Академический Документы
Профессиональный Документы
Культура Документы
Training manual
VIComposer
Revision 04 / 2005
Impressum
Publisher:
Bosch Rexroth AG
BRC/SAL2
Author: Helmut Kleinhans BRC / SAL2
Chapter 1
IndraWorks
VCPPanel
Project
Menu parameters
IndraWorks VCPPanel Project CHAP 1 2
6. Drag the selected Target System with the left mouse button still
pressed onto the Project name and release the left mouse button
as soon as a line is displayed below the Project name
Note !
by clicking with the right mouse button
onto the icon Logic, the communication
window can be called up again by selecting
Properties
IndraWorks VCPPanel Project CHAP 1 7
Gateway Server
L40
Project directory
PLCProgram files
3. Check, if the directory for the I/O Configuration (GSD Files) is correct
Default setting : C:\Program files\Rexroth\IndraWorks\IndraLogic\Targets\Config\
IndraWorks I/O Configuration CHAP 1 10
4. Enter the ProfibusDP station address of the VCP operating terminal module, and
take over the station address (Bus address) by clicking onto the Finish button
Note !
The window with the Station address
can be called up again by double clicking
onto the corresponding basic module
7. Enter the I/O Start address, and take over the new address by clicking onto the
Apply button (Caution ! Obey Word / Byte addressing mode)
Note ! For the first time installation, it is recommended to set the Transmission
rate to 1500kBit. As soon as the ProfibusDP runs in an error free state,
the Transmission rate can be increased to the maximum value.
IndraWorks PLCProgram CHAP 1 15
2. Click onto the tab Resources and open the I/OConfiguration window by double clicking
with the left mouse button onto PLC Configuration (<R> = is managed by IndraWorks)
Note !
Adaptions of the functions is only possible, if the Target
System is checked out from the ENIDatabase
2. Select directory in which the Symbol file is located, using Windows Explorer
IndraWorks PLCProgram CHAP 1 20
2. After loading is completed, start the PLC Program using Online / Run
Chapter 2
VIComposer
Installation
The following operation sequence installs the VIComposerSoftware on your hard drive.
During installation all required files will be copied into the selected directory and the Windows
system files will be updated.
Possible functions
Install VIDownload Tool This installs a separate software, which can be used to download
the VIComposer project file
5. Start installation by clicking with the left mouse button onto the Next button
6. Confirm the acceptance of the license agreement with a click onto the Yes button
Yes
Accept license
agreement and continue
with next dialogue
No
Do not accept
the license agreement
and cancel installation
< Back
Return to previous
dialogue screen
< Back
Return to previous
dialogue screen
Next >
go to next dialogue
screen of VIComposer
installation and take over
user information
Cancel
Cancel installation and
return to installation
startup screen
Browse
Change installation
directory to another name
< Back
return to previous
dialogue screen
Next >
go to next dialogue
screen, and take over
selected installation
directory
Cancel
Cancel installation,
return to VIComposer
Installation startup
screen
< Back
return to previous
dialogue screen
Next >
go to next dialogue
screen, and take over
installation type
Cancel
Cancel installation,
return to VIComposer
Installation startup
screen
Installation is running, all files will be copied into the selected directory
11. Click onto button Finish to return to the main installation screen
Chapter 3
VIComposer
Project
Management
10. Select Variable list and click onto the Edit button to
check the variables from the allocated Symbol file
11. To close the Variable list window, click onto the x button
VIComposer Project Management CHAP 3 7
25 5
DSub DSub
Male 25 pin Female 9 pin
Setup on L20/L40 Controller
RS232 : COM SERV
11. To close the Variable list window, click onto the x button
VIComposer Project Management CHAP 3 10
Note !
1. If the selected memory size does not match the real memory size of your VCPPanel, the
project file cannot be loaded into the panel.
2. Whenever the memory size is altered, a new compiler run must be carried out.
VIComposer Project Management CHAP 3 11
Note ! The screen saver is not usable with every panel type. This means that you can select
always one of the screen saver settings, but you may not been able to enter a Delay
time
Enter select next input variable If the Enter key is pressed, the cursor moves on to
the next input variable field
this speeds up operation, if several variable values
have to entered in a mask
Note !
For normal operation the Default setting with No link can be used
VIComposer Project Management CHAP 3 15
Note !
If errors are found during the
compilation process, no
.S3 File will be generated.
If warnings are displayed, a
.S3 File is generated, but it is
recommended to check and cor-
rect the warnings
VIComposer Project Management CHAP 3 17
Load compiled .S3 project file into VCPPanel (first time only)
Note !
This operation is only required, if one of the following is true:
the compiled .S3 File is loaded the first time into the VCPPanel
If function Automatic download is deactivated
To erase the FlashEPROM of the VCP_Panel to enter the download mode, the following steps
must be carried out:
1. Disconnect VCPPanel from supply voltage (unplug connector from X1)
2. Set Switch 4 of the DIPSwitch located behind the flap on the rear side to ON
3. Connect VCPPanel to supply voltage (insert plug into X1)
the following is displayed on the VCPPanel screen
4. Set Switch 4 of the DIPSwitch located behind the flap on the rear side back to OFF
Note ! Do not switch the power off !!!!
the following is displayed on the VCPPanel screen
>>>>>>>>>>>>>>>
VIComposer Project Management CHAP 3 18
1. Click onto button Download to load the .S3 File into the VCPPanel
Chapter 4
VIComposer
Mask
Creation
During the startup phase of the VCPPanel a so called Startup mask is displayed for
a certain time, before the system is switching to the so called Main mask.
With the following operation, these 2 mask can be changed.
However it is recommended to use the two standard masks Startup and Main and
adapt them accordingly.
2. Callup the Property window by double clicking onto the text object
2. Select the object which is to be copied by clicking with the left mouse button on it
Note !
ASCIIGraphic characters are treated like
normal text, this means that they can be
copied, moved, pasted and cut
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
& ( ) * + , . / 0 1 2 3 4 5 6 7 8
57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75
9 : ; < = > ? @ A B C D E F G H I J K
76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94
L M N O P Q R S T U V W X Y Z [ \ ] ^
95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113
_ a b c d e f g h i j k l m n o p q
114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132
r s t u v w x y z { | }
133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151
152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170
Pt a o
171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189
1
2
1
4
190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208
209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227
228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246
247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265
n 2 SP
VIComposer Mask Creation CHAP 4 9
2. Position your cursor at the position where you want to add the variable
3. Press the left mouse button and keep it pressed
4. Move the mouse with the left mouse button still pressed until the variable field has the
required size, than release the mouse button
Function:
By pressing / releasing the function
keys,the assigned PLC signals will be
Set or Reset in the PLC.
In this way they can be used to control
other parts of the program in the PLC 6. Select a variable
from the symbol file
8. Carry out the same operation for the field Release variable
VIComposer Mask Creation CHAP 4 17
Function:
By pressing the function
keys, the assigned
mask number will be
called up and displayed
This function can be used to insert a bitmap file as a background image for a mask. If the bitmap is
placed on the background of the mask, variables can still be defined and displayed on the foreground
of the mask
Note:
The bitmap file has to be saved in the formats ..BMP or .WMF
the file has to be a Black / White graphics file
the maximum size of graphic must not exceed 240 x 128 Pixel (in order to display the graphic
between the mask header line and the menubar, the size should not exceed 240 x 110 Pixels)
1. Select Program management
information 7 Pictures
13. Press the left mouse button and keep it pressed, move the mouse until you
have marked the area, into which the Bitmap has to be inserted
14. As soon as you release the mouse button, a selection window with the
available graphic files is displayed