of Table 204-2 - Minimum Design Dead Loads (kPa) Section 422. COVERINGS, Roof and Wall ORDINARY REINFORCED CONCRETE STRUCTURAL WALL is a wall complying with the CONCRETE MASONRY UNITS requirements of Sections 401 through 418. Hollow Concrete Masonry units (Unplastered, add 0.24 kPa for each face plastered) INTERMEDIATE PRECAST STRUCTURAL WALL is a wall complying with all applicable 204.1 General requirements of Sections 401 through 418 in Dead loads consist of the weight of all materials addition to 421. of construction incorporated into the building or other structure. including but not limited to wall s, SPECIAL STRUCTURAL WALL is a cast-in-place floors, roofs. ceilings. stairways, built-in other or precast wall shall comply with the similarly incorporated architectural and n requirements of Sections 421.3.3 through partitions. finishes, cladding and other similarly 421.3.7, 421.8 and 421.15 as applicable, in incorporated architectural and structural items, addition to the requirements for ordinary and fixed service equipment, including the weight reinforced concrete structural walls. of cranes. 405.12 Curing 206.5 Interior Wall Loads Interior walls, permanent partitions and 405.12.1 Concrete (other than high-early- temporary partitions that exceed 1.8 m in height strength) shall be maintained above 10degC and shall be designed to resist all loads to which they in a moist condition for at least the first seven are subjected but not less than a load, L, of 0.25 days after placement, except when cured in kPa applied perpendicular to the walls. The 0.25 accordance with Section 405.123. kPa load need not be applied simultaneously with wind or seismic loads. The deflection of such 407.6 Placing Reinforcement walls under it load of 0.25 kPa shall not exceed 407.6.1 Reinforcement, prestressing tendons and 1/240 of the span for walls with brittle finishes ducts shall be accurately placed and adequately and 1/120 of the span for wall s with flexible supported before concrete is placed. and shall be finishes. See Table 208-12 for earthquake design secured against displacement within tolerances of requirements where such requirements are more this section. 407.6.2 Unless otherwise specified restrictive. by the engineer of record, reinforcement, prestressing tendons and prestressing ducts shall 208.2 Definitions be placed within the following tolerances:
407.6.2.1 Tolerance for depth d, and minimum
concrete cover in flexural members, walls and compression members shall be as follows:
except that tolerance for the clear distance
formed soffits shall be minus 6 mm and tolerance for cover shall not exceed minus one-third the SHEAR WALL is a wall designed to resist lateral minimum concrete cover required by the forces parallel to the plane of the wall (sometimes approved plans or specifications. referred to as vertical diaphragm or structural wall). 407.7.5 In walls and slabs other than concrete joist construction, primary flexural reinforcement Chapter 4 shall not be spaced farther span than three times STRUCTURAL CONCRETE the wall or slab thickness, nor farther than 450 mm. STRUCTURAL WALL is a wall proportioned to resist combinations of shears, moments, and 407.8 Concrete Protection for Reinforcement axial forces. A shear wall is a structural wall. A structural wall designated as part of the seismic- 407.8.2 Precast Concrete (Manufactured Under force-resisting system shall be categorized as Plant Control Conditions) follows: Unless a greater cover is required by Section 407.8.6 or 407.8.8, specified cover for prestressed and nonprestressed reinforcement, ducts. and end fittings shall not less than the following:
Minimum Cover
I. Concrete exposed to earth or weather:
a. Wall panels:
42 mm and 58 mm bars: 40 mm 36 bar and smaller, prestressing tendons larger than 40 mm and smaller, MW200 or MD200 wire and smaller.: 20 mm
b. Other members:
42 and 58 bars, prestressing tendons larger
than 40 mm: 50 mm 20 through 36 bars, prestressing tendons larger than 16 mm through 40mm: 40 mm 16 bar and smaller, prestressing tendons 16 mm diameter and smaller, MW200 or MD200 wire, and smaller: 30 mm
2. Concrete not exposed to weather or in contact
with ground:
a. Slabs, walls, joists:
42 mm and 58 mm bars, prestressing tendons
larger than 40 mm: 30 mm Prestressing tendons 40 mm and smaller: 20 mm 36 mm bar and smaller, MW200 or MD200 wire 411.11.2 Design of horizontal section for shear in and smaller: 15 mm plane of wall shall be based on Eqs. 411-1 and 411 -2, where shear strength Vc shall be in b. Beams, columns: accordance with Section 4 11 .11.5 or 4 11. 116 and shear strength Vs shall be in accordance with Primary reinforcement db but not less than 15 Section 411. 11.9. mm and need not exceed: 40 mm Ties, stirrups, spirals: 10 mm 411.11.3 Shear strength VII at any horizontal section for shear in plane of wall shall not be c. Shells, folded plate members: taken greater than (5/6) f'c hd, where h is thickness or wall, and d is defined in Section Prestressing tendons: 20 mm 411.11 .4. 20mm bar and larger: 15 mm 16mm bar, MW2000r MD200 wire, and smaller: 411.11.4 For design for horizontal shear forces in 20 mm plane of wall, d shall be taken equal to 0,8lw. A larger value of d, equal to the distance from extreme compression fiber to center of force of all 411.11 Provisions for Walls reinforcement in tension, shall be permitted to be used when determined by a strain compatibility 411.11.1 Design for shear forces perpendicular to analysis. face of wall shall be in accordance with provisions for slabs in Section 411 .13. Design for horizontal 411.11.5 Unless a more detailed calculation is shear forces in plane of wall shall be in made in accordance with Section 411. 11 ,6, accordance with Section 411. 11 .2 through 411 . shear strength Vc shall not be taken greater than 11.9. Alternatively, it shall be permitted to design (1/6) fc hd for walls subject to axial walls with a height not exceeding two times the compression, or Vc shall not be taken greater length of the wall for horizontal shear forces in than the value given in Section 41 1.4 .2.3 for accordance with Sections 427 and 411.11.9,2 walls subject to axial tension. through 411.11.9.5. 411.11.6 Shear strength Vc shall be permitted to be lesser or the values computed from Eqs. 411 33 and 411 14.