Академический Документы
Профессиональный Документы
Культура Документы
Energy
journal homepage: www.elsevier.com/locate/energy
a r t i c l e i n f o a b s t r a c t
Article history: Due to the depletion of fossil fuel reserves, it is feared that the world will run out of its energy resources
Received 7 June 2015 soon. Besides, unpredictable uctuation of diesel prices in electricity generation is affecting the economy
Received in revised form of a country. Thus, for developing country that's economically leans on the use of energy, renewable
27 April 2016
energy resources should be utilized to meet the increasing energy demand. In this regards, the cogen-
Accepted 11 June 2016
eration system using renewable energy sources is appropriate, because it has the advantage of producing
both electrical power and heat energy from a single fuel. It is suitable for commercial clients like hospital
buildings which requires to supply both electric and heat load. Therefore, the aim of this study is to
Keywords:
Cogeneration
assess the viability to develop a cogeneration system for a hospital building load in Malaysia. The pro-
Solar PV posed cogeneration system consists of grid connected photovoltaic (PV), fuel cell, and battery. Hybrid
Fuel cell optimization model for electric renewable (HOMER) simulation software is used to perform the techno-
Battery economic analysis of the proposed system. The proposed system is then compared with other possible
HOMER optimization congurations. The economical comparison is based on the total net present cost (TNPC), levelized cost of
Hybrid system energy (LCOE), renewable fraction, excess energy production and the pollutant gas emission of the
system. The simulation result shows that, the proposed cogeneration system has the lowest TNPC, LCOE
and operating cost which are $ 106,551, 0.091 $/kWh and 7245 $/yr respectively. Besides, the proposed
cogeneration system is proven environmentally friendly as it only produces total 25,873 kg/yr of
pollutant gas. The sensitivity analysis where fuel prices and annual interest rate are considered as
sensitive parameters, shows impact on the TNPC and LCOE. Finally, the benet from the Feed in Tariff
(FiT) program provided by the government also has been presented.
2016 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.energy.2016.06.056
0360-5442/ 2016 Elsevier Ltd. All rights reserved.
76 N.M. Isa et al. / Energy 112 (2016) 75e90
the use of renewable energy and bring a signicant reduction of mostly applied in process industries, like glass and steel where very
CO2. Nowadays, cogeneration system or combined heat and power high temperature is needed. In latest technology, the topping and
(CHP) systems are broadly used in micro-grids either in standalone bottoming cycle are joined together to form the combined cycle
system [6,7] or in grid connected system [8,9] because of their which has better efciency. Fig. 2 shows the operation of combined
advantages in electricity and thermal power generation. Re- cycle based cogeneration system.
searchers have conducted a few studies on CHP system focusing on Basically, cogeneration systems are classied based on their
the technical aspects of the systems [10e12]. The studies on prime movers that run the power generation process [21]. There are
cogeneration system are more focused on the technical aspect ve type of prime mover including gas turbine, steam turbine,
including the development and testing of the cogeneration system. micro turbine, reciprocating engine and fuel cell. Previously, the
They are mostly based on Middle East and European countries. turbine base prime movers were widely used in cogeneration
However, researches on cogeneration system development based system whereas, recently fuel cell prime movers are very popular.
on the tropical climate especially in Malaysia is very limited This is because, fuel cell technology provides various benets
[12e14]. Cogeneration system is suitable for hospital building, as it including high efciency, less moving part, low cost, quiet opera-
needs large amount of heat demand for hot water all year round. tion and can be sited almost everywhere. Currently, several re-
Besides, some health equipment also has the continuous demand of searchers have been investigating the combination of fuel cell
heating power [15]. In addition, the hospital has critical load situ- cogeneration with some renewable energy like solar PV, biomass
ations in its 24/7 operation time which need electrical and thermal and wind turbine in cogeneration system. Thilak et al. provides a
supply with emergency backup [33]. Some researchers studied the review on the possibility of renewable energy to work together in a
viability of cogeneration system in hospital buildings of Europe CHP system [10]. The impact of PV penetration and battery storage
using diesel engines and gas turbines in Refs. [16,17]. However on energy production is studied in article [22]. The study also
there is no study performed to develop a cogeneration system using consider the cost of energy (COE) and number of operational hours
alternative energy sources for hospital building in Malaysia. of diesel generators for the given hybrid congurations. Thanakorn
Therefore, this paper presents a cogeneration system develop- et al. developed an economic and environmental friendly CHP
ment for hospital building in Malaysia which uses renewable en- system for the application of building energy management system
ergy resources. The cogeneration system proposed in this study for a large shopping complex, where the impact of the cogeneration
consist of grid connected PV, fuel cell and battery. HOMER simu- operation on the environment, multi-objective cost functions,
lation software was used to determine the optimal design of including total operating cost, the minimum total carbon dioxide
cogeneration topology in a hospital building. The economic analysis (CO2) emission, and optimal energy ows are considered [11]. K. R.
was based on total net present cost (TNPC), levelized cost of energy Ullah prove experimentally that a single tubular solid oxide fuel cell
(LCOE) and operating cost, together with emission effect to the (SOFC) can produce the heat to be used in cogeneration system [12].
environment. A comparison of different operating strategies for small scale CHP
In this study, rstly the cogeneration system is overviewed plants red by natural gas and solid biomass to serve the residential
followed by the input parameters of HOMER simulation tool. Next, energy demand is studied in Ref. [23]. This includes the combina-
the economic feasibility analysis parameters are discussed. A tion of photovoltaic (PV), battery and fuel cell either in stand-alone
description of the proposed cogeneration system is presented in or grid connected mode. The performance of battery and fuel cell
the next section, which elaborates different component specica- installed in a residential by considering the impact of electricity
tions and their economic data. The simulation, optimization results tariff is investigated in the reference [24]. An optimization tech-
and sensitivity analysis is done thereafter. In this section, other nique has been developed in order to determine the optimal ca-
possible systems are also simulated and analyzed to check the pacities of CHP and boiler in Ref. [25]. Also, an energy management
viability of the systems. Finally, a discussion on the results of the strategy is proposed using the fuzzy logic to determine the opti-
assessment is presented. mum ranges for boiler and CHP capacities. The objective function is
based on the net present value (NPV). The author in Ref. [26]
2. Cogeneration or combined heat and power (CHP) system employed a mixed integer linear programming (MILP) as an opti-
mization algorithm to determine the yearly operational strategy of
Cogeneration or combined heat and power (CHP) is a system a cogeneration plant. The strategy also denes the sizing method
that has the ability to generate both electricity and heat at the same for the plant incorporated in commercial microgrid. A cost-benet
time. The CHP system with alternative energy sources like fuel cell analysis to improve the reliability of a cogeneration plant is dis-
or micro-turbine also can produce sufcient electrical and thermal cussed in article [27]. In the study, the economic feasibility analysis
energy [18,19]. Fig. 1 show the diagram of a conventional CHP was performed based on various costs and benets factors of CHP
system that combine several sources to produce electricity and heat based distributed energy resources (DER) system. Another small
for building load consumption. Generally, throughout the elec- scale CHP system is analyzed in article [28], which has three modes
tricity generation process, CHP captures the wasted heat and uses of operation: one-way connection (OWC) mode, two-way connec-
this heat to produce thermal energy and it can be utilized onsite for tion (TWC) mode, and heat demand following (HDF) mode. In this
industrial heating or producing steam, space conditioning and study, the economic decision making is based on net present worth
producing hot water. It increases power system efciency and at (NPW). A multi-objective approach is employed in Ref. [16] to
the same time reduces the operating cost. The operation process of determine the optimal conguration for a CHP plant. This study
cogeneration system can be divided into three cycles: topping cy- shows that the energy and economic benets produced by CHP
cle, bottoming cycle and combined cycle [20]. In topping cycle, fuel plants is dependent on the plant and user characteristics, plant
is rst used to generate the electricity or mechanical energy and a layout, management strategies and economic variables. Another
portion of the waste heat from power generation is used to provide analysis presents a technical simulation and economic model of
useful thermal energy. On the other hand, bottoming cycle type of three small-scale CHP plants which has 15 kV wood gasication
cogeneration systems rst produce useful heat for a manufacturing unit coupled to 6 kWe petrol generator [29]. The system is
process throughout fuel combustion or another heat-generating compared to the 6 kWe diesel generator and fed to the of cogene-
chemical reaction and recover some portion of the exhaust heat ration system electricity network in the southwest part of Western
to generate electricity. Normally bottoming cycle cogeneration is Australia (WA). A design and techno-economic optimization of a
N.M. Isa et al. / Energy 112 (2016) 75e90 77
Combustor
Gas
Compressor Electricity output
Turbine
Air
inlet
Exhaust
Economizer Steam
Electricity output
turbine
Pump
Condensor
stand-alone PV/FC and battery hybrid power system has been shows the solar radiation data for the studied location. The irradi-
studied in Refs. [30] and [31]. ance ranges from 4.792 kWh/m2/day to 5.491 kWh/m2/day and the
annual average of solar irradiance is estimated to be 5.05 kWh/m2/
3. Input parameters description day. It is noticed that solar irradiance is high in February, March,
April, September and October, and is low in May and November.
Simulation in HOMER requires several input parameters to The reason of low solar irradiation is because of the South-West
calculate the optimum results of different topologies. Normally, the Monsoon season during this period.
input parameters consist of primary load inputs, solar irradiation,
wind speed, and initial costs per unit for each component. These 3.3. Diesel price
parameters will be elaborated in the coming sections.
According to [36], the latest diesel price in Malaysia is MYR 1.60/
3.1. Load prole of hospital building L or 0.39 $/L (the currency exchange rate is according to the trade
currency of December 2015, US $1 equivalent to MYR 4.31.).
In this study, the Universiti Kebangsaan Malaysia Medical Centre Malaysian Government can remove the subsidy on diesel and
(UKMMC) building is chosen for evaluation. This hospital was petrol in future, thus the price may change extensively. The diesel
established as an educational hospital in 1997. It is located in price may rise up to MYR 7.50/L or 1.70 $/L in 25 years period.
Cheras, Selangor which geographical coordinates are 3 50 5500 Therefore, the diesel prices are varied from 0.39 $/L to 3.0 $/L in the
North, 101 430 2700 East. UKMMC has been divided into four major sensitivity analysis, to investigate the effect of fuel price on the
parts: clinical and teaching block, United Nation University (UNU), system cost.
Kolej Tun Dr Ismail (KTDI) Doctors College and Nurses College.
Generally, in the hospital building, the electrical energy will be 3.4. HOMER software
apportioning to several parts including pumps, kitchen utilities,
biomedical equipment, heating, ventilation and air conditioning The HOMER software is a powerful tool that used for designing
(HVAC) systems [32]. UKMMC uses the electricity for air condi- and analyzing the hybrid power systems. This software was origi-
tioning, lighting, and lifts, and for medical equipment, while ther- nally developed by the United States (US) National Renewable
mal energy for boiler heating [33,34]. The study is focused on the Energy Laboratory (NREL), but now licensed to HOMER Energy [42].
clinical and teaching block area, and the load prole shows the Generally, the hybrid systems contain a combination of conven-
power consumption of this area. The overall electricity and gas tional generators, wind turbines, solar PV, hydro power, batteries,
consumption of the year 2010 is shown in Fig. 3. It is clear that, fuel cells, biomass and other inputs. In HOMER, three main tasks
UKMMC has the highest electricity consumption in August of can be performed: simulation, optimization and sensitivity anal-
3,873,860 kWh and the highest gas consumption in May of ysis. In the simulation process, HOMER can model the performance
111,299 kg. The load prole for the building is generated in HOMER of various hybrid systems and determines their technical feasibility
software using this monthly data and also the daily load data from and life cycle cost (LCC). In the optimization process, HOMER
the same source. The daily load prole for UKMMC is shown in simulates various system congurations to come up with the
Fig. 4(a), and the variation of the monthly load prole is illustrated optimal system congurations which satisfy the technical con-
in Fig. 4(b). The highest load consumption in this hospital is 13 kW straints at the lowest TNPC. In the sensitivity analysis, HOMER
daily in peak time from 8.00 a.m. to 6.00 p.m. This is due to the performs multiple optimizations under a range of input sensitivity
activity of the hospital routine in the clinical and education block. parameter assumptions to calculate the changes or uncertainties in
The average load consumption is 250 kWh/day distributed as peak the model. Because of these facilities, this software has been
load of 22.5 kW, with load factor of 0.464. applied for research in many simulations [22]. For an example, in
Ref. [37], a model of possible small hybrid power generation is
3.2. Solar radiation studied in terms of technical aspects along with the economic
analysis through HOMER software. A.M. Abdilahi in his work [38]
The solar radiation data was obtained from National Aeronautics use HOMER to investigate the possibility of supplying an elec-
and Space Administrative, NASA [35]. The data is 22-year average tricity from a renewable energy system to Hargeisa, Somalia. The
monthly solar radiation data of the location. The latitude and study presented out the economic and technical view on how to
longitude, 3.0422 oN, and 101.7706 oE were considered in the supply the electricity to a sampled residential load. He also
HOMER software, from which it received the radiation data. Fig. 5 analyzed the effect of diesel price increase on the system in future.
Fig. 3. Gas and electricity consumption in UKMMC building for year 2010.
N.M. Isa et al. / Energy 112 (2016) 75e90 79
Fig. 4. Load prole for the studied building in UKMMC (a): Daily variation, (b) Monthly variation.
4. Economic parameter
i1 iN
In HOMER simulation, the required economic input parameters CRFi;N (3)
are annual real rate interest and project lifetime. The annual real 1 iN 1
rate interest is dene as the discount rate which is used to convert
between one-time costs and annualized costs. Annual real rate of
interest is related to the nominal interest rate by following the Where Cann;tot total annual cost ($/yr),
equation in (1). CRF capital recovery factor
i interest rate (%)
io f Rproj Project lifetime (N)
i (1)
1f
Where i, is the real interest rate, io is the nominal interest rate and f 4.2. Levelized cost of energy (LCOE)
is the annual ination rate. In this analysis, the annual rate interest
is set to be 6%. The levelized cost of energy (LCOE) in HOMER software is
The project lifetime in HOMER simulation means the length of dened as the average cost per kWh of useful electrical energy
time over which the cost of the system is occurred. HOMER uses the produced by the system. In order to calculate the LCOE, HOMER
project lifetime to measure the annualized replacement cost and divides the annualized cost of produced electricity (the total
annualized capital cost of each component. Generally, project life- annualized cost minus the cost of serving the thermal load) by the
time is 20e25 years depending on the component lifetime. total useful electric energy production. The equation for the LCOE is
80 N.M. Isa et al. / Energy 112 (2016) 75e90
Water
DC bus AC bus
Electrolyzer
Unit FUEL CELL
DC Pfc
H2
Tank Grid
DC
Reformer Pgrid
Unit
Photovoltaic
Natural DC
Gas DC Ppv
AC
DC Pload
LOAD
Battery
Pbat
DC
t
DC
from Rolls battery [47] with 4 V, 1900 Ah and 10,569 kW power unit. The generator model used in this simulation is 5 kw
throughput lifetime is chosen in this simulation work. The mini- Changchai diesel generator. The initial capital and replacement
mum state of charge is 40% and the round trip of efciency is 80%. costs are assumed to be $ 500 for a 5 kW generator. The O&M cost of
The lifetime of this battery is 4 year. In order to produce higher the diesel generator is 0.030 $/h for the generator system [37,49].
energy capacity, batteries are connected in series that form the The diesel generator has the lifetime of 15,000 h and minimum load
batteries string that consist of 15 batteries in each string. The ratio of 30%. Fig. 8 show the fuel efciency curve of the diesel
maximum capacity of charging is 1887 Ah with capacity ratio is generator.
0.254 and rate constant is 0/528/hour. A description of the battery
system is summarized in Table 3. The initial capital and replace- 5.6. Reformer unit
ment cost are assumed to be $ 1259 and $ 1100, respectively and the
O&M cost is 0.02 $/yr. Normally, a reformer generates hydrogen by reforming a hy-
drocarbon, which is typically natural gas. In this simulation, the
5.4. Converter built in reformer unit installed in the HOMER software is used.
Therefore, the parameters used are provided by HOMER software as
The converter used in this simulation is divided into 40 kW well as it suits the system requirement. Both initial capital and
inverter and 40 kW rectier which gives total of rated 80 kW output replacement cost are assumed to be $ 3500. The operational and
power [48]. There are 2 types of energy conversion occur in the maintenance cost are anticipated to be $/yr 200. The reformer size
system, ac to dc and dc to ac power. Thus both rectier and inverter is 25 kg and it has an efciency of 68.6% with 25 years of lifetime. A
are essential for the system. The inverter efciency is considered natural gas used in the simulation has the characteristic as shown
90% and the lifetime is 15 years, which means the inverter has to be in Table 4.
changed once in 25 years period of lifetime. On the other hand,
rectier has the 100% capacity relative to inverter and efciency is 6. System operating strategy
90%. Proper control systems must be provided to the designated
system such as the use of multilevel converter control schemes In the proposed cogeneration system, the solar PV and fuel cell
applicable to a general multilevel converter and to any types of the systems work simultaneously to supply power to the hospital load.
renewable energy resources. The initial capital of the converter is $ The battery is used to improve the load power dispatch efciency as
800 and the replacement cost is $ 750. There is no O&M cost for well as functioning as back-up power sources in case of lack of solar
converters. Thus this amount is zero. radiation availability and during fault occurrence. Since the hospital
is has 24/7 operating system, the grid is utilized to ensure the
5.5. Diesel generator continuous electricity supply to the load. The operating strategies
are implemented to enhance the efciency of the developed sys-
The diesel generator is an easy means of power generation. tem. During the daytime, when the electricity demand of the
Usually in hybrid systems, diesel generators are used as back-up hospital is high, the electricity will be supplied by PV and fuel cell
82 N.M. Isa et al. / Energy 112 (2016) 75e90
Table 1 Table 2
Economic and technical specication for the components used in the proposed Specication of fuel cell for distributed generation.
cogeneration system.
Rated power (kW) 2.4e10.5
Component Data specication
Rated currents (A) 135
Photovoltaic panel [46] Voltage (V) 17.5e77.6 V DC
Size (kW) 120 Cell efciency (%) 54e64
Capital/Replacement cost ($) 7000/6000 Fuel consumption Hydrogen
O&M cost ($/yr) 10
Lifetime (years) 20
Battery [47]
Model Surrete 4KS25P Table 3
String 10 Surrete 4KS25P specication [47].
Nominal capacity 4V
Nominal capacity 1900 Ah
State of charge 40%
Capital/replacement ($/pc) 1259/1100 Nominal voltage 4V
O&M cost ($/yr) 0.02 Round trip efciency 80%
Lifetime throughput (kWh) 10,569 Minimum SOC 40%
Converter [48] Float life 12 years
Size (kW) 40 Lifetime throughput 10,569 kWh
Capital/replacement cost ($/kW) 800/750 Suggested 10,494 kWh
O&M cost ($/kWh) 0 Maximum charge rate 1 A/Ah
Lifetime 15 Maximum charge current 67.5 A
Efciency 90
Diesel generator [49]
Rated power (kW) 5
Capital cost ($) 500
Replacement cost ($/kW) 500
O&M cost ($/h) 0.03
Lifetime (hours) 15,000
Minimum load ratio 30%
Fuel cell [50]
Size (kW) 100
Capital/Replacement cost ($/kW) 450/400
O&M cost ($/h) 0.150
Lifetime 15,000
Minimum load ration 30%
Hydrogen tank [41]
Sizes (kg) 80
Capital cost ($/kg) 1300
Replacement cost ($/kg) 1200
O&M cost ($/yr) 15
Lifetime (years) 25
Table 4
Natural gas characteristic.
low, only the fuel cell system will supply the load along with the
grid. The PV system cannot work at night due to the unavailability
of solar radiation. The excess energy from fuel cell will charge the
battery until it is fully charged. As the fuel cell system is still
working at night, there will be heat supply for the heating appli-
cations. Fig. 9: illustrate the energy ow in the proposed system.
system along with the grid. A reformer and hydrogen tank are also There are ve different congurations simulated by HOMER
considered for the provision of uniform hydrogen supply to the fuel software in this study. They are: standalone diesel system, grid
cell system. Natural gas is used to produce hydrogen using the fuel connected PV system, grid connected PV-battery system, grid
reformer and stored in the hydrogen tank. The heat produced by connected PV-fuel cell system and grid connected PV-fuel cell-
the fuel cell and reformer is used in water boilers and the sterilizing battery system. The main purpose of the simulation is to evaluate
equipment in the hospital. At night, when the load is comparatively and compare the feasibility of each system in terms of economics
N.M. Isa et al. / Energy 112 (2016) 75e90 83
and emission effect. The optimization results of the ve scenarios show that the initial capital of grid-connected PV is $ 33,000. The
are discussed below. TNPC and LCOE are $ 148,764 and 0.128 $/kWh, respectively. Ac-
cording to the simulations results, the grid connected PV system
has total electrical energy production of 91,692 kWh/yr from which
7.1.1. Standalone diesel based system
PV produces 4423 kWh/yr and 87,270 kWh/yr is supplied by the
Conventionally, the hospital building uses diesel generators as a
grid purchases.
backup system for any fault or interruption occurrence in the power
system. In this study, a stand-alone diesel based system is analyzed
to evaluate the cost for implementing only diesel system. The 7.1.3. Grid connected PV/battery system
HOMER simulation diagram is shown in Fig. 10. The diesel price is The simulation results give the optimal congurations which
considered here 0.4 $/L according to the current market price. Ac- consist of 100 kW of grid power, 3 kW PV panel, 15 kW inverter and
cording to the optimization result, the system has the TNPC of $ 15 kW rectier, as shown in Fig. 12. This analysis is performed to
206,710. The LCOE for the diesel only system is $ 0.179/kWh. In this evaluate the effectiveness of battery installation. The optimization
system, the AC load is 91,228 kWh of annual average electricity results are shown in Table 7. The simulation results show the op-
demand. The diesel generator can produce 91,815 kWh/yr of elec- timum conguration where, the AC load consumption requires
tricity with 567 kWh/yr of excess electricity. The exhaust emissions 91,250 kWh per year and it is full lled by the power from PV panel
produced by the system contains carbon dioxide, carbon monoxide with 4423 kWh/yr and another 87,278 kWh/yr is supplied by the
and nitrogen dioxide of 96,712 kg/year, 239 kg/year and 2130 kg/ grid purchases. This optimal result gives the TNPC $154,955. The
year, respectively. According to David Biello, the world may cause a LCOE for the system is 0.133 $/kWh. The system produces 456 kWh
peak warming of 2 C when a trillion tons of carbon was released of excess electricity that can be sold to the grid. The TNPC and
into the atmosphere [54]. Therefore, the power generation systems operating cost of the system are $ 154,955 and 9343 $/yr respec-
design should focus on the carbon emission. The result shows that, tively. The system produces 55,155 kg/yr of carbon dioxide and
the fuel cost inuences the total cost of overall system. Table 5 239 kg/yr of sulfur dioxide and Nitrogen dioxide of 117 kg/yr.
shows the optimization results.
7.1.4. Grid connected with PV/FUEL cell system
7.1.2. Grid connected PV system Another conguration of grid connected PV panel and fuel cell
This analysis is performed to evaluate the feasibility of a grid without batteries is simulated as shown in Fig. 13. The optimization
connected PV system installation to the hospital building. Fig. 11 result shows that, there are ve optimized results produced which
shows the conguration of simulated system and Table 6 provide are ranked based on the TNPC. Table 8 show the optimize output
the optimization result for the grid connected system. The results from the HOMER simulation. The optimum conguration for this
system consist of a 100 kW power from the grid, 140 kW PV, 50 kW
fuel cell, 80 kW power converter and 5 kg/h reformer. The simu-
lation gives the TNPC equal to $ 99,094 and LCOE equal to 0.085
$/kWh. Moreover, the total amount of power production in the
system is 251,313 kWh/yr from which 206,389 kWh/yr come from
photovoltaic panel and the rest is supplied by the grid. In this
system, 91,250 kWh/yr is used for AC primary load and
77,206 kWh/yr is sold to the grid.
Table 5
Optimization results of standalone diesel based system.
Gen (kw) Initial capital ($) Operating cost ($/yr) TNPC ($) LCOE ($/kWh) Renewable fraction Capacity shortage Diesel (L/yr) Gen (hrs)
Table 6
Optimization result of grid connected PV system.
Grid (kw) PV (kw) Converter (kw) Capital cost ($) Operating cost ($/yr) TNPC ($) LCOE ($/kWh) Renewable fraction Capacity shortage
Table 7
Optimization result of grid connected PV-Battery system.
Grid (kw) PV (kw) Conv (kw) Battery Capital cost ($) Operating cost ($/yr) TNPC ($) LCOE ($/kWh) Ren fraction Capacity shortage
component since the hydrogen reformer is required to extract the 7.2. Sensitivity analysis
hydrogen from the fuel if a hydrocarbons source is used. In this
analysis, the fuel is assumed to use natural gas. There are ve A sensitivity analysis is performed on the uncertain parameters
optimization results rank according to the total NPC shown in Table that have been estimated during the system design. These might
N.M. Isa et al. / Energy 112 (2016) 75e90 85
Government may reduce the subsidy on the fuel prices, which can
increase the diesel price in future. The ination rates that uctuate
in every year may give the impact on the annual interest rate. Ac-
cording to Bank Negara Malaysia (BNM) [55], the annual interest
rate varies from 1% to 3.25% (current). Nevertheless, in this sensi-
tivity analysis, the annual interest rate is assumed from 1% to 6% for
25 years of lifetime. In other hand, the changes in diesel prices from
0.4 $/L (MYR 1.60) to 3 $/L (MYR 10.23) is considered for the 25
years of lifetime. The sensitivity parameters are set in order to
observe the effect to the total NPC and LCOE. Fig. 16 shows the effect
of annual rate of interest change and diesel price change on TNPC.
The sensitivity analysis of standalone diesel generator based
system considers the annual interest rate from 1% to 6% and also the
diesel price from 0.4 $/L to 3 $/L for 25 years. The effect of change in
these variables results in the increment of TNPC from $ 354,797 to $
1,406,054. The LCOE increases at the same time from 0.179 $/kWh
to 1.221 $/kWh. The main reason for this increment is the raise of
diesel price. Generally, at constant diesel price, the TNPC decreases
with the increase of interest rate. As the both the diesel price and
interest rate is varied here, thus the result is different. The grid
Fig. 13. Grid connected PV and fuel cell system. connected PV system has TNPC of $ 236,847 when annual interest
Table 8
Optimization Result of grid connected PV/Fuel cell system.
Grid (kW) PV (kW) Conv (kW) FC (kW) Reformer (kg/h) Capital cost ($) Operating cost ($/yr) TNPC ($) LCOE ($/kWh) Ren fraction Capacity shortage
Table 9
Optimization output of grid connected PV/Fuel Cell and battery system.
Grid PV Conv FC Battery Reformer Capital cost Operating cost TNPC LCOE Renewable Capacity
(kW) (kW) (kW) (kW) Pc (kg/h) ($) ($/yr) ($) ($/kWh) fraction shortage
Fig. 15. Monthly Average of electric production by grid PV panels and FC.
cost for each conguration are represented in Table 10. Among all
the congurations, the grid connected PV and fuel cell system has
the lowest capital cost as it only requires $ 9217. In contrast, the grid
connected PV/fuel cell/battery system requires $ 13,938 of initial
capital. Conventionally, diesel generator has been used as a backup,
therefore the stand alone diesel system also been simulated in this
work. The results have $ 1500 for initial capital cost which is lower
than the proposed system. Another topology, grid connected PV
system required capital cost of $ 33,000 and a grid connected PV
ebattery system needs $ 35,518 for initial capital.
Grid connected PV/battery system has the highest replacement
cost of $ 11,943 while the grid connected PV/Fuel cell system has
the lowest replacement cost which is $ 2496. The grid connected PV
system has replacement cost of $ 10,307. It is clear that battery cost
inuence the increment in replacement cost allocation. Moreover,
the grid connected PV/fuel cell/battery has the replacement cost of
$ 5,564, which also proves the inuence of battery cost.
Fig. 16. Effect of increase in annual rate of interest on the systems.
The highest O&M cost is required by the grid connected PV/
Battery system which is $ 111,983. Next, the grid connected PV
8. Discussion system, grid connected PV/fuel cell/battery system and grid con-
nected PV/fuel cell system require $ 11,944, $ 8614 and, $ 8245
The techno-economic feasibility of the proposed system is respectively. Again, the difference between the system with battery
investigated in this paper. The simulation results were analyzed and without batteries clearly shows that battery cost can increase
based on economical point of view as it will help to predict and the cost of the system.
design the optimal cogeneration system. According to the simula-
tion results, the system consist of PV/fuel cell and battery is the
8.2. Energy parameter assessment
optimal conguration. Moreover, four other topologies have also
been simulated to evaluate and compare the feasibility of the sys-
In this study, the variations of energy parameters of the
tem. Furthermore, the impact to the environment and the effec-
analyzed congurations are also observed. Among all congura-
tiveness of battery installation in the system also has been analyzed
tions, the proposed grid connected PV, fuel cell and battery system
in the simulation and the results are discussed in the following
produces the highest energy which 251,760 kWh/yr. Whereas, the
subsection.
consumption is only 168,776 kWh energy per year. Thus, the excess
electricity of this system is 69,003 kWh/yr, which can be stored in
8.1. Economical evaluation the battery. The grid connected PV and fuel cell without battery
system produce 251,313 kWh/yr for energy consumption of
There are several economic parameters simulated in HOMER 168,456 kWh/yr. The excess electricity of this conguration is
software. The comparison of initial capital, replacement cost, O&M 69,131 kWh/yr. As there is no storage component installed in this
N.M. Isa et al. / Energy 112 (2016) 75e90 87
Table 10
Comparison of cost allocation for each system.
System Initial capital ($) Replacement ($) O&M ($) Fuel ($) TNPC ($)
conguration, the excess energy is wasted. In comparison, stand- 91,692 kWh/yr and 91,740 kWh/yr respectively. Grid connected PV
alone diesel system produced 91,815 kWh/yr and the energy con- system has an energy consumption of 91,250 kWh/yr with 0.005
sumption is 91,228 kWh/yr. The system has an excess electricity of excess electricity while the grid connected PV/battery system has
587 kWh/yr with 21.9 kWh/yr of unsatised load. The result depicts energy consumption of 91,284 kWh/yr with 0.06 kWh/yr excess
that; the diesel based system is inefcient in terms of satisfying the electricity. Although these two systems are also capable of satis-
load. As the system is for hospital load, the capacity shortage is not fying the load, and have low excess power generation, they are not
tolerated. Thus the diesel based system is not applicable although it suggested because the TNPC and LCOE of these systems are higher
has low excess electricity production. The energy production in grid than the grid connected PV/fuel cell/battery system. Table 11 shows
connected PV system and grid connected PV-battery system are the comparison of energy parameters according to the simulation
88 N.M. Isa et al. / Energy 112 (2016) 75e90
Table 11
Comparison of Energy parameters.
System Energy production (kWh/yr) Energy consumption (kWh/yr) Excess electricity (kWh/yr) Unmet electricity (kWh/yr)
Table 12
Pollutant gas emission from the analyzed systems.
Carbon dioxide Carbon monoxide Unburned hydrocarbon Particulate matter SOX NOX
results in HOMER. 55,154 kg/yr, 25,708 kg/yr and 20,402 kg/yr, respectively. The result
shows that the stand alone diesel system is not environment
8.3. FiT benets friendly as it not only produces the highest carbon dioxide, but it
also produce carbon monoxide, sulfur dioxide and nitrogen dioxide
In general, the grid connected systems provide more cost- of 239 kg/yr, 194 kg/yr and 2130 kg/yr, respectively. In this regard, it
effective solutions. The proposed system that consists grid con- has negative impact on the environment, and the atmosphere can
nected PV/fuel cell and battery system is feasible since it has the be infected. In addition, the uctuation in global fuel prices has
lowest TNPC of $ 98,318 and the lowest LCOE of $ 0.084. This system made the traditional system less effective.
has some excess electricity generation and also it uses a battery The grid connected PV/fuel cell system is environmental friendly
bank to store energy. The battery bank is for emergency backup as it only produces 20,402 kg/yr of carbon dioxide, 239 kg/yr of
during fault occurrence. The excess energy and battery stored en- sulfur dioxide and 117 kg/yr of nitrogen oxide. The grid connected
ergy can be sold to the grid using the FiT program. The incentive PV/fuel cell and battery system produces 25,708 kg/yr of carbon
provided by the government for FiT program can be a source of dioxide, 111 kg/yr of sulfur dioxide and 54.5 kg/yr of nitrogen oxide.
income to the hospital management if it fullls the requirement of Although there is small increment in emission when the system is
Sustainable Energy Development Authorization (SEDA). The added with battery, it can be considered as environment friendly
installation of cogeneration system which consists of the PV panel compared to the existing traditional power generation in the hos-
will allow the building owner to claim the FiT benets. Conven- pital building. This system can help the hospital community to
tionally, the electricity charge is provided by the main utility maintain healthy and economical green environment. Table 12
company, Tenaga Nasional Berhad (TNB) as a monthly bill. The tariff simplied the results of emission produced in the simulation.
is categorized according to the client. According to TNB, hospitals
fall under Tariff C2 which charges the customers a at rate of RM 9. Conclusion
0.365/kWh (0.116 $/kWh) at peak period and RM 0.224/kWh (0.071
$/kWh) during off-peak period. FiT program determines the elec- This paper has demonstrated that cogeneration system con-
tricity prices from PV generation, which is upto 4 kW is 0.8249 RM/ sisting grid connected hybrid PV, fuel cell and battery is promising
kWh and upto 72 kW is 0.6139 RM/kWh. Also, additional incentive alternative to the conventional power system. Large energy
amount of 0.1550 is given for the installation of PV panel in a consuming centers like hospital should consider installing cogen-
building. The payback cost in sales and purchase activity with the eration system considering all the benets. Five congurations
authorized utility returns 20%e30% prot in duration of 21 years have been simulated in HOMER in order to study the feasibility of
agreement with SEDA [41]. This cogeneration system is able to the proposed system from an economic point of view. The results
produce the 206,389 kWh/yr electricity from the PV panel, which show that the proposed conguration which consists of grid con-
allows the hospital manager to claim the incentive of 1.0184 RM/ nected PV/fuel cell and battery is reasonable to supply the load
kWh. Means, for total 206,389 kWh/yr energy produced, the demand and at the same time the emission effect is also low.
amount can be claim from the TNB is MYR 223,725.6 per year. Thus, Conventionally in hospital building, diesel power generation sys-
per month the claim will be 18643.8 MYR. Therefore, by installing tem are used to provide the electricity while the heat is provided by
the cogeneration system in the hospital system, the amount of the natural gas through combustion process in a boiler. In cogen-
electricity and gas bill can be reduced. eration system, both electricity and heat energy can be generated
simultaneously from single system using single fuel. Hence, in this
8.4. Environment impact paper, a cogeneration system consist of fuel cell, photovoltaic and
battery system is proposed to fulll the hospital building demand.
Among all conguration simulated, the stand-alone diesel sys- University Kebangsaan Malaysia Medical Centre (UKMMC) building
tem has the highest amount of the carbon dioxide emission of is chosen as a case study. According to the simulation results of
96,712 kg/yr, followed by the grid connected PV/battery system, HOMER, the proposed cogeneration system needs only $ 12,771 of
grid connected PV system, grid connected PV/fuel cell/battery initial capital and $ 5564 for the replacement cost. The TNPC of this
system and grid connected PV/fuel cell system of 55,163 kg/yr, system is $ 98,318 and LCOE is $0.0841/kWh. The sensitivity
N.M. Isa et al. / Energy 112 (2016) 75e90 89
analysis of the system proves that, the system is sustainable to the 2013;54(2):488e96.
[16] Gimelli A, Muccillo M. Optimization criteria for cogeneration systems: multi-
increase of diesel price and the annual rate of real interest change.
objective approach and application in an hospital facility. Appl Energy Apr.
Although the initial investment of this system is high, it will be 2013;104:910e23.
protable to the hospital when it is included in the FiT program , M. Man
[17] C. J. Renedo, A. Ortiz, D. Silio ~ ana, S. Pe
rez, and J. Carcedo, Cogene-
provided by the Malaysian Government. With the installation of ration in a hospital: a case study.
[18] Electric L, Utility G. A cogeneration overview by a large electric and gas utility.
proposed cogeneration system in the selected hospital, cost on no. 3. 1985. p. 232e8.
power generation can be saved up to 30%. In addition, this proposed [19] Onovwiona HI, Ugursal VI. Residential cogeneration systems: review of the
system is also suitable for environment, because it has low emission current technology. Renew Sustain Energy Rev 2006;10:389e431.
[20] Cogeneration Process. [Online]. Available: http://www.c2es.org/technology/
of gases. It only produces 25,708 kg/yr of carbon dioxide, 111 kg/yr factsheet/CogenerationCHP. (accessed 26.01.16).
of sulfur dioxide and 54.5 kg/yr of nitrogen oxide. It is important for [21] Gu W, Wu Z, Bo R, Liu W, Zhou G, Chen W, et al. Electrical power and energy
the hospital community to ensure the area as a healthiest premise systems modeling, planning and optimal energy management of combined
cooling, heating and power microgrid: a review. Int J Electr Power Energy Syst
and green area. Nevertheless, the results from the simulation prove 2014;54:26e37.
that the cogeneration system is feasible to be implemented in the [22] Lau KY, Yousof MFM, Arshad SNM, Anwari M, Yatim aH M. Performance
hospital building in Malaysia. analysis of hybrid photovoltaic/diesel energy system under Malaysian con-
ditions. Energy Aug. 2010;35(8):3245e55.
[23] Pantaleo AM, Camporeale S, Shah N. Natural gas e biomass dual fuelled
Acknowledgement microturbines: comparison of operating strategies in the Italian residential
sector. Appl Therm Eng 2014;71(2):686e96.
[24] Javad M, Hossein S, Gharehpetian B, Heat C. An optimal dispatch algorithm for
The authors would like to pay gratitude to Universiti Teknologi managing residential distributed energy resources. 2013.
Malaysia (UTM) for supporting with lab and library facilities and [25] Moradi MH, Hajinazari M, Jamasb S, Paripour M. An energy management
National Renewable Energy Laboratories (NREL) for providing leg- system ( EMS ) strategy for combined heat and power ( CHP ) systems based
on a hybrid optimization method employing fuzzy programming. Energy
acy version of HOMER software and its free technical support. In 2013;49:86e101.
addition, the authors would like to express their appreciation to the [26] Costa A, Fichera A. A mixed-integer linear programming (MILP) model for the
Ministry of Higher Education, Malaysia (MOHE). They also evaluation of CHP system in the context of hospital structures. Appl Therm
Eng Oct. 2014;71(2):921e9.
acknowledge funding provided by fundamental research grant
[27] A. K. Basu, S. Chowdhury, S. P. Chowdhury, A. Distributed, and E. Resource,
scheme (FRGS) under vote 4F596, Universiti Teknologi Malaysia Strategic Deployment of CHP-based Distributed Energy Resources in Micro-
(UTM).Lastly thanks to those colleagues who have either directly or grids, pp. 1e6, 2009.
indirectly contributed to the completion of this work. Special [28] Meybodi MA, Behnia M. A study on the optimum arrangement of prime
movers in small scale microturbine-based CHP systems. Appl Therm Eng
thanks to Dr. M. J. Sanjari for his valuable comments and support 2012;48:122e35.
from time to time. [29] Mchenry MP. Technical, mitigation, and nancial comparisons of 6 kW e grid-
connected and stand-alone wood gasiers, versus mineral diesel and biodiesel
generation for rural distributed generation. Energy 2012;40(1):428e37.
References [30] Wu W, Indah V, Chen S, Hwang J. Design and techno-economic optimization
of a stand-alone PV ( photovoltaic )/FC ( fuel cell )/battery hybrid power
[1] Chua SC, Oh TH. Review on Malaysia's national energy developments: key system connected to a wastewater-to-hydrogen processor. Energy 2015;84:
policies, agencies, programmes and international involvements. Renew Sus- 462e72.
tain Energy Rev 2010;14(9):2916e25. [31] Karakoulidis K, Mavridis K, Bandekas DV, Adoniadis P, Potolias C, Vordos N.
[2] Gan PY, Komiyama R, Li Z. A low carbon society outlook for Malaysia to 2035. Techno-economic analysis of a stand-alone hybrid photovoltaic-diesel e
Renew Sustain Energy Rev 2013;21:432e43. battery-fuel cell power system. Renew Energy 2011;36(8):2238e44.
[3] Elektrik P. Interim report on the performance of the electricity supply services [32] Saidur R, Hasanuzzaman M, Yogeswaran S, Mohammed H a, Hossain MS. An
in Malaysia for rst half year 2010. 2010. end-use energy analysis in a Malaysian public hospital. Energy Dec.
[4] Seong C, Lalchand G. A review on sustainable power generation in Malaysia to 2010;35(12):4780e5.
2030: historical perspective, current assessment, and future strategies. Renew [33] Moghimi S, Azizpour F, Mat S, Lim CH, Salleh E, Sopian K. Building energy
Sustain Energy Rev 2014;29:952e60. index and end-use energy analysis in large-scale hospitalsdcase study in
[5] Chong H, Lam W. Ocean renewable energy in Malaysia: the potential of the Malaysia. Energy Efc Jul. 2013;7(2):243e56.
Straits of Malacca. Renew Sustain Energy Rev 2013;23:169e78. [34] Moghimi S, Lim C, Mat S. Building energy index (BEI) in large scale hospital:
[6] Urtasun A, Sanchis P, Barricarte D, Marroyo L. Energy management strategy case study of Malaysia. In: 4th WSEAS int.; 2011. p. 167e70.
for a battery-diesel stand-alone system with distributed PV generation based [35] Givler T, Lilienthal P. Using HOMER software, NREL's micropower optimi-
on grid frequency modulation. Renew Energy Jun. 2014;66:325e36. zation model, to explore the role of gen-sets in small solar power systems case
[7] Dufo-lo R, Bernal-Agustn Jose L, Contreras Javier. Optimization of control study: Sri Lanka using HOMER software, NREL's micropower optimization
strategies for stand-alone renewable energy systems with hydrogen storage. model, to explore the role of gen-sets in smal. no. May, 2005.
Renew Energy 2007;32:1102e26. [36] Sohag K, Ara R, Mastura S, Abdullah S. Dynamics of energy use, technological
[8] Nottrott A, Kleissl J, Washom B. Energy dispatch schedule optimization and innovation, economic growth and trade openness in Malaysia. Energy
cost bene t analysis for grid-connected, photovoltaic-battery storage sys- 2015;90:1497e507.
tems. Renew Energy 2013;55:230e40. [37] Das HS, Yatim AHM, Wei C, Lau KY. Proposition of a PV/tidal powered micro-
[9] Karabiber A, Keles C, Kaygusuz A, Alagoz BB. An approach for the integration hydro and diesel hybrid system: a southern Bangladesh focus. Renew Sustain
of renewable distributed generation in hybrid DC/AC microgrids. Renew En- Energy Rev 2016;53:1137e48.
ergy 2013;52:251e9. [38] Mohamed A, Halim A, Yatim M, Wazir M, Tahseen O, Fahad A, et al. Feasibility
[10] Raj NT, Iniyan S, Goic R. A review of renewable energy based cogeneration study of renewable energy-based microgrid system in Somaliland's urban
technologies. Renew Sustain Energy Rev 2011;15(8):3640e8. centers. Renew Sustain Energy Rev 2014;40:1048e59.
[11] Petkajee T, Banjerdpongchai D. Multi-objective approach to economic and [39] Ngan MS, Tan CW. Assessment of economic viability for PV/wind/diesel
environmental optimal operations of cogeneration for building energy man- hybrid energy system in southern Peninsular Malaysia. Renew Sustain Energy
agement system. In: 2013 10th int. conf. electr. eng. comput. telecommun. inf. Rev 2012;16(1):634e47.
technol.; May 2013. p. 1e6. [40] Lau KY, Tan CW, Yatim AHM. Photovoltaic systems for Malaysian islands:
[12] Ullah KR, Akikur RK, Ping HW, Saidur R, Hajimolana S a, Hussain M a. An effects of interest rates, diesel prices and load sizes. Energy 2015;83:204e16.
experimental investigation on a single tubular SOFC for renewable energy [41] Dursun B. Determination of the optimum hybrid renewable power generating
based cogeneration system. Energy Convers Manag 2015;94:139e49. systems for Kavakli campus of Kirklareli University, Turkey. Renew Sustain
[13] Shaaban M, Nor KM, Member S. Prospects of cogeneration for the iron and Energy Rev Oct. 2012;16(8):6183e90.
steel industry in Malaysia. no. June. 2011. p. 6e7. [42] HOMER Help Files.
[14] Ganjeh Kaviri HBAA, Mohd Jaafar MN, Tholudin ML. Exergy analysis of a [43] Mahlia TMI, Chan PL. Life cycle cost analysis of fuel cell based cogeneration
cogeneration heat and power (CHP) system (rst and second law analysis). system for residential application in Malaysia. Renew Sustain Energy Rev
2011. p. 29e33. 2011;15(1):416e26.
[15] Alexis GK, Liakos P. A case study of a cogeneration system for a hospital in [44] Kongjun Z, Haijun L, Xingzhe H. Application of LCC theory on the watthour
Greece. Economic and environmental impacts. Appl Therm Eng May meter management. 2006.
90 N.M. Isa et al. / Energy 112 (2016) 75e90
[45] Khan MJ, Iqbal MT. Dynamic modeling and simulation of a small windefuel html?sp. (accessed 20.01.16.).
cell hybrid energy system. Renew Energy Mar. 2005;30(3):421e39. [50] Product Portfolio: Fuel cell Ballard Product. [Online]. Available: http://www.
[46] S. Power, I. B. C. Solar, and A. Class, Suntech Power STP200e18/Ud, STP205- ballard.com/les/PDF/ProductPortfolio.pdf. (accessed 18.08.14.).
18Ud, STP210-18/Ud Polycrystalline solar modules. [Online]. Available: [51] Sharaf OZ, Orhan MF. An overview of fuel cell technology: fundamentals and
https://www.ibc-solar.pt/leadmin/content/homepage/produtos/Download/ applications. Renew Sustain Energy Rev Apr. 2014;32:810e53.
Datasheet_Suntech_Power_STP_200_205_210_18Ud_(101029)_EN.pdf. [52] R. Output, M OT I V E..
[47] rollsbatteryengineering. [Online]. Available: http://rollsbattery.com/motive_ [53] no. August Interim system performance report the center for fuel cell research
power/. and applications. 2004. p. 1e9.
[48] Inverter. [Online]. Available: http://solar-catalog.com/inverter_grid-tie. [54] Biello D. How much is too much? The false promise of biofuels. Sci Am
html#PV_POWERED. (accessed 15.03.14.). 2011;1:58e65.
[49] 5 kw changchai diesel generator. [Online]. Available: http://www.alibaba. [55] Malaysia interest rate. [Online]. Available: http://www.tradingeconomics.
com/product-detail/Low-price-5kw-changchai-diesel-generator_534115932. com/malaysia/interest-rate. (accessed 17.11.15.).