Key Plan

A
BL
QI
Notes

1 3 4 5 6 150 mm FIRE PIPE FROM PUMP ROOM AT U/G


100mm LV & FHR PIPE T/A
FOR MAIN BUILDING LV & FHR SYSTEM
80mm SPRINKLER PIPE T/A FOR CONT. REFER DWG. NO. 76-10526-F101
2 FOR ZCV-3 IN STRUCTURAL VEHICLES PARKING
150 mm FIRE PIPE FROM PUMP ROOM AT U/G
FOR MAIN BUILDING SPRINKLER SYSTEM
FOR CONT. REFER DWG. NO. 76-10526-F101
FOR CONTINUATION REFER TO PART DWG. No. 76-10526-F122
80 80
E
25 25 25 25
WORKSHOP
FE1,FE2 80mm SPRINKLER PIPE T/A

50
40 150mm SPR. PIPE LOOP

150
50
40

100
65
FOR ZCV-3 IN ARFF VEHICLES PARKING
25 25 25 25

40
150
150

150
150 FIRE MAN'S LOBBY 100mm LV & FHR PIPE T/A

25

25
25
FOR ZCV-3 IN ARFF VEHICLES PARKING

25
SHIFT COMMANDER - 25 25 32 25 25

50
STRL.

100
50
50
65 TRAINING ROOM 25mm TEST & DRAIN VALVE
25 25 TO BE CONNECTED TO THE NEAREST DRAIN POINT
32 50 50 FE1,FE2
25 25

150mm SPR. PIPE LOOP

50
32 150mm LV & FHR PIPE RISER F/B-T/A

150
STAIR # 1 LIFT 25 25

25
40

25

25
25 25 50mm TEST & DRAIN PIPE RISER F/A-T/B

25

40
150mm ZONE CONTROL VALVE (ZCV-1)
SHIFT COMMANDER -
25 25 ARFF
D

32
TR. OFFICER 25 25 25mm SPR. PIPE DROP TO L/L
25 25 25 SIDEWALL MOUNTED SPRINKLER

25

25
25

25
INSTALLED IN LIFT PIT

25
25 40 50
32 40 50 A ISSUED FOR TENDER ARN BM* AH* 08.03.15
PPE STORE GYMNASIUM FE1,FE2 ALARM CHECK VALVE (ACV-1)

FOR CONTINUATION REFER TO PART DWG. No. 76-10526-F123


50

25
50 INSTALLED IN VERTICAL No Revision
Job Project
Drawn Manager Director Date

25

25
25

25
150mm SPRINKLER PIPE RISER F/B-T/A
WITH ALARM CHECK VALVE INSTALLED

25
25

150mm SPR. PIPE LOOP


65 50 50 50 40 25 Note: * indicates signatures on original issue of drawing or last revision of drawing
25 25 DAY ROOM Conditions of Use. This document may only be used by GHD's client (and any other
FOR SPRINKLER REFER LEVEL 1
STAIR # 3

person who GHD has agreed can use this document) for the purpose for which it was
DWG. NO. 76-10526-F112 prepared and must not be used by any other person or for any other purpose.

25
MALE LOCKERS DINING

40
C
Master Developper / Owner

25 25
25 25
25 25
CORRIDOR
BA COMPRESSOR & BA STORE 40 32 25 25
25

Abu Dhabi Airports Company PJSC


W/SHOP 25 25 80 Planning & Development
25 25 PO Box 94449, Abu Dhabi, U.A.E
32 T: +971 (0) 2 505 5000
F: +971 (0) 2 575 8300
SPARE 25

25
25

25

25
ABLUTION
PRAYER

25
50 40 25

50
80mm FIRE PIPE DROP TO FHC KITCHEN
65mm LV, 40mm HOSE RACK WITH FE2,FE3
SPARE
25

25 40 25

25
25

25

PORTABLE FIRE EXTINGUISHERS 80mm FIRE PIPE DROP TO FHC


25 25

25 25
25 25

25 25
Lead Consultant

25
FE-1 (WATER TYPE 9 LTR.) &

25

25
32 40 FB 65mm LV, 40mm HOSE RACK WITH

50
FE-2 (CO2 TYPE 5 KG) FHC 25 25
150mm SPR. PIPE LOOP PORTABLE FIRE EXTINGUISHERS
50

80
32

FE-1 (WATER TYPE 9 LTR.) &


FHC FE-2 (CO2 TYPE 5 KG)

50
JANITOR
50

50
50
25 25 25 25
25
25 25
80
25 25
B

25
FE1,FE2
LV ROOM FHC GHD GLOBAL PTY LTD
25

IT SERVER 3rd Floor, Guardian Tower, Danet Community

50
150mm SPR. PIPE LOOP

40 50
50 50

40 50
PROTECTED WITH FM-200

50
40

FE3 PROTECTED
40 PO Box 45921 Abu Dhabi United Arab Emirates

32
WITH FM-200 T 971 2 6968700 F 971 2 4472915
25 25 GEAR WASH

40
40
E abumail@ghd.com W www.ghd.com
FE2,FE3 25
25 25 25 25

MALE SHOWER &


MALE SHOWER &
FE4 MALE TOILET 25 25
SER. CORRIDOR

CHANGING
CHANGING

32
40

40
40

32
Specialist Consultant
25

25

25

DIESEL GENERATOR FOR SPRINKLER REFER LEVEL 1

25
32

25
32

32
TELECOM DWG. NO. 76-10526-F112

STAIR # 2
PROTECTED WITH DELUGE FOAM /
PROTECTED 25 25 25 25 25 25 25 25
WATER SPRAY SYSTEM Fire Life Safety, Planning

25

25
25
WITH FM-200

25
SPARE FAHU 25 and Regulatory Specialist
FE2,FE3 FE2,FE3 FE2,FE3
A
FE6
Specialist Consultant

Third Party
Operational Advisor

Client
ADAC
Project
MIDFIELD TERMINAL FIRE
STATION
FIRE PROTECTION SERVICES - GROUND LEVEL PLAN -
Title FIRE PROTECTION SERVICES -
PART 1 GROUND LEVEL PLAN - PART
SCALE 1 : 100 1
Scale 1 : 100 DO NOT SCALE
Drawn A. NOCEJA Designer P. MOHD.
Drafting Design
Check Check
Approved
(Project Director)
Date
0 1000 2000 3000 4000 5000 mm This Drawing must not be used for Construction unless signed as Approved
Original Size
SCALE 1: 100 AT ORIGINAL SIZE Drawing No:
A1
DETAIL DESIGN 76-10526- F121 Rev: A
Plot Date: 7/03/2015 10:16:02 PM Cad File No: C:\Users\fvillete\Documents\76-10526_Midfield Fire Station MEP-Central_fvillete.rvt