash hazard training, labeling, protection
32 with existing safe work practice codes and standards. boundaries, PPE.
De-energized procedures and equipment exist and are used. Lockout, tagout, proper grounding; Remote Power
Racking to safely de-energize breaker.
33 Written safety procedures and energized work
permitting processes exist and are followed.
Electrical safety training.
Equipment is grounded and ground system Grounding studies, electrical safety training.
34 is tested periodically.
Proper maintenance practices are followed, especially Electrical safety training, Performance Based
for fault protection equipment. Maintenance (PBM), IR Windows and Arcflash
35 Reduction Maintenance System for safer maintenance.
Recent (less than five years old) relay/fuse coordination study Coordination and short-circuit studies.
exists, and relays are calibrated to the setting recommended.
36 Arc flash analysis has been performed for this site
(calculations, labeling and arc flash boundaries).
Arc flash hazard analysis.
1 Checklist adapted from IEEE Guide for Maintenance, Operation and Safety of Industrial and Commercial Power Systems (Yellow Book)
37 Document Number: IEEE 902-1998
38
39
40
41
42
43
Superior Protection With the Eaton products and expert services, brief description of each product and
22
Eaton has the experience and Page 41.3-6 for a hazard analysis and
Right Products and Services applications expertise to develop a training overview.
total arc flash solution for your facility.
Eatons arc flash solutions encompass To view an interactive version 23
the industrys broadest range of arc This electrical room illustration shows of this electrical room, visit
flash related products and services. how Eatons products can be applied www.arcflashsafetysolutions.com.
From a comprehensive arc flash to mitigate arc flash hazards. Please 24
hazard analysis to highly engineered refer to Pages 41.3-4 and 41.3-5 for a
25
26
1
q 6
2 27
BN
j
3 r 28
r
n
29
9
5
30
4
BK
31
s
7
BL
m o
k
l BM 8 32
t p
33
Table 41.3-2. Low and Medium Voltage Equipment to Limit Exposure of Personnel to Arc Flash Hazards
Limits Frequency
of Arc Flash Incidents
Reduces Arc Flash
Event Durations
Reduces Arc
Fault Currents 1
34
1 1200 A bypass isolation ATS
2 Arcflash Reduction Maintenance System 35
3 Arc-resistant medium voltage control
4 Arc-resistant switchgear 36
5 Bus differential schemes
6 Circuit breaker trip units with zone selective interlocking
7 Current limiting reactors 37
8 Digitrip trip unit with Arcflash Reduction Maintenance System
9 FlashGard motor control center
38
j Feeder protective relay with Arcflash Reduction Maintenance System settings
k High impedance transformers
l High resistance grounding systems 39
m Insulated bus in switchgear
n Infared (IR) windows
o KIRK key interlock
40
p Lighting panelboards
q Low voltage switchgear with Arcflash Reduction Maintenance System 41
r MCC bucket and safety switch with viewing window
s Online infared (IR) monitoring
t Partial discharge sensors
42
BK Protective devices with current limiting and high speed operation
BL
BM
Remote monitoring, control and diagnostics 43
Remote power racking
BN Secondary fault clearing using conversion of primary breaker
1 Caution: Lowering the fault current may result in a longer clearing time by the upstream device. Please contact Eaton to ensure proper application.
23 Your Industry within your electrical system. When built on arc free designs intended
a fault is detected, tripping occurs to drastically lower the probability
1 1200 A Bypass Isolation ATS instantaneously for faults only of the creation of an arc flash. The
The bypass isolation transfer switch within that particular zone, leading features of this motor control center
24 capitalizes on Eatons experience in to greater reliability throughout the include: three-position MCC bucket
designing and building low voltage facility, increased personnel safety, (connected, test and withdrawn),
switchgear. Many features from our and elimination of intentional time through-the-door racking mecha-
25 Magnum switchgear have been delay. Eaton can engineer a system nism and high short-circuit ratings.
incorporated for improved safety of bus differential schemes on new
j Feeder Protective Relay with
and reduced arc flash hazards, or conversion equipment.
26 including dedicated wireway and 6 Circuit Breaker Trip Units with
Arcflash Reduction Maintenance
safety barriers isolating personnel System Settings
from line and load. Zone Selective Interlocking When properly applied to a power
27 Zone selective interlocking breaker, the FP-5000 feeder relay
2 Arcflash Reduction deactivates the preset delay on the and a selector switch use control
Maintenance System circuit breaker closest to the fault, logic to automatically change
28 Available as a trip unit conversion which then trips with no intentional the overcurrent settings to reduce
to a low voltage power breaker, the delay. This reduces the amount of fault clearing time and to lower
Arcflash Reduction Maintenance time current flows and the amount the available arc flash energy at
29 System uses technology to reduce of arc flash energy and stress (I2t) the connected downstream devices.
fault clearing time and to lower the the system encounters during The result is a reduction of the
available arc flash energy at the fault conditions, resulting in incident energy, allowing for
30 connected downstream devices. improved personnel protection improved personnel safety while
The system may be activated at the and prolonged equipment life. eliminating the need for higher
breaker or from a remote location. levels of costly PPE.
7 Current Limiting Reactors
31 The result is a reduction of the
Current limiting reactors connected k High Impedance Transformers
incident energy, allowing for
improved personnel safety while in series are primarily used to Eatons transformers with increased
32 eliminating the need for higher reduce fault currents and to match impedance values drastically
levels of costly personal protective the impedance of parallel feeders. reduce the available arc fault
equipment (PPE). For example, low voltage motor con- current. The lower arc flash energy
33 trol centers can be supplied in a system generally translates into
3 Arc-Resistant Medium with three single-phase reactors improved personnel safety.
Voltage Control that limit available short-circuit
l High Resistance
34 AMPGARD medium voltage current, providing a reduction in the
available fault and arcing current Grounding Systems
control affords the highest levels of
at the equipment. Eatons high resistance grounding
safety and flexibility in the industry.
system limits the magnitude of
35 The SL-400 vacuum contactor has 8 Digitrip Trip Unit with Arcflash current during a ground fault,
the highest interrupting rating
Reduction Maintenance System thus reducing arc flash energy to
(8500 A), providing full coordination
Eatons Digitrip trip units for low increase personnel and equipment
36 with the starter main fuses. The
and medium voltage applications protection. Operators are alerted to
isolation switch is rated for 10,000
feature an integral selector switch faulted conditions and can easily
mechanical operations, offering
with five arc flash reduction locate the ground source via built-in
37 reliability even when the switch is
settings, enabling the operator fault tracing. Application of high
frequently operated. The unique
to pre-select the maximum arc resistance grounding systems
features of arc-resistant AMPGARD
flash reduction level possible to limits the current and resulting
38 ensure that the highest energy
avoid nuisance tripping during energy in the event of a single-
levels are directed to the rear of
maintenance operations. Testing line to ground fault, significantly
the structure and away from
has confirmed the maximum increasing personnel safety.
39 the operator.
protection setting can significantly
4 Arc-Resistant Switchgear reduce incident energy, resulting in
In addition to providing maximum a lower incident energy and thus,
40 safety through circuit separation reduced PPE requirements.
and isolation preventing access to
live parts, Eatons arc-resistant
41 medium voltage switchgear incor-
porates sealed joints, top-mounted
pressure relief vents, reinforced
42 hinges or latches, and through-
the-door racking, minimizing
exposure to harmful gases and
43 significantly reducing the risk of
injury to facility personnel in the
event of an arc flash event.
22 A Comprehensive Arc Flash You can be certain that Eatons exten- We understand that a one-size-fits-all
sive experience in arc flash hazard approach to training doesnt fit every
Hazard Analysis analysis will provide the best solutions situation, so in addition to our power
to protect what you value most. systems training classes, we offer
23 An arc flash hazard analysis is critical to
the safety of plant personnel working
customized training specifically
designed for your companys unique
on or near exposed energized electrical An Industry-Leading Arc Flash requirements. Furthermore, if its not
24 equipment. The analysis will quantify
Safety Training Program practical for your staff to train at one of
the release of thermal energy associ- Eatons facilities, we can conduct the
ated with potential arc flash hazards A top-notch safety plan incorporates training at your site.
25 and will describe safety recommenda- not only arc flash hazard analysis
tions such as establishing protection recommendations, but also practical The following is a brief overview of
boundaries and specifying protective training for personnel who operate Eatons one-day Understanding
26 equipment for personnel. and maintain energized electrical Arc Flash training program.
Many offer this service, but few offer equipment. Eaton offers both. Existing and proposed standards
such extensive expertise backed by a While some trainers simply recite Determining safe approach
27 full line of mitigating products and information from published manuals, distance
services as Eaton. Eatons trainers are the same electrical Methods for calculating
28 Eatons highly qualified power engineers who perform arc flash prospective short-circuit current
systems engineers (PSE) have hazard analyses and install, NFPA 70E methods for calculating
performed thousands of studies for commission, troubleshoot and flash protection boundary distance
29 all types of industries. Every PSE has maintain electrical equipment and incident energy value
access to a variety of analysis tools to every day. When you train with us,
IEEE standard 1584 methods
best address the safety risks of your youre assured of getting the most
for calculating arc flash protection
30 unique system. Our combined use of current information, techniques
boundary distance and incident
commercial and proprietary software and procedures available to keep
your personnel safe and your energy value
uses IEEE and NFPA equations and
Selecting protective clothing and
31 methods for comprehensive and processes running.
PPE using incident energy exposure
accurate calculations, including fault
current momentary duty, device EducationThe Key to Better value and the PPE matrix
32 clearing time, arcing fault currents, Arc Flash Safety Arc ratings for common types
duration of arc and incident energy. of garments
Eatons arc flash safety training will
Eatons PSEs draw on past experience, Practical methods for reducing
33 show you how to determine the
training and understanding to analyze arc-flash hazards
incident energy value and flash
the figures and to develop recommen- protection boundary distances for the Eaton can award 0.8 CEUs for the
dations that are compiled in a written equipment in your facility. Youll learn
34 report. Upon request, the PSE will to use that information in selecting
successful completion of this training.
verbally present the findings in clear electrical components designed to To learn more, contact Eatons electrical
and easily understandable terms. minimize arc flash hazards, and how training group at 724-779-5852 or
35 to choose personal protection EETraining@eaton.com.
A comprehensive arc flash hazard
analysis includes the following equipment (PPE) according to the Partnering with Eaton to perform arc
36 services: National Fire Protection Associations flash analysis, to implement mitigation
Standard 70E (NFPA 70E). And techniques, and to train your personnel
Arc flash system studies, because we know that PPE can will give you confidence that you
calculations and consulting
37 be bulky, uncomfortable, limit have an enterprise-wide arc flash
Arc flash labeling dexterity and expose workers to heat compliance program that ensures
Creation and/or verification exhaustion problems, we continually employees are safe from arc
38 of one-line electrical drawings search for, and incorporate into our flash hazards.
training, safe ways to minimize the use
Short-circuit and coordination
of PPE. Our training will reveal how
studies
39 Recommendations to help achieve
a proper examination of your power
distribution system can help you
a safer environment for personnel avoid overdressing for necessary
include:
40 Arc flash boundaries
operational and maintenance tasks.
Power System The InsulGard and BushingGard The Instant Response Center is the
relay remote monitoring offering vanguard of Eatons Knowledge 22
Monitoring Services can provide advanced notification of Management Services. Knowledge
impending failure of equipment in Management is a broad term that
Electrical distribution systems are time to have it repaired before cata- describes the application of a variety 23
being subjected to higher loads and strophic failure and longer more of related technologies and expert
greater harmonics than ever. Real-time expensive downtimes occur analytical services that transform
monitoring and remote control of data into information, and information 24
power systems helps identify problem into knowledge. Data is collected by
areas, pinpoint the root cause, enable Instant Response remotely monitoring customers
quick resolution, and if necessary, enact
Center Services electrical distribution and related 25
remote control of power distribution systems via the Internet, and trending
equipment. These actions prevent key parameters related to energy and
General Description
costly outage and loss of productivity utilities, power quality, predictive 26
and equipment, while extending the Eatons Instant Response CenterSM diagnostics, environment and key
life of the electrical system. (IRC) is staffed by power systems events. This data is converted to
In addition, with the advent of utility
engineering and power quality information through expert analysis 27
experts, monitoring your electrical by power systems engineering, power
deregulation, having accurate power distribution system in real-time. The
usage values enables you to negotiate quality and energy management
a better position for power purchases.
IRC continuously monitors power experts. This information is then 28
distribution equipment for changes transformed into knowledge using
in performance or other conditions data mining techniques and the
that could signal an impending application of predictive algorithms 29
power failure. When changes exceed to extract trends and patterns that
predetermined thresholds, the IRC will predict equipment failure, provide
issues alerts to service personnel short- and long-term maintenance 30
via Internet, e-mail, text or voice recommendations and identify energy
messages and wireless page. cost reduction opportunities.
Eaton power systems experts can then
31
Using the latest communications
remotely and securely access real-time technologies, such as wireless
data from the subscribers system, videography, it is also possible to 32
often correcting a problem before extend this high-end expertise
electrical service is impacted, deliver- to field technicians or customer
ing to customers a quantifiable return personnel to guide them through 33
on investment based on maximum sophisticated problem diagnosis,
uptime, extended equipment lifetime, troubleshooting or repairs.
and reduced energy costs. 34
System outages can be prevented or Benefits
mitigated, equipment life extended, Experts are readily available
and operating, maintenance and Eliminates the cost of bringing
35
energy costs reduced by monitoring experts on site
key system wellness parameters
such as: Event analysis 36
No employee turnover
Current, voltage and energy
Plant-Wide Electrical Power Power quality and harmonic content 37
Monitoring and Control Partial discharge
Vibration
Plant-wide electrical power distribution 38
system monitoring and control can Temperature
be cost-effectively implemented during Power factor (transformer bushings)
new construction. Eaton electrical
Key events (oscilligraphy) 39
products allow for communications
through all levels of the power Energy monitoring
distribution and power protection Inverter monitoring 40
network. For example: Environmental condition monitoring
such as humidity, temperature, dust,
Eatons Power Xpert Architecture
allows for plant-wide monitoring
smoke and the presence of water 41
and control from a single work-
station or from any number of
workstations connected to a plant
42
LAN, company, intranet or Internet
Power Xpert and Foreseer systems Eatons Instant Response Center 43
give administrators full visibility
over networked UPSs across the
enterprise, along with other elements
of the critical facilities infrastructure
41
42
43
Transformer neutral sensor 15 kV; tank, core or cable Transformer Bushing Monitoring
22
shield grounding 2.5 kV; and isophase Software (Digital Option)
Predictive Diagnostics sheath 1.5 kV. The sensor system also The Eaton monitoring software
includes overvoltage protection to is compatible with systems using
suppress all overvoltages, arising Microsoft Windows 95 or higher 23
during transformer operation, below operating systems. With this software,
this level. Temperature sensor, if used an analyst can display power factor
with a digital device, is of a standard (PF) value for the group of three 24
RTD type. Sensors also have provisions bushings (up to three groups), store
for periodic partial discharge measure- and trend PF value for all monitored
ments online, using separate instru- groups (up to three), show trends of PF
25
mentation designed for this purpose. readings versus temperature, set alarm
thresholds, receive alarms when PF
values reach preset thresholds, and
26
print and plot historical data.
Transformer Bushing Monitoring 27
Calibration, Manuals and
Baseline Measurements
Bushing Power Factor, Partial Eaton provides full field calibration
28
Discharge and Vibro-Acoustics and startup. A separate independent
power factor test is performed of each
Transformers, with a primary voltage
bushing as part of the startup and
29
at or above 68 kV, and containing
capacitive taps on the primary bushing, calibration process. Transformer
should be equipped with a continuous bushings are calibrated and baseline 30
monitoring system to allow for pre- measurements obtained. Part of the
and post-shipment measurement of field startup service includes obtaining
bushing power factor and internal post-installation baseline measure- 31
partial discharges. ments to ensure no defects have
Online Transformer Insulation
resulted during bushing installation
Monitoring System
Transformer Bushing Monitoring System and/or transformer transportation, 32
Eatons system monitors the changes Transformer Bushing Monitoring installation and startup. A report with
in bushing insulation, for the set of Instrumentation any recommendations is also provided.
three bushings in a group, based on Eaton predictive analysis instrumenta- A complete manual is supplied for both 33
changes in bushing capacitance or tion delivers precise continuous the instrumentation and the software,
bushing power factor. The system measurement of capacitive current describing the operation of the
detects changes of power frequency through the bushing insulation while instrumentation, calibration and 34
current through the bushing insulation. the transformer is energized. The troubleshooting.
If the transformer has six or nine bush- minimum detectable change in current Online Transformer Partial
ings (two or three windings), additional is 0.1% of initial current. Temperature Discharge Monitoring 35
systems can be installed as required. deviation of the signal is the same
The measured current through the order. The display is available from the Eaton also installs partial discharge
bushing insulation cannot be less bushing monitoring instrumentation sensors to allow for online PD
measurements within a transformer.
36
than 2 mA. The system also provides for one complex PF signal per bushing
for connecting instrumentation for group, which will include the display Partial discharge measurement
periodical partial discharge measure- of the current power factor value. can be periodically obtained while 37
ments using portable equipment The following output signals can the transformer is online and in
without requiring a transformer also be provided as required: two normal operation, using separate
outage or any modifications to the alarm signals (dry contacts) for a instrumentation designed for this 38
sensing circuit. local alarm system, and additionally purpose. The measurement system
420 mA DC output for an analog can assess the insulation condition
Transformer Bushing based on PD measurement of the 39
re-transmitting or serial interface for
MonitoringSensors bushings and transformer windings
digital re-transmitting. Instrumenta-
The power factor sensors are tion is completely isolated from high insulation. The system is also capable
connected to the bushing capacitance voltages and features immunity to of detecting sparking in the core, 40
taps. All sensors are designed for out- high voltage transients. Full field sparking associated with connections,
door installation within the ambient calibration procedures are supplied and sparking associated with
temperature minus 50 C to plus 50 C. with the instruments operation the static electrical discharges. 41
Insulation level (withstand 1 minute manual. All necessary connections
AC voltage) between primary and for the selected options are supplied
secondary circuits is: bushing sensor with startup and baseline calibration. 42
1.5 kV plus overvoltage protection;
43
Online Transformer Monitoring Online Transformer MonitoringPeriodic Partial Discharge Testing of Medium
22 Sensors and Instrumentation Partial Discharge Analysis Software and High Voltage Equipment
Sensors are noninvasive and have The Eaton expert monitoring system
no connection to the energized applies analysis software, during Online Monitoring and Partial
23 components. Sensors are designed periodic measurements, with the Discharge Analysis
for outdoor installation, to plus or following features: display of PD data, Approximately 80 percent of all
minus 50C of ambient temperature. statistical processing of the PD
24 Sensors are connected, as required data, data storage and editing, and
equipment failures occur on a random
basis and are not age-related. Certainly,
based on the field conditions, to the instrumentation control. All data a well-designed, time-based preventive
following locations: bushing capacitor from the test is automatically saved
25 taps, transformer neutral connection, to a database and stored on a hard
maintenance program can reduce
failure rates, but what about these
tank grounding, core grounding, disk in a data format compatible with 80 percent of equipment failures that
electrostatic shield grounding, surge Microsoft Windows applications such
26 arresters, isophase bus enclosure as Word, Excel and Access. All
occur on no timetable? You could
increase the rate of preventive
bonds and grounds. The sensor standard Microsoft Windows control maintenance activities, but that is
frequency range of operation is 500 kHz functions, such as printing and cut-
27 to 50 MHz. Insulation level (withstand and-paste operations, are available
no solution. These activities tend to
be invasive, introducing new defects
1 minute AC voltage) between primary within the software. Upon initiation, that can actually increase failure
and secondary circuits is: bushing the software performs self-diagnostic
28 sensor 1.5 kV plus overvoltage procedures to ensure all components
rates, resulting in infant-mortality
failure patterns.
protection; neutral sensor 15 kV; are operating correctly.
tank, core or cable shield grounding Under pressure to deliver ever higher
29 2.5 kV; and isophase sheath 1.5 kV. Online Transformer Monitoring levels of availability, facilities managers
Calibration, Manuals and are looking for a better way. Predictive
The sensor system also includes Baseline Measurements technologies increase system reliability
30 overvoltage protection to suppress Part of the field startup service includes without undue, invasive preventive
all overvoltages, arising during obtaining post-installation baseline maintenance tasks. Eaton predictive
transformer operation, below this measurements to ensure no defects diagnostics offers predictive diagnostic
31 level. Part of the field startup service have resulted during bushing installa- equipment and systems for medium
includes obtaining post-installation tion and/or transformer transportation, and high voltage equipment. Much
baseline measurements to ensure no installation and startup. A report with of our technology is based on the
32 defects have resulted during bushing recommendations is also provided. measurement and analysis of partial
installation and/or transformer trans- discharges (PD). Partial discharges are
portation, installation and startup. A Traditional Transformer Startup a well-known and an industry-accepted
33 report with any recommendations is and Acceptance Testing indicator of insulation deterioration
also provided. The transformer predictive diagnostics that lead to equipment failure.
34 Online Transformer Monitoring and field startup tests described in
this section are completed by Eaton InsulGard Predictive Relay for
Measurement Parameters Continuous Monitoring and Analysis
personnel, in addition to traditional
The Eaton instrumentation measures transformer factory and field accep- of Partial Discharges
35 the following: apparent partial dis- tance testing, in accordance with ANSI, The InsulGard system can be used for
charge magnitude of each impulse, IEEE and other applicable testing applications rated for 400038,000 V,
number of impulses per cycle, phase
36 position of each discharge impulse,
standards. For example, a separate including the following equipment:
independent power factor test is
impulse repetition rate, impulse required of each bushing as part of the Motors/generators (RTDs are also
discharge power, and peak discharge used as sensors)
37 magnitude of the impulses.
startup and calibration process. These
Switchgear systems
additional tests immediately indicate
The following quantities are plotted any problem related to manufacture, Bus ducts
38 and displayed in a report format: transportation, installation and startup. Power center transformers
apparent discharge magnitude of In addition, Eaton predictive diagnos-
Gas insulated substations
each impulse, number of impulses tics provides a method to complete
Splices and terminations of cables
39 per cycle, phase position of each future predictive diagnostics, online,
discharge impulse, impulse repletion without any equipment outage, Eaton has a complete suite of
rate, impulse discharge power, peak therefore extending equipment life predictive diagnostic solutions as
40 discharge magnitude of the impulses, and enhancing equipment uptime. shown in Table 41.4-3.
impulse count and PD magnitude
versus phase position representation
41 and impulse PD power. This informa-
tion is provided to support the findings
and recommendations, which are
42 contained in a field report.
43
38
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Circuit Breaker Conversion Reconditioning Service for Low Factors that affect the life of these
22
circuit breaker subsystems include:
and Replacement Services Voltage Power Circuit Breakers time, ambient temperature, humidity,
General DescriptionApplication cleanliness of the environment (con-
Eaton has more than 50 years of tamination and corrosive elements), 23
experience in manufacturing power Low voltage power circuit breakers number of normal load operations,
distribution and protection systems, is are designed to be serviceable over number of fault current interruptions,
a member of the National Electrical a long service life. These breakers load current magnitude and 24
Manufacturers Association (NEMA), and associated switchgear have been maintenance cycle.
has representation on IEEE/ANSI C37 available in the industry for more
Switchgear Working and Balloting than 50 years, and there is a large While periodic maintenance, cleaning, 25
Groups, and owns and operates an installed base of equipment from lubrication and testing of the circuit
engineering services organization with many manufacturers throughout the breaker can and will prolong its life,
more than 30 field service locations. United States and Canada. at some point, the circuit breaker must 26
You can count on Eaton for effective either be completely reconditioned
conversion and replacement products The low voltage switchgear is essen- or replaced. Failure or mis-operation
tially static. It consists of structures,
and services to modernize your circuit
buswork, control wiring and metering
of any of the breakers subsystems will 27
breakers and motor control systems. render it ineffective for its intended
components. If periodically cleaned, purpose and dangerous for personnel
Conversion and replacement services it will last almost indefinitely. Low
are performed by experienced, voltage power breakers are the
or downstream equipment. 28
factory-trained field engineers and essential elements of the switchgear. Class 1 reconditioning of the low
technicians who are familiar with the These devices are required to properly voltage power circuit breaker is a
installation and startup of replacement conduct the normal load current for the cost-effective method to restore all
29
products and retrofit kitsas well as vast majority of time, and still provide of the breakers subsystems to full
testing and commissioning procedures the means of interrupting an overload functionality and prolong the life of
required for failsafe operation. Field or fault current whenever it may occur. the breaker for many additional years.
30
engineers have product expertise that
enables them to offer initial training These breakers contain insulation Reconditioning Service for Circuit
to the owners on-site operators and systems (600 Vac normal three-phase Breakers from Many Manufacturers 31
maintenance personnel while commis- voltage or less), conductors (from Class 1 reconditioning is available for
sioning new/replacement equipment. 225 to more than 6000 continuous all major manufacturers low voltage
amperes), a mechanism to open and power circuit breakers that have been
32
Representative services: close the breaker, a trip system to produced over the last 50 years.
provide protection of the circuit and These breakers are rated at 600 Vac,
LV and MV recondition and the circuit breaker, and an interruption 2256000 A continuous, 15,000
33
remanufacture system (arc chutes and contact 200,000 A interrupting. Manufacturers
LV breaker conversions for all structures) that can handle fault include, but are not limited to: 34
OEM products currents as high as 200,000 A.
AR Series LV air replacement Westinghouse
breakers While some breakers are fixed
Cutler-Hammer
VR Series, medium voltage (MV)
mounted (bolted into the switchgear),
General Electric
35
most are drawout versions for ease
vacuum replacement circuit of inspection and maintenance, as ITE
breakers for many OEMs well as to provide maximum isolation ABB 36
MCC recondition and of the load. These drawout breakers Allis-Chalmers
remanufacture include primary disconnects (for
Siemens
Network protector service the three-phase conductors), secondary 37
disconnects (for breaker control Square D
Navy shipboard breakers
wiring), a levering-in mechanism Federal Pacific
Commercial products for dedication
in Nuclear Class 1E safety-related (to assist in the insertion and with- Federal Pioneer 38
applications drawal of the breaker) and an interlock
system (to ensure that a closed breaker
cannot be inserted or withdrawn 39
from the connected position).
Additional common options to low 40
voltage power circuit breakers include
electric operation of the mechanism,
shunt trip and close coils for remote 41
operation of the breaker, undervoltage
trip systems, and additional auxiliary
switches for annunciation and 42
control schemes.
43
Advantages of Eaton Quality Control and National Standards Measure the trip button/actuator
22 Reconditioning Services All reconditioning will be conducted device force using a force gauge
Eatons electrical business is the world under the direction of a quality control Verify continuity of current
leader in low voltage power circuit and reconditioning standard, pursuant limiting fuses (if equipped) and
23 breaker and trip systems technology. to ISO-9001 certification. A quality measure the resistance using
Our EESS group is uniquely positioned certificate will document the progress a 10 A conductor; check blown
to provide Class 1 reconditioning of of each breaker through the recondi- fuse indicators integrity
24 low voltage power circuit breakers. tioning process. Eaton has multiple Verify overcurrent trip device
locations (minimum of five) strategi- operation via primary injection
All Class 1 reconditioning is done at cally located throughout North America
25 Eatons Power Breaker Reconditioning that share best practices of recondition-
(not required if a trip unit retrofit
Center (PBRC) facilities dedicated to is to be installed)
ing and work to a consistent national
this purpose. These facilities use state- standard. They use the same task- Additional tests for electrically
26 of-the-art equipment to clean, plate, specific equipment for cleaning and operated breakers:
assemble and test the breakers. Each testing at all locations to ensure the Charge the breaker; close and
facility uses identical standards and quality of the product. trip electrically
27 procedures in the reconditioning
Verify undervoltage, pickup and
process. Reconditioned breakers are Receiving and Data Collection
dropout (if equipped)
tested to the same standards as new Upon receipt at the reconditioning
28 production breakers. Breaker test center, the following process will be Check auxiliary switch operation
results are stored in a North American performed on each breaker: and condition
database, which facilitates predictive The results of all the above tests and
29 maintenance and trending. All Assign a unique job and breaker measurements will be entered into the
manufacturers breaker information identification number Eaton centralized database.
is stored in our Power DB Database and Record all nameplate data,
30 is available to every PBRC performing customer identification, existing trip Breaker Disassembly, Cleaning
the work. Original OEM replacement settings, and all numbers unique and Preparation
parts are exclusively used to replace to each breaker by direct entry The circuit breaker will be
31 broken, out of specification or missing into a national computer database completely disassembled to its
components. archive for future use and retrieval component parts. All parts will be
If electrically operated, record inspected for wear and physical
32 Supported Standards for Circuit
all accessories included on the damage
Breaker Reconditioning
circuit breaker, as well as the close, All heavily carbonized components
The converted breaker will be trip and charge volts. The latest copy will be cleaned and degreased
33 designed, manufactured, applied, of the customers control schematic in a Vaque Wet Blast System to
installed and certification tested will be obtained prior to disassem- produce a smooth finish without
in accordance with the latest bly and/or test. Eaton can retrieve degrading the components surface
34 applicable sections of the control schematics for the breakers All current carrying parts, main/
following industry standards: it manufactured arcing contacts, ground contacts
35 IEEE/ANSI C37.13 The circuit breaker will be inspected and primary disconnects will be
IEEE/ANSI C37.16 for physical damage. Parts that need cleaned, burnished and polished in
to be replaced will be recorded. a TOREX vibratory system loaded
IEEE/ANSI C37.17
36 IEEE/ANSI C37.50
A quotation will be issued to with a medium specifically designed
the customer for replacement to clean silver plating. Dry blasting
IEEE/ANSI C37.59-1996 of the defective part(s) or other abrasive cleaning systems
37 IEEE/ANSI C37.100
Preliminary Testing and Inspection
that can remove silver plating or
UL 1066 (for originally UL listed distort the contacts surfaces will
The breaker will be manually and/or not be used
and labeled designs)
38 electrically operated. The following All pole piece moldings and insulat-
tests will be performed. ing components will be cleaned
Tests for all breakers: in a Giant ceramic polisher that
39 Each primary pole insulator will
cleans and polishes the components
surface without scratching. After
be tested for dielectric integrity
cleaning, each component shall
40 by applying 1000 Vdc between
each conductor and ground, and
be dried to obtain 1000 megohms
when megger tested at 1000 Vdc.
between line and load
They will be sealed with a dielectric
41 With the breaker closed, the grade sealant
contact resistance using a 10 A
conductor will be measured
42 Measure the trip bar force
using a force gauge
43
All heavily soiled and/or greasy Circuit Breaker Reassembly Test Procedures
items including mechanisms will be and Adjustment 22
initially cleaned in a nonabrasive General Production Testing
The process includes the
agitator filled with a biodegradable following steps: Each reconditioned LV power circuit
cleaning solution capable of breaker will be tested to the applicable 23
degreasing, de-scaling and Reassemble the circuit breaker sections of IEEE/ANSI C37.50 Section 6
deburring without degrading the frame using new yellow zinc and UL 1066 if the breaker was
components surface and without the dichromate-plated hardware originally UL labeled. The testing 24
introduction or embedding of grit or Search the database of manufac- will include but not be limited to:
other abrasive materials turer specifications to determine the Measuring and recording trip 25
All frames will be stripped to bare originally recommended lubricants. bar force
metal in preparation for plating If the original lubricant formulation
Setting of the microprocessor trip
After cleaning, all ferrous metal is no longer available, substitute a
frames, mechanism parts and link- comparable or superior alternative Performing control and secondary 26
ages will be plated with yellow zinc designated by the new breaker wiring and device check tests
dichromate to provide superior rust design group Performing dielectric
resistance to exposed and hidden Reassemble, lubricate and reinstall withstand tests 27
surfaces. Painting of covers, handles the operating mechanism on the Performing no-load operations tests
and indicators will be done circuit breaker frame Verifying interlock and cell interface 28
A detailed inspection will be Reassemble, lubricate and install the Test position dielectric withstand
performed on all mechanism main and arcing contact compo- (original UL labeled breakers only)
components and linkages to detect nents as recommended by the 29
stress fractures and excessive wear original manufacturers Information Trip Bar Force Measurement
that can cause premature failure. Reassemble, lubricate install Measure and record the circuit
Magnification will be used on and align the racking mechanism breakers trip bar force. 30
small components if necessary and electrical and/or mechanical
Arc chutes will be hand-wiped charging mechanism (if applicable) Microprocessor Trip Device Setting
and cleaned with a clean dry cloth. Install all electrical components Direct-acting trip devices will be 31
They will be megger tested at and secure wiring harness (if tested/calibrated to determine
1000 Vdc. If the megger value is less applicable) their conformance to published trip
than 1000 megohms, the arc chute Align the contacts for proper surface
characteristic curves. Each breaker 32
assembly will be dried and retested. will be primary injection tested using
wipe and mating. Perform a contact a sinusoidal-wave-shape, single-phase
If the retest value is greater than wipe test. Verify that the percent
1000 megohms, then arc chute contact wipe and the wipe width
60 Hz current at a convenient voltage. 33
surface will be sealed with the The primary injection test device will be
are per the original manufacturers computer controlled to ensure accuracy
manufacturers recommended information
dielectric grade clear sealant. in the applied currents. The primary 34
Adjust the main contacts for injection test device will be capable
If the retest value is still less than
1000 megohms, then the arc proper gap, pressure and contact of direct output of the test results
chute will be replaced resistance, and adjust arcing to a printer or storage device. The appli- 35
contacts for proper gap per the cable tests will be performed.
Charging motor (if so equipped) will original manufacturers Information
be removed. The drive shaft bush-
ings will be inspected and replaced Install new Eaton Digitrip Long-time-delay-element pickup 36
microprocessor trip system Short-time-delay-element pickup
if worn. The motor will be cleaned
and reconditioned. All ratchet pawls where specified Instantaneous-element pickup
and springs will be inspected and When a new trip device is added to Time delay of long-time-delay 37
replaced or repaired if necessary the breaker or when changes are element
made to the original mechanism Time delay of short-time-delay
Gearbox (if equipped) will be
or arc interruption system, an element
38
removed, disassembled and
additional nameplate shall be
fully inspected. Any defective Ground-element pickup
installed in accordance with
or leaking components will be
IEEE/ANSI C37.59-1996 section Time delay of the ground element 39
repaired and cleaned
8.3 and shall include the unique Control, Secondary Wiring
serial/identification number and Devices Check Test 40
Perform control, secondary wiring,
and devices checks per IEEE/ANSI
C37.50.6.3 to verify that all connections 41
are correct per the wiring diagram.
Those circuits for which operation or
testing is not feasible will be checked 42
for continuity.
43
40
41
42
43
39
40
41
42
43
36
37
38
39
40
41
42
43
40
41
42
43
22 Low Voltage Breaker The expected life of an LV-VSR vacuum VSR Designs
starter would be over 50 years. Westinghouse DS
Drawout Vacuum Starter
The LV-VSR vacuum starter uses GE
23 Replacement state-of-the-art Eaton vacuum inter- ITE
rupters. The interrupters employ the and others
latest vacuum technology with long
24 life, resistance to environmental Contact EESS at 877-276-9379 for
contaminants, and positive contact more details.
wear indicators.
Life
25 The integral, solid-state trip units Exceptional electrical and mechanical
used on the air circuit breakers are life is offered by the V201 contactor
designed primarily for cable and up to 1,000,000 electrical operations
26 transformer protection. Motors require and 2,500,000 mechanical operations,
more precisely set overcurrent devices even under harsh conditions.
that prevent motor damage as well
27 as avoiding nuisance tripping. A Drawout Capability
solid-state relay, Eaton Type C440, The LV-VSR is mounted on a drawout
provides overload protection and frame and maintains the safety inter-
28 phase unbalance protection. This locking system of the LV switchgear.
relay was exclusively designed for
DB-25 LV-VSR Ease of Installation
motor protection.
29 The LV-VSR may be inserted into a
General Description Motor Starter standard breaker compartment with-
Eatons low voltage VSR is a self- The LV-VSR consists of an Eaton out modification to the compartment.
30 contained vacuum starter replacement V201 vacuum contactor, Class J The primary and secondary contact
for a low voltage drawout air circuit current limiting fuses, multi-function structures and drawout mechanism
breaker used for motor starting motor protective relay, three current are identical. The LV-VSR control
31 applications. transformers and an integral control scheme will interface with standard
power transformer. switchgear wiring with no cell
In some cases, LV air circuit breakers modifications and remote control
32 are used for motor starting applications. Vacuum Contactor schemes, if existing, are maintained.
Air circuit breakers are not designed Eatons V201 vacuum contactor is
to withstand the frequent switching designed for starting and controlling Safety Features
33 service and mechanical stresses three-phase, 50/60 Hz AC motors. The LV-VSR vacuum starter retains
associated with repetitive motor Current interruption is contained all the safety features of the LV
starting duty. This is due to the breaker within the vacuum bottles and no arc switchgear including:
34 mechanism that must be designed byproducts are vented to the outside
to close and latch against a fault. In environment. Contact condition is Racking the LV-VSR vacuum starter
order to meet these requirements, the given by wear indicators. is prevented while the contactor is in
35 mechanism must close at high speeds the closed position. Closing the
with a great deal of force. Frequent Series Current Limiting Fuses LV-VSR vacuum starter is prevented
closing operations stress and deterio- Class J current limiting fuses provide while racking
36 rate the breaker mechanisms. short-circuit protection and allow a Breaker position indication
combination rating of 100 kA at 480 V is provided (connected, test,
Eatons LV-VSR is a self-contained
or 600 V. disconnect, remove)
37 replacement vacuum starter for an LV
The LV-VSR vacuum starter is
drawout air circuit breaker. The LV-VSR C440 Electronic Overload Relay
is interchangeable with the drawout padlockable (optional) in either the
Eatons C440 multi-function electronic, connect, test or disconnect positions
38 breaker element and requires no motor protection relay provides the
cell modifications. Positive ground connection
following features:
is maintained
39 Features Overload protection, Class 10A, 10, Closed door tripping
20 or 30 Closed-door control, if existing,
Advantages Phase unbalance protection, can be maintained
40 The use of an LV-VSR vacuum starter selectable (ON/OFF)
can prolong device life and signifi- Ground fault selectable (ON/OFF)
cantly reduce maintenance repair
41 Remote reset
and downtime.
Alarm relay output contact
A low voltage air circuit breaker has LED status indication
42 an effective life of 4000 operations
Communication modules
while an LV-VSR vacuum starter
has an effective life of 1,000,000 Modbus RTU RS-485
43 operations. For example, a motor DeviceNet with IO
starting application that required two PROFIBUS with IO
starts per hour on continuous duty
would require a major rebuild of the
LV breaker within three months.
LV-VSR Control Features The LV-VSR uses the same line and
LV-VSR vacuum starter offers the load finger clusters, secondary contact 22
following standard control features. assemblies and drawout mechanism
Other devices can be supplied on as the original circuit breaker. Renewal
request. parts are readily available. 23
Start-stop pushbuttons Technical Data and Specifications
and run pilot light 24
Eaton C440 electronic overload relay Ratings
2A/2B auxiliary contact The LV-VSR vacuum starter is rated
1A/1B trip contact (overload or as follows: 25
short circuit) Maximum continuous current425 A
Provision for remote control Maximum voltage rating600 V 26
operation Short-circuit rating at 240600 V
Integral control power transformer 200 kA
Custom-designed wiring schemes Maximum motor hp at 480 V, 235 hp
27
Westinghouse DB-25 Vacuum
Ease of Maintenance Maximum motor hp at 240 V, 117 hp Starter Replacement
A
Line Stabs
(Top)
Size 6 = 600A
Type LPJ
Contactor
Type V201
Current
Sensor
Load Stabs
(Bottom) 30
B
C
A B M C1 C2 C3 C0 31
10 500
FNQ-R
FNQ-R
1.5A
1.5A
See Fig. 1 3
32
for Wiring
H4 240, 480 & H1 CPT Wiring
600 VAC Wire H1 to
H1 = 600V
H4 H3 H2 H1
Control Power
Transformer 150VA
H2 = 480V
H3 = 240V
H4 = Common to All 33
FNQ X1 X2 X3
10A 120VAC
F E T
+ Available Voltages
120 Vac 240 Vac
B
OTR
A 98
48 Vdc 110 Vdc
34
F M OL B A
CR
CLOSE 3 4
RUN
R1
Remote
Reset
R2
Left- Right- Left- Right- K
7
CR
4
R
N
96
OL
95
G
OPEN
8 2B
M
35
Pin Pin Pin Pin 9 3 A B
M B A
R TR
Line-1 U Line-1 V TR J STOP START 1B 2A TR 17
Line-2 Line-2 M
36
(Micro-SW) (Micro-SW) CLOSE
M-1A AUX1
100 Ohms
50 Watts
Trip
AUX2
**
Typical Existing Switchgear Control Wiring & Devices
** CAUTION:
37
Mis-Coordination Between Breaker Cell Wiring and the
DS-VSR May Cause Injury or Severe Equipment Damage.
X1 X2 T
OL
G Many DS Breaker Cells Will be Compatible with this Schematic.
IQ502A
3.4-66 AMP Trip (secondary AMPs)
Verify that all Existing Breaker Cell Wiring Will Coordinate with
this Scheme. If in Doubt, Contact Eaton Before Installing the
38
New Unit in the Cell.
Remote Reset Connection Contactor Interlock Layout Auxiliary Contacts Alarm Contacts
Remove Jumper
R1 R2
1A
A B
3A
13 21 15 23 37 45 41 43 11 9
39
1B 3B
M
Bell
2A 4A 3A 3B 4A 4B Alarm
M M M M AUX1 AUX1 AUX2 AUX2 Device
(OTS)
40
Device Terminal Number
Customer Wiring 2B 4B
Customer-Supplied 14 22 16 24 38 46 42 44 12 10 Wire Number
Contact Normally-
Open Interlock Normally-
Closed
To Reset the OL Relay from a Remote Location, Remove Front View Interlock
the Factory-Supplied Jumper and Add a NC Contact Connected to Switchgear seconda ry of Contactor Mechanically Operated Electrically Operated
Contact Terminals & , When this Contact is Opened, the OL relay wi ll Reset
and Allow the Motor to Restart.
From Rear
of DSVSR 41
WARNING:
Do Not Use this Feature if a Remote Restart May Cause Injury or Equipment Damage.
43
22 VR Series MV Vacuum Most MV air-magnetic circuit All VR Series breakers are available
breakers also contain asbestos in their with Eatons Sure Close MOC operator
Replacement Circuit Breakers arc chutes. Asbestos is a hazardous technology. Sure Close is guaranteed
material that should be removed. not to stall a circuit breaker during
23 General Description Replacement asbestos-free arc chutes, closing and prevents damage to
Breaker problems? If your electrical if available, are expensive. This makes existing MOC switches. VR Series
power system uses vintage medium the cost of rebuilding MV breakers breakers are design tested to
24 voltage (MV) switchgear and air- prohibitive because interruption relies applicable IEEE/ANSI Standards.
magnetic power circuit breakers, heavily on the performance of the
arc chutes. In most cases, asbestos A line of fused MV breaker-to-motor
you may be experiencing some
25 common problems. Age, the lack of arc chutes can not be effectively starter replacements (MV-VSR) is also
maintained and their performance available for the most popular 4.76 kV
maintenance, environment, duty cycle, breakers. The MV-VSR is designed to
changes in system fault levels and decays at an undetectable rate.
26 regulatory changes can turn relatively
provide more than 150,000 operations
Breaker Solutions (a performance level that no circuit
benign devices into problematic breaker can achieve, regardless of
There are three possible solutions to
drains on system reliability, safety
27 and profitability.
the problems. technology) and can start motors up
to 2500 hp. The MV-VSR is fully inter-
Replace the switchgear and locked, has anti-pump control circuits
Because they are the main arteries
28 for incoming power, MV power
breakers with new equipment. and latching contactors, and is design
This approach eliminates the issues tested to replace breakers that are
circuit breakers are often omitted
but is very expensive and requires being used as motor starters.
during routine maintenance outages.
29 Lack of maintenance and lubrication
an extensive outageand generally
slows mechanism opening and closing
requires installing new MV cables Application Description
speeds. As breakers age and accumu- Existing structures can be retro- Most medium voltage air magnetic
30 late operations, regular and frequent filled with breaker mini-modules power circuit breakers have been in
maintenance must be performed and bus modifications to accept service for 30 years and some for as
to ensure interlock functionality to current production vacuum break- long as 70 years. They were reliable
31 protect employees and to prevent ers. This also requires an extensive and for many years and maintainable.
breaker failure. Replacement parts outage, is slightly less expensive Increased short-circuit capabilities in
are more difficult to find and their than the first option, and cables utility and industrial power systems
32 costs increase at alarming rates. can usually remain unchanged have created over-duty situations
Deterioration in performance will Replace the existing air-magnetic with many of these breakers. Parts
eventually dictate more frequent devices with new vacuum replace- availability has also increased the
33 and extensive maintenance. ment circuit breakers (VR Series). cost of maintaining the breakers in
This approach provides the most peak condition.
Exposure to moisture, contaminants complete and cost-effective solution
34 and excessive heat causes a loss of In the mid 1970s, circuit breaker
insulation dielectric strength. This leads VR Series breakers provide modern manufacturers began introducing
to an increase in partial discharge, vacuum interrupter technology without vacuum technology for MV power
35 corona and possible BIL failure. requiring an outage to replace the circuit breakers. It was desirable and
switchgear and cables. Usually, no feasible to incorporate the advantages
Incoming system changes can structure modifications are required to of vacuum technology into replacement
36 increase short-circuit currents to accommodate the VR Series breakers. breakers that would interchange with
levels greater than existing breaker Short-circuit levels can also be the existing MV air magnetic power cir-
ratings and render them inadequate to increased within the same physical cuit breakers to extend the useful life of
37 interrupt a fault. A failure to interrupt size and bus bracing can be increased their existing switchgear. Most users
a primary fault can damage a plants and the structures certified to match wanted a replacement
entire electrical system and injure the new momentary levels of the that was functionally interchangeable,
38 nearby employees. higher short-circuit ratings. both electrically and mechanically,
Many power circuit breakers are with their existing MV air magnetic
Eaton manufactures an extensive line
improperly applied as motor starters. power circuit breakers that required
39 High inrush currents and frequent
of VR Series breakers (over 200 different
little or no cell modifications.
ratings) to replace air-magnetic circuit
operation erodes contacts, shortens breakers manufactured by: The market responded by offering
mechanism life and requires additional
40 maintenance. The level of mainte- Westinghouse
retrofits that used the existing breaker
trucks (frames) and vacuum circuit
nance will increase and the time General Electric breaker modules. These alternatives
between maintenance intervals will
41 decrease to a point where it seems
Allis-Chalmers (Siemens) provided extended life for electrical
ITE (ABB) equipment, reduced maintenance,
maintenance is a constant requirement. and allowed increased capabilities for
Federal Pacific Electric
42 many distribution systems. IEEE/ANSI
established a standard for conversions
(IEEE/ANSI C37.59) in 1991 that put
43 consistency in the conversion process
and established design testing
requirements.
43
35
36
37
38
39
40
41
42
43
Design and Certification (Type) Testing Momentary tests per IEEE/ANSI Short-time current tests for 3 seconds
Each new VR Series vacuum replace- C37.20.2.5.2.4 will be performed at K*I current will be performed to 22
ment circuit breaker supplied will of the completed vacuum replace- confirm the breakers I2t capability.
have type tests performed on its ment breaker including the vacuum The test will be performed in a
base design to certify it to IEEE/ANSI breaker element, bushings, primary switchgear cell. 23
standards. All Certification (Type) disconnects (finger clusters), all bus
in the breaker unit, and all insulators Continuous rated current testing per
will be performed in a switchgear
cell/structure when required or an and braces per ANSI C37.09, 4.6.2.4. ANSI C37.04-1979 without exceeding 24
This test is to prove the mechanical 65C hotspot rise with a maximum
equivalent structure where permitted ambient not to exceed 40C. This
by ANSI C37.09. Written test reports, strength and integrity of the conductor
data logs and digital reproductions and frame assembly of the complete test is performed in a breaker cell or a 25
new vacuum replacement breaker. cell structure of the same equivalent
of the pulse used to perform the BIL volume, dimensions and ventilation as
test will be on hand for review by This test is performed in a switchgear
the buyer. BIL60 kV for 4.76 kV cell designed to accommodate the the original switchgear structure. Low 26
circuit breaker being tested. Anti- Frequency Withstand19 kV rms for
applications, 95 kV for 8.25 and 15 kV 4.76 kV applications, 36 kV rms for
applications as a minimum> crest with rotation devices may be added to
1.2 sec x 50 sec x 50% wave shape the cell if required to prevent rotation. 8.25 kV and 15 kV applicationsper 27
If anti-rotation devices are used in the ANSI 37.09, 4.5.3.1. Interlock functional
per ANSI C37.09.4.5.4. test per ANSI C37.20.2, 6.2.4.
test breaker, then they will be installed
The tests will be conducted per in all the switchgear cells intended All production tests as stated in ANSI 28
IEEE STD 4-1995. This test shall be to accommodate the new breakers. C37.09-1979.5. Timing values per
performed in a breaker cell or cell pole will be provided for the vacuum
equivalent with controlled humidity element in msec. 29
levels. Corrections for barometric pres-
sure and ambient temperature will be
applied to the test parameters. The 30
breaker must pass a total of 54 shots.
Mechanical operations tests of 31
each breaker design are performed
in a switchgear cell designed to
accommodate MOC switches. The 32
maximum number of auxiliary MOC
devices or their equivalent force will
be applied during the test to ensure 33
that the vacuum breaker has sufficient
power to operate the auxiliary devices,
successfully closes and latches during 34
each operation, and that no fatigue or
failure occurs. Consideration is given
to designing a system that will not 35
damage the MOC switch in the
switchgear cell structure.
36
37
38
VR Series Breakers 39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43