Вы находитесь на странице: 1из 7

Non-Load Bearing Wall ORDINARY STRUCTURAL PLAIN CONCRETE

WALL is a wall complying with the requirements


of
Table 204-2 - Minimum Design Dead Loads (kPa) Section 422.
COVERINGS, Roof and Wall
ORDINARY REINFORCED CONCRETE
STRUCTURAL WALL is a wall complying with the
CONCRETE MASONRY UNITS
requirements of Sections 401 through 418.
Hollow Concrete Masonry units (Unplastered, add
0.24 kPa for each face plastered)
INTERMEDIATE PRECAST STRUCTURAL WALL
is a wall complying with all applicable
204.1 General
requirements of Sections 401 through 418 in
Dead loads consist of the weight of all materials
addition to 421.
of construction incorporated into the building or
other structure. including but not limited to wall s,
SPECIAL STRUCTURAL WALL is a cast-in-place
floors, roofs. ceilings. stairways, built-in other
or precast wall shall comply with the
similarly incorporated architectural and n
requirements of Sections 421.3.3 through
partitions. finishes, cladding and other similarly
421.3.7, 421.8 and 421.15 as applicable, in
incorporated architectural and structural items,
addition to the requirements for ordinary
and fixed service equipment, including the weight
reinforced concrete structural walls.
of cranes.
405.12 Curing
206.5 Interior Wall Loads
Interior walls, permanent partitions and
405.12.1 Concrete (other than high-early-
temporary partitions that exceed 1.8 m in height
strength) shall be maintained above 10degC and
shall be designed to resist all loads to which they
in a moist condition for at least the first seven
are subjected but not less than a load, L, of 0.25
days after placement, except when cured in
kPa applied perpendicular to the walls. The 0.25
accordance with Section 405.123.
kPa load need not be applied simultaneously with
wind or seismic loads. The deflection of such
407.6 Placing Reinforcement
walls under it load of 0.25 kPa shall not exceed
407.6.1 Reinforcement, prestressing tendons and
1/240 of the span for walls with brittle finishes
ducts shall be accurately placed and adequately
and 1/120 of the span for wall s with flexible
supported before concrete is placed. and shall be
finishes. See Table 208-12 for earthquake design
secured against displacement within tolerances of
requirements where such requirements are more
this section. 407.6.2 Unless otherwise specified
restrictive.
by the engineer of record, reinforcement,
prestressing tendons and prestressing ducts shall
208.2 Definitions be placed within the following tolerances:

407.6.2.1 Tolerance for depth d, and minimum


concrete cover in flexural members, walls and
compression members shall be as follows:

except that tolerance for the clear distance


formed soffits shall be minus 6 mm and tolerance
for cover shall not exceed minus one-third the
SHEAR WALL is a wall designed to resist lateral minimum concrete cover required by the
forces parallel to the plane of the wall (sometimes approved plans or specifications.
referred to as vertical diaphragm or structural
wall). 407.7.5 In walls and slabs other than concrete
joist construction, primary flexural reinforcement
Chapter 4 shall not be spaced farther span than three times
STRUCTURAL CONCRETE the wall or slab thickness, nor farther than 450
mm.
STRUCTURAL WALL is a wall proportioned to
resist combinations of shears, moments, and 407.8 Concrete Protection for Reinforcement
axial forces. A shear wall is a structural wall. A
structural wall designated as part of the seismic- 407.8.2 Precast Concrete (Manufactured Under
force-resisting system shall be categorized as Plant Control Conditions)
follows: Unless a greater cover is required by Section
407.8.6 or 407.8.8, specified cover for
prestressed and nonprestressed reinforcement,
ducts. and end fittings shall not less than the
following:

Minimum Cover

I. Concrete exposed to earth or weather:


a. Wall panels:

42 mm and 58 mm bars: 40 mm
36 bar and smaller, prestressing tendons larger
than 40 mm and smaller, MW200 or MD200 wire
and smaller.: 20 mm

b. Other members:

42 and 58 bars, prestressing tendons larger


than 40 mm: 50 mm
20 through 36 bars, prestressing tendons
larger than 16 mm through 40mm: 40 mm
16 bar and smaller, prestressing tendons 16
mm diameter and smaller, MW200 or MD200
wire, and smaller: 30 mm

2. Concrete not exposed to weather or in contact


with ground:

a. Slabs, walls, joists:

42 mm and 58 mm bars, prestressing tendons


larger than 40 mm: 30 mm
Prestressing tendons 40 mm and smaller: 20 mm
36 mm bar and smaller, MW200 or MD200 wire 411.11.2 Design of horizontal section for shear in
and smaller: 15 mm plane of wall shall be based on Eqs. 411-1 and
411 -2, where shear strength Vc shall be in
b. Beams, columns: accordance with Section 4 11 .11.5 or 4 11. 116
and shear strength Vs shall be in accordance with
Primary reinforcement db but not less than 15 Section 411. 11.9.
mm and need not exceed: 40 mm
Ties, stirrups, spirals: 10 mm 411.11.3 Shear strength VII at any horizontal
section for shear in plane of wall shall not be
c. Shells, folded plate members: taken greater than (5/6) f'c hd, where h is
thickness or wall, and d is defined in Section
Prestressing tendons: 20 mm 411.11 .4.
20mm bar and larger: 15 mm
16mm bar, MW2000r MD200 wire, and smaller: 411.11.4 For design for horizontal shear forces in
20 mm plane of wall, d shall be taken equal to 0,8lw. A
larger value of d, equal to the distance from
extreme compression fiber to center of force of all
411.11 Provisions for Walls reinforcement in tension, shall be permitted to be
used when determined by a strain compatibility
411.11.1 Design for shear forces perpendicular to analysis.
face of wall shall be in accordance with provisions
for slabs in Section 411 .13. Design for horizontal 411.11.5 Unless a more detailed calculation is
shear forces in plane of wall shall be in made in accordance with Section 411. 11 ,6,
accordance with Section 411. 11 .2 through 411 . shear strength Vc shall not be taken greater than
11.9. Alternatively, it shall be permitted to design (1/6) fc hd for walls subject to axial
walls with a height not exceeding two times the compression, or Vc shall not be taken greater
length of the wall for horizontal shear forces in than the value given in Section 41 1.4 .2.3 for
accordance with Sections 427 and 411.11.9,2 walls subject to axial tension.
through 411.11.9.5.
411.11.6 Shear strength Vc shall be permitted to
be lesser or the values computed from Eqs. 411
33 and 411 14.

Вам также может понравиться