TECHNICAL UNIVERSITY OF CIVIL ENGINEERING, Bucharest, Romania,
2
TRANSYLVANIA UNIVERSITY OF BRAOV, Romania,
3
SC DOSETIMPEX SRL, Timioara, Romania
Abstract. This paper presents the results of research on ammonia-water absorption refrigeration systems for
small and medium powers, operated with renewable energy resources [solar energy, geothermal] and bivalent,
with renewable energy and conventional sources. It were built two absorption refrigeration machine, one driven
only with renewable energy sources, a 5 kW cooling capacity, and another 17 kW cooling capacity, driven
bivalent. The equipment of the systems are compact heat exchangers, with mini and micro channels.
Refrigeration systems are equipped with thermal energy storage. Such systems are designed for comfort and
commercial climate. Absorption heat pumps and chillers with ammonia-water can save considerably fuel by
using renewable heat sources or waste heat available at temperature that is low enough. A reduction of the carbon
dioxide emission together with a global warming potential is resulting. Some performance data will be indicated
emphasizing the viability of this system based on micro/mini channels heat exchangers.
Keywords: absorption ammonia/water, mini and micro channel, renewable energy.
14 TERMOTEHNICA 2/2014
LOW POWER ABSORPTION REFRIGERATION SYSTEMS, WITH STORAGE, FOR AIR CONDITIONIG
Consequently, high capacity absorption ammonia- through the solar collectors, 1, transfer heat to the
water heat pumps have been designed and realized water from the 4000 l tank 3, by means of the plate
(Kim and Infante Ferreira, 2005), like: heat exchanger 2.
2000 kW resorption system driven by con-
ventional fuel and using waste warm-water having
a temperature of 20 to 30 oC was able to produce
60-65 oC warm water;
hybrid compression-absorption heat pump
system, electric driven, with a heating capacity of
7000 kW, recovering heat from the warm water
having 20 to 30oC, and producing warm water of
60 to 70oC;
resorption heat transformer being driven by
geothermal water of 35-40oC, using it as a heat Fig. 3. Solar Cooling installation diagram:
source also, and producing 55-60oC warm water 1 flat solar collectors; 2- plate heat exchanger; 3 warm
(Fig. 2). water tank; 4 boiler; 5 distributor; 6 absorption chiller
Li Br/water; 7 cooling tower; 8 circulators; 9 hydraulic
unit; 10 hydraulic unit control; 11 chilled water consumer
for air conditioning; 12 hot water consumer;
TC temperature sensors.
TERMOTEHNICA 2/2014 15
F. CHIRIAC, A. ERBAN, L. DRUGHEAN, A. ILIE, I. BOIAN, I. DOBOI, R. CALOT, G. NSTASE
There are studied two cases as a function of the machine and the heat pump can be operated in a
temperature of the chilled water at the outlet of the reversible mode as a chiller or as a heater using
evaporator, 8/12 C. During the testing, the out- heat energy to provide cooling or heating. Both
door temperature was the same for the two plants. equipment are interconnected supplying with chilled
Also, the pressure measured at the rectifier exit and or warm water the fan coils located into the faculty
at the absorber exit had the same values for both rooms depending on the seasonal requirements.
plants [1]. The absorption heat pump is preparing warm water
up to 60oC recovering heat from the outside air.
5. SMALL CAPACITY ABSORPTION The ammonia is the refrigerant being absorbed by
AMMONIA-WATER SYSTEM WITH the water the absorption fluid. For the balancing
CHILLER AND HEAT PUMP of the water circuits a hydraulic separator is used.
The nominal temperature of the chilled water is
The Transylvania University Building Services 7.2C returning back to the unit with 12.7C for an
Department has completed and now operates a outside air temperature of 35C. A 150 l storage
complex HVAC system for cooling and heating of tank for hot water is installed in the underground
indoor spaces through the interconnection of two room next to the heater. The rest of the equipment,
ammonia-water absorption systems (see Figure 9) circulation pumps, accumulators, filters, and the
manufactured by ROBUR Company. electrical wiring, direct measuring devices, and the
Both equipment have been placed on a platform loggers for the acquisition of data provided by the
outside the building. This way the chiller fan noise sensor are located in the adjacent room.
(57 dB) and accidental ammonia contamination are Two ROBUR absorption machines single-
avoided. The chiller is operated as refrigeration effect gas fired one operating only as a chiller and
TERMOTEHNICA 2/2014 17
F. CHIRIAC, A. ERBAN, L. DRUGHEAN, A. ILIE, I. BOIAN, I. DOBOI, R. CALOT, G. NSTASE
the other, reversible, working as a chiller or as a heat It has a capacity of 32.5 kW and is provided with a
pump are connected as shown in Figure 10 [4]. storage tank installed in the inside vicinity. To
avoid the danger of possible freezing during the
heating season the circuit between the heating mo-
dule and the storage tank is filled with antifreeze
solution [1].
The chilled water at 7C provided by the chiller
and by the heat pump operated as a chiller too is
pumped into the fan coils placed inside the rooms.
As a result the inside air is cooled and dried and
the water returns warmer at approx. 12C to the
refrigeration units.
During the heating season the heat pump sup-
plies the above mentioned fan-coils with warm
Fig. 9. Small capacity Robur ammonia-water absorption water having a maximum temperature of 60 oC even
systems with chiller and heat pump.
at negative ambient-air temperatures, i.e. -20C. But
The chiller is an AYF 60-119/4 standard version the heating performance is affected by the outside
having a cooling capacity of 17.49 kW at a nominal dry bulb temperature and also by the hot water
chilled water flow of 2735 l/h and a gas consump- temperature leaving the unit, This installation was
tion of 2.51 m3/h. The maximal sound pressure realized to be used for different research studies at
level is 57 dB(A). The complementary heating doctoral and MSc level but it is also useful for
module supplying 2000 l/h of domestic hot water testing activities (AHU, cooling rooms, hydronic
can be operated in both heating and cooling seasons. coils for heating/cooling, radiators) [4].
stitutions such as UNEP, IIR, and the Council of & computational science, WSEAS Conference, Valencia,
Europe adopt measures to amend the standards and Spain, 2013.
[3] Chiriac Florea, erban Alexandru, Nstase Gabriel. Heat
norms of design, construction and operation of re- exchanger with minichanel for absorption chillers, with
frigeration, heat pumps and air conditioning systems. ammonia-water solution, for small cooling power. 4th IIR
In developed countries, companies have switched Conference on Thermophysical Properties and Transfer
to using natural refrigerants and cooling systems Processes of Refrigerants, Delft, The Netherlands, 2013.
that uses renewable and recoverable energy sources, [4] erban A., Chiriac F., Nstase G., Boian I. Cooling
systems for buildings, with low power absorption chillers
instead of transition refrigerants and classical driven by renewable energy sources, Conferina CIBV
cooling systems. 2012, ISSN 2285-7656, ISSN-L 2248-7648, Editura
In our country professional and scientific societies Universitii Transilvania din Braov, 2012.
should contribute to changing internal rules designed [5] Chiriac F., Chiriac V., erban A. Energy recovery
systems for the efficient cooling of data centers using
to protect the environment and conserve the energy.
absorption chillers and renewable energy resources. En-
Absorption heat pumps and chillers with am- vironmental Engineering and Management Journal,
monia water can save considerably fuel by using Vol. 10, Nr. 9, ISSN: 1582-9596, 2011.
renewable heat sources or waste heat available at [6] Chiriac F., erban A., Nstase G., Boian I. The role of
natural refrigerants in future refrigeration and heat pump
temperature that is low enough. A reduction of the
systems. Environmental Engineering and Management
carbon dioxide emission together with a global Journal, Vol. 10, Nr. 9, ISSN: 1582-9596, 2011.
warming potential is resulting. In fact absorption [7] Popa V., Popa C.L., erban A. Using ammonia-water
systems exchange heat with three thermal reservoirs absorption cooling subsystem in BCCHP. IIR Conference
Ammonia Refrigeration Technology, Ohrid, Republic of
contributing to overall energy efficiency. The use
Macedonia, ISBN: 978-2-913149-85-4, 14-16 Aprilie
of an absorption chiller during high summer-cooling 2011.
demand periods or even in normal operating hours [8] erban A., Chiriac F., Nstase G. Platform interactiv
is economically beneficial especially in case of a pentru studeni nvare instalaii frigorifice online,
Conferina Naional de Instalaii, Sinaia 2012.
favourable cost ratio of electricity to natural gas or
[9] Chiriac F., Drughean L., Boian I., Ilie A., erban A.,
by using the solar energy. Doboi I. S., Duna ., Nstase G. Utilizarea agenilor
In the paper are presented some researches naturali i a surselor de energie regenerabile i recupe-
regarding the small absorption chiller driven by rabile n instalaiile frigorifice i de clim, Conferina
conventional or solar energy. Two small chillers Naional de Instalaii, Sinaia 2012.
[10] Serban A., Chiriac F., Boian I., Nastase G. Radiant and
installed in the laboratories of the Transylvania convective heating & cooling using renewable energy.
University of Brasov and of Technical University testing laboratory, The 5th Romanian Conference on
of Civil Engineering of Bucharest are used for PhD Energy Performance of Buildings (RCEPB-V)29 30th
Thesis. It is demonstrated that small absorption of May, 2013, Bucharest, ROMANIA.
[11] Serban A., Nastase G. Interactive platform for students.
chiller with ammonia-water is a good, economically Online learning refrigeration. Bulletin of the Transilva-
and environmental friendly solution for the re- nia University of Braov Vol. x (xx) - 2013 Series I:
sidential and commercial applications. Engineering Sciences.
[12] Alexandru erban, Florea Chiriac, Ioan Boian, Gabriel
Nstase. A new concept for NH3-H2O absorption refrige-
Acknowledgments ration system. CLIMA 2013 11th REHVA World
The authors would like to acknowledge the Congress and the 8th International Conference on Indoor
Air Quality, Ventilation and Energy Conservation in
interest, the assistance and the continuous financial Buildings 16. - 19. 6. 2013 Prague Congress Centre, 5.
aid of SC CRIOMEC SA, Galati for the develop- kvtna 65, 140 21 Praha 4, Czech Republic.
ment of many of these research projects. [13] Alexandru Serban, Boieriu Lucia, Gabriel Nastase. Study
concerning solar sorption refrigeration systems for resi-
dential buildings. Energy and environment technologies
REFERENCES
and equipment, WSEAS Conceference Brasov, Romania,
[1] erban A., Boian I., Chiriac F., Nstase G., Calot R. 2013.
Absorption refrigeration and heat pump systems using [14] Serban A., Chiriac V., Chiriac F., Nstase G. Energy
ammonia, Gustav Lorenzen Interantional Conference, TU recovery systems for the efficient cooling of data centers
Delft, Olanda, 2012. using absorption chillers and renewable energy resources.
[2] Serban A., Chiriac F., Boian I., Boieriu L. The role of Recent advances in intelligent control, modelling & com-
natural refrigerants in future refrigeration and heat pump putational science, WSEAS Conference, Valencia, Spain,
systems. Recent advances in intelligent control, modelling 2013.
TERMOTEHNICA 2/2014 19