Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document. Drawings and diagrams are not binding.
Copyright 2016 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1 Issued: February 2016
Revision: A
ABB 3
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
WA1 REC670 A30 Double busbar in single breaker arrangement 12AI (6I + 6U)
WA2_VT MET UN
VN MMXU
QC2
3 Control 3 Control 3 Control
S CILO S CSWI S XSWI
LINE_CT
MET I MET Isqi MET P/Q U>/I<
C MMXU C MSQI CV MMXN FUF SPVC
63 71 3 Control
S SIMG S SIML R ESIN
Optional Functions
87 Id> 50 3I>> 51_67 4(3I>) 50N IN>> 51N_67N 4(IN>) 46I2 4(I2>) 67N IN> 26 > 26 >
HZ PDIF PH PIOC OC4 PTOC EF PIOC EF4 PTOC NS4 PTOC SDE PSDE LC PTTR LF PTTR
49 > 37 P< 32 P> 27 2(3U<) 59 2(3U>) 59N 2(U0>) 81 f< 81 f> 81 df/dt<>
TR PTTR GUP PDUP GOP PDOP UV2 PTUV OV2 PTOV ROV2 PTOV SA PTUF SA PTOF SA PFRC
2(I>/U<) 90 U 90 U 21FL FL 85 85 85 85
CV GAPC TR1 ATCC TR8 ATCC LMB RFLO ZC PSCH ZCRW PSCH ZCLC PSCH EC PSCH ECRW PSCH
IEC05000837-4-en.vsd
IEC05000837 V4 EN
4 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
WA1
REC670 A31 Bus Coupler Bay arrangement 12AI (6I + 6U)
WA2
QA1
MET UN
VN MMXU
WA1_VT
QA1_CT
MET I MET Isqi
C MMXU C MSQI
3 Control 3 Control
Q CBAY Q CRSV
Optional Functions
87 Id> 50 3I>> 51_67 4(3I>) 50N IN>> 51N_67N 4(IN>) 46I2 4(I2>) 67N IN> 26 ?> 26 ?>
HZ PDIF PH PIOC OC4 PTOC EF PIOC EF4 PTOC NS4 PTOC SDE PSDE LC PTTR LF PTTR
49 ?> 37 P< 32 P> 27 2(3U<) 59 2(3U>) 59N 2(U0>) 81 f< 81 f> 81 df/dt<>
TR PTTR GUP PDUP GOP PDOP UV2 PTUV OV2 PTOV ROV2 PTOV SA PTUF SA PTOF SA PFRC
IEC15000413 V1 EN
ABB 5
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
WA1
REC670 B30 - Double breaker arrangement 12AI (6I + 6U)
WA2
LINE_CT1
63 71 3 Control
S SIMG S SIML R ESIN
Optional Functions
87 Id> 50 3I>> 51_67 4(3I>) 50N IN>> 51N_67N 4(IN>) 46I2 4(I2>) 67N IN> 26 > 26 >
HZ PDIF PH PIOC OC4 PTOC EF PIOC EF4 PTOC NS4 PTOC SDE PSDE LC PTTR LF PTTR
49 > 37 P< 32 P> 27 2(3U<) 59 2(3U>) 59N 2(U0>) 81 f< 81 f> 81 df/dt<>
TR PTTR GUP PDUP GOP PDOP UV2 PTUV OV2 PTOV ROV2 PTOV SA PTUF SA PTOF SA PFRC
2(I>/U<) 90 U 90 U 21FL FL 85 85
CV GAPC TR1 ATCC TR8 ATCC LMB RFLO ZC PSCH ZCRW PSCH ZCLC PSCH EC PSCH ECRW PSCH
1)
IEC05000838 V4 EN
6 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
WA1
REC670C30 Complete one-and a half breaker diameter arrangement 24AI (6I + 6U, 6I+6U)
TIE_QA1
3 Control 3 Control 3 Control MET U MET Usqi MET UN
S CILO S CSWI S XCBR V MMXU V MSQI VN MMXU
TIE_CT
MET I MET Isqi MET P/Q U>/I<
S
QB62 C MMXU C MSQI CV MMXN FUF SPVC
LINE2_QB9
3 Control 3 Control 3 Control MET W/Varh
S CILO S CSWI S XSWI ETP MMTR
63 71 3 Control
S SIMG S SIML R ESIN 60 Ud>
Optional Functions VD SPVC
87 Id> 50 3I>> 51_67 4(3I>) 50N IN>> 51N_67N 4(IN>) 46I2 4(I2>) 67N IN> 26 ?> 26 ?> 49 ?>
HZ PDIF PH PIOC OC4 PTOC EF PIOC EF4 PTOC NS4 PTOC SDE PSDE LC PTTR LF PTTR TR PTTR
37 P< 32 P> 27 2(3U<) 59 2(3U>) 59N 2(U0>) 81 f< 81 f> 81 df/dt<> U</I> 90 U??
GUP PDUP GOP PDOP UV2 PTUV OV2 PTOV ROV2 PTOV SA PTUF SA PTOF SA PFRC CV GAPC TR1 ATCC
IEC05000839 V4 EN
ABB 7
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
The basic delivery includes one binary input module and one the system, object or application. Optional functions and
binary output module, which is sufficient for the default optional IO ordered will not be configured at delivery. It should
configured IO to trip and close circuit breaker. All IEDs can be be noted that the standard only includes one binary input and
reconfigured with the help of the ACT configuration tool in the one binary output module and only the key functions such as
PCM600 engineering platform. The IED can be adapted to tripping are connected to the outputs in the signal matrix tool.
special applications and special logic can be developed, such The required total IO must be calculated and specified at
as logic for automatic opening of disconnectors and closing of ordering.
ring bays, automatic load transfer from one busbar to the other,
and so on. The configurations are as far as found necessary provided with
application comments to explain why the signals have been
The basic IED configuration is provided with the signal matrix, connected in the special way. On request, ABB is available to
mimic and the application configuration prepared for the support the re-configuration work, either directly or to do the
functions included in the product by default. All parameters design checking.
should be verified by the customer, since these are specific to
8 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
2. Available functions
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
(Customized)
Differential protection
HZPDIF 87 1Ph high impedance differential protection 0-6 3-A02 3-A02 3-A02 6-A07
ABB 9
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
(Customized)
Current protection
OC4PTOC 51_671) Four step phase overcurrent protection 0-6 1-C51 1-C51 2-C52 2-C53
EFPIOC 50N Instantaneous residual overcurrent 0-6 1-C51 1-C51 2-C52 2-C53
protection
EF4PTOC 51N Four step residual overcurrent protection 0-6 1-C51 1-C51 2-C52 2-C53
67N2)
NS4PTOC 46I2 Four step directional negative phase 0-6 1-C51 1-C51 2-C52 2-C53
sequence overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent 0-6 1-C16 1C16 1-C16 1-C16
and power protection
LCPTTR 26 Thermal overload protection, one time 06 1-C51 1-C51 1-C52 1-C53
constant, Celsius
LFPTTR 26 Thermal overload protection, one time 06 1-C51 1-C51 1-C52 1-C53
constant, Fahrenheit
TRPTTR 49 Thermal overload protection, two time 0-6 1-C51 1-C51 1-C52 1-C53
constant
CCRBRF 50BF Breaker failure protection 0-6 1-C51 1-C51 1-C52 1-C53
Voltage protection
UV2PTUV 27 Two step undervoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
OV2PTOV 59 Two step overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
ROV2PTOV 59N Two step residual overvoltage protection 0-2 2-D02 2-D02 2-D02 2-D02
Frequency protection
10 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
(Customized)
Multipurpose protection
CVGAPC General current and voltage protection 0-9 4-F01 4-F01 4-F01 4-F01
General calculation
1) 67 requires voltage
2) 67N requires voltage
ABB 11
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
Control
TR1ATCC 90 Automatic voltage control for tap changer, single control 0-4 1-H11 1-H11 1-H11 2-H16
TR8ATCC 90 Automatic voltage control for tap changer, parallel control 0-4 1-H15 1-H15 1-H15 2-H18
Secondary system
supervision
12 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
VDSPVC 60 Fuse failure supervision based on voltage difference 0-4 1-G03 1-G03 1-G03 1-G03
Logic
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-280 40-280 40-280 40-280 40-280
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Monitoring
ABB 13
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
CVMMXN, Measurements 6 6 6 6 6
VMMXU, CMSQI,
VMSQI, VNMMXU
CMMXU Measurements 10 10 10 10 10
Metering
14 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
AND 280
GATE 40
INV 420
LLD 40
OR 280
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
AND 180
GATE 49
INV 180
LLD 49
OR 180
PULSETIMER 59
SLGAPC 74
SRMEMORY 110
TIMERSET 49
VSGAPC 130
XOR 49
ABB 15
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Communication
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
(Customized)
Station communication
RS485GEN RS485 1 1 1 1 1
MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10
MULTICMDSND
16 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
REC670 (C30)
REC670 (B30)
REC670 (A30)
REC670 (A31)
REC670
(Customized)
PRP IEC 62439-3 parallel redundancy protocol 0-1 1-P03 1-P03 1-P03 1-P03
Remote communication
Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3
Scheme communication
ZCPSCH 85 Scheme communication logic for distance or 0-1 1-K01 1-K01 1-K01 1-K01
overcurrent protection
ZCRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-K01 1-K01 1-K01 1-K01
distance protection
ECPSCH 85 Scheme communication logic for residual 0-1 1-C51 1-C51 1-C52 1-C53
overcurrent protection
ECRWPSCH 85 Current reversal and weak-end infeed logic for 0-1 1-C51 1-C51 1-C52 1-C53
residual overcurrent protection
ABB 17
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
INTERRSIG
SELFSUPEVLST Self supervision with internal event list
18 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
SESRSYN function includes a built-in voltage selection scheme Multiple autoreclosing functions are provided for multi-breaker
for double bus and 1 breaker or ring busbar arrangements. arrangements. A priority circuit allows one circuit breaker to
close first and the second will only close if the fault proved to be
Manual closing as well as automatic reclosing can be checked transient.
by the function and can have different settings.
Each autoreclosing function is configured to co-operate with
For systems, which are running asynchronous, a synchronizing the synchrocheck function.
function is provided. The main purpose of the synchronizing
function is to provide controlled closing of circuit breakers when The autoreclosing function provides high-speed and/or delayed
two asynchronous systems are going to be connected. The three pole autoreclosing.
synchronizing function evaluates voltage difference, phase
angle difference, slip frequency and frequency rate of change
ABB 19
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
20 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
1Ph High impedance differential protection HZPDIF All IEC and ANSI time-delayed characteristics are available
The 1Ph High impedance differential protection HZPDIF together with an optional user defined characteristic.
functions can be used when the involved CT cores have the
same turns ratio and similar magnetizing characteristics. It EF4PTOC can be set directional or non-directional
utilizes an external CT secondary current summation by wiring. independently for each of the steps.
Actually all CT secondary circuits which are involved in the
differential scheme are connected in parallel. External series IDir, UPol and IPol can be independently selected to be either
resistor, and a voltage dependent resistor which are both zero sequence or negative sequence.
mounted externally to the IED, are also required.
Second harmonic blocking can be set individually for each step.
The external resistor unit shall be ordered under IED
EF4PTOC can be used as main protection for phase-to-earth
accessories in the Product Guide.
faults.
HZPDIF can be used to protect tee-feeders or busbars,
EF4PTOC can also be used to provide a system back-up for
reactors, motors, auto-transformers, capacitor banks and so
example, in the case of the primary protection being out of
on. One such function block is used for a high-impedance
service due to communication or voltage transformer circuit
restricted earth fault protection. Three such function blocks are
failure.
used to form three-phase, phase-segregated differential
protection. Several function block instances (for example, six) Directional operation can be combined together with
can be available in a single IED. corresponding communication logic in permissive or blocking
teleprotection scheme. Current reversal and weak-end infeed
5. Current protection functionality are available as well.
Instantaneous phase overcurrent protection PHPIOC Residual current can be calculated by summing the three phase
The instantaneous three phase overcurrent function has a low currents or taking the input from neutral CT
transient overreach and short tripping time to allow use as a
Four step negative sequence overcurrent protection
high set short-circuit protection function.
NS4PTOC
Four-step phase overcurrent protection OC4PTOC Four step negative sequence overcurrent protection
The four step three-phase overcurrent protection function (NS4PTOC) has an inverse or definite time delay independent
OC4PTOC has an inverse or definite time delay independent for for each step separately.
step 1 to 4 separately.
All IEC and ANSI time delayed characteristics are available
All IEC and ANSI inverse time characteristics are available together with an optional user defined characteristic.
together with an optional user defined time characteristic.
The directional function is voltage polarized.
The directional function needs voltage as it is voltage polarized
NS4PTOC can be set directional or non-directional
with memory. The function can be set to be directional or non-
independently for each of the steps.
directional independently for each of the steps.
NS4PTOC can be used as main protection for unsymmetrical
A second harmonic blocking level can be set for the function
fault; phase-phase short circuits, phase-phase-earth short
and can be used to block each step individually.
circuits and single phase earth faults.
Instantaneous residual overcurrent protection EFPIOC
NS4PTOC can also be used to provide a system backup for
The Instantaneous residual overcurrent protection EFPIOC has
example, in the case of the primary protection being out of
a low transient overreach and short tripping times to allow the
service due to communication or voltage transformer circuit
use for instantaneous earth-fault protection, with the reach
failure.
limited to less than the typical eighty percent of the line at
minimum source impedance. EFPIOC is configured to measure Directional operation can be combined together with
the residual current from the three-phase current inputs and corresponding communication logic in permissive or blocking
can be configured to measure the current from a separate teleprotection scheme. The same logic as for directional zero
current input. sequence current can be used. Current reversal and weak-end
infeed functionality are available.
22 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Sensitive directional residual overcurrent and power Breaker failure protection CCRBRF
protection SDEPSDE Breaker failure protection (CCRBRF) ensures a fast backup
In isolated networks or in networks with high impedance tripping of the surrounding breakers in case the own breaker
earthing, the earth fault current is significantly smaller than the fails to open. CCRBRF can be current-based, contact-based or
short circuit currents. In addition to this, the magnitude of the an adaptive combination of these two conditions.
fault current is almost independent on the fault location in the
network. The protection can be selected to use either the A current check with extremely short reset time is used as
residual current or residual power component 3U03I0cos j, check criterion to achieve high security against inadvertent
for operating quantity with maintained short circuit capacity. operation.
There is also available one nondirectional 3I0 step and one 3U0
Contact check criteria can be used where the fault current
overvoltage tripping step.
through the breaker is small.
No specific sensitive current input is needed. SDEPSDE can be
CCRBRF can be single- or three-phase initiated to allow use
set as low 0.25% of IBase.
with single phase tripping applications. For the three-phase
Thermal overload protection, one time constant LCPTTR/ version of CCRBRF the current criteria can be set to operate
LFPTTR only if two out of four for example, two phases or one phase
The increasing utilization of the power system closer to the plus the residual current start. This gives a higher security to the
thermal limits has generated a need of a thermal overload back-up trip command.
protection for power lines.
CCRBRF function can be programmed to give a single- or
A thermal overload will often not be detected by other three-phase re-trip of its own breaker to avoid unnecessary
protection functions and the introduction of the thermal tripping of surrounding breakers at an incorrect initiation due to
overload protection can allow the protected circuit to operate mistakes during testing.
closer to the thermal limits.
Stub protection STBPTOC
When a power line is taken out of service for maintenance and
The three-phase current measuring protection has an I 2 t
the line disconnector is opened in multi-breaker arrangements
characteristic with settable time constant and a thermal
the voltage transformers will mostly be outside on the
memory. The temperature is displayed in either Celsius or
disconnected part. The primary line distance protection will
Fahrenheit, depending on whether the function used is LCPTTR
thus not be able to operate and must be blocked.
(Celsius) or LFPTTR (Fahrenheit).
The stub protection STBPTOC covers the zone between the
An alarm level gives early warning to allow operators to take
current transformers and the open disconnector. The three-
action well before the line is tripped.
phase instantaneous overcurrent function is released from a
Estimated time to trip before operation, and estimated time to normally open, NO (b) auxiliary contact on the line
reclose after operation are presented. disconnector.
Thermal overload protection, two time constant TRPTTR Pole discordance protection CCPDSC
If a power transformer reaches very high temperatures the An open phase can cause negative and zero sequence currents
equipment might be damaged. The insulation within the which cause thermal stress on rotating machines and can
transformer will experience forced ageing. As a consequence of cause unwanted operation of zero sequence or negative
this the risk of internal phase-to-phase or phase-to-earth faults sequence current functions.
will increase.
Normally the own breaker is tripped to correct such a situation.
The thermal overload protection estimates the internal heat If the situation persists the surrounding breakers should be
content of the transformer (temperature) continuously. This tripped to clear the unsymmetrical load situation.
estimation is made by using a thermal model of the transformer
The Pole discordance protection function CCPDSC operates
with two time constants, which is based on current
based on information from auxiliary contacts of the circuit
measurement.
breaker for the three phases with additional criteria from
Two warning levels are available. This enables actions in the unsymmetrical phase currents when required.
power system to be done before dangerous temperatures are
Directional over/underpower protection GOPPDOP/
reached. If the temperature continues to increase to the trip
GUPPDUP
value, the protection initiates a trip of the protected
The directional over-/under-power protection GOPPDOP/
transformer.
GUPPDUP can be used wherever a high/low active, reactive or
The estimated time to trip before operation is presented. apparent power protection or alarming is required. The
functions can alternatively be used to check the direction of
ABB 23
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
active or reactive power flow in the power system. There are a Two step overvoltage protection (OV2PTOV) function can be
number of applications where such functionality is needed. used to detect open line ends, normally then combined with a
Some of them are: directional reactive over-power function to supervise the
system voltage. When triggered, the function will cause an
detection of reversed active power flow alarm, switch in reactors, or switch out capacitor banks.
detection of high reactive power flow
OV2PTOV has two voltage steps, each of them with inverse or
Each function has two steps with definite time delay. definite time delayed.
Broken conductor check BRCPTOC OV2PTOV has a high reset ratio to allow settings close to
The main purpose of the function Broken conductor check system service voltage.
(BRCPTOC) is the detection of broken conductors on protected
power lines and cables (series faults). Detection can be used to Two step residual overvoltage protection ROV2PTOV
give alarm only or trip the line breaker. Residual voltages may occur in the power system during earth
faults.
Voltage-restrained time overcurrent protection VRPVOC
Voltage-restrained time overcurrent protection (VRPVOC) Two step residual overvoltage protection ROV2PTOV function
function can be used as generator backup protection against calculates the residual voltage from the three-phase voltage
short-circuits. input transformers or measures it from a single voltage input
transformer fed from an open delta or neutral point voltage
The overcurrent protection feature has a settable current level transformer.
that can be used either with definite time or inverse time
characteristic. Additionally, it can be voltage controlled/ ROV2PTOV has two voltage steps, each with inverse or definite
restrained. time delay.
One undervoltage step with definite time characteristic is also Reset delay ensures operation for intermittent earth faults.
available within the function in order to provide functionality for
overcurrent protection with undervoltage seal-in. Voltage differential protection VDCPTOV
A voltage differential monitoring function is available. It
Capacitor bank protection (CBPGAPC) compares the voltages from two three phase sets of voltage
Shunt Capacitor Banks (SCB) are used in a power system to transformers and has one sensitive alarm step and one trip
provide reactive power compensation and power factor step. Alternatively, it can be used as voltage differential
correction. They are as well used as integral parts of Static Var protection (VDCPTOV) for shunt capacitor banks.
Compensators (SVC) or Harmonic Filters installations.
Capacitor bank protection (CBPGAPC) function is specially Loss of voltage check LOVPTUV
designed to provide protection and supervision features for Loss of voltage check LOVPTUV is suitable for use in networks
SCBs. with an automatic system restoration function. LOVPTUV
issues a three-pole trip command to the circuit breaker, if all
three phase voltages fall below the set value for a time longer
6. Voltage protection than the set time and the circuit breaker remains closed.
Two step undervoltage protection UV2PTUV The operation of LOVPTUV is supervised by the fuse failure
Undervoltages can occur in the power system during faults or supervision FUFSPVC.
abnormal conditions. Two step undervoltage protection
(UV2PTUV) function can be used to open circuit breakers to
prepare for system restoration at power outages or as long- 7. Frequency protection
time delayed back-up to primary protection.
Underfrequency protection SAPTUF
UV2PTUV has two voltage steps, each with inverse or definite Underfrequency occurs as a result of a lack of generation in the
time delay. network.
UV2PTUV has a high reset ratio to allow settings close to Underfrequency protection SAPTUF measures frequency with
system service voltage. high accuracy, and is used for load shedding systems, remedial
action schemes, gas turbine startup and so on. Separate
Two step overvoltage protection OV2PTOV definite time delays are provided for operate and restore.
Overvoltages may occur in the power system during abnormal
conditions such as sudden power loss, tap changer regulating SAPTUF is provided with undervoltage blocking.
failures, and open line ends on long lines.
The operation is based on positive sequence voltage
measurement and requires two phase-phase or three phase-
neutral voltages to be connected. For information about how to
24 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
connect analog inputs, refer to Application manual/IED It is possible to create functionality with more than one
application/Analog inputs/Setting guidelines frequency band limit by using multiple instances of the function.
This can be achieved by a proper configuration based on the
Overfrequency protection SAPTOF turbine manufacturer specification.
Overfrequency protection function SAPTOF is applicable in all
situations, where reliable detection of high fundamental power
system frequency is needed. 8. Multipurpose protection
Overfrequency occurs because of sudden load drops or shunt General current and voltage protection CVGAPC
faults in the power network. Close to the generating plant, The General current and voltage protection (CVGAPC) can be
generator governor problems can also cause over frequency. utilized as a negative sequence current protection detecting
unsymmetrical conditions such as open phase or
SAPTOF measures frequency with high accuracy, and is used unsymmetrical faults.
mainly for generation shedding and remedial action schemes. It
is also used as a frequency stage initiating load restoring. A CVGAPC can also be used to improve phase selection for high
definite time delay is provided for operate. resistive earth faults, outside the distance protection reach, for
the transmission line. Three functions are used, which
SAPTOF is provided with an undervoltage blocking. measures the neutral current and each of the three phase
voltages. This will give an independence from load currents and
The operation is based on positive sequence voltage this phase selection will be used in conjunction with the
measurement and requires two phase-phase or three phase- detection of the earth fault from the directional earth fault
neutral voltages to be connected. For information about how to protection function.
connect analog inputs, refer to Application manual/IED
application/Analog inputs/Setting guidelines Voltage-restrained time overcurrent protection VRPVOC
Voltage-restrained time overcurrent protection (VRPVOC)
Rate-of-change frequency protection SAPFRC function can be used as generator backup protection against
The rate-of-change frequency protection function SAPFRC short-circuits.
gives an early indication of a main disturbance in the system.
SAPFRC measures frequency with high accuracy, and can be The overcurrent protection feature has a settable current level
used for generation shedding, load shedding and remedial that can be used either with definite time or inverse time
action schemes. SAPFRC can discriminate between a positive characteristic. Additionally, it can be voltage controlled/
or negative change of frequency. A definite time delay is restrained.
provided for operate.
One undervoltage step with definite time characteristic is also
SAPFRC is provided with an undervoltage blocking. The available within the function in order to provide functionality for
operation is based on positive sequence voltage measurement overcurrent protection with undervoltage seal-in.
and requires two phase-phase or three phase-neutral voltages
to be connected. For information about how to connect analog
9. Secondary system supervision
inputs, refer to Application manual/IED application/Analog
inputs/Setting guidelines. Current circuit supervision CCSSPVC
Open or short circuited current transformer cores can cause
Frequency time accumulation protection FTAQFVR
unwanted operation of many protection functions such as
Frequency time accumulation protection FTAQFVR is based on
differential, earth-fault current and negative-sequence current
measured system frequency and time counters. FTAQFVR for
functions.
generator protection provides the START output for a particular
settable frequency limit, when the system frequency falls in that Current circuit supervision (CCSSPVC) compares the residual
settable frequency band limit and positive sequence voltage current from a three phase set of current transformer cores with
within settable voltage band limit. The START signal triggers the the neutral point current on a separate input taken from another
individual event timer, which is the continuous time spent within set of cores on the current transformer.
the given frequency band, and the accumulation timer, which is
the cumulative time spent within the given frequency band. A detection of a difference indicates a fault in the circuit and is
Once the timers reach their limit, an alarm or trip signal is used as alarm or to block protection functions expected to give
activated to protect the turbine against the abnormal frequency inadvertent tripping.
operation. This function is blocked during generator start-up or
shut down conditions by monitoring the circuit breaker position Fuse failure supervision FUFSPVC
and current threshold value. The function is also blocked when The aim of the fuse failure supervision function FUFSPVC is to
the system positive sequence voltage magnitude deviates from block voltage measuring functions at failures in the secondary
the given voltage band limit which can be enabled by circuits between the voltage transformer and the IED in order to
EnaVoltCheck setting. avoid inadvertent operations that otherwise might occur.
ABB 25
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
The fuse failure supervision function basically has three different communication schemes for permissive underreaching,
detection methods, negative sequence and zero sequence permissive overreaching, blocking, delta based blocking,
based detection and an additional delta voltage and delta unblocking and intertrip are available.
current detection.
The built-in communication module (LDCM) can be used for
The negative sequence detection algorithm is recommended scheme communication signaling when included.
for IEDs used in isolated or high-impedance earthed networks.
It is based on the negative-sequence quantities. Current reversal and weak-end infeed logic for distance
protection ZCRWPSCH
The zero sequence detection is recommended for IEDs used in The ZCRWPSCH function provides the current reversal and
directly or low impedance earthed networks. It is based on the weak end infeed logic functions that supplement the standard
zero sequence measuring quantities. scheme communication logic. It is not suitable for standalone
use as it requires inputs from the distance protection functions
The selection of different operation modes is possible by a and the scheme communications function included within the
setting parameter in order to take into account the particular terminal.
earthing of the network.
On detection of a current reversal, the current reversal logic
A criterion based on delta current and delta voltage provides an output to block the sending of the teleprotection
measurements can be added to the fuse failure supervision signal to the remote end, and to block the permissive tripping at
function in order to detect a three phase fuse failure, which in the local end. This blocking condition is maintained long
practice is more associated with voltage transformer switching enough to ensure that no unwanted operation will occur as a
during station operations. result of the current reversal.
Fuse failure supervision VDSPVC On verification of a weak end infeed condition, the weak end
Different protection functions within the protection IED infeed logic provides an output for sending the received
operates on the basis of measured voltage at the relay point. teleprotection signal back to the remote sending end and other
Some example of protection functions are: output(s) for local tripping. For terminals equipped for single-
and two-pole tripping, outputs for the faulted phase(s) are
Distance protection function.
provided. Undervoltage detectors are used to detect the faulted
Undervoltage function.
phase(s).
Energisation function and voltage check for the weak
infeed logic. Local acceleration logic ZCLCPSCH
To achieve fast clearing of faults on the whole line, when no
These functions can operate unintentionally, if a fault occurs in
communication channel is available, local acceleration logic
the secondary circuits between voltage instrument
ZCLCPSCH can be used. This logic enables fast fault clearing
transformers and the IED. These unintentional operations can
and re-closing during certain conditions, but naturally, it can not
be prevented by VDSPVC.
fully replace a communication channel.
VDSPVC is designed to detect fuse failures or faults in voltage
The logic can be controlled either by the autorecloser (zone
measurement circuit, based on phase wise comparison of
extension) or by the loss-of-load current (loss-of-load
voltages of main and pilot fused circuits. VDSPVC blocking
acceleration).
output can be configured to block functions that need to be
blocked in case of faults in the voltage circuit. Scheme communication logic for residual overcurrent
protection ECPSCH
Multipurpose filter SMAIHPAC
To achieve fast fault clearance of earth faults on the part of the
The multi-purpose filter function block, SMAIHPAC, is arranged
line not covered by the instantaneous step of the residual
as a three-phase filter. It has very much the same user interface
overcurrent protection, the directional residual overcurrent
(e.g. inputs and outputs) as the standard pre-processing
protection can be supported with a logic that uses
function block SMAI. However the main difference is that it can
communication channels.
be used to extract any frequency component from the input
signal. Thus it can, for example, be used to build sub- In the directional scheme, information of the fault current
synchronous resonance protection for synchronous generator. direction must be transmitted to the other line end. With
directional comparison, a short operate time of the protection
10. Scheme communication including a channel transmission time, can be achieved. This
short operate time enables rapid autoreclosing function after
Scheme communication logic for distance or overcurrent the fault clearance.
protection ZCPSCH
To achieve instantaneous fault clearance for all line faults, The communication logic module for directional residual current
scheme communication logic is provided. All types of protection enables blocking as well as permissive under/
26 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
overreaching, and unblocking schemes. The logic can also be according to the specific application needs for settable pulse or
supported by additional logic for weak-end infeed and current steady output.
reversal, included in Current reversal and weak-end infeed logic
for residual overcurrent protection ECRWPSCH function. Group alarm logic function ALMCALH
The group alarm logic function ALMCALH is used to route
Current reversal and weak-end infeed logic for residual several alarm signals to a common indication, LED and/or
overcurrent protection ECRWPSCH contact, in the IED.
The Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH is a supplement to Scheme Group warning logic function WRNCALH
communication logic for residual overcurrent protection The group warning logic function WRNCALH is used to route
ECPSCH. several warning signals to a common indication, LED and/or
contact, in the IED.
To achieve fast fault clearing for all earth faults on the line, the
directional earth fault protection function can be supported with Group indication logic function INDCALH
logic that uses tele-protection channels. The group indication logic function INDCALH is used to route
several indication signals to a common indication, LED and/or
This is why the IEDs have available additions to the scheme contact, in the IED.
communication logic.
Basic configurable logic blocks
If parallel lines are connected to common busbars at both The basic configurable logic blocks do not propagate the time
terminals, overreaching permissive communication schemes stamp and quality of signals (have no suffix QT at the end of
can trip unselectively due to fault current reversal. This their function name). A number of logic blocks and timers are
unwanted tripping affects the healthy line when a fault is cleared always available as basic for the user to adapt the configuration
on the other line. This lack of security can result in a total loss of to the specific application needs. The list below shows a
interconnection between the two buses. To avoid this type of summary of the function blocks and their features.
disturbance, a fault current reversal logic (transient blocking
logic) can be used. These logic blocks are also available as part of an extension
logic package with the same number of instances.
Permissive communication schemes for residual overcurrent
protection can basically operate only when the protection in the AND function block. Each block has four inputs and two
remote IED can detect the fault. The detection requires a outputs where one is inverted.
sufficient minimum residual fault current, out from this IED. The
GATE function block is used for whether or not a signal
fault current can be too low due to an opened breaker or high-
should be able to pass from the input to the output.
positive and/or zero-sequence source impedance behind this
IED. To overcome these conditions, weak-end infeed (WEI) INVERTER function block that inverts one input signal to the
echo logic is used. The weak-end infeed echo is limited to 200 output.
ms to avoid channel lockup.
LLD function block. Loop delay used to delay the output
signal one execution cycle.
11. Logic
OR function block. Each block has up to six inputs and two
Tripping logic SMPPTRC
outputs where one is inverted.
A function block for protection tripping is always provided as
basic for each circuit breaker involved in the tripping of the fault. PULSETIMER function block can be used, for example, for
It provides a settable pulse prolongation to ensure a trip pulse pulse extensions or limiting of operation of outputs, settable
of sufficient length, as well as all functionality necessary for pulse time.
correct co-operation with autoreclosing functions.
RSMEMORY function block is a flip-flop that can reset or set
The trip function block also includes a settable latch an output from two inputs respectively. Each block has two
functionality for evolving faults and breaker lock-out. outputs where one is inverted. The memory setting controls
if, after a power interruption, the flip-flop resets or returns to
Trip matrix logic TMAGAPC
the state it had before the power interruption. RESET input
The trip matrix logic TMAGAPC function is used to route trip
has priority.
signals and other logical output signals to different output
contacts on the IED. SRMEMORY function block is a flip-flop that can set or reset
an output from two inputs respectively. Each block has two
The trip matrix logic function has 3 output signals and these
outputs where one is inverted. The memory setting controls
outputs can be connected to physical tripping outputs
if, after a power interruption, the flip-flop resets or returns to
ABB 27
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
the state it had before the power interruption. The SET input
has priority. Boolean 16 to Integer conversion with logic node
representation BTIGAPC
TIMERSET function has pick-up and drop-out delayed Boolean 16 to integer conversion with logic node
outputs related to the input signal. The timer has a settable representation function BTIGAPC is used to transform a set of
time delay. 16 binary (logical) signals into an integer. The block input will
freeze the output at the last value.
XOR function block. Each block has two outputs where one is
inverted. BTIGAPC can receive remote values via IEC 61850 depending
on the operator position input (PSTO).
Logic rotating switch for function selection and LHMI Integer to Boolean 16 conversion with logic node
presentation SLGAPC representation ITBGAPC
The logic rotating switch for function selection and LHMI Integer to boolean conversion with logic node representation
presentation SLGAPC (or the selector switch function block) is function ITBGAPC is used to transform an integer which is
used to get an enhanced selector switch functionality transmitted over IEC 61850 and received by the function to 16
compared to the one provided by a hardware selector switch. binary coded (logic) output signals.
Hardware selector switches are used extensively by utilities, in
order to have different functions operating on pre-set values. ITBGAPC function can only receive remote values over IEC
Hardware switches are however sources for maintenance 61850 when the R/L (Remote/Local) push button on the front
issues, lower system reliability and an extended purchase HMI, indicates that the control mode for the operator is in
portfolio. The selector switch function eliminates all these position R (Remote i.e. the LED adjacent to R is lit ), and the
problems. corresponding signal is connected to the input PSTO ITBGAPC
function block. The input BLOCK will freeze the output at the
Fixed signal function block last received value and blocks new integer values to be received
The Fixed signals function FXDSIGN generates nine pre-set and converted to binary coded outputs.
(fixed) signals that can be used in the configuration of an IED,
either for forcing the unused inputs in other function blocks to a Comparator for integer inputs INTCOMP
certain level/value, or for creating certain logic. Boolean, The function gives the possibility to monitor the level of integer
integer, floating point, string types of signals are available. values in the system relative to each other or to a fixed value. It
is a basic arithmetic function that can be used for monitoring,
One FXDSIGN function block is included in all IEDs. supervision, interlocking and other logics.
Elapsed time integrator with limit transgression and overflow Comparator for real inputs REALCOMP
supervision (TEIGAPC) The function gives the possibility to monitor the level of real
The Elapsed time integrator function TEIGAPC is a function that value signals in the system relative to each other or to a fixed
accumulates the elapsed time when a given binary signal has value. It is a basic arithmetic function that can be used for
been high. monitoring, supervision, interlocking and other logics.
28 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Supervision of mA input signals The event list logs all binary input signals connected to the
The main purpose of the function is to measure and process Disturbance recorder function. The list may contain up to 1000
signals from different measuring transducers. Many devices time-tagged events stored in a ring-buffer.
used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current Indications DRPRDRE
values, usually in the range 4-20 mA or 0-20 mA. To get fast, condensed and reliable information about
disturbances in the primary and/or in the secondary system it is
Alarm limits can be set and used as triggers, e.g. to generate important to know, for example binary signals that have
trip or alarm signals. changed status during a disturbance. This information is used
in the short perspective to get information via the local HMI in a
The function requires that the IED is equipped with the mA input straightforward way.
module.
There are three LEDs on the local HMI (green, yellow and red),
Disturbance report DRPRDRE which will display status information about the IED and the
Complete and reliable information about disturbances in the Disturbance recorder function (triggered).
primary and/or in the secondary system together with
continuous event-logging is accomplished by the disturbance The Indication list function shows all selected binary input
report functionality. signals connected to the Disturbance recorder function that
have changed status during a disturbance.
Disturbance report DRPRDRE, always included in the IED,
acquires sampled data of all selected analog input and binary Event recorder DRPRDRE
signals connected to the function block with a, maximum of 40 Quick, complete and reliable information about disturbances in
analog and 352 binary signals. the primary and/or in the secondary system is vital, for example,
time-tagged events logged during disturbances. This
The Disturbance report functionality is a common name for information is used for different purposes in the short term (for
several functions: example corrective actions) and in the long term (for example
functional analysis).
Event list
Indications The event recorder logs all selected binary input signals
Event recorder connected to the Disturbance recorder function. Each
Trip value recorder recording can contain up to 150 time-tagged events.
Disturbance recorder
Fault locator The event recorder information is available for the disturbances
locally in the IED.
The Disturbance report function is characterized by great
flexibility regarding configuration, starting conditions, recording The event recording information is an integrated part of the
times, and large storage capacity. disturbance record (Comtrade file).
ABB 29
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Generic communication function for Single Point indication The fault locator is an impedance measuring function giving the
SPGAPC distance to the fault in km, miles or % of line length. The main
Generic communication function for Single Point indication advantage is the high accuracy achieved by compensating for
SPGAPC is used to send one single logical signal to other load current and for the mutual zero-sequence effect on double
systems or equipment in the substation. circuit lines.
Generic communication function for Measured Value MVGAPC The compensation includes setting of the remote and local
Generic communication function for Measured Value MVGAPC sources and calculation of the distribution of fault currents from
function is used to send the instantaneous value of an analog each side. This distribution of fault current, together with
signal to other systems or equipment in the substation. It can recorded load (pre-fault) currents, is used to exactly calculate
also be used inside the same IED, to attach a RANGE aspect to the fault position. The fault can be recalculated with new source
an analog value and to permit measurement supervision on that data at the actual fault to further increase the accuracy.
value.
Especially on heavily loaded long lines, where the source
Measured value expander block RANGE_XP voltage angles can be up to 35-40 degrees apart, the accuracy
The current and voltage measurements functions (CVMMXN, can be still maintained with the advanced compensation
CMMXU, VMMXU and VNMMXU), current and voltage included in fault locator.
sequence measurement functions (CMSQI and VMSQI) and IEC
61850 generic communication I/O functions (MVGAPC) are Event counter with limit supervison L4UFCNT
provided with measurement supervision functionality. All The 30 limit counter L4UFCNT provides a settable counter with
measured values can be supervised with four settable limits: four independent limits where the number of positive and/or
low-low limit, low limit, high limit and high-high limit. The negative flanks on the input signal are counted against the
30 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
setting values for limits. The output for each limit is activated (STARTACC and STOPACC) and EnaAcc setting and it can be
when the counted value reaches that limit. reset to initial values with RSTACC input.
Overflow indication is included for each up-counter. The maximum demand for active and reactive powers are
calculated for the set time interval tEnergy and these values are
Running hour-meter (TEILGAPC) updated every minute through output channels. The active and
The Running hour-meter (TEILGAPC) function is a function that reactive maximum power demand values are calculated for
accumulates the elapsed time when a given binary signal has both forward and reverse direction and these values can be
been high. reset with RSTDMD input.
Applicable to very long time accumulation ( 99999.9 14. Human machine interface
hours)
Supervision of limit transgression conditions and rollover/ Local HMI
overflow
Possibility to define a warning and alarm with the
resolution of 0.1 hours
Retain any saved accumulation value at a restart
Possibilities for blocking and reset
Possibility for manual addition of accumulated time
Reporting of the accumulated time
13. Metering
measured active and reactive power as input and calculates the IEC13000239 V2 EN
accumulated active and reactive energy pulses, in forward and Figure 5. Local human-machine interface
reverse direction. Energy values can be read or generated as
pulses. Maximum demand power values are also calculated by
the function. This function includes zero point clamping to The LHMI of the IED contains the following elements:
remove noise from the input signal. As output of this function: Graphical display capable of showing a user defined single
periodic energy calculations, integration of energy values, line diagram and provide an interface for controlling
calculation of energy pulses, alarm signals for limit violation of switchgear.
energy values and maximum power demand, can be found. Navigation buttons and five user defined command buttons
to shortcuts in the HMI tree or simple commands.
The values of active and reactive energies are calculated from 15 user defined three-color LEDs.
the input power values by integrating them over a selected time Communication port for PCM600.
tEnergy. The integration of active and reactive energy values will
happen in both forward and reverse directions. These energy
The LHMI is used for setting, monitoring and controlling.
values are available as output signals and also as pulse outputs.
Integration of energy values can be controlled by inputs
ABB 31
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
15. Basic IED functions automation systems but the main use is for Substation
Monitoring Systems SMS.
Time synchronization
The time synchronization function is used to select a common IEC 60870-5-103 communication protocol
source of absolute time for the synchronization of the IED when A single glass or plastic port is provided for the IEC
it is a part of a control and a protection system. This makes it 60870-5-103 standard. This allows design of simple substation
possible to compare events and disturbance data between all automation systems including equipment from different
IEDs within a station automation system and in between sub- vendors. Disturbance files uploading is provided.
stations. A common source shall be used for IED and merging
unit when IEC 61850-9-2LE process bus communication is DNP3.0 communication protocol
used. An electrical RS485 and an optical Ethernet port is available for
the DNP3.0 communication. DNP3.0 Level 2 communication
with unsolicited events, time synchronizing and disturbance
16. Station communication reporting is provided for communication to RTUs, Gateways or
HMI systems.
Communication protocols
Each IED is provided with a communication interface, enabling Multiple command and transmit
it to connect to one or many substation level systems or When IEDs are used in Substation Automation systems with
equipment, either on the Substation Automation (SA) bus or LON, SPA or IEC 60870-5-103 communication protocols, the
Substation Monitoring (SM) bus. Event and Multiple Command function blocks are used as the
communication interface for vertical communication to station
Available communication protocols are:
HMI and gateway, and as interface for horizontal peer-to-peer
IEC 61850-8-1 communication protocol communication (over LON only).
IEC 61850-9-2LE communication protocol
IEC 62439-3 Parallel Redundancy Protocol
LON communication protocol
Redundant station bus communication according to IEC
SPA or IEC 60870-5-103 communication protocol
62439-3 Edition 1 and IEC 62439-3 Edition 2 parallel
DNP3.0 communication protocol
redundancy protocol (PRP) are available as options when
Several protocols can be combined in the same IED. ordering IEDs. Redundant station bus communication
according to IEC 62439-3 uses both port AB and port CD on
IEC 61850-8-1 communication protocol the OEM module.
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in PCM600.
The IED is equipped with single or double optical Ethernet rear
17. Remote communication
ports (order dependent) for IEC 61850-8-1 station bus
communication. The IEC 61850-8-1 communication is also Analog and binary signal transfer to remote end
possible from the electrical Ethernet front port. IEC 61850-8-1 Three analog and eight binary signals can be exchanged
protocol allows intelligent electrical devices (IEDs) from different between two IEDs. This functionality is mainly used for the line
vendors to exchange information and simplifies system differential protection. However it can be used in other products
engineering. IED-to-IED communication using GOOSE and as well. An IED can communicate with up to 4 remote IEDs.
client-server communication over MMS are supported.
Disturbance recording file (COMTRADE) uploading can be done Binary signal transfer to remote end, 192 signals
over MMS or FTP. If the communication channel is used for transfer of binary
signals only, up to 192 binary signals can be exchanged
IEC 61850-9-2LE communication protocol between two IEDs. For example, this functionality can be used
Single optical Ethernet port communication standard IEC to send information such as status of primary switchgear
61850-9-2LE for process bus is provided. IEC 61850-9-2LE apparatus or intertripping signals to the remote IED. An IED can
allows Non Conventional Instrument Transformers (NCIT) with communicate with up to 4 remote IEDs.
Merging Units (MU) or stand alone Meging Units to exchange
information with the IED and simplifies SA engineering. Line data communication module, short and medium range
LDCM
LON communication protocol The line data communication module (LDCM) is used for
Existing stations with ABB station bus LON can be extended communication between the IEDs situated at distances <110
with use of the optical LON interface. This allows full SA km/68 miles or from the IED to optical to electrical converter
functionality including peer-to-peer messaging and with G.703 or G.703E1 interface located on a distances < 3
cooperation between the IEDs. km/1.9 miles away. The LDCM module sends and receives
data, to and from another LDCM module. The IEEE/ANSI
SPA communication protocol
C37.94 standard format is used.
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
32 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
bus) that use the IEC 61850-8-1 protocol (OEM rear port A, B).
Galvanic X.21 line data communication module X.21-LDCM The process bus use the IEC 61850-9-2LE protocol (OEM rear
A module with built-in galvanic X.21 converter which e.g. can port C, D). The module has one or two optical ports with ST
be connected to modems for pilot wires is also available. connectors.
Galvanic interface G.703 resp G.703E1 Serial and LON communication module SLM, supports
The external galvanic data communication converter G.703/G. SPA/IEC 60870-5-103, LON and DNP 3.0
703E1 makes an optical-to-galvanic conversion for connection The serial and LON communication module (SLM) is used for
to a multiplexer. These units are designed for 64 kbit/s resp SPA, IEC 60870-5-103, DNP3 and LON communication. The
2Mbit/s operation. The converter is delivered with 19 rack module has two optical communication ports for plastic/plastic,
mounting accessories. plastic/glass or glass/glass. One port is used for serial
communication (SPA, IEC 60870-5-103 and DNP3 port) and
18. Hardware description one port is dedicated for LON communication.
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
IEC08000165 V1 EN
E
Figure 7. Case with rear cover and 19 rack mounting kit
A
D
B
C
IEC08000163-2-en.vsd
IEC06000182-2-en.vsd
IEC08000163 V2 EN
IEC06000182 V2 EN
Case size A B C D E F G H J K
(mm)/(inches)
6U, 1/2 x 19 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00
6U, 3/4 x 19 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00
6U, 1/1 x 19 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00
34 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Mounting alternatives See ordering for details about available mounting alternatives.
19 rack mounting kit
Flush mounting kit with cut-out dimensions:
1/2 case size (h) 254.3 mm/10.01 (w) 210.1 mm/8.27
3/4 case size (h) 254.3 mm/10.01 (w) 322.4 mm/12.69
1/1 case size (h) 254.3 mm/10.01 (w) 434.7 mm/17.11
Wall mounting kit
ABB 35
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
The latest versions of the connection diagrams can be Connection diagram, REC670 2.1, B30 1MRK002803-FB
downloaded from http://www.abb.com/substationautomation.
Connection diagram, REC670 2.1, C30 1MRK002803-FC
Connection diagrams for Customized products
Connection diagrams for Customized products
Connection diagram, 670 series 2.11MRK002801-AF
Connection diagram, 670 series 2.1 1MRK002802-AF
36 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified
requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Table 7. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) Ir
Frequency fr = 50/60 Hz 5%
Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Frequency fr = 50/60 Hz 5%
ABB 37
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Power consumption -
each mA-board 2W
each mA input 0.1 W
Number of channels 1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118 and port C, D for IEC 61850-9-2LE / IEEE
C37.118)
1 or 2 (port A, B for IEC 61850-8-1 / IEEE C37.118)
Auxiliary DC voltage
38 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Binary inputs 16 -
Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
110/125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
ABB 39
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos > 0.4 250 V/8.0 A 250 V/8.0 A
40 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
ABB 41
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
42 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
90-250 V DC 20%
Interruption interval
050 ms
No restart
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr 2.0%
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr 10.0%
protection (10% content)
Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr 3.0% / Hz
ABB 43
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 6100049, Class V
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
44 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Change of temperature test Test Nb for 5 cycles at -25C to +70C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55C and humidity 93 to 95% (1 cycle = 24 IEC 60068-2-30
hours)
Test According to
Immunity EN 6025526
Emissivity EN 6025526
ABB 45
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Differential protection
46 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Current protection
ABB 47
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Inverse time characteristics, see 16 curve types See table 143, table 144 and table 145
table 143, table 144 and table 145
48 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Table 32. Four step residual overcurrent protection EF4PTOC technical data
Inverse time characteristics, see 16 curve types See Table 143, Table 144 and
Table 143, Table 144 and Table Table 145
145
ABB 49
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Inverse time characteristics, see 16 curve types See table 143, table 144 and table
table 143, table 144 and table 145
145
50 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Table 34. Sensitive directional residual overcurrent and power protection SDEPSDE
Inverse characteristics, see 16 curve types See table "", table "" and table ""
table "", table "" and table ""
ABB 51
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Operate time: Time constant t = (11000) IEC 60255-149, 5.0% or 200 ms whichever is greater
minutes
I - Ip
2 2
t = t ln
2 2 TTrip - TAmb 2
I - Ip - T I ref
ref
EQUATION13000039 V2 EN (Equation 1)
Operate time: Ip = load current before overload 5.0% or 200 ms whichever is greater
occurs
I 2 - I p2 Time constant = (0.10500.00)
t = t ln 2 minutes
I - I ref 2
EQUATION1356 V2 EN (Equation 2)
Alarm level 1 and 2 (5099)% of heat content operate 2.0% of heat content trip
value
Reset level temperature (1095)% of heat content trip 2.0% of heat content trip
52 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Phase current level for blocking of contact function (5-200)% of lBase 1.0% of Ir at I Ir
1.0% of I at I > Ir
Time delay for back-up trip at multi-phase start at 0 to 2 x Iset (0.000-60.000) s 0.2% or 20 ms whichever is
greater
Additional time delay for a second back-up trip at 0 to 2 x Iset (0.000-60.000) s 0.2% or 20 ms whichever is
greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s 0.2% or 15 ms whichever is
greater
ABB 53
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
S r = 1.732 U r I r
Independent time delay to operate for Step 1 (0.01-6000.00) s 0.2% or 40 ms whichever is greater
and Step 2 at 2 to 0.5 x Sr and k=0.000
Max. = 25 ms
Max. = 55 ms
Independent time delay to operate for Step 1 (0.01-6000.00) s 0.2% or 40 ms whichever is greater
and Step 2 at 0.5 to 2 x Sr and k=0.000
54 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Operate value, voltage protection function for harmonic overload (Definite (10-500)% 0.5% of Ur at U Ur
time) 0.5% of U at U > Ur
Operate value, voltage protection function for harmonic overload (Inverse (80-200)% 0.5% of Ur at U Ur
time) 0.5% of U at U > Ur
Inverse time characteristic According to IEC 60871-1 (2005) and 20% or 200 ms
IEEE/ANSI C37.99 (2000) whichever is greater
Independent time delay, reactive power overload function at 0 to 2 x (1.00-6000.00) s 0.2% or 100 ms
QOL> whichever is greater
ABB 55
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Voltage protection
Inverse time characteristics for step 1 and step 2, see table 147 - See table 147
Definite time delay, step 1 at 1.2 to 0 x Uset (0.00-6000.00) s 0.2% or 40ms whichever is
greater
Definite time delay, step 2 at 1.2 to 0 x Uset (0.000-60.000) s 0.2% or 40ms whichever is
greater
56 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Inverse time characteristics for steps 1 and 2, see table 146 - See table 146
Definite time delay, low step (step 1) at 0 to 1.2 x Uset (0.00 - 6000.00) s 0.2% or 45 ms whichever is greater
Definite time delay, high step (step 2) at 0 to 1.2 x Uset (0.000-60.000) s 0.2% or 45 ms whichever is greater
Inverse time characteristics for low and high step, see table 148 - See table 148
Definite time delay low step (step 1) at 0 to 1.2 x Uset (0.006000.00) s 0.2% or 45 ms whichever is
greater
Definite time delay high step (step 2) at 0 to 1.2 x Uset (0.00060.000) s 0.2% or 45 ms whichever is
greater
ABB 57
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Time delay to block when all three (0.00060.000) s 0.2% or 35 ms whichever is greater
phase voltages are not low
58 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Frequency protection
Operate time, definite time function at fset + 0.02 Hz to (0.000-60.000)s 0.2% or 100 ms whichever is greater
fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 Hz to fset (0.000-60.000)s 0.2% or 120 ms whichever is greater
+ 0.02 Hz
Exponent
U - UMin
t= ( tMax - tMin ) + tMin
UNom - UMin
EQUATION1182 V1 EN (Equation 3)
U=Umeasured
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz 2.0 mHz
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s 0.2% 100 ms
whichever is greater
Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s 0.2% 120 ms,
whichever is greater
ABB 59
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Definite time delay for frequency gradient trip (0.200-60.000) s 0.2% or 120 ms whichever is
greater
Operate value, frequency high limit level at (35.00 90.00) Hz 2.0 mHz
symmetrical three phase voltage
Operate value, voltage high and low limit for (0.0 200.0)% of UBase 0.5% of Ur at U Ur
voltage band limit check 0.5% of U at U > Ur
Operate value, current start level (5.0 100.0)% of IBase 1.0% of Ir or 0.01 A at IIr
Independent time delay for the continuous time (0.0 6000.0) s 0.2% or 200 ms whichever is greater
limit at fset+0.02 Hz to fset-0.02 Hz
Independent time delay for the accumulation (10.0 90000.0) s 0.2% or 200 ms whichever is greater
time limit at fset+0.02 Hz to fset-0.02 Hz
60 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Multipurpose protection
Independent time delay, overcurrent at 0 to 2 x Iset, step 1 - 2 (0.00 - 6000.00) s 0.2% or 35 ms whichever is
greater
Independent time delay, undercurrent at 2 to 0 x Iset, step 1 - 2 (0.00 - 6000.00) s 0.2% or 35 ms whichever is
greater
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 143, 144 and table 145 16 curve types See table 143, 144 and table 145
Overcurrent:
Minimum operate time for inverse curves, step 1 - 2 (0.00 - 6000.00) s 0.2% or 35 ms whichever is
greater
Voltage level where voltage memory takes over (0.0 - 5.0)% of UBase 0.5% of Ur
Independent time delay, overvoltage at 0.8 to 1.2 x Uset, step 1 - 2 (0.00 - 6000.00) s 0.2% or 35 ms whichever is
greater
ABB 61
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Independent time delay, undervoltage at 1.2 to 0.8 x Uset, step 1 - (0.00 - 6000.00) s 0.2% or 35 ms whichever is
2 greater
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 146 4 curve types See table 146
Undervoltage:
Inverse time characteristics, see table 147 3 curve types See table 147
High and low voltage limit, voltage dependent operation, step 1 - 2 (1.0 - 200.0)% of UBase 1.0% of Ur at U Ur
1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
62 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Table 54. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4
ABB 63
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Max. = 30 ms
Max. = 30 ms
Inverse time characteristics, 13 curve types See tables 143 and 144
see tables 143 and 144
Minimum operate time for inverse time characteristics (0.00 - 60.00) s 0.2% or 35 ms whichever is
greater
High voltage limit, voltage dependent operation (30.0 - 100.0)% of UBase 1.0% of Ur
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate, undervoltage at 2 to 0 x Uset (0.00 - 6000.00) s 0.2% or 35 ms whichever is
greater
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 to 0 x Uset
Impulse margin time 15 ms typically
64 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
ABB 65
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
66 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Control
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase 0.5% of Ur at U Ur
0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz 2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees 2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u 0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between bus (0.000-60.000) s 0.2% or 35 ms whichever is
and line jumps from PhaseDiff + 2 degrees to PhaseDiff - 2 degrees greater
tMaxSynch, which resets synchronizing function if no close has been made (0.000-6000.00) s 0.2% or 35 ms whichever is
before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% of (0.000-60.000) s 0.2% or 100 ms whichever is
Urated greater
Operate time for synchrocheck function when angle difference between bus Min. = 15 ms
and line jumps from PhaseDiff + 2 degrees to PhaseDiff - 2 degrees Max. = 30 ms
Operate time for energizing function when voltage jumps from 0 to 90% of Min. = 70 ms
Urated Max. = 90 ms
ABB 67
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle (0.00-6000.00) s 0.2% or 35 ms
whichever is greater
Wait time after close command before proceeding to next shot (0.000-60.000) s 0.2% or 45 ms
whichever is greater
68 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Time delay for lower command when fast step down mode is activated (1.0100.0) s -
Time delay (long) for automatic control commands (31000) s 0.2% or 600 ms
whichever is greater
Time delay (short) for automatic control commands (11000) s 0.2% or 600 ms
whichever is greater
Duration time for the reverse action block signal (306000) s 0.2% or 600 ms
whichever is greater
Level for number of counted raise/lower within one hour (030) operations/hour -
Alarm level of active power in forward and reverse direction at (10-200)% of (-9999.999999.99) MW 1.0% of Sr
Sr and (85-120)% of UBase
Alarm level of reactive power in forward and reverse direction at (10-200)% (-9999.999999.99) MVAr 1.0% of Sr
of Sr and (85-120)% of UBase
Time delay for alarms from power supervision (16000) s 0.2% or 600 ms
whichever is greater
ABB 69
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Time after position change before the value is accepted (160) s 0.2% or 200 ms
whichever is greater
70 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Scheme communication
Table 62. Scheme communication logic for distance or overcurrent protection ZCPSCH
Table 63. Scheme communication logic for residual overcurrent protection ECPSCH
Table 64. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH
ABB 71
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Logic
3 ms 8 ms 100 ms
SMPPTRC 6 - -
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
3 ms 8 ms 100 ms
ALMCALH - - 5
3 ms 8 ms 100 ms
WRNCALH - - 5
3 ms 8 ms 100 ms
INDCALH - 5 -
3 ms 8 ms 100 ms
AND 60 60 160
3 ms 8 ms 100 ms
GATE 10 10 20
72 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
INV 90 90 240
3 ms 8 ms 100 ms
LLD 10 10 20
3 ms 8 ms 100 ms
OR 60 60 160
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XOR 10 10 20
ABB 73
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
ANDQT - 20 100
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
3 ms 8 ms 100 ms
INVALIDQT - 6 6
3 ms 8 ms 100 ms
INVERTERQT - 20 100
3 ms 8 ms 100 ms
ORQT - 20 100
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
74 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XORQT - 10 30
3 ms 8 ms 100 ms
AND 40 40 100
GATE - - 49
INV 40 40 100
LLD - - 49
OR 40 40 100
PULSETIMER 5 5 49
SLGAPC 10 10 54
SRMEMORY - - 110
TIMERSET - - 49
VSGAPC 10 10 110
XOR - - 49
3 ms 8 ms 100 ms
B16I 6 4 8
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
ABB 75
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
3 ms 8 ms 100 ms
IB16 6 4 8
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
Table 97. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours 0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours 0.1% of set value
76 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Monitoring
Phase angle at symmetrical load (0.1-4.0) Ir 1.0 degrees at 0.1 Ir < I 0.5 Ir
0.5 degrees at 0.5 Ir < I 4.0 Ir
ABB 77
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
78 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Time delay for pressure alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s 0.2% or 250ms whichever is greater
ABB 79
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Time delay for oil alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s 0.2% or 250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s 0.2% or 250ms whichever is greater
Independent time delay for spring charging time (0.00 60.00) s 0.2% or 30 ms whichever is greater
alarm
Independent time delay for gas pressure alarm (0.00 60.00) s 0.2% or 30 ms whichever is greater
Independent time delay for gas pressure lockout (0.00 60.00) s 0.2% or 30 ms whichever is greater
Function Value
Resolution 1 ms
80 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Function Value
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at 50 Hz
channels, typical value) 280 seconds (80 recordings) at 60 Hz
ABB 81
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
82 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Station communication
Function Value
Protocol DNP3.0
Function Value
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
ABB 83
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Insulation 1 kV
Table 130. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
84 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
ABB 85
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Hardware
IED
Table 133. Water and dust protection level according to IEC 60529
Electrical safety
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
Because of limitations of space, when ring between two adjacent IO cards. Please refer
lug terminal is ordered for Binary I/O to the ordering particulars for details.
connections, one blank slot is necessary
86 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values 1.0 ms typically
Time to reliable time reference after a power loss longer <15 minutes
than 48 hours
Time to reliable time reference after a power loss shorter <5 minutes
than 48 hours
Function Value
Accuracy +/-1s
ABB 87
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Electrical connector:
Amplitude modulated
low level 1-3 Vpp
high level 3 x low level, max 9 Vpp
Accuracy +/-10s for IRIG-B 00x and +/-100s for IRIG-B 12x
Optical connector:
Accuracy +/- 1s
88 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Inverse characteristic
Reset characteristic:
tr
t = k
(I 2
-1 )
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ABB 89
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
I = Imeasured/Iset
TR
t = k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
I
t = 5.8 - 1.35 In
k
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
90 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
U> = Uset
U = Umeasured
k 480
t = + 0.035
2.0
32 U U > 0.5
U >
EQUATION1437-SMALL V2 EN
k 480
t = + 0.035
3.0
32 U U > 0.5
U >
EQUATION1438-SMALL V2 EN
ABB 91
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
U< = Uset
U = Umeasured
k 480
t = + 0.055
2.0
32 U < -U - 0.5
U <
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
92 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
U> = Uset
U = Umeasured
ABB 93
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0
Example of a complete code: REC670*2.1-F00X00 - A00000060000000 - B0000000000000000000000000 - C6600666666660036221300300 - D22206020 - E6662 - F9
- S6 - G642 - H26461114444 - K10101110 - L0611 - M61 - P01 - B1X0 - AC - MB - B - A3X0 - D1D1ARGN1N1XXXXXXX - AAFXXX - AX
Impedance protection -
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Current protection -
C 00 00 0 0 0 0 -
Remote end serial communication - Serial communication unit for station communication
-
Product REC670*
Software version 2.1
Configuration alternatives
Bay Control REC670 F00
Bay control REC670 61850-9-2LE N00
Selection:
ACT configuration
ABB Standard configuration X00
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14
A 0 0 0 0 0 0 0 0 0 0 0 0 0
94 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Po 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
siti
on
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Pos 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
itio
n
C 00 00 0 0 0 0
Position 1 2 3 4 5 6 7 8
D 0 0 0
Position 1 2 3 4
E
ABB 95
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Position 1
F
Position 1
S
Position 1 2 3
G
Position 1 2 3 4 5 6 7 8 9 10 11
H
96 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Position 1 2 3 4 5 6 7 8
K 0 0 0
ABB 97
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Position 1 2
L
Position 1 2
M
Position 1 2 3 4 5 6 7 8 9 10 11 12 13
P 0 0 0 0 0 0 0 0 0 0 0
First local HMI user dialogue language Selection Notes and Rules
HMI language, English IEC B1
Additional HMI language
No additional HMI language X0
HMI language, English US A12
Selected
98 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Mounting details with IP40 of protection from the front Selection Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selected
ABB 99
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Note: When ordering I/O modules, observe the maximum quantities according to the table below
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19, one (1) TRM 14 6 4 4 14 cards, including a combination of four cards of type BOM, SOM and MIM
1/1 x 19, two (2) TRM 11 6 4 4 11 cards, including a combination of four cards of type BOM, SOM and MIM
3/4 x 19, one (1) TRM 8 6 4 4 8 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
3/4 x 19, two (2) TRM 5 5 4 4 5 cards, including a combination of four cards of type BOM, SOM and maximun oen MIM
1/2 x 19, one (1) TRM 3 3 3 1 3 cards
100 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
in 3/4 rack with 1 TRM, 5 in 3/4
1/2 Case with 1 TRM rack with 2 TRM ,11 in 1/1 rack
with 2 TRM and 14 in 1/1 rack with
3/4 Case with 1 TRM 1 TRM
3/4 Case with 2 TRM
1/1 Case with 1 TRM
1/1 Case with 2 TRM
No board in slot X X X X X X X X X X X X X X
Binary output module 24 A A A A A A A A A A A A A A
output relays (BOM)
BIM 16 inputs, RL24-30 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
VDC, 50 mA
BIM 16 inputs, RL48-60 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
VDC, 50 mA
BIM 16 inputs, D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110-125 VDC, 50 mA
BIM 16 inputs, E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220-250 VDC, 50 mA
BIM 16 inputs, 220-250 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
VDC, 120mA
BIMp 16 inputs, RL24-30 F F F F F F F F F F F F F F
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, RL48-60 G G G G G G G G G G G G G G
VDC, 30 mA, for pulse
counting
BIMp 16 inputs, H H H H H H H H H H H H H H
RL110-125 VDC, 30 mA,
for pulse counting
BIM 16 inputs, K K K K K K K K K K K K K K
RL220-250 VDC, 30 mA,
for pulse counting
IOM 8 inputs, 10+2 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
output, RL24-30 VDC, 50
mA
IOM 8 inputs, 10+2 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
output, RL48-60 VDC, 50
mA
IOM 8 inputs, 10+2 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
output, RL110-125 VDC,
50 mA
IOM 8 inputs, 10+2 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
output, RL220-250 VDC,
50 mA
IOM 8 inputs 10+2 output P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
relays, 220-250 VDC,
110mA
IOM with MOV 8 inputs, U U U U U U U U U U U U U U
10-2 output, 24-30 VDC,
30 mA
IOM with MOV 8 inputs, V V V V V V V V V V V V V V
10-2 output, 48-60 VDC,
30 mA
IOM with MOV 8 inputs, W W W W W W W W W W W W W W
10-2 output, 110-125
VDC, 30 mA
IOM with MOV 8 inputs, Y Y Y Y Y Y Y Y Y Y Y Y Y Y
10-2 output, 220-250
VDC, 30 mA
mA input module MIM 6 R R R R R R R R R R R R R R
channels
ABB 101
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Remote end communication, DNP serial comm. and time synchronization modules Selection Notes and Rules
Slot position (rear view) Note: The maximum number and
X312
X313
X302
X303
X322
X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2, 3/4 and 1/1 case with 1TRM Note: Max 2 LDCM in 1/2 case
Available slots in 3/4 and 1/1 case with 2 TRM
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Max 2 LDCM (same or
different type) can be selected
Optical medium range, LDCM 1310 nm B B B B B B
Rule: Always place LDCM
Optical long range, LDCM 1550 nm C C C C C C modules on the same board to
Galvanic X21 line data communication module E E E E E E support redundant
communication; in P30:2 and
P30:3, P31:2 and P31:3 or P32:2
and P32:3.
IRIG-B Time synchronization module F F F F F F
Galvanic RS485 communication module G G G G G G
GPS time synchronization module S S S S
Selected
Serial communication unit for station communication Selection Notes and Rules
Slot position (rear view)
X301
X311
102 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REC670 *2.1-A30X00- A02H02-B1A3-AC-MB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-13 specified as
REC670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 8-9-10 10 10 10-11 11 11 11 11 11 11 11 11 11 11-12 12 12 12 12 12-13 13
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REC670* - - - - - . - -
10 - 11 - 12 - 13
- . -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 2.1
Selection for position #1.
ABB 103
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
104 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with fibre
connection (SLM, OEM, LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
Connection type for Input/output and Communication modules #8 Notes and Rules
Compression terminals P
Selection for position #8.
ABB 105
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Binary input/output module, mA and time synchronizating #11 Notes and Rules
boards.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included in A30 and A31. 2 BIM and 1 BOM included in B30 and C30.
Slot position (rear view) Note: Max 3 positions in 1/2 rack, 8
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
in 3/4 rack with 1 TRM, 5 in 3/4
rack with 2 TRM, 14 in 1/1 rack
with 1 TRM and 11 in 1/1 rack with
2 TRM
1/2 Case with 1 TRM
3/4 Case with 1 TRM
3/4 Case with 2 TRM
1/1 Case with 1 TRM
1/1 Case with 2 TRM
No board in slot X X X X X X X X X X X X X X
Binary output module 24 output relays (BOM) A A A A A A A A A A A A A Note: Maximum 4 (BOM+SOM
+MIM) boards. X51 not in B30/
C30.
BIM 16 inputs, RL24-30 VDC, 50 mA B B B B B B B B B B B B B
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL48-60 VDC, 50 mA C C C C C C C C C C C C C
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL110-125 VDC, 50 mA D D D D D D D D D D D D D
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, RL220-250 VDC, 50 mA E E E E E E E E E E E E E
1 1 1 1 1 1 1 1 1 1 1 1 1
BIM 16 inputs, 220-250 VDC, 120mA E E E E E E E E E E E E E
2 2 2 2 2 2 2 2 2 2 2 2 2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting F F F F F F F F F F F F Note: X51 not in B30/C30.
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting G G G G G G G G G G G G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting H H H H H H H H H H H H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting K K K K K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L L L L L L L L L L L L
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M M M M M M M M M M M M
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N N N N N N N N N N N N
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P P P P P P P P P P P P
1 1 1 1 1 1 1 1 1 1 1 1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA P P P P P P P P P P P P
2 2 2 2 2 2 2 2 2 2 2 2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA U U U U U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA V V V V V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA W W W W W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA Y Y Y Y Y Y Y Y Y Y Y Y
mA input module MIM 6 channels R R R R R R R R R R R R Note: maximum 1 MIM in 1/2 case.
X51 not in B30/C30.
SOM Static output module, 12 outputs, 48-60 VDC T T T T T T T T T T T T Note: SOM must not to be placed
1 1 1 1 1 1 1 1 1 1 1 1 in position nearest to NUM; 1/2
case slot P5, 3/4 case 1 TRM slot
SOM static outputs module, 12 outputs, 110-250 VDC T T T T T T T T T T T T
P10, 3/4 case 2 TRM slot P7, 1/1
2 2 2 2 2 2 2 2 2 2 2 2
case 1 TRM slot P16, 1/1 case 2
TRM slot P13
X51 not in B30/C30.
Selection for position #11.
106 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Remote end communication, DNP serial comm. and time synchronization modules #12 Notes and Rules
Slot position (rear view) Note: The maximum number and
X312
X313
X302
X303
X322
X323
type of LDCM modules supported
depend on the total amount of
modules (BIM, BOM, LDCM,
OEM, GTM, SLM, RS485, IRIG-B)
in the IED.
Available slots in 1/2 case with 1 TRM Note: Max 2 LDCM in 1/2 case
Available slots in 3/4 and 1/1 case with 1 TRM
Available slots in 3/4 and 1/1 case with 2 TRM slots
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Max 2 LDCM (same or
different type) can be selected
Optical medium range, LDCM 1310 nm B B B B B B
Rule: Always place LDCM
modules on the same board to
support redundant
communication; in P30:2 and
P30:3, P31:2 and P31:3 or P32:2
and P32:3
IRIG-B Time synchronization module, with PPS F F F F F F
Galvanic RS485 communication module G G G G G G
GPS Time Module, GTM S S S S
Selection for position #12.
Serial communication unit for station communication #13 Notes and Rules
Slot position (rear view)
X301
X311
No first communication board included X
No second communication board included X
Serial and LON communication module (plastic) A
Serial (plastic) and LON (glass) communication module B
Serial and LON communication module (glass) C
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selection for position #13.
ABB 107
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Accessories
GPS antenna and mounting details
Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA
Due to the high flexibility of our product and the wide variety of The normally open "In test mode" contact 29-30 on the RTXP
applications possible the test switches needs to be selected for test switches should be connected to the input of the test
each specific application. function block to allow activation of functions individually during
testing.
Select your suitable test switch base on the available contacts
arrangements shown in the reference documentation. Test switches type RTXP 24 is ordered separately. Please refer
to Section Related documents for references to corresponding
However our proposals for suitable variants are; documents.
Single breaker/Single or Three Phase trip with internal neutral RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and the
on current circuits (ordering number RK926 315-AK). on/off switch for dc-supply are ordered separately. Please refer
to Section Related documents for references to corresponding
Single breaker/Single or Three Phase trip with external neutral documents.
on current circuits (ordering number RK926 315-AC).
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19 Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19 Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19 Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19 Quantity: 1MRK 002 420-AA
108 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V 1 2 3
operating voltage Quantity: RK 795 101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V Quantity: RK 795 101-MB
operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 100-400V 1 2 3
operating voltage Quantity: RK 795 101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 100-400V Quantity: RK 795 101-DC
operating voltage
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual,
Installation manual, Commissioning manual, Application manual and Getting started guide), Connectivity
packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AD
ABB 109
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 511 358-UEN
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 349-UEN
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 350-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 351-UEN
110 ABB
1MRK 511 361-BEN A
Bay control REC670 2.1 IEC
Product version: 2.1
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Related documents
670 series manuals Document numbers
Documents related to REC670 Document numbers Operation manual IEC:1MRK 500 123-UEN
ANSI:1MRK 500 123-UUS
Application manual IEC:1MRK 511 358-UEN
ANSI:1MRK 511 358-UUS Engineering manual IEC:1MRK 511 355-UEN
ANSI:1MRK 511 355-UUS
Commissioning manual IEC:1MRK 511 360-UEN
ANSI:1MRK 511 360-UUS Installation manual IEC:1MRK 514 024-UEN
ANSI:1MRK 514 024-UUS
Product guide 1MRK 511 361-BEN
Communication protocol manual, 1MRK 511 348-UUS
Technical manual IEC:1MRK 511 359-UEN DNP3
ANSI:1MRK 511 359-UUS
Communication protocol manual, 1MRK 511 351-UEN
Type test certificate IEC:1MRK 511 361-TEN IEC 60870-5-103
ANSI:1MRK 511 361-TUS